AUMA Multi-Turn Actuator Operation Guide
AUMA Multi-Turn Actuator Operation Guide
SA 07.1 – SA 48.1
SAR 07.1 – SAR 30.1
AUMA NORM
ISO 9001
ISO 14001
Certificate Registration No.
12 100 4269
12 104 4269
Operation instructions
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
AUMA NORM Operation instructions
Scope of these instructions: These instructions are valid for multi-turn actuators of the type range
SA 07.1 – SA 48.1 and SAR 07.1 – SAR 30.1 in version AUMA NORM.
These operation instructions are only valid for “clockwise closing”, i.e.
driven shaft turns clockwise to close the valve.
2
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
Operation instructions AUMA NORM
Page
15. Setting the mechanical position indicator (option) 23
16. Closing the switch compartment 23
17. Enclosure protection IP 68 (option) 24
18. Applications in Ex Zone 22 (Option) 25
19. Maintenance 26
20. Lubrication 26
21. Disposal and recycling 27
22. Service 27
23. Spare parts list Multi-turn actuator SA(R) 07.1 - SA(R) 16.1 with plug/ socket connector 30
24. Spare parts list Multi-turn actuator SA 25.1 - SA 48.1/SAR 25.1 - SAR 30.1 32
25. Declaration of Conformity and Declaration of Incorporation 34
Index 35
Addresses of AUMA offices and representatives 36
3
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
AUMA NORM Operation instructions
1. Safety instructions
1.1 Range of application AUMA actuators are designed for the operation of industrial valves, e.g.
globe valves, gate valves, butterfly valves and ball valves. For other
applications, please consult us. The manufacturer is not liable for any
possible damage resulting from use in other than the designated
applications. Such risk lies entirely with the user.
Observance of these operation instructions is considered as part of the
actuator’s designated use.
1.2 Commissioning During electrical operation, certain parts inevitably carry lethal voltages.
(electrical connection) Work on the electrical system or equipment must only be carried out by a
skilled electrician himself or by specially instructed personnel under the
control and supervision of such an electrician and in accordance with the
applicable electrical engineering rules.
1.3 Maintenance The maintenance instructions (refer to page 26) must be observed,
otherwise a safe operation of the actuator is no longer guaranteed.
1.4 Warnings and notes Non-observance of the warnings and notes may lead to serious injuries or
damage. Qualified personnel must be thoroughly familiar with all warnings
and notes in these operation instructions.
Correct transport, proper storage, mounting, and installation, as well as
careful commissioning are essential to ensure a trouble-free and safe
operation.
During operation, the multi-turn actuator warms up and surface
temperatures > 60 °C may occur. Check the surface temperature prior to
contact in order to avoid burns.
The following references draw special attention to safety-relevant
procedures in these operation instructions. Each is marked by the
appropriate pictograph.
This pictograph means: Note!
“Note” marks activities or procedures which have major influence on the
correct operation. Non-observance of these notes may lead to
consequential damage.
This pictograph means: Electrostatically endangered parts!
If this pictograph is attached to a printed circuit board, it contains parts
which may be damaged or destroyed by electrostatic discharges. If the
boards need to be touched during setting, measurement, or for exchange, it
must be assured that immediately before a discharge through contact with
an earthed metallic surface (e.g. the housing) has taken place.
This pictograph means: Warning!
“Warning” marks activities or procedures which, if not carried out correctly,
can affect the safety of persons or material.
2. Short description AUMA multi-turn actuators type SA 07.1 – SA 48.1 and SAR 07.1 – SAR 30.1
have a modular design. The limitation of travel is realised via limit switches in
both end positions. Torque seating is also possible in both end positions. The
type of seating is determined by the valve manufacturer.
4
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
Operation instructions AUMA NORM
3. Technical data
Table 1: Multi-turn actuator SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
Multi-turn actuators AUMA NORM require electric controls. AUMA offers the controls AUMA MATIC AM or AUMATIC AC for
the sizes SA(R) 07.1 - SA(R) 16.1. These can also easily be mounted to the actuator at a later date.
