BACnet Gateway-3 Installation Guide
BACnet Gateway-3 Installation Guide
A
Document 53372
5/6/09 Rev:
P/N: 53372:A ECN: 08-717
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of smoke detec- bedrooms), smoking in bed, and violent explosions (caused by escap-
tors, heat detectors, manual pull stations, audible warning devices, ing gas, improper storage of flammable materials, etc.).
and a fire alarm control panel with remote notification capability—can Heat detectors do not sense particles of combustion and alarm only
provide early warning of a developing fire. Such a system, however, when heat on their sensors increases at a predetermined rate or
does not assure protection against property damage or loss of life reaches a predetermined level. Rate-of-rise heat detectors may be
resulting from a fire. subject to reduced sensitivity over time. For this reason, the rate-of-
The Manufacturer recommends that smoke and/or heat detectors be rise feature of each detector should be tested at least once per year
located throughout a protected premise following the recommenda- by a qualified fire protection specialist. Heat detectors are designed to
tions of the current edition of the National Fire Protection Association protect property, not life.
Standard 72 (NFPA 72), manufacturer's recommendations, State and IMPORTANT! Smoke detectors must be installed in the same room
local codes, and the recommendations contained in the Guide for as the control panel and in rooms used by the system for the connec-
Proper Use of System Smoke Detectors, which is made available at tion of alarm transmission wiring, communications, signaling, and/or
no charge to all installing dealers. These documents can be found at power. If detectors are not so located, a developing fire may damage
[Link] the alarm system, crippling its ability to report a fire.
A study by the Federal Emergency Management Agency (an agency Audible warning devices such as bells may not alert people if these
of the United States government) indicated that smoke detectors may devices are located on the other side of closed or partly open doors or
not go off in as many as 35% of all fires. While fire alarm systems are are located on another floor of a building. Any warning device may fail
designed to provide early warning against fire, they do not guarantee to alert people with a disability or those who have recently consumed
warning or protection against fire. A fire alarm system may not provide drugs, alcohol or medication. Please note that:
timely or adequate warning, or simply may not function, for a variety
of reasons: • Strobes can, under certain circumstances, cause seizures in people
with conditions such as epilepsy.
Smoke detectors may not sense fire where smoke cannot reach the
• Studies have shown that certain people, even when they hear a fire
detectors such as in chimneys, in or behind walls, on roofs, or on the
alarm signal, do not respond or comprehend the meaning of the signal.
other side of closed doors. Smoke detectors also may not sense a fire
It is the property owner's responsibility to conduct fire drills and other
on another level or floor of a building. A second-floor detector, for training exercise to make people aware of fire alarm signals and
example, may not sense a first-floor or basement fire. instruct them on the proper reaction to alarm signals.
Particles of combustion or “smoke” from a developing fire may not • In rare instances, the sounding of a warning device can cause tempo-
reach the sensing chambers of smoke detectors because: rary or permanent hearing loss.
• Barriers such as closed or partially closed doors, walls, or chimneys A fire alarm system will not operate without any electrical power. If
may inhibit particle or smoke flow. AC power fails, the system will operate from standby batteries only for
• Smoke particles may become “cold,” stratify, and not reach the ceiling a specified time and only if the batteries have been properly main-
or upper walls where detectors are located. tained and replaced regularly.
• Smoke particles may be blown away from detectors by air outlets. Equipment used in the system may not be technically compatible
• Smoke particles may be drawn into air returns before reaching the with the control panel. It is essential to use only equipment listed for
detector. service with your control panel.
The amount of “smoke” present may be insufficient to alarm smoke Telephone lines needed to transmit alarm signals from a premise to a
detectors. Smoke detectors are designed to alarm at various levels of central monitoring station may be out of service or temporarily dis-
smoke density. If such density levels are not created by a developing abled. For added protection against telephone line failure, backup
fire at the location of detectors, the detectors will not go into alarm. radio transmission systems are recommended.
