Three-Phase Monitoring Relays Data
Three-Phase Monitoring Relays Data
Characteristics Approvals
–– Monitoring of three-phase mains for phase sequence, A UL 508, CAN/CSA C22.2 No.14
phase failure, phase unbalance
C GL
–– TRMS measuring principle
–– Threshold value for phase unbalance is adjustable as D GOST
absolute value K CB scheme pending
–– Tripping delay Tv adjustable or switched off by means of a
E CCC
logarithmic scale (0 s; 0,1-30 s)
–– ON-delayed tripping delay L RMRS
–– Powered by the measuring circuit
–– Precise adjustment by front-face operating controls
–– Screw connection technology or Marks
Easy Connect Technology available
a CE
–– Housing material for highest fire protection classification
UL 94 V-0 b C-Tick
–– Tool-free mounting on DIN rail as well as demounting
–– 2 c/o (SPDT) contacts
–– 22.5 mm (0.89 in) width
–– 3 LEDs for the indication of operational states
Order data
Accessories
Type Description Order code
ADP.01 Adapter for screw mounting 1SVR 430 029 R0100
MAR.01 Marker label for devices without DIP switches 1SVR 366 017 R0100
COV.11 Sealable transparent cover 1SVR 730 005 R0100
–– Tool-free connection of rigid and flexible wires with –– Terminal spaces for different wire sizes:
wire end ferrule according to DIN 46228-1-A, fine‑strand with/without wire end ferrule:
DIN 46228-4-E 1 x 0.5-2.5 mm² (2 x 20 - 14 AWG),
Wire size: 2 x 0.5-1.5 mm², (2 x 20 - 16 AWG) 2 x 0.5-1.5 mm² (2 x 20 - 16 AWG)
–– Easy connection of flexible wires without wire end rigid:
ferrule by opening the terminals 1 x 0.5-4 mm² (1 x 20 - 12 AWG),
–– No retightening necessary 2 x 0.5-2.5 mm² (2 x 20 - 14 AWG)
–– One operation lever for opening both connection –– One screw for opening and closing of both cages
terminals –– Pozidrive screws for pan- or crosshead screwdrivers
–– For triggering the lever and disconnecting of wires according to DIN ISO 2380-1 Form A 0.8 x 4 mm
you can use the same tool (Screwdriver according to (0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm
DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157 (0.177 in)
in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in))
–– Constant spring force on terminal point independent
of the applied wire type, wire size or ambient
conditions (e. g. vibrations or temperature changes)
–– Opening for testing the electrical contacting
–– Gas-tight
Both the Easy Connect Technology with push-in terminals and screw connection technology with double-chamber cage
connection terminals have the same connection geometry as well as terminal position.
Operating controls
Application
The three-phase monitoring relays CM-PAS.x1 are designed for use in three-phase mains for monitoring the phase
parameters phase sequence, phase failure as well as phase unbalance.
The CM-PAS.x1 provide an adjustable ON-delay and work according to the closed-circuit principle.
Operating mode
The CM-PAS.x1 have 2 c/o (SPDT) contacts and are available for 3-wire AC systems. The units are adjusted with front-
face operating controls. Potentiometers, with direct reading scale, allow the adjustment of the threshold value for phase
unbalance (Asym %) and the tripping delay Tv. The tripping delay Tv is adjustable over a range of instantaneous to a 30 s
delay. Timing is displayed by a flashing yellow LED labelled R/T.
Adjustment potentiometer
Threshold values
By means of three separate potentiometers with direct reading scales, the threshold values for over- and undervoltage as
well as for phase unbalance can be adjusted within the measuring range.
Measuring range for phase unbalance
CM-PAS.31
2-25 % of average of phase voltages
CM-PAS.41
Tripping delay Tv
The tripping delay Tv can be adjusted within a range of 0.1 to 30 s by means of a potentiometer with logarithmic scale.
By turning to the left stop, the tripping delay can be switched off.