Features and functions
Type of duty 1) Standard: SA Short time duty S2 - 15 min
SAR Intermittent duty S4 - 25 %
Option: SA Short time duty S2 - 30 min
SAR Intermittent duty S4 -50 %
Intermittent duty S5 - 25 %
Motors Standard: 3-ph AC asynchronous motor, type IM B9 according to IEC 34
Options: 1-ph AC motor, type IM B14 according to IEC 34
DC shunt motor, type IM B14 according to IEC 34
DC compound motor, type IM B14 according to IEC 34
Special motors
Insulation class Standard: F, tropicalized
Option: H, tropicalized
Motor protection Standard: Thermoswitches (NC)
Option: PTC thermistors (according to DIN 44082)
Supply voltage Refer to motor nameplate
Self-locking yes; for output speeds from 4 to 90 rpm and from size SA 35.1 for output speeds from 4 to 22 rpm
Limit switching Counter gear mechanism for end positions CLOSED and OPEN
for 1 to 500 turns per stroke (optional for 1 to 5,000 turns per stroke)
Standard: Single switch (1 NC and 1 NO) for each end position:
Options: Tandem switch (2 NC and 2 NO) for each end position; switches galvanically isolated
Triple switch (3 NC and 3 NO) for each end position, switches galvanically isolated
Intermediate position switch (DUO limit switching)
Torque switching adjustable torque switching for direction OPEN and CLOSE
Standard: Single switch (1 NC and 1 NO) for each direction
Options: Tandem switch (2 NC and 2 NO) for each direction, switches galvanically isolated
Non-intrusive setting Magnetic limit and torque transmitter MWG for the sizes SA 07.1 - SA 16.1
(option) (only possible in combination with actuator controls AUMATIC)
for 1 to 500 turns per stroke or for 10 to 5,000 turns per stroke
Position feedback signal, Potentiometer or 0/4 – 20 mA
analogue (options) For further details see separate data sheet
Torque feedback signal, Only in combination with magnetic limit and torque transmitter MWG and actuator controls
analogue (option) AUMATIC
Mechanical position Continuous indication, adjustable indicator disc with symbols OPEN and CLOSED
indicator
Running indication Blinker transmitter (for SA standard, for SAR option)
Heater in switch Standard: self-regulating PTC heater, 5 – 20 W, 110 – 250 V DC/AC
compartment Options: 24 – 48 V DC/AC or 380 – 400 V AC
A resistance type heater (5 W, 24 V DC) is installed in the actuator in combination with the
actuator controls AUMA MATIC.
Motor heater (option) SA(R) 07.1 – 10.1: 12.5 W
SA(R) 14.1 – 16.1: 25 W
SA(R) 25.1 – 30.1: 50 W
SA 35.1 – 48.1: 50 W
Manual operation Manual drive for setting and emergency operation, handwheel does not rotate during electrical
operation.
Option: Handwheel lockable
Electrical connections Standard: SA(R) 07.1 – 16.1: AUMA plug/ socket connector with screw type connection,
SA(R) 25.1 – 48.1: Control connections on AUMA plug/ socket connector,
motor connection via terminals
Option: for special motors: Motor connection directly via terminal board at the motor
Threads for cable glands Standard: Metric threads
Options: Pg-threads, NPT-threads, G-threads
Terminal plan Terminal plan according to commission number included in delivery
Output drive types A, B1, B2, B3, B4 according to EN ISO 5210
A, B, D, E according to DIN 3210
C according to DIN 3338
Special output drives: AF, AK, AG, IB1, IB3
1) Based on 20 °C ambient temperature and at an average load with running torque according to Technical data SA(R).
5
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
AUMA NORM Operation instructions
Service conditions
Enclosure protection Standard: IP 67
according to EN 60 5292) Options: IP 68
IP 67-DS (Double Sealed)
IP 68-DS (Double Sealed)
(Double Sealed = terminal compartment additionally sealed against interior)
Corrosion protection Standard: KN Suitable for installation in industrial units,
in water or power plants with a low pollutant concentration
Options: KS Suitable for installation in occasionally or permanently aggressive
atmosphere with a moderate pollutant concentration (e.g. in
wastewater treatment plants, chemical industry)
KX suitable for installation in extremely aggressive atmosphere with high
humidity and high pollutant concentration
KX-G same as KX, however aluminium-free version (outer parts)
Finish coating Standard: two-component iron-mica combination
Colour Standard: silver-grey (DB 701, similar to RAL 9007)
Option: Other colours are possible on request
Ambient temperature 3) Standard: SA - 25 °C to + 80 °C
SAR - 25 °C to + 60 °C
Options: SA - 40 °C to + 60 °C (low temperature)
- 50 °C to + 60 °C (extreme low temperature)
- 60 °C to + 60 °C (extreme low temperature)
- 0 °C to +120 °C (high temperature)
SAR - 40 °C to + 60 °C (low temperature)
Vibration resistance 2 g, for 10 to 200 Hz (only for sizes SA(R) 07.1 – SA(R) 16.1 without controls)
according to IEC 60068-2-6
Lifetime4) Type Operating cycles (OPEN–CLOSE–OPEN)
with 30 turns per stroke
SA 07.1 – SA 10.1 20,000
SA 14.1 – SA 16.1 15,000
SA 25.1 – SA 30.1 10,000
SA 35.1 – SA 48.1 5,000
Type Starts in Number of starts per hours based on S4 - 25 %, for an
millions expected lifetime of a minimum of operation hours
Other information
Reference documents Product description “Electric multi-turn actuators SA”
Dimension sheets SA(R)
Electrical data sheets SA/SAR
Technical data sheets SA/SAR
2) For 3-phase asynchronous motors in enclosure protection IP 68, higher corrosion protection KS or KX is strongly recommended. Additionally, for enclosure
protection IP 68, we recommend to use the double sealed terminal compartment DS.