Smoke detectors, even when working properly, have sensing limita- The most common cause of fire alarm malfunction is inadequate
tions. Detectors that have photo-electronic sensing chambers tend to maintenance. To keep the entire fire alarm system in excellent work-
detect smoldering fires better than flaming fires, which have little visi- ing order, ongoing maintenance is required per the manufacturer's
ble smoke. Detectors that have ionizing-type sensing chambers tend recommendations, and UL and NFPA standards. At a minimum, the
to detect fast-flaming fires better than smoldering fires. Because fires requirements of NFPA 72 shall be followed. Environments with large
develop in different ways and are often unpredictable in their growth, amounts of dust, dirt or high air velocity require more frequent mainte-
neither type of detector is necessarily best and a given type of detec- nance. A maintenance agreement should be arranged through the
tor may not provide adequate warning of a fire. local manufacturer's representative. Maintenance should be sched-
uled monthly or as required by National and/or local fire codes and
Smoke detectors cannot be expected to provide adequate warning of should be performed by authorized professional fire alarm installers
fires caused by arson, children playing with matches (especially in
FCC Warning
WARNING: This equipment generates, uses, and can radi- Canadian Requirements: This digital apparatus does not
ate radio frequency energy and if not installed and used in exceed the Class A limits for radiation noise emissions
accordance with the instruction manual, may cause inter- from digital apparatus set out in the Radio Interference
ference to radio communications. It has been tested and Regulations of the Canadian Department of Communica-
found to comply with the limits for class A computing tions. This Class A digital apparatus complies with Cana-
device pursuant to Subpart B of Part 15 of FCC Rules, dian ICES-003.
which is designed to provide reasonable protection against Le present appareil numerique n'emet pas de bruits radio-
such interference when operated in a commercial environ- electriques depassant les limites applicables aux appareils
ment. Operation of this equipment in a residential area is numeriques de la classe A prescrites dans le Reglement
likely to cause interference, in which case the user will be sur le brouillage radioelectrique edicte par le ministere des
required to correct the interference at his own expense. Communications du Canada. Cet appareil numerique de la
classe A est conforme a la norme NMB-003 du Canada.
Acclimate Plus™, HARSH™, NOTI•FIRE•NET™, VeriFire™, NION™, NOTIFER Intergrated Systems™ and ONYXWorks™ are trademarks, and
ONYX®, FlashScan®, UniNet®, VIEW®, NOTIFIER® are registered trademarks of Honeywell. Simplex® is registered trademark of Tyco
International Ltd. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint
Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of
General Electric Company.
© 2009 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
NOTE: This manual is written with the understanding that its user is trained in BACnet operations
and services. The information provided here is solely for the configuration of the Gateway to
communicate event information to an existing BACnet network.
1.3.1 Compliance
This product has been investigated to, and found to be in compliance with the following standards.
National Fire Protection Association
• NFPA 72—National Fire Alarm Code
Underwriters Laboratories
• UL-864—Control Units for Fire Alarm Systems, Ninth Edition
• UL-2017—General-Purpose Signaling Devices and Systems, First Edition
Underwriters Laboratories Canada
• CAN/ULC-S527-99—Standard for Control Units for Fire Alarm Systems, Second Edition
1.3.2 Installation
This product is intended to be installed in accordance with the following regulatory agencies.
Local
• AHJ—Authority Having Jurisdiction
National Fire Protection Association
• NFPA 70—National Electrical Code
• NFPA 72—National Fire Alarm Code
• NFPA 101—Life Safety Code
Underwriters Laboratories
• UL-1076—In certified applications, the unit shall be installed in accordance with Proprietary
Burglar Alarm Units and Systems, Fifth Edition
Underwriters Laboratories Canada
• C22.1–98—Canadian Electrical Code, Part I (Twentieth Edition), Safety Standard for
Electrical Installation
• CAN/ULC-S524-06—Standard for the installation of Fire Alarm Systems, Fifth Edition
• CAN/ULC-S561-03—Installation and Services for Fire Signal Receiving Centres and
Systems, First Edition
WARNING: Installation
! Improper installation, maintenance, and lack of routine testing could result in system malfunction.