L1, L2, L3
2CDC 252 094 F0207
Measured value L1, L2, L3 L1, L3, L2 L1, L2, L3 L1, L2 L1, L2, L3 L1 L1, L2, L3
Ts L3 L2, L3
15-18
15-16
25-28
25-26
L1, L2, L3
Measured value
L1, L2, L3 L1, L2
Unbalance + Hysteresis
Unbalance
Ts Tv <Tv Tv
15-18
15-16
25-28
25-26
Electrical connection
L1, L2, L3 Control supply voltage = measuring voltage
L1 L2 L3
15-16/18 Output contacts - closed-circuit principle
25-26/28
L1 L2 L3 15 25
16 18 26 28
2CDC 252 037 F0008
26 25 28
16 15 18
Input circuit
Type CM-PAS.31 CM-PAS.41
Supply circuit = measuring circuit L1, L2, L3
Rated control supply voltage Us = measuring voltage 3 x 160-300 V AC 3 x 300-500 V AC
Rated control supply voltage Us tolerance -15...+10 %
Rated frequency 50/60 Hz
Frequency range 45-65 Hz
Typical current / power consumption 25 mA / 10 VA (230 V AC) 25 mA / 18 VA (400 V AC)
Timing circuit
Start-up delay Ts fixed 200 ms
Tripping delay Tv ON-delay
0 s; 0.1-30 s adjustable
Repeat accuracy (constant parameters) < w0.2 %
Accuracy within the rated control supply voltage tolerance Dt 0.5 %
Accuracy within the temperature range Dt 0.06 % / °C
User interface
Indication of operational states
Relay status / timing R/T yellow LED
Fault message F1 red LED
Fault message F2 red LED
Details see table ‚LEDs, status information and fault messages‘ on page 5 and ‚Function descriptions / diagrams‘ on page 5.
General data
MTBF on request
Duty time 100 %
Dimensions (W x H x D) product dimensions 22.5 x 85.6 x 103.7 mm (0.89 x 3.37 x 4.08 in)
packaging dimensions 97 x 109 x 30 mm (3.82 x 4.29 x 1.18 in)
Weight Screw connection technology Easy Connect Technology (push-in)
net weight CM-PAS.31 0.133 kg (0.293 lb) 0.124 kg (0.273 lb)
CM-PAS.41 0.132 kg (0.291 lb) 0.123 kg (0.271 lb)
gross weight CM-PAS.31 0.158 kg (0.348 lb) 0.149 kg (0.328 lb)
CM-PAS.41 0.157 kg (0.346 lb) 0.148 kg (0.326 lb)
Mounting DIN rail (IEC/EN 60715), snap-on mounting without any tool
Mounting position any
CM-PAS.31 CM-PAS.41
Minimum distance to other units horizontal 10 mm (0.39 in) in case of continuous voltage of ...
> 220 V > 400 V
Material of housing UL 94 V-0
Degree of protection housing IP50
terminals IP20
1) Closed-circuit principle: Output relay(s) de-energize(s) if measured value exceeds or falls below the adjusted threshold value.
Environmental data
Ambient temperature ranges operation -25...+60 °C
storage -40...+85 °C
Damp heat, cyclic (IEC/EN 60068-2-30) 55 °C, 6 cycles
Climatic category 3K3
Vibration, sinusoidal (IEC/EN 60255-21-1) Class 2
Shock (IEC/EN 60255-21-2) Class 2
Isolation data
Type
Rated insulation input circuit / output circuit 600 V
voltage Ui output circuit 1 / output circuit 2 300 V
Rated impulse withstand voltage Uimp input circuit 6 kV, 1.2/50 µs
(IEC/EN 60664) output circuit 4 kV, 1.2/50 µs
Test voltage between all isolated circuits (routine test) 2.5 kV, 50 Hz, 1 s
Basic insulation input circuit / output circuit 600 V
Protective separation input circuit /
-
(IEC/EN 61140, EN 50178) output circuit
Pollution degree (IEC/EN 60664, IEC/EN 60255-5) 3
Overvoltage category (IEC/EN 60664, IEC/EN 60255-5) III
Standards
Product standard IEC/EN 60255-6, EN 50178
Low Voltage Directive 2006/95/EC
EMC directive 2004/108/EC
RoHS directive 2002/95/EC
Technical diagrams
V V
300 300
V 200 V 200
resistive load
resistive load
100 100
80 80
60 60
50 50
40 40
30 30
20 20
2CDC 252 194 F0205
1.0
Switching cycles
0.9
0.8
F
0.7 250 V
resistive load
0.6
0.5
2CDC 252 192 F0205
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
cos ϕ
2CDC 252 148 F0206
Contact lifetime
113.4 4.47”
105.9 4.17” 22.5 0.89”
85.6 3.37”
Accessories
in mm and inches
8 0.32”
22.5 0.89” 4.8 0.19”
68 2.68”
0.453”
11.5
0.256”
62.5 2.461”
6.5
0.315”
2CDC 252 008 F0010
0.787”
3A11
8
10
20
Further documentation
You can find the documentation on the internet at www.abb.com/lowvoltage -> Control Products ->
Electronic Relays and Controls -> Three Phase Monitors.
Note:
We reserve the right to make technical changes
or modify the contents of this document without
prior notice. With regard to purchase orders, the
agreed particulars shall prevail. ABB AG does
not accept any responsibility whatsoever for
potential errors or possible lack of information in
this document.