For 1-phase AC motors, DC motors, or special motors, the enclosure protection according the name plate applies.
3) Versions with RWG up to max. to + 70 °C
4) The lifetime in operation hours (h) depends on the load and the number of starts. A high starting frequency will rarely improve the modulating accuracy. To
reach the longest possible maintenance and fault-free operation time, the number of starts per hour chosen should be as low as permissible for the process.
6
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
Operation instructions AUMA NORM
. hoist.
If multi-turn actuator is mounted on valve, attach ropes or hooks for the
purpose of lifting by hoist to valve and not to multi-turn actuator.
Fitting the handwheel: For transport purposes, handwheels from a diameter of 400 mm are
supplied separately.
.. Attach handwheel onto the red change-over lever on shaft (figure A-2).
Secure handwheel using the circlip supplied.
Figure A-1 Figure A-2
85°
.. a wooden pallet.
Cover to protect against dust and dirt.
Apply suitable corrosion protection agent to bright surfaces.
If multi-turn actuators are to be stored for a long time (more than 6 months),
in addition, the following points must imperatively be observed :
. Prior to storage: Protect bright surfaces, in particular the output drive parts
4.3 Packaging Our products are protected by special packaging for the transport ex works.
The packaging consists of environmentally friendly materials which can
easily be separated and recycled.
We use the following packaging materials: wood, cardboard, paper and PE
foil. For the disposal of the packaging material, we recommend recycling
and collection centres.
7
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
AUMA NORM Operation instructions
5. Mounting to valve/ gearbox . Prior to mounting the multi-turn actuator must be checked
for damage. Damaged parts must be replaced by original
. spare parts.
After mounting, check multi-turn actuator for damage to
paint finish. If damage to paint-finish has occurred after
mounting, it has to be touched up to avoid corrosion.
Mounting is most easily done with the valve shaft/ gearbox shaft pointing
vertically upward. But mounting is also possible in any other position.
The multi-turn actuator leaves the factory in position CLOSED (limit switch
CLOSED tripped).
The output drive types B1, B2, B3, or B4 (figure A-3) are delivered with bore
and keyway (usually according to ISO 5210).
Figure A-3
Output drive type B1/ B2 Output drive type B3/ B4
Plug sleeve Bore with keyway
For output drive type A (figure B-1), the internal thread of the stem nut must
match the thread of the valve stem. If not ordered explicitly with thread, the
stem nut is unbored or with pilot bore when delivered. For finish machining
..
of stem nut refer to next page.
Check whether bore and keyway match the input shaft of valve/ gearbox.
Thoroughly degrease mounting faces at multi-turn actuator and valve/
..
gearbox.
Apply a small quantity of grease to input shaft of valve/ gearbox.
Place actuator on valve/ gearbox and fasten. Fasten bolts (quality min. 8.8,
refer to table 2) evenly crosswise.
8
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
Operation instructions AUMA NORM
80.3
80.01/ 80.02
80.2
The output drive flange does not have to be removed from the actuator.
.. When fixing in the chuck, make sure stem nut runs true!
Clean the machined stem nut.
Apply Lithium soap EP multi-purpose grease to thrust bearing and races,
.. that dogs are placed correctly in the slots of the hollow shaft.
Screw in spigot ring until it is firm against the shoulder.
Press Lithium soap EP multi-purpose grease on mineral oil base into the
grease nipple with a grease gun (for quantities, refer to table):
.
Protection tube for rising valve stem
Protection tubes may be supplied loose. Seal thread with hemp, Teflon
9
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
AUMA NORM Operation instructions
6. Manual operation The actuator may be operated manually for purposes of setting and
commissioning, and in case of motor failure or power failure.
Manual operation is engaged by an internal change-over mechanism.
Engaging manual operation: . Lift up change-over lever in the centre of the handwheel to approx. 85°,
while slightly turning the handwheel back and forth until manual operation
engages (figure C).
Figure C Figure D
. Release change-over lever (should snap back into initial position by spring
action, figure D), if necessary, push it back manually.