The contents of this manual are important and must be kept in close proximity of the hardware. If
building ownership is changed, this manual and all other testing and maintenance information must
also be passed to the current owner of the facility. A copy of this manual was shipped with the
equipment and is also available from the manufacturer.
NOTE: Refer to Appendix A, “PIC Statement”, on page 41 for the BACnet PIC statement.
1.5 Compatibility
NOTE: The BACnet GW-3 requires that at least one node on the NFN network be an ONYX
series panel. BACnet GW-3 does not run on an NFN network with no ONYX series panels.
Refer to Appendix B, “BACnet GW-3 Compatible Node Types”, on page 47 for supported panels
and annunciators.
IP connection over
Ethernet
BACnet GW-3
NUP connection
FACP
IP Network
BACnet/IP Client with Workstation Front End BACnet/IP Client with Workstation Front End
HS-NCM W/SF/MF
or
NCM W/F
BACnet GW-3
NFN Network
IP Network
Workstation/
PC Gateway
BACnet/IP Client with Workstation Front End
HS-NCM W/SF/MF
or
NCM W/F
Workstation/Echelon
Gateway
BACnet GW-3
Style 4 or 6 NION
Echelon
Network Wire NION
NFN Network or Fiber NFN Network
NION
NOTE: No HS-NCM-W/SF/MF board or NCM-W/F board is required when the BACnet GW-3
connects directly to a supported NOTIFIER® panel or annunciator when it is a standalone panel
or annunciator. Refer to “Panel Communication Connection Table” on page 47 for a list of
supported panels.
“Installing a CAB3/CAB4
Cabinet” on page 18
To Section 3, “BACnet
GW-3 Configuration”, on
page 27
Ethernet Connector
(J8)
TB6:
NO
Com Not Used
NC
TB1:
-24 V Out
+24 V Out
-24 V In
+24 V In
NOTE: The CAB3/CAB4 cabinet is ordered separately. For installation details, refer to the CAB-3/
CAB-4 Series Installation Document, 15330 and or the panel’s or annunciator’s documentation.
NOTE: Knockouts are provided on the unit so that the field wiring may be run in conduit if
required by the local authority having jurisdiction. All field wiring connections are intended to be
made at the installation wiring terminals provided as part of the unit.
1 General
All cabinets are fabricated from 16 gauge steel. The cabinet consists of two basic components: a backbox and a locking
door.
The key-locked door is provided with a pin-type hinge, two keys, and the necessary hardware to mount the door to the
backbox. The backbox has been engineered to provide ease-of-entry for the installer. Knockouts are positioned at
numerous points to let the installer bring conduit into the enclosure easily. Doors can be mounted on the left or right-hand
side. The same hinge works in both configurations, so that this choice can be made in the field. The door opens 180°.
Cabinets are available in five sizes: A through D, and AA. The outside dimensions are noted on each enclosure diagram.
“A” size accommodates one chassis, a power supply, and two 26 AH batteries; “D” size accommodates four chassis, a
power supply, and two 26 AH batteries; “AA” size holds one chassis with no compartment for batteries. A trim ring
option is available for semi-flush mounting. The CAB-3/CAB-4 Series is compatible with multiple chassis including the
CHS-M2, CHS2-M2, CHS-M3, CHS-4, CHS-4L, CHS-4N, CHS-BH, CHS-PS, CA-1, and CA-2. Note: CAB-4 series
backboxes and doors are sold separately.
the doors can be opened “barn door” style, permitting an open work
space. Note that in this type of installation it is necessary to leave
enough space between cabinets to insert a key into the locks on the
door frames.
