Siemens SITRANS TF Temperature Transmitter
Siemens SITRANS TF Temperature Transmitter
Temperature measurement
Temperature transmitters
Field transmitters/field indicator
SITRANS TF - Transmitter, 2-wire system and SITRANS TF - Field indicator for 4 to 20 mA
■ Overview ■ Function
Configuration
The communication capability over the HART protocol V 5.9 of
the SITRANS TF with an integrated SITRANS TH300 permits pa-
2 rameterization using a PC or HART communicator (hand-held
communicator). The SIMATIC PDM makes it easy.
For the SITRANS TF with integrated programmable
SITRANS TH200, parameters are assigned with the PC. Avail-
able for this purpose are a special modem and the software tool
SIPROM T.
Mode of operation
Mode of operation of SITRANS TF as temperature transmitter
The sensor signal, whether resistance thermometer, thermocou-
ple element or or mV signal, is amplified and linearized. Sen-
sor and output side are electrically isolated. An internal cold
junction is integrated for measurements with thermocouples.
The device outputs a temperature-linear direct current of 4 to 20
Our field devices for heavy industrial use mA. As well as the analog transmission of measured values from
• HART, Universal 4 to 20 mA, the HART version also supports digital communica-
tion for online diagnostics, measured value transmission and
• 4 to 20 mA, universal configuration.
• Field indicator for 4 to 20 mA signals
SITRANS TF automatically detects when a sensor should be in-
The temperature transmitter SITRANS TF works where others terrupted or is indicating a short-circuit. The practical test termi-
feel uncomfortable. nals allow direct measurement of 4 to 20 mA signals over an am-
meter without interrupting the output current loop.
■ Benefits Mode of operation of SITRANS TF as field indicator
• Universal use Any 4 to 20 mA signal can be applied to the generous terminal
- as transmitter for resistance thermometer, thermocouple ele- block. As well as a range of predefined measurement units, the
ment, or mV signal adjustable indicator also supports the input of customized units.
- as field indicator for any 4 to 20 mA signals This means that any 4 to 20 mA signal can be represented in any
• Local sensing of measured values over digital display unit, e.g. pressure, flow rate, level or temperature.
• Rugged two-chamber enclosure in die-cast aluminum or
stainless steel
• IP66/67/68 degree of protection Power supply
SITRANS TF
• Test terminals for direct read-out of the output signal without Sensor SITRANS TH300 0000 8
breaking the current loop TC RTD 1 3 4
00°C
5
2 9
• Can be mounted elsewhere if the measuring point A D
μP Load
- is difficult to access D A
- has high temperatures
- experiences vibrations due to the process cell
- is to avoid long neck pipes and thermowells 7
6
• Can be mounted directly on American-design sensors 1 Analog-to-digital converter
• Wide range of approvals for use in potentially explosive atmo- 2 Electrical isolation
spheres. Types of protection "Intrinsically safe, non-sparking 3 Microprocessor
and flameproof", for Europe and the USA.
4 Digital-to-analog converter
• SIL2 (with order note C20), SIL2/3 (with C23)
5 Power supply
■ Application 6 PC/laptop
7 HART modem
SITRANS TF can be used everywhere where temperatures need
8 Digital display (option)
to be measured under particularly adverse conditions, or where
a convenient local display is ideal. Which is why users from all 9 Test connector
industries have opted for this field device. The rugged enclosure
protects the electronics. The stainless steel model is almost
completely resistant to sea water and other aggressive sub-
stances. The inner workings offer high measuring accuracy, uni- Mode of operation of SITRANS TF with integrated SITRANS TH300 and
versal input and a wide range of diagnostic options. digital display
Temperature measurement
Temperature transmitters
Field transmitters/field indicator
SITRANS TF - Transmitter, 2-wire system and SITRANS TF - Field indicator for 4 to 20 mA
■ Technical specifications
Input Thermocouples
Resistance thermometer Measured variable Temperature
Measured variable Temperature Sensor type (thermocouples)