Figure E Figure F
Disengaging manual operation: Manual operation is automatically disengaged when the motor is started
again.
The handwheel does not rotate during motor operation.
10
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
Operation instructions AUMA NORM
50.01
. (50.0).
Insert cable glands suitable for connecting cables.
(The enclosure protection stated on the name plate is only ensured if
51.01
. Connect cables according to order-related terminal plan.
The terminal plan applicable to the actuator is attached to the handwheel
in a weather-proof bag, together with the operation instructions. In case
the terminal plan is not available, it can be obtained from AUMA (state
commission no., refer to name plate) or downloaded directly from the
Internet ([Link]).
Figure G-2: Parking frame (accessory)
A special parking frame (figure G-2) for protection against touching the bare
contacts and against environmental influences is available.
Parking frame
11
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
AUMA NORM Operation instructions
7.2 Motor connection for the sizes SA(R) 25.1/SAR 30.1 – SA 48.1.
From the size SA(R) 25.1, the power for the motor is connected to separate
terminals. For this, the cover at the motor connection compartment has to
be removed.
The control contacts are connected to the AUMA plug/ socket connector.
7.4 Delay time The delay time is the time from the tripping of the limit or torque switches to
the motor power being removed. To protect the valve and the actuator, we
recommend a delay time < 50 ms. Longer delay times are possible provided
the output speed, output drive type, valve type, and the type of installation
are taken into consideration.
We recommend to switch off the corresponding contactor directly by the limit
or torque switch.
7.5 Controls made by AUMA In case the required reversing contactors are not to be installed in the
control cabinet, the controls AUMA MATIC or AUMATIC for the sizes SA(R)
07.1 – SA(R) 16.1 can be easily mounted to the actuator at a later date.
For enquiries and more information, please state our commission no. (refer
to actuator name plate).
7.6 Heater AUMA multi-turn actuators have a heater installed as standard. To prevent
condensation, the heater must be connected.
7.7 Motor protection In order to protect against overheating and impermissibly high temperatures
at the actuator, PTC thermistors or thermoswitches are embedded in the
motor winding. The thermoswitch is tripped as soon as the max. permissible
winding temperature has been reached.
12
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
Operation instructions AUMA NORM
Only the same potential can be switched on the two circuits (NC/ NO
Figure G-5 contact) of a limit or torque switch. If different potentials are to be switched
I Single switch simultaneously, tandem switches are required.
To ensure correct signalisation, the leading contacts of the tandem switches
RD
BK
must be used for that purpose and the lagging contacts for switching off.
Mechanical
RD
BK
BK 2
BK
DC
2A 0,5 A 0.4 A
(resistive load)
with gold plated
min. 5 V, max. 50 V
contacts
Current min. 4 mA, max. 400 mA
RD 2
BK 2
RD
BK
. Insert the socket carrier (51.0) into the plug cover (50.0) and fasten it with
.. screws (51.01).
Clean sealing faces at the plug cover and the housing.
. Replace plug cover (50.0) and fasten bolts (50.01) evenly crosswise.
Fasten cable glands with the specified torque to ensure the required
enclosure protection.
13
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
AUMA NORM Operation instructions
8. Opening the switch To be able to carry out the following settings (clauses 9. to 15.), the switch
compartment compartment must be opened and, if installed, the indicator disc must be
removed.
These settings are only valid for “clockwise closing”, i.e. driven shaft turns
clockwise to close the valve.
. If installed, pull off indicator disc (figure J). Open end wrench
(approx. 14 mm) may be used as lever.
RSD
RDW
Indicator disc
14
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
Operation instructions AUMA NORM
T P
B
E
C F
A D
9.2 Setting the end position OPEN (white section)
. approximately ½ a turn.
Press down and turn setting spindle D (figure K-1) with screw driver
(5 mm) in direction of arrow, thereby observe pointer E.
While a ratchet is felt and heard, the pointer E moves 90° every time.
When pointer E is 90° from mark F, continue turning slowly. When pointer
E has reached the mark F, stop turning and release setting spindle. If you
override the tripping point inadvertently (ratchet is heard after the pointer
has snapped), continue turning the setting spindle in the same direction
and repeat setting process.
9.3 Checking the limit switches The red test buttons T and P (figure K-1) are used for manual operation of
the limit switches.
.. Turning T in direction of the arrow LSC (WSR) triggers limit switch CLOSED.
Turning P in direction of the arrow LSO (WÖL) triggers limit switch OPEN.