IMPORTANT: Attach the two hinges and two alignment tabs to the
backbox before any equipment is installed. With chassis installed,
space is very limited.
Display Interface Assembly Note: When the door is left-hand
mounted, the Display Interface Assembly (DIA) dress panel cannot be
opened when the door is at less than a 120° angle to the cabinet. If you are using the left-hand mounting option, be sure
that the door can open at least 120°. This is especially important if the cabinet is to be mounted in a closed area, such as a
closet or utility room.
Grounding area
NOTE: There must be enough clearance on the right side of the printed circuit board to allow an
Ethernet cable to be connected to the Ethernet port.
NOMINAL
TB1
24 V IN
NOTE: All wiring from the power supply is power limited, and a separation of at least ¼” (6.35
mm) must be maintained between power limited and non-power limited wiring.
For specific information about power configurations involving fire alarm control panels and
network communications modules, refer to Embedded Gateway Power Connections, PN 53600.
NOTE: USB and NUP wiring connections to the HS-NCM must be located within 20 feet and
encased in conduit within the same room.
NOTE: In Canada, if the gateway is installed in a separate cabinet, the cabinet must be
connected to the Fire Alarm Control Panel (FACP) with a close nipple fitting.
RS232 (NUP)
• Line Impedance 5k ohm
• Max Distance 50 feet
Ethernet
• Line Impedance 100 ohm
• Max Distance 100 meters
USB
• Line Impedance 90 ohm ±15%
• Max Distance 40 meters
HIGH SPEED NFN NETWORKS—USE HS-NCM ONLY NFN NETWORKS—USE NCM ONLY
Use the High Speed Network Control Module circuit board Use the Control Module circuit board configuration that fits
configuration that fits your installation needs. your installation needs.
• HS-NCM-W with twisted pair wire • NCM-W with twisted pair wire
• HS-NCM-SF with single mode fiber-optic cable • NCM-F with fiber-optic cable
• HS-NCM-MF with multimode fiber-optic cable
12 Clintonville Road
Northford, CT 06472-1610 USA 12 Clintonville Road
203-484-7161 • FAX 203-484-7118 Northford, CT 06472-1653 USA
[Link] 203-484-7161 • FAX 203-484-7118
HS-NCM-W, HS-NCM-MF, HS-NCM-SF, [Link]
HS-NCM-WMF, HS-NCM-WSF, HS-NCM-MFSF Network Communications Module NCM-W/F
High Speed Network Communications Module Product Installation Document
PN 54014:A 01/23/08 07-XXX Product Installation Document
PN 51533:C 12/28/2006 06-069
1 Product Overview
The High-Speed Network Communications Module (HS-NCM) provides a means for connecting specific Notifier fire 1 UL 864 Compliance
alarm control products to High-Speed NOTI•FIRE•NET™. There are six types of HS-NCMs available: HS-NCM-W for
connecting nodes with twisted-pair wire; HS-NCM-MF and HS-NCM-SF are used for connecting nodes with fiber-optic 1.1 Products Subject to AHJ Approval
cable; HS-NCM-WMF and HS-NCM-WSF are used for connecting nodes with fiber-optic cables to nodes with twisted-
pair wire; HS-NCM-MFSF for connecting nodes with multi-mode fiber cable to nodes with single-mode fiber cable. The This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire
following UL 9th Edition equipment may be used with the HS-NCM: Alarm Systems, UL 864 9th Edition.
• NFS2-3030 The following products have not received UL 864 9th Edition certification and may only be used in retrofit applications.
• NFS2-640
Operation of the NCM-W, NCM-F with products not tested for UL 864 9th Edition has not been evaluated and may not
comply with NFPA 72 and/or the latest edition of UL 864. These applications will require the approval of the local
• NFS-320
Authority Having Jurisdiction (AHJ).