Input type • Type B Pt30Rh-Pt6Rh acc. to IEC 584 2
• According to IEC 60751 Pt25 … Pt1000 • Type C W5%-Re acc. to ASTM 988
• Acc. to JIS C 1604; a=0.00392 K-1 Pt25 … Pt1000 • Type D W3%-Re acc. to ASTM 988
• According to IEC 60751 Ni25 … Ni1000 • Type E NiCr-CuNi acc. to IEC 584
• Type J Fe-CuNi acc. to IEC 584
Units °C and °F • Type K NiCr-Ni acc. to IEC 584
Connection • Type L Fe-CuNi acc. to DIN 43710
• Standard connection 1 resistance thermometer (RTD) in 2- • Type N NiCrSi-NiSi acc. to IEC 584
wire, 3-wire or 4-wire connection • Type R Pt13Rh-Pt acc. to IEC 584
• Averaging Series or parallel connection of sev- • Type S Pt10Rh-Pt acc. to IEC 584
eral resistance thermometers in the 2-
• Type T Cu-CuNi acc. to IEC 584
wire connection for the generation of
average temperatures or for adapta- • Type U Cu-CuNi acc. to DIN 43710
tion to other device types Units °C or °F
• Differentiation 2 resistance thermometers (RTD) in
2-wire connection (RTD 1 – RTD 2 or Connection
RTD 2 – RTD 1) • Standard connection 1 thermocouple (TC)
• Averaging 2 thermocouples (TC)
Connection
• Differentiation 2 thermocouples (TC)
• 2-wire connection Line resistance can be configured
(TC 1 – TC 2 or TC 2 – TC 1)
100 (loop resistance)
• 3-wire connection No trim necessary Response time 250 ms for 1 sensor with break
• 4-wire connection No trim necessary monitoring
Response time 250 ms for 1 sensor with break Reference junction compensation
monitoring • Internal With integrated Pt100 resistance ther-
mometer
Break monitoring Always active (cannot be switched
• External With external Pt100 IEC 60751 (2-wire
off)
or 3-wire connection)
Short-circuit monitoring Can be switched on/off (default value: • External fixed Reference junction temperature can
ON) be set as fixed value
Measuring range Assignable (see "Digital measuring Measuring range Assignable (see "Digital measuring
error" table) error" table)
Min. measuring span 10 °C (18 °F) Min. measuring span Min. 40 ... 100 °C (72 ... 180 °F) (see
"Digital measuring error" table)
Characteristic curve Temperature-linear or special charac-
teristic Characteristic curve Temperature-linear or special charac-
teristic
Resistance-based sensor
mV sensor
Measured variable Actual resistance
Measured variable DC voltage
Sensor type Resistance-based, potentiometers
Sensor type DC voltage source (DC voltage
Units
source possible over an externally
Connection connected resistor)
• Standard connection 1 resistance-based sensor (R) in 2- Units mV
wire, 3-wire or 4-wire connection
• Averaging 2 resistance-based sensors in 2-wire Response time 250 ms for 1 sensor with break
connection for averaging monitoring
• Differentiation 2 resistance-based sensors in 2-wire Break monitoring Can be switched off
connection (R 1 – R 2 or R 2 – R 1)
Measuring range -10 ... +70 mV
Connection -100 ... +1100 mV
• 2-wire connection Line resistance can be configured
Min. measuring span 2 mV or 20 mV
100 (loop resistance)
• 3-wire connection No trim necessary Overload capability of the input -1.5 ... +3.5 V DC
• 4-wire connection No trim necessary Input resistance 1 M
Sensor current 0.45 mA Characteristic curve Voltage-linear or special characteris-
Response time 250 ms for 1 sensor with break tic
monitoring
Break monitoring Can be switched off
Short-circuit monitoring Can be switched off (value is adjust-
able)
Measuring range Assignable max. 0 ... 2200 (see
"Digital measuring error" table)
Min. measuring span 5 ... 25 (see "Digital measuring
error" table)
Characteristic curve Resistance-linear or special charac-
teristic
Temperature measurement
Temperature transmitters
Field transmitters/field indicator
SITRANS TF - Transmitter, 2-wire system and SITRANS TF - Field indicator for 4 to 20 mA
Output Certificates and approvals
Output signal 4 ... 20 mA, 2-wire Explosion protection ATEX
Communication with SITRANS TH300 According to HART Rev. 5.9 • "Intrinsic safety" type of protection With digital display:
II 2 (1) G Ex ib [ia Ga] IIC T4 Gb
Digital display II 2 G Ex ib IIC T4 Gb
II 1D Ex ia IIIC T100 °C Da
2 Digital display (optional)
Display
In current loop
Max. 5 digits
Without digital display:
II 2 (1) G Ex ib [ia Ga] IIC T6 Gb
II 2 G Ex ib IIC T6 Gb
Digit height 9 mm (0.35")
II 1D Ex ia IIIC T100 °C Da
Display range -99 999 ... +99 999 • EC type-examination certificate ZELM 11 ATEX 0471 X
Units Any (max. 5 char.) • "Non-sparking and energy-limited II 3 G Ex ic IIC T6/T4 Gc
equipment for Zone 2" type of pro- II 3 G Ex nA IIC T6/T4 Gc
Setting: Using 3 buttons tection II 3 G Ex nA [ic] IIC T6/T4 Gc
Zero point, full-scale value and unit • EC type-examination certificate ZELM 11 ATEX 0471 X
Load voltage 2.1 V • "Flameproof enclosure" type of pro- II 2 G Ex d IIC T6/T5 Gb
tection II 2 D Ex tb IIIC T100 °C Db
Measuring accuracy
• EC type-examination certificate ZELM 11 ATEX 0472 X
Digital measuring error See "Digital measuring error" table
Explosion protection acc. to FM Certificate of Compliance 3017742
Reference conditions • Identification (XP, DIP, NI, S) • XP/I/1/BCD/T5 Ta = 85 °C (185 °F),
• Auxiliary power 24 V ± 1 % T6 Ta = 60 °C (140 °F), Type 4X
• Load 500 • DIP/II, III/1/EFG/T5 Ta = 85 °C
• Ambient temperature 23 °C (73.4 °F) (185 °F), T6 Ta = 60 °C (140 °F),
• Warming-up time > 5 min Type 4X
Error in the analog output (digital/ana- < 0.025 % of measuring span • NI/I/2/ABCD/T5 Ta = 85 °C (185 °F),
log converter) T6 Ta = 60 °C (140 °F), Type 4X
Error due to internal reference junction < 0.5 °C (0.9 °F) • S/II, III/2/FG/T5 Ta = 85 °C (185 °F),
T6 Ta = 60 °C (140 °F), Type 4X
Effect of ambient temperature
• Analog measuring error 0.02 % of meas. span/10 °C (18 °F) Other certificates IECEx, EAC Ex(GOST), INMETRO,
NEPSI, KOSHA
• Digital measuring error
Hardware and software require-
• with resistance thermometers 0.06 °C (0.11 °F)/10°C (18 °F) ments
• with thermocouples 0.6 °C (1.1 °F)/10°C (18 °F) • For the SIPROM T parameterization
Auxiliary power effect < 0.001 % of meas. span/V software for SITRANS TF with TH200
• Personal computer PC with CD-ROM drive and USB
Effect of load impedance < 0.002 % of meas. span/100 interface
Long-term drift • PC operating system Windows 98, NT, 2000, XP, 7 and Win
• In the first month < 0.02 % of measuring span 8
• After one year < 0.2 % of measuring span • For the SIMATIC PDM parameteriza- See section 8 "Digitalization and com-
• After 5 years < 0.3 % of measuring span tion software for SITRANS TH300 munication", "SIMATIC PDM"
Temperature measurement
Temperature transmitters
Field transmitters/field indicator
SITRANS TF - Transmitter, 2-wire system and SITRANS TF - Field indicator for 4 to 20 mA
Digital measuring error
Resistance thermometer Thermocouples
Input Measuring range Minimum Digital accuracy Input Measuring range Minimum Digital accuracy
measuring span measuring span
According to
°C (°F) °C (°F) °C (°F)
Type B
°C (°F)
100 ... 1820
°C
100
(°F)
(180)
°C
2 1)
(°F)
(3.6) 1)
2
IEC 60751 (212 ... 3308)
Pt25 -200 ... +850 10 (18) 0.3 (0.54) Type C (W5) 0 ... 2300 100 (180) 2 3.6
(-328 ... +1562) (32 ... 4172)
Pt50 -200 ... +850 10 (18) 0.15 (0.27) Type D (W3) 0 ... 2300 100 (180) 12) (1.8)2)
(-328 ... +1562) (32 ... 4172)
Pt100 ... Pt200 -200 ... +850 10 (18) 0.1 (0.18) Type E -200 ... +1000 50 (90) 1 (1.8)
(-328 ... +1562) (-328 ... +1832)
Pt500 -200 ... +850 10 (18) 0.15 (0.27) Type J -200 ... +1200 50 (90) 1 (1.8)
(-328 ... +1562) (-328 ... +2192)
Pt1000 -200 ... +350 10 (18) 0.15 (0.27) Type K -200 ... +1370 50 (90) 1 (1.8)
(-328 ... +662) (-328 ... +2498)
According to Type L -200 ... +900 50 (90) 1 (1.8)
JIS C1604-81 (-328 ... +1652)
Pt25 -200 ... +649 10 (18) 0.3 (0.54) Type N -200 ... +1300 50 (90) 1 (1.8)
(-328 ... +1200) (-328 ... +2372)
Pt50 -200 ... +649 10 (18) 0.15 (0.27) Type R -50 ... +1760 100 (180) 2 (3.6)
(-328 ... +1200) (-58 ... +3200)
Pt100 ... Pt200 -200 ... +649 10 (18) 0.1 (0.18) Type S -50 ... +1760 100 (180) 2 (3.6)
(-328 ... +1200) (-58 ... +3200)
Pt500 -200 ... +649 10 (18) 0.15 (0.27) Type T -20 ... +400 40 (72) 1 (1.8)
(-328 ... +1200) (-328 ... +752)
Pt1000 -200 ... +350 10 (18) 0.15 (0.27) Type U -200 ... +600 50 (90) 2 (3.6)
(-328 ... +662) (-328 ... +1112)
Ni 25 ... Ni1000 -60 ... +250 10 (18) 0.1 (0.18) 1)
The digital accuracy in the range 100 to 300 °C (212 to 572 °F) is 3 °C
(-76 ... +482) (5.4 °F).