15
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
AUMA NORM Operation instructions
T P
C F
H L
G K
10.2 Setting the direction OPEN (white section)
10.3 Checking the DUO switches The red test buttons T and P (Figure K-2) are used for manual operation of
DUO limit switches.
. Turning T in direction of the arrow TSC (DSR) triggers DUO limit switch CLOSED.
16
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
Operation instructions AUMA NORM
O P O P
. operation.
The torque switching acts as overload protection over full
travel, also when stopping in the end positions by limit
switching.
The red test buttons T and P (figure K-2) are used for manual operation of
the torque switches:
. CLOSED.
Turning P in direction of the arrow TSO (DÖL) triggers torque switch
. OPEN.
If a DUO limit switching (optional) is installed in the actuator, the
intermediate position switches will be operated at the same time.
17
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
AUMA NORM Operation instructions
S1/S2
Table 6:
Direction of rotation of the indicator disc:
counterclockwise correct
Direction of rotation of the hollow shaft:
clockwise correct
12.2 Check limit switching .. Move actuator manually into both end positions of the valve.
Check if limit switching is set correctly. Hereby observe that the
appropriate switch is tripped in each end position and released again after
the direction of rotation is changed. If this is not the case, the limit
switching must first be set, as described from page 15.
.
If no other options (clauses 13. to 15.) require setting:
Close switch compartment (see page 23, clause 16.).
18
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
Operation instructions AUMA NORM
E2
19
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
AUMA NORM Operation instructions
The position transmitter board (figure P-1) is located under the cover plate
(figure P-2).
20
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
Operation instructions AUMA NORM
Cover plate
E2
.. This ensures that the signal remains above the dead and live zero point.
Move valve to end position OPEN.
21
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
AUMA NORM Operation instructions
..
14.2 Setting the 3-/ 4- wire system 4 – 20 mA
Connect voltage to electronic position transmitter.
..
Move valve to end position CLOSED.
If installed, pull off indicator disc.
Connect ammeter for 0 – 20 mA to measuring points (figure P-2).
Cover plate
E2
.. reached.
Move valve to end position OPEN.
22
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
Operation instructions AUMA NORM
Indicator disc
Mark
23
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
AUMA NORM Operation instructions
..
following requirements according to AUMA:
Duration of submersion in water max. 72 hours
..
Head of water max. 6 m
Up to 10 operations during submersion
Modulating duty is not possible during submersion
Cable glands . For the entries of the motor and control cables appropriate, cable glands
in enclosure protection IP 68 must be used. The size of the cable glands
must be suitable for the outside diameter of the cables, refer to
. For delivery, the threads are sealed with plugs in the factory.
When ordered, cable glands can also be supplied by AUMA at an
additional charge. For this, it is necessary to state the outside diameter of
. the cables.
The cable glands must be sealed against the housing at the thread with an
. O-ring.
It is recommended to additionally apply a liquid sealing material (Loctite or
similar).
Commissioning
..
When commissioning, the following should be observed:
Sealing faces of housing and covers must be clean
..
O-rings of the covers must not be damaged
A thin film of non-acidic grease should be applied to sealing faces
Covers should be tightened evenly and firmly
24
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
Operation instructions AUMA NORM
. The connection plug may only be plugged in or pulled out when the mains
are switched off.
. The cable glands used have also to meet the requirements of category
II3D and must at least comply with enclosure protection IP 67.
. The screw plug (part no. 27) or the protection tube with cap (part nos.
160.1 and 160.2) for sealing the hollow shaft must imperatively be
mounted to guarantee the combustible dust hazard protection.
25
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
AUMA NORM Operation instructions
19. Maintenance After maintenance, check multi-turn actuator for damage to paint finish. If
damage to paint-finish has occurred, it has to be touched up to avoid
corrosion. Original paint in small quantities can be supplied by AUMA.
It is also very important that the O-rings at the covers are placed correctly
and cable glands fastened firmly to prevent ingress of dirt or water.
We recommend additionally:
. If rarely operated, perform a test run about every 6 months. This ensures
20. Lubrication .. The gear housing is filled with lubricant in the factory.
A grease change is recommended after the following operation time:
26
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
Operation instructions AUMA NORM
.. electronic scrap
.. various metals
plastics
greases and oils
.
The following generally applies:
Collect greases and oils during disassembly. As a rule, these substances
.
are hazardous to water and must not be released into the environment.
See disassembled material to a sound disposal or to separate recycling
.
according to materials.
Observe the national regulations for waste disposal.
22. Service AUMA offers extensive services such as maintenance and inspection for
actuators. Addresses of AUMA offices and representatives can be found on
page 36 and on the Internet ([Link]).