• NCA-2
• AM2020/AFP1010
• DVC
• MIB
One HS-NCM can provide network communication for up to two nodes (including fire alarm control panels and network
annunciators). • NAM-232
The HS-NCM can also be configured as a repeater. In this configuration, the HS-NCM can boost data signals between
network nodes to extend communication distances or to pass data transmissions between two differently configured 2 Product Overview
network segments when wire and fiber co-exist on a network. For limitations and network wiring information for the HS-
The Network Communications Module (NCM) provides a means for connecting specific Notifier fire alarm control
NCM in repeater mode, refer to the High-Speed Noti•Fire•Net Manual. When using the HS-NCM as a repeater, the node
address for the HS-NCM must be set to zero (default). The node address can be changed through a fire alarm control
products to NOTI•FIRE•NET™. There are two types of NCMs available: NCM-W for connecting nodes with twisted-
panel’s network programming or through VeriFire Tools. Refer to the VeriFire™ Tools CD on-line help file. pair wire, and NCM-F for connecting nodes with fiber-optic cable.
For instructions on the additional capabilities available with the DVC, refer to the DVC Manual. In most applications, one NCM is required per NOTI•FIRE•NET™ node (including fire alarm control panels and
network annunciators) . Even though the NCM has two NUP ports, only one may be connected to a NOTI•FIRE•NET™.
• Input power requirements: 24 VDC, 0.375 amps, regulated, power-limited compatible power supply UL/ULC listed node. Except in some DVC applications, do not connect two NCMs via NUP ports (aka “NUP to NUP”).
for fire protective signalling use.
• Communications circuit requirements: Refer to the High-Speed Noti•Fire•Net Manual for segment length limitations. For instructions on the additional capabilities available with the DVC, refer to the DVC Manual.
• Input power requirements: 24 VDC , 0.11 amps, regulated, power-limited compatible power supply UL/ULC listed
2 The Network Communications Module for Wire (HS-NCM-W) for fire protective signalling use.
• Communications circuit requirements: Refer to the NOTI•FIRE•NET™ Manual (Network Version 4.0 and Higher)
Channel A Channel B
• Supports twisted-pair wire medium. Connection Connection for wiring length and threshold information.
• NFPA Style 4 (Class B) operation or NFPA Style 7 USB
Connections
(Class A) operation.
• Transformer coupling provides electrical isolation EtherNet
Ground Fault Connection
between nodes. Detection
• Pluggable terminal wiring with strain relief. Switches
S1=CH. A
• Pluggable service connector (feeds signal directly S2=CH. B NUP
Ports
through) in the event that power must be removed from
a node (HS-NBB).
• Data is regenerated at each node.
• Two network ports to allow simultaneous connection to
[Link]
Figure 1 HS-NCM-W
Figure 2.7 HS-NCM Installation Document Figure 2.8 NCM Installation Document
PN 54014 PN 51533
BE SURE TO INSTALL THE CORRECT SPEED NETWORK CONTROL MODULE, BASED ON WHETHER YOU
HAVE AN NFN NETWORK OR A HIGH SPEED NFN NETWORK.
Ethernet
Customer Supplied Cable
Connector (J8)
NOTE: The Ethernet wire must be connected through the PNET-1 surge suppressor.
Step 3. Follow the displayed instructions to install the BACNet Gateway Configuration Tool.
Step 4. Record your current Internet Protocol (TCP/IP) property settings so you can restore them
later.
Step 5. Click Use the following IP address, and then type 192.168.1.X into the IP address field.
NOTE: X can be any number between 0 and 255 except for 2 (since the BACnet GW-3 default IP
address is [Link]).
Step 6. Click OK, and then close all remaining open windows.
Step 1. Launch the BACNet Gateway Configuration Tool by clicking Start Ö All Programs Ö
BACnet Gateway Config Tool from the Windows taskbar.
Step 2. Click the Address field, and then click the default gateway IP address [Link] in the
menu that drops down.
Step 4. Type the default password, 00000000, and then click OK.