2)
Resistance-based sensor The digital accuracy in the range 1750 to 2300 °C (3182 to 4172 °F) is 2 °C
(3.6 °F).
Input Measuring Minimum Digital accuracy mV sensor
range measuring span
Input Measuring Minimum Digital accuracy
range measuring span
Resistance 0 ... 390 5 0.05
mV mV V
Resistance 0 ... 2200 25 0.25
mV sensor -10 ... +70 2 40
mV sensor -100 ... +1100 20 400
Temperature measurement
Temperature transmitters
Field transmitters/field indicator
SITRANS TF - Transmitter, 2-wire system and SITRANS TF - Field indicator for 4 to 20 mA
Temperature measurement
Temperature transmitters
Field transmitters/field indicator
SITRANS TF - Transmitter, 2-wire system and SITRANS TF - Field indicator for 4 to 20 mA
Options Order code Accessories
Append suffix "-Z" to article no., add order code Article No.
and plain text, if applicable. Additional accessories for assembly, connec-
Customer-specific programming tion and transmitter configuration, see page
2/251.
Measuring range to be set Y012)
Specify in plain text (max. 5 digits):
Y01:... to ... °C, °F
Modems
Modem with USB interface 7MF4997-1DB
2
3) Modem with USB interface and SIPROM T soft- 7NG3092-8KN
Measuring point number (TAG) max. 8 characters Y17
ware
Measuring point description, max. 16 characters Y234)
SIMATIC PDM parameterization software See section 8
Measuring point description, max. 32 characters Y244) Also for SITRANS TH300
Labeling of measuring point plate only, specify Y224) Mounting bracket and fastening parts
in plain text: Measuring range
Made of steel for 7NG313.-..B.. 7MF4997-1AC
Pt100 (IEC) 2-wire, RL = 0 U02 5)
Made of steel for 7NG313.-..C.. 7MF4997-1AB
Pt100 (IEC) 3-wire U035)
Made of stainless steel for 7NG313.-..B.. 7MF4997-1AJ
Pt100 (IEC) 4-wire U045)
Made of stainless steel for 7NG313.-..C.. 7MF4997-1AH
Type B thermocouple U205)6)
Made of stainless steel 316L for 7NG313.-..B.. 7MF4997-1AQ
Type C thermocouple (W5) U215)6)
Made of stainless steel 316L for 7NG313.-..C.. 7MF4997-1AP
Type D thermocouple (W3) 5)6) U225)6)
Digital display1) 7MF4997-1BS
Type E thermocouple U235)6)
Connection board A5E02226423
Type J thermocouple U245)6)
For supply units, see Catalog FI 01 section "Supplementary components".
Type K thermocouple U255)6)
1)
Type L thermocouple U265)6) Retrofitting not possible with Ex devices.
Temperature measurement
Temperature transmitters
Field transmitters/field indicator
SITRANS TF - Transmitter, 2-wire system and SITRANS TF - Field indicator for 4 to 20 mA
Article No. Options Order code
SITRANS TF field indicator 7NG3130 - 7 7 7 7 7 Append suffix "-Z" to article no., add order code
For 4 ... 20 mA signals and plain text, if applicable.
Click on the Article No. for the online Cable gland ½ NPT ADE 4F, Stainless steel D59
configuration in the PIA Life Cycle Portal. (CAPRI 848699 and 810634) included
Test report (5 measuring points) C11 Additional accessories for assembly, connec-
tion and transmitter configuration, see page
Explosion protection 2/251.
• Explosion protection Ex ia according to E251) Mounting bracket and fastening parts
INMETRO (Brazil) (only for 7NG313.-1...)