27
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
AUMA NORM Operation instructions
Notes
28
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
Operation instructions AUMA NORM
Notes
29
30
79.0
S2 S2
S2
AUMA NORM
SA16.1 50.0
SAR 16.1
160.2
S1 / S2
79.0 51.0
S2
54.0 55.0
SA 07.1 – SA 14.1 160.1
S2
SAR 07.1 – SAR 14.1 53.0 153.2
56.0 58.0
57.0 153.1
152.2
70.0 27 153.3
151.0
20.0 52.0
S1 / S2 152.1 153.0 155.0
S1 / S2
S1 / S2 39
S2
24
59.0 153.5
5.7 5.0
25.0 19.0 5.12 S2
019 17.0
020
70.1 24.0 / 23.0 5.8 9.0
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
49.0 22.0
5.37 30.0
S2 5.32
10.0
S2
053 S2
18
105.0 012
S1 / S2 1.0 6
3.0
14
80.001
156.0 107
60.0
100 80.0
106.0 90.001
80.3
61.0 S2
S2 80.001 85.001
90.0
15.0 Sample name plate 2.0
85.0
- Temperature range
Operation instructions
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
Operation instructions AUMA NORM
Notes:
When placing orders for spare parts, it is essential to mention type of actuator and our commission number (refer to
actuator name plate). Delivered spare parts may slightly vary from the representation in these instructions.
1) SA 16.1 with output speeds of 32 to 180 rpm or SAR 16.1 with output speeds of 32 and 45 rpm without
plug/ socket connector; motor directly wired to pin carrier (No. 52.0) .
2) not available for all output speeds
3) not included in basic equipment
31
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
AUMA NORM Operation instructions
24. Spare parts list Multi-turn actuator SA 25.1 - SA 48.1/SAR 25.1 - SAR 30.1
- Commission number
in CLOSE/ OPEN
- Protection type
- Works number
- Actuator type
Torque range
- Lubricant
Sample name plate
32
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
Operation instructions AUMA NORM
Notes:
When placing orders for spare parts, it is essential to mention type of actuator and our commission number (refer to
actuator name plate). Delivered spare parts may slightly vary from the representation in these instructions.
33
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
AUMA NORM Operation instructions
34
Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
Operation instructions AUMA NORM
Index
C M T
Corrosion protection 7 Maintenance 4 Tandem switches 13
Manual operation 10 Technical data 5
D
Mechanical position indicator 23 Test run 18
Declaration of Conformity 34
Motor protection 12 Thermoswitches 12
Declaration of Incorporation 34
Mounting to valve/ gearbox 8 Torque setting 17
DUO limit switching 16
Transport 7
O
E Tripping torque 17
Output drive types 8
Electrical connection 11
Electronic position transmitter RWG P
20 Packaging 7
2-wire system 21 Position indicator 23
3-/ 4-wire system 22 Position transmitter RWG 20
Enclosure protection IP 68 24 Potentiometer 19
Protection tube 9
F
PTC thermistors 12
Finish machining of stem nut 9
R
H
Remote indication 19,20
Handwheel 10
Heater 12 S
Safety instructions 4
I
Service 27
Indicator disc 23
Spare parts list 30,32
Internet 35
Storage 7
L
Limit switches 13
Limit switching 15,16
Lubrication 26
Information also available Terminal plan, inspection records, and further actuator information
on the Internet can be downloaded directly from the Internet by entering the order no.
or comm no. (refer to name plate).
Our website: [Link]
35
Europe AUMA (Schweiz) AG
CH-8965 Berikon
MEGA Endüstri Kontrol Sistemieri Tic. Ltd. Sti.
TR-06460 Övecler Ankara
Asia
AUMA Riester GmbH & Co. KG Tel +41 566 400945 Tel +90 312 472 62 70 AUMA (INDIA) PRIVATE LIMITED
Factory Müllheim Fax +41 566 400948 Fax +90 312 472 62 74 IN-560 058 Bangalore
DE-79373 Müllheim [Link]@[Link] megaendustri@[Link] Tel +91 80 2839 4655
Tel +49 7631 809 - 0 AUMA Servopohony spol. s.r.o. Fax +91 80 2839 2809
Fax +49 7631 809 - 250 CZ-10200 Praha 10 Africa info@[Link]
riester@[Link] [Link]
Tel +420 272 700056 AUMA South Africa (Pty) Ltd.
[Link] Fax +420 272 704125 ZA-1560 Springs AUMA JAPAN Co., Ltd.