NOTE: By default, the BACnet GW-3 synchronizes its internal clock with the NFN network time,
or with the Fire Alarm Control Panel in the case of a direct connection. Configuring the SNTP
server is only necessary if you want the gateway to synchronize with another server, such as an
ONYXWorks® Workstation or an SNTP time server.
Step 1. In the left pane of the BACNet Gateway Configuration Tool under the Gateway heading,
click SNTP Configuration.
Step 2. Click the SNTP Server Address field under the Value heading, and then type the address
of the SNTP server.
Configure IP Settings
Step 1. In the left pane of the BACNet Gateway Configuration Tool under the Gateway heading,
click IP Configuration.
Step 2. Click the fields under the Value heading, and type the IP, Subnet Mask, and Gateway
(router) addresses this BACnet GW-3 will use on your network.
Step 3. Click Apply to activate these settings.
Step 4. Enter the settings you recorded earlier into the Internet Protocol (TCP/IP) Properties
dialogue, and then click OK to return your configuration computer to your IP network.
Finalize the BACnet GW-3 Configuration
Log into the BACnet GW-3
Step 1. Click View Ö Refresh Gateway List to refresh the gateway address list.
Step 2. Click the Address field, and then, from the menu that drops down, click the IP address
you assigned this BACnet GW-3.
Step 4. Type the default password, 00000000, and then click OK.
The BACNet Gateway Configuration Tool now displays the remaining configurable
settings for the BACnet GW-3. Click the fields under the Value heading to enter
appropriate values, following the guidelines in the following steps.
Gateway Properties
• We recommend you select the Life Safety Notification Type if your system supports it.
Otherwise, virtually all clients support Multi State notification.
• If you are adding the BACnet GW-3 to a network that already includes another gateway or
gateways, assign the Network Number based on the highest Network Number used by any
gateway already on the network. The Network Number for the new BACnet GW-3 must be
greater than the highest Network Number by one thousand. For example, if the network
already includes a gateway with a Network Number of 1001, then the lowest Network Number
which can be assigned to the new BACnet GW-3 is 2001.
BBMD Configuration
• If the BACnet GW-3 and the Building Management System (BMS) are connected to the IP
network across different subnets, they must be connected through a BACnet Broadcast
Management Device (BBMD). When using a BBMD, set the Foreign Device value to True
and enter values for IP Address, Port and Register Time.
Multiple Gateways
• NFN networks with more than 15 nodes must be monitored using the Multiple Gateway
option.
• When using this Multiple Gateway option, set the Multiple Gateway value to True, and enter a
value for each network node to be monitored by this BACnet GW-3.
• You may enter up to 14 nodes for FACPs to be monitored, since the BACnet GW-3 can support
15 nodes including itself.
Apply Settings
Step 5. Once all BACnet GW-3 settings have been properly configured, click Apply at the bottom
of the Value pane to apply the settings and reboot the gateway.
NOTE: If you are changing settings on a BACnet GW-3 previously configured with monitored
nodes, this screen button will be labeled Apply And Delete Objects.
NOTE: The NFN network must be stable with very few events in order for the discovery process
to discover all objects upon initial configuration. After initial configuration, the BACnet GW-3
updates the network daily at its specified Network Update Time (the default time is [Link]).
It is helpful to launch the Gateway Activity window before connecting the BACnet GW-3 to an
NFN network or directly to a Fire Alarm Control Panel, so you can monitor the messages the
BACnet GW-3 generates in its initial Auto Discovery and Property Search routines. To open the
Gateway Activity window:
Step 1. Log into the BACnet GW-3 (refer to “Log into the BACnet GW-3” on page 30).
Step 2. Click View Ö Gateway Activity.
The Gateway Activity window opens. Network traffic will affect the time required to populate the
Gateway Activity window.