1) Made of steel for 7NG313.-..B.. 7MF4997-1AC
• Explosion protection Ex d according to E26
INMETRO (Brazil) (only for 7NG313.-4...) Made of steel for 7NG313.-..C.. 7MF4997-1AB
• Explosion protection Ex nA according to E271)
INMETRO (Brazil) (only for 7NG313.-2...) Made of stainless steel for 7NG313.-..B.. 7MF4997-1AJ
• Explosion protection Ex i according to NEPSI E551) Made of stainless steel for 7NG313.-..C.. 7MF4997-1AH
(China) (only for 7NG313.-1...)
• Explosion protection Ex d according to NEPSI E561) Made of stainless steel 316L for 7NG313.-..B.. 7MF4997-1AQ
(China) (only for 7NG313.-4...) Made of stainless steel 316L for 7NG313.-..C.. 7MF4997-1AP
• Explosion protection Ex nA according to E571)
NEPSI (China) (only for 7NG313.-2...) Digital display1) 7MF4997-1BS
• Explosion protection Ex d according to E701) Connection board A5E02226423
KOSHA (Korea) (only for 7NG313.-4...) For supply units, see Catalog FI 01 section "Sup-
1)
• Explosion protection Ex i according to EAC E81 plementary components".
(Russia/Belarus/Kazahstan) (only for
7NG313.-1...) Ordering example 1
• Explosion protection Ex d according to EAC E821)
(Russia/Belarus/Kazahstan) (only for 7NG3130-0AB10-Z Y01+Y23
7NG313.-4...) Y01: -5 ... 100 °C
• Explosion protection Ex nA according to EAC E831)
(Russia/Belarus/Kazakhstan) (only for Y23: TICA1234HEAT
7NG313.-2...)
Ordering example 2
Marine approvals
• Det Norske Veritas Germanischer Lloyd (DNV D01 7NG3130-0AC11-Z Y01+Y23+Y24
GL) Y01: 0 ... 20 BAR
• Bureau Veritas (BV) D02
Y23: PICA 1234 ABC
• Lloyd’s Register of Shipping (LR) D04
• American Bureau of Shipping (ABS) D05 Y24: HEATING BOILER 67890
Two-layer coating of enclosure and cover G10 Factory setting of the display
(PU on epoxy)
4 ... 20 m
Transient protection J01
Cable gland CAPRI ½ NPT ADE 4F, nickel- D57
plated brass (CAPRI 848694 and 810634)
included
Cable gland ½ NPT ADE 1F, cable diameter D58
6 ... 12 (CAPRI 818694 and 810534) included
Temperature measurement
Temperature transmitters
Field transmitters/field indicator
SITRANS TF - Transmitter, 2-wire system and SITRANS TF - Field indicator for 4 to 20 mA
■ Dimensional drawings
(0.79)
138* (5.43) 28
52 (2.05)
20
6 2
50* (1.97) (1.10)
(1.97)
50
80 (3.15)
117 (4.61)
3
a
237 (9.33)
8 5 4
68 (2.68)
120 (4.72)
36.5 (1.44)
1
72 (2.83)
105 (4.13)
1 Sensor connection (screwed gland M20x1.5 or ½-14 NPT)
6 Protective cover (without function)
2 Blanking plug
7 Mounting bracket (option) with clamp for securing to a
3 Electrical connection (screwed gland M20x1.5 or ½-14 NPT) vertical or horizontal pipe
4 Terminal side, output signal 8 Cover with window for digital display
5 Terminal side, sensor
Temperature measurement
Temperature transmitters
Field transmitters/field indicator
SITRANS TF - Transmitter, 2-wire system and SITRANS TF - Field indicator for 4 to 20 mA
■ Circuit diagrams
2
3 6 3 6 3 6
3 + - 6 3 + - 6 3 + - 6
3-W
3-W
3-W
4 5 4 5 4 5
4 5 4 5 4 5
+ TC -
RTD R
3 6 3 6 3 6
3 + - 6 3 + - 6 + -
3 6
3-W
3-W
3-W
4 5 4 5 4 5
4 5 4 5 4 5
+ TC -
RTD R
RTD
3 6
3 6 3 + - 6
3-W
+ - 3 6 4 5
3 6 + -
3-W
3 6
3-W
4 5 4 5
4 5
4 5 4 5
+ TC -
RTD RTD
R
3 6 + -
3-W
4 5 4 5 3 4 3-W 5
6
4 5 4 5 4 5
R1
RTD1
3 6 3 6
+ - 3 + - 6
3 6
3-W
3-W
4 5 4 5
4 5 4 5
+ - R
U
+ -
I
Temperature measurement
Temperature transmitters
Field transmitters/field indicator
SITRANS TF - fieldbus transmitter
• Can be mounted directly on American-design sensors
■ Overview • Wide range of approvals for use in potentially explosive atmo-
spheres. "Intrinsically safe, non-sparking and flameproof" type
of protection, for Europe and USA
■ Application 2
The SITRANS TF can be used everywhere where temperatures
need to be measured under particularly harsh conditions. Which
is why users from all industries have opted for this field device.