Factory Ostfildern-Nellingen auma-s@[Link] Tel +27 11 3632880 JP-210-0848 Kawasaki-ku,
DE-73747 Ostfildern OY AUMATOR AB Fax +27 11 8185248 Kawasaki-shi Kanagawa
Tel +49 711 34803 - 0 FI-02270 Espoo aumasa@[Link] Tel +81 44 329 1061
Fax +49 711 34803 - 34 Tel +35 895 84022 [Link] Fax +81 44 366 2472
riester@[Link] Fax +35 895 8402300 mailbox@[Link]
A.T.E.C.
Service Centre Cologne auma@[Link] EG- Cairo AUMA ACTUATORS (Singapore) Pte Ltd.
DE-50858 Köln AUMA France Tel +20 2 3599680 - 3590861 SG-569551 Singapore
Tel +49 2234 20379 - 00 FR-95157 Taverny Cédex Fax +20 2 3586621 Tel +65 6 4818750
Fax +49 2234 20379 - 99 Tel +33 1 39327272 atec@[Link] Fax +65 6 4818269
Service@[Link] Fax +33 1 39321755 sales@[Link]
Service Centre Magdeburg [Link]@[Link] America [Link]
DE-39167 Niederndodeleben AUMA ACTUATORS Ltd. AUMA ACTUATORS INC. AUMA Middle East Rep. Office c/o Al Ayman
Tel +49 39204 759 - 0 Ind. Eqpts.
GB- Clevedon North Somerset BS21 6QH US-PA 15317 Canonsburg
Fax +49 39204 759 - 19 Tel +44 1275 871141 Tel +1 724-743-AUMA (2862) AE- Dubai
Service@[Link] Fax +44 1275 875492 Fax +1 724-743-4711 Tel +971 4 3682720
mail@[Link] mailbox@[Link] Fax +971 4 3682721
Service Centre Bavaria auma@[Link]
DE-85748 Garching-Hochbrück AUMA ITALIANA S.r.l. [Link]
Tel +49 89 329885 - 0 AUMA Chile Respresentative Office PERFECT CONTROLS Ltd.
IT-20020 Lainate Milano
Fax +49 89 329885 - 18 Tel +39 0 2 9317911 CL- La Reina Santiago de Chile HK- Tsuen Wan, Kowloon
Riester@[Link] Fax +39 0 2 9374387 Tel +56 2 8214108 Tel +852 2493 7726
info@[Link] Fax +56 2 2778478 Fax +852 2416 3763
North Office, Ship building sector joeip@[Link]
DE-21079 Hamburg [Link] aumachile@[Link]
Tel +49 40 791 40285 AUMA BENELUX B.V. LOOP S. A. DW Controls Co., Ltd.
Fax +49 40 791 40286 NL-2314 XT Leiden AR-C1140ABP Buenos Aires KR-153-803 Seoul Korea
[Link]@[Link] Tel +31 71 581 40 40 Tel +54 11 4307 2141 Tel +82 2 2113 1100
Fax +31 71 581 40 49 Fax +54 11 4307 8612 Fax +82 2 2113 1088/1089
North Office, Industry sichoi@[Link]
DE-29664 Walsrode office@[Link] contacto@[Link]
[Link]
Tel +49 5167 504 AUMA Polska Asvotec Termoindustrial Ltda.
Fax +49 5167 565 AL-ARFAJ Eng. Company W. L. L.
PL-41-310 Dabrowa Górnicza BR-13190-000 Monte Mor/ SP.
[Link]@[Link] Tel +48 32 26156 68 Tel +55 19 3879 8735 KW-22004 Salmiyah
Fax +48 32 26148 23 Fax +55 19 3879 8738 Tel +965 4817448
East Office Fax +965 4817442
DE-39167 Niederndodeleben [Link]@[Link] [Link]@[Link]
[Link] arfaj@[Link]
Tel +49 39204 75980 TROY-ONTOR Inc.
Fax +49 39204 75989 AUMA Priwody OOO BEHZAD Trading Enterprises
CA-L4N 5E9 Barrie Ontario
[Link]@[Link] RU-141400 Moscow region Tel +1 705 721-8246 QA- Doha
Tel +7 095 221 64 28 Fax +1 705 721-5851 Tel +974 4433 236
West Office Fax +974 4433 237
DE-45549 Sprockhövel Fax +7 095 221 64 38 troy-ontor@[Link]
aumarussia@[Link] behzad@[Link]
Tel +49 2339 9212 - 0 MAN Ferrostaal de Colombia Ltda.
Fax +49 2339 9212 - 15 ERICHS ARMATUR AB Sunny Valves and Intertrade Corp. Ltd.
CO- Bogotá D.C.
[Link]@[Link] SE-20039 Malmö Tel +57 1 4 011 300 TH-10120 Yannawa Bangkok
Tel +46 40 311550 Fax +57 1 4 131 806 Tel +66 2 2400656
SoutheWest Office Fax +66 2 2401095
DE-69488 Birkenau Fax +46 40 945515 [Link]@[Link]
info@[Link] [Link] sunnyvalves@[Link]
Tel +49 6201 373149
Fax +49 6201 373150 [Link] PROCONTIC Procesos y Control Automático Top Advance Enterprises Ltd.
[Link]@[Link] GRØNBECH & SØNNER A/S EC- Quito TW- Jhonghe City Taipei Hsien (235)
Tel +886 2 2225 1718
Württemberg Office DK-2450 København SV Tel +593 2 292 0431
Tel +45 33 26 63 00 Fax +593 2 292 2343 Fax +886 2 8228 1975
DE-73747 Ostfildern ta3530@[Link]
Tel +49 711 34803 80 Fax +45 33 26 63 21 info@[Link]
Fax +49 711 34803 81 GS@[Link] IESS DE MEXICO S. A. de C. V. AUMA Beijing Representative Office
[Link]@[Link] [Link] MX-C.P. 02900 Mexico D.F. CN-100029 Beijing
IBEROPLAN S.A. Tel +52 55 55 561 701 Tel +86 10 8225 3933
Baden Office Fax +86 10 8225 2496
DE-76764 Rheinzabern ES-28027 Madrid Fax +52 55 53 563 337
Tel +34 91 3717130 informes@[Link] mailbox@[Link]
Tel +49 7272 76 07 - 23 [Link]
Fax +49 7272 76 07 - 24 Fax +34 91 7427126 Multi-Valve Latin America S. A.
iberoplan@[Link]
[Link]@[Link]
D. G. Bellos & Co. O.E.
PE- San Isidro Lima 27 Australia
Power plant sector Tel +511 222 1313
GR-13671 Acharnai Athens Fax +511 222 1880 BARRON GJM Pty. Ltd.
DE-79373 Müllheim
Tel +49 7631 809 192 Tel +30 210 2409485 multivalve@[Link] AU-NSW 1570 Artarmon
Fax +30 210 2409486 Tel +61 294361088
Fax +49 7631 809 294 PASSCO Inc.
info@[Link] Fax +61 294393413
[Link]@[Link] PR-00936-4153 San Juan info@[Link]
Büro Bavaria SIGURD SØRUM A. S. Tel +18 09 78 77 20 87 85 [Link]
DE-93356 Teugn/Niederbayern NO-1301 Sandvika Fax +18 09 78 77 31 72 77
Tel +49 9405 9410 24 Tel +47 67572600 Passco@[Link]
Fax +49 9405 9410 25 Fax +47 67572610 Suplibarca
[Link]@[Link] post@[Link] VE- Maracaibo Estado, Zulia
AUMA Armaturenantriebe GmbH INDUSTRA Tel +58 261 7 555 667
2005-04-11
AT-2512 Tribuswinkel PT-2710-297 Sintra Fax +58 261 7 532 259
Tel +43 2252 82540 Tel +351 2 1910 95 00 suplibarca@[Link]
Fax +43 2252 8254050 Fax +351 2 1910 95 99
office@[Link] jpalhares@[Link]
AUMA Riester GmbH & Co. KG AUMA Riester GmbH & Co. KG ISO 9001
P. O. Box 1362 P. O. Box 1151 ISO 14001
D - 79373 Müllheim D - 73747 Ostfildern Certificate Registration No.
Tel +49 (0)7631/809-0 Tel +49 (0)711 / 34803 0 12 100 4269
12 104 4269
Fax +49 (0)7631/809 250 Fax +49 (0)711 / 34803 34
riester@[Link] riester@[Link]
[Link] [Link]
A comprehensive spare parts list is crucial for ensuring quick repair and maintenance, reducing downtime, and maintaining continuous operations. It allows maintenance personnel to swiftly identify and procure necessary components, thereby minimizing operational interruptions. For multi-turn actuators, having a detailed spare parts inventory aligns with proactive maintenance strategies and supports reliability and longevity of the equipment, critical in operations where actuator performance directly influences productivity .
Proper cable gland selection is essential to maintain IP 68 protection because it ensures a sealed connection that prevents water ingress. The correct size must match the outside diameter of the cables, and glands should be appropriately sealed with O-rings and possibly liquid sealing materials. This detail is crucial for preserving the long-term functionality and safety of actuators, especially in environments where exposure to moisture or submersion is possible, as it prevents short circuits and potential actuator failures .
Incorrect limit switch settings can lead to actuators failing to stop at designated end positions, potentially causing mechanical damage to the valve or actuator. This