...to a high speed NFN network consisting exclusively of Section 3.2.1, “Connecting BACnet GW-3 to a High
High Speed compatible panels Speed NFN Network Control Module” on page 35
directly to a fire alarm control panel to be accessed Section 3.2.3, “Connecting BACnet GW-3 Directly to a
through the BACnet GW-3 Fire Alarm Control Panel” on page 38
USB cable
BACnet GW-3
HS-NCM-W/MF/SF
NUP A (J6)
USE NUP A ONLY
Connect to an HS-NCM-W/SF/MF
using NUP “A” only
NUP A (J6)
Use NUP “A” only.
Connect to an NCM-W/F,
NUP A (J6)
Use NUP “A” only.
Connect to FACP
Step 1. Log into the BACnet GW-3 (refer to “Log into the BACnet GW-3” on page 30).
Step 2. Click Tools Ö Backup Gateway.
Step 3. Navigate to where you want to store the backup file, type a name for the file, and then
click Save.
Step 3. Navigate to where the backup file (.bnk) was saved, click on the file name, and then click
Open.
(Detector) Loop 5, Detector 83: L005D083 (BACnet Life Safety Point or Multi-state Input Object)
(Zone) Zone 134: ZONE0134 (BACnet Life Safety Zone or Multi-state Input Object)
Any Node, Loop 5, Control Module 12: L005C012 (BACnet Binary Output Object)
An AM2020 as node 120: .Name = 120_AM2020 (_ denotes spaces) (BACnet Device Object)
An NCM as node 11 connected to BACnet GW: .Name = 011_ _ _ BACGW (BACnet Device Object)
(Module) Loop 9, Module 120: L009M120 (BACnet Life Safety Point or Multi-state Input Object)
(Zone) Zone 1003: ZONE1003 (BACnet Life Safety Zone or Multi-state Input Object)
(Panel Internal Devices)--LOOP 8, LOOP10, BATTERY, ANNUN021, ACPOWER, PANEL (BACnet Life Safety Point or
Multi-state Input Object)
DS-WP-B DS-WPM-B
AE-N-I-B AE-ACK-B
AE-ASUM-B AE-INFO-B
DM-DDB-B
DM-DOB-A DM-DOB-B
DM-LM-B
Segmentation Capability
• Segmented requests supported, Window Size 1024 max.
• Segmented responses supported, Window Size 1024 max.