The rugged enclosure protects the electronics. The stainless
steel model is almost completely resistant to sea water and other
aggressive substances. The inner workings offer high measur-
ing accuracy, universal input and a wide range of diagnostic op-
tions.
■ Function
Features
General
• Polarity-neutral bus connection
• 24-bit analog-digital converter for high resolution
Our field devices for heavy industrial use
• Galvanic isolation
• FOUNDATION fieldbus
• Version for use in hazardous areas
• PROFIBUS PA
• Special characteristic
The SITRANS TF temperature transmitter works where others
can't cope. • Sensor redundance
Transmitter with PROFIBUS PA communication
■ Benefits • Function blocks: 2 x analog
• For universal use as a transmitter for resistance thermometers,
thermocouple elements, or mV signals Transmitter with FOUNDATION fieldbus communication
• Rugged two-chamber enclosure in die-cast aluminum or • Function blocks: 2 x analog and 1 x PID
stainless steel • Functionality: Basic or LAS
• IP66/67/68 degree of protection
Mode of operation
• Can be mounted elsewhere if the measuring point
- is difficult to access The following function diagram explains the mode of operation
- has high temperatures of the transmitter.
- experiences vibrations due to the process cell The only difference between the two versions of the SITRANS TF
- is to avoid long neck pipes and thermowells (7NG3137-... and 7NG3138-...) is the type of field bus protocol
used (PROFIBUS PA or FOUNDATION fieldbus).
Transformer
Input 1
Input 2
Differential
Optional inputs: Mean value
Redundancy
- Resistance thermometer Terminal temperature
Engineering units
- Thermocouple Diagnostic functions
- mV sensor Table linearization
Polynomial linearization
- Resistance-based sensors Process calibration
Electrically
isolated
6
Ex power circuit
Input 1 1
5
A/D
converter CPU Communication Bus connection
4
2
Input 2
3
Temperature measurement
Temperature transmitters
Field transmitters/field indicator
SITRANS TF - fieldbus transmitter
System communication Thermocouple
According to IEC 584 Measuring range
Bus terminator PROFIBUS PA • Type B 400 ... 1820 °C (752 ... 3308 °F)
• Type E -100 ... +1000 °C (-148 ... +1832 °F)
Segment • Type J -100 ... +1000 °C (-148 ... +1832 °F)
2 coupler • Type K
• Type N
-100 ... +1200 °C (-148 ... +2192 °F)
-180 ... +1300 °C (-292 ... +2372 °F)
• Type R -50 ... +1760 °C (-58 ... +3200 °F)
SITRANS TF
• Type S -50 ... +1760 °C (-58 ... +3200 °F)
with TH400 PA
• Type T -200 ... +400 °C (-328 ... +752 °F)
According to DIN 43710
• Type L -200 ... +900 °C (-328 ... +1652 °F)
• Type U -200 ... +600 °C (-328 ... +1112 °F)
Bus terminator FOUNDATION Fieldbus According to ASTM E988-90
• Type W3 0 ... 2300 °C (32 ... 4172 °F)
Segment • Type W5 0 ... 2300 °C (32 ... 4172 °F)
coupler
External reference junction compen- -40 ... +135 °C (-40 ... +275 °F)
sation
SITRANS TF Sensor fault detection
with TH400 FF • Sensor break detection Yes
• Sensor short-circuit detection Yes, < 3 mV
• Sensor current in the event of open- 4 A
circuit monitoring
SITRANS TF with TH400, communication interface
mV sensor - voltage input
■ Technical specifications Measuring range -800 ... +800 mV
Input resistance 10 M
Input
Output
Analog/digital conversion
Filter time (programmable) 0 ... 60 s
• Measurement rate < 50 ms
• Resolution 24-bit Update time < 400 ms
Resistance thermometer Measuring accuracy
Accuracy is defined as the higher
Pt25 ... Pt1000 acc. to IEC 60751/JIS value of general values and basic val-
C 1604 ues.
• Measuring range -200 ... +850 °C (-328 ... +1562 °F)
General values
Ni25 ... Ni1000 acc. to DIN 43760
Type of input Absolute Temperature
• Measuring range -60 ... +250 °C (-76 ... +482 °F)
accuracy coefficient
Cu10 ... Cu1000, = 0.00427
All ± 0.05 % of the ± 0.002 % of the
• Measuring range -50 ... +200 °C (-58 ... +392 °F) measured value measured
Line resistance per sensor cable Max. 50 value/°C
Temperature measurement
Temperature transmitters
Field transmitters/field indicator
SITRANS TF - fieldbus transmitter
Rated conditions Communication
Ambient conditions Parameterization interface
Ambient temperature -40 ... +85 °C (-40 ... +185 °F) • PROFIBUS PA connection
- Protocol A&D profile, Version 3.0
Storage temperature -40 ... +85 °C (-40 ... +185 °F) - Protocol standard EN 50170 Volume 2
Relative humidity
Insulation strength
98 %, with condensation - Address (for delivery)
- Function blocks
126
2 x analog
2
• Test voltage 500 V AC for 60 s • FOUNDATION Fieldbus connection
• Continuous operation 50 V AC/75 V DC - Protocol FF protocol
- Protocol standard FF design specifications
Electromagnetic compatibility - Functionality Basic or LAS
NAMUR NE21 - Version ITK 4.6
EMC 2014/30/EU Emission and Noise EN 61326-1, EN 61326-2-5 - Function blocks 2 x analog and 1 x PID
Immunity Factory setting
Design For SITRANS TH400 PA
Weight Approx. 1.5 kg (3.3 lb) without Sensor Pt100 (IEC)
options
Type of connection 3-wire connection
Dimensions See "Dimensional drawings"
Unit °C
Enclosure materials • Die-cast aluminum, low in copper,
GD-AlSi 12 or stainless steel Failure mode Last valid value
• Polyester-based lacquer for GD AlSi
Filter time 0s
12 enclosure
• Stainless steel rating plate PA address 126
Electrical connection, • Screw terminals PROFIBUS Ident No. Manufacturer-
sensor connection • Cable inlet via M20 x 1.5 or ½-14 specific
NPT screwed gland
• Bus connection with M12 device For SITRANS TH400 FF
plug (optional) Sensor Pt100 (IEC)
Mounting bracket (optional) Steel, galvanized and chrome-plated Type of connection 3-wire connection
or stainless steel
Unit °C
Degree of protection IP66/67/68 according to EN 60529
Failure mode Last valid value
Auxiliary power
Filter time 0s
Supply voltage
• Standard, Ex "d", Ex "nA", Ex "nL", XP, 10.0 ... 32 V DC Node address 22
NI
• Ex "ia", Ex "ib" 10.0 ... 30 V DC
• In FISCO/FNICO installations 10.0 ... 17.5 V DC
Power consumption < 11 mA
Max. increase in power consumption < 7 mA
in the event of a fault
Certificates and approvals
Explosion protection ATEX
EC type-examination certificate ZELM 11 ATEX 0471 X
• "Intrinsic safety" type of protection II 2 (1) G Ex ib [ia Ga] IIC T6 Gb
(version: 7NG313x-1xxxx) II 2 G Ex ib IIC T6 Gb
II 1D Ex ia IIIC T100 °C Da
Conformity statement ZELM 11 ATEX 0471 X
• "Non-sparking and energy-limited II 3 G Ex ic IIC T6/T4 Gc
equipment" type of protection II 3 G Ex nA IIC T6/T4 Gc
(version: 7NG313x-2xxxx) II 3 G Ex nA [ic] IIC T6/T4 Gc
EC type-examination certificate ZELM 11 ATEX 0472 X
• "Flame-proof enclosure" type of pro- II 2 G Ex d IIC T6/T5 Gb
tection (version: 7NG313x-4xxxx) II 2 D Ex tb IIIC T100 °C Db
Explosion protection: FM for USA
• FM approval FM 3017742
• Type of protection XP, DIP, NI and S • XP / I / 1 / BCD / T5,T6; Type 4X
(version 7NG313x-5xxxx) • DIP / II, III / 1 / EFG / T5,T6; Type 4X
• NI / I / 2 / ABCD / T5,T6; Type 4X
• S / II, III / 2 / FG T5,T6; Type 4X
Other certificates EAC Ex(GOST), INMETRO, NEPSI,
KOSHA
Temperature measurement
Temperature transmitters
Field transmitters/field indicator
SITRANS TF - fieldbus transmitter
Temperature measurement
Temperature transmitters
Field transmitters/field indicator
SITRANS TF - fieldbus transmitter
Options Order code Accessories
Append suffix "-Z" to article no., add order code Article No.
and plain text, if applicable. Additional accessories for assembly, connec-
Customer-specific programming tion and transmitter configuration, see page
2/251.
Measuring range to be set Y013)
Specify in plain text (max. 5 digits):
Y01:... to ... °C, °F
SIMATIC PDM parameterization software
Also for SITRANS TH300
See section 8
2
Measuring point number (TAG) max. 8 charac- Y15 4) Mounting bracket and fastening parts
ters Made of steel for 7NG313.-..B.. 7MF4997-1AC
Measuring point description, max. 16 characters Y234) Made of steel for 7NG313.-..C.. 7MF4997-1AB
Measuring point description, max. 32 characters Y245) Made of stainless steel for 7NG313.-..B.. 7MF4997-1AJ
Specify bus address in plain text Y254) Made of stainless steel for 7NG313.-..C.. 7MF4997-1AH
Pt100 (IEC) 2-wire, RL = 0 U026) Made of stainless steel 316L for 7NG313.-..B.. 7MF4997-1AQ
Pt100 (IEC) 3-wire U036) Made of stainless steel 316L for 7NG313.-..C.. 7MF4997-1AP
Pt100 (IEC) 4-wire U046) Connection board A5E02226423
Type B thermocouple U206)7) For supply units, see Catalog FI 01 section "Supplementary components".
Type C thermocouple (W5) U216)7)
Ordering example 1
Type D thermocouple (W3) U226)7)
7NG3137-0AB01-Z Y01+Y15+Y25+U03
Type E thermocouple U236)7)
Y01: -10 ... +100 °C
Type J thermocouple U246)7)
Y15: TICA1234HEAT
Type K thermocouple U256)7)
Y25: 33
Type L thermocouple U266)7)
Type N thermocouple U276)7) Ordering example 2
Type R thermocouple U28 6)7) 7NG3137-0AC01-Z Y01+Y15+Y25+U25
Type S thermocouple U29 6)7) Y01: -10 ... +100 °C
Type T thermocouple U306)7) Y15: TICA 1234 ABC 5678
Type U thermocouple U316)7) Y25: 35
For TC: Cold junction compensation: U41 Factory setting
external (Pt100, 3-wire)
For SITRANS TH400 PA:
For TC: Reference junction compensation: Y50
external with fixed value: specify in plain text • Pt100 (IEC); 3-wire connection
Enter special deviating customer-specific set- Y098) • Unit: °C
ting in plain text • Failure mode: Last valid value
1)
Not possible with explosion protection Ex d or XP. • Filter time: 0 s - PA address: 126
2)
Option does not include ATEX/IECEx approval, only country-specific • PROFIBUS Ident No.: Manufacturer-specific
approval. For specification on TAG plate, please select Y22.
3)
For customer-specific programming for RTD and TC, the start value and For SITRANS TH400 FF:
the end value of the required measuring span must be specified here. For • Pt100 (IEC); 3-wire connection
specification on TAG plate, please select Y23.
4)
If only Y15, Y23 or Y25 is ordered and if the labeling is only noted on the • Unit: °C
measuring point plate, do not specify Y01. • Failure mode: Last valid value
5)
For this selection, Y01 or Y09 must also be selected. • Filter time: 0 s
6)
For this selection, Y01 must also be selected.
7)
• Node address: 22
Internal reference junction compensation is selected as the default for TC.
8)
For customer-specific programming, for example mV and ohm, the start
value and the end value of the required measuring span and the unit must
be entered here.
Temperature measurement
Temperature transmitters
Field transmitters/field indicator
SITRANS TF - fieldbus transmitter
■ Dimensional drawings
20 (0.79)
144 (5.67) 55 (2.17) 80 (3.15)
138* (5.43) b 100* (3.94)
52 (2.05) 28 6 2
2 50* (1.97) (1.10)
50 (1.97)
Ø 80 (3.15)
117 (4.61)
3
a
237 (9.33)
5 4
68 (2.68)
120 (4.72)
36.5 (1.44)
72 (2.83)
Temperature measurement
Temperature transmitters
Field transmitters/field indicator
SITRANS TF - fieldbus transmitter
■ Circuit diagrams
+ -
2-wire connection 1) Internal 2-wire connection 1)
cold junction compensation
+ -
+ -
2 2
+ - 2
1 1 1
+ -
Voltage measurement
2
2 + -
1 +1 -
2
1 + -
1) + -
Programmable line resistance for the purpose of correction.
Measurement of mean value, differential and
redundancy with 2 voltage sources