Standard Object Types Supported - Life Safety Point/Life Safety Zone
2 IssA larm Fire A larm , S ecurity A larm (Life/P rope rty), C ritical P rocess A larm
(Life/P rope rty), M edical E m ergency
3 IssFault S ecurity Trouble, Fire Trouble, Non-Fire Trouble, Fire D evice or Zone
D isabled , Non-Fire D evice D isabled
2 IssA larm Fire A larm , S ecurity A larm (Life/P rope rty), C ritical P rocess A larm
(Life/P rope rty), M edical E m ergency
3 IssFault S ecurity Trouble, Fire Trouble, Non-Fire Trouble, Fire D evice or Zone
D isabled , Non-Fire D evice D isabled
7 IssA ctive Non-Fire A ctivation
1 E sFault S ecurity Trouble, Fire Trouble, Non-Fire Trouble, Fire D evice or Zone
D isabled , Non-Fire D evice D isabled
2 E sO ffNorm al A ll statuses other than norm al and fault.
10 Ism E nabled S et if point has bee n disabled and subsequently enabled since startup.
11 Ism D isabled Fire D evice or Zone D isab led , Non-Fire D evice D isabled
toFault
1,0,0,0 InA larm Fire A larm , S ecurity A larm (Life/P rope rty), C ritical P rocess A larm
(Life/P rope rty), M edical E m ergen , P reA larm
1,0,0,1 InA larm , O utO fService Fire D evice or Zone D isab led , Non-Fire D evice D isabled
2 IssAlarm Fire Alarm , Security Alarm (Life/Prope rty), C ritical Process A larm
(Life/P roperty), M edical E m ergency
3 IssFault S ecurity Trouble, Fire Trouble, Non-Fire Trouble, Fire D evice or Zone
D isabled, Non-Fire D evice D isabled
7 IssA ctive Non-Fire A ctivation
2 IssAlarm Fire Alarm , Security Alarm (Life/Prope rty), C ritical Process A larm
(Life/P roperty), M edical E m ergency
3 IssFault S ecurity Trouble, Fire Trouble, Non-Fire Trouble, Fire D evice or Zone
D isabled, Non-Fire D evice D isabled
7 IssA ctive Non-Fire A ctivation
1 EsFault S ecurity Trouble, Fire Trouble, Non-Fire Trouble, Fire D evice or Zone
D isabled, Non-Fire D evice D isabled
2 E sO ffNorm al All statuses other than norm al and fault.
10 Ism E nabled S et if point has been disabled and subsequently enabled since startup.
toFault
1,0,0,0 InA larm Fire Alarm , Security Alarm (Life/Prope rty), C ritical Process A larm
(Life/P rope rty), M edical E m ergen , PreA larm
1,1,0,0 InA larm , Fault S ecurity Trouble, Fire Trouble, Non-Fire Trouble
1,0,0,1 InA larm , O utO fS ervice Fire D evice or Zone D isabled, Non-Fire D evice D isabled
Networking Options:
• Select - Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-
MS/TP, etc. BACnet to Proprietary ARCnet Fire Network
• Annex H, BACnet Tunneling Router over IP
• BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign Devices?
• Yes
• Select - No
NFS-320
NFS2-640
NFS2-3030
NCM
NFS-640
NFS-3030
NOTE: This procedure is only necessary if you are configuring an BACnet GW-3 using a
Configuration computer that is not already on the same IP network as the BACnet GW-3. Refer to
“Connecting BACnet GW-3 to an IP Network” on page 23.
NOTE: A direct connection requires that a cross over Ethernet cable to be made or purchased
by the customer.
Ethernet
Customer Supplied Cable
Connector (J8)
Step 2. You have completed the connections, proceed to “Add the IP Subnet of the BACnet GW-3
into the Configuration PC” on page 28.
The cross over cable can be purchased or you can make one. Please use the following information
for the correct pinout requirements for each end of the cable. EIA/TIA wire color-code standard
568B is applicable.
1 White/Orange 1 White/Green
2 Orange 2 Green
3 White/Green 3 White/Orange
4 Blue 4 Blue
5 White/Blue 5 White/Blue
6 Green 6 Orange
7 White/Brown 7 White/Brown
8 Brown 8 Brown
D M
Data Link Layer Options 45 Max Distance 21
device Multi-state Input 7
BACnet names 40
Device Address Binding 45
Device Compatibility 8
N
Device Objects 7 NCM board 22
Network Cable Connection 35
Network Communication Module Installation 22
E Network Interface Board 15
EIA/TIA wire color-code standard 50 NFN Network Connections 23
Ethernet Normative 41
Line Impedance 21 Notification Class 45
Max Distance 21 Notification Objects 7
Ethernet cross over cable NUP
specifications 49 Line Impedance 21
Ethernet Network Max Distance 21
about 9 NUP to NUP Cable 15
NUP to NUP Cable Connection 36, 37
F
fiber-optic cable 22 O
object
G BACnet names 40
Gateway
assembly 15
P
PIC STATEMENT 41
PNET-1 15
Power Connections 20
R
Related Documentation 8
RS232
Line Impedance 21
Max Distance 21
S
Segmentation Capability 41
Serial Configuration Tool
operating system 10
Standard Object Types Supported 41
Supported - Binary Output 44
System Requirements 10
T
twisted pair wire 22
U
USB
Line Impedance 22
Max Distance 22
W
Wiring
Power 20
NOTIFIER® BACnet Gateway-3 - Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09 55
World Headquarters
12 Clintonville Road
Northford, CT 06472-1610 USA
203-484-7161
fax 203-484-7118
[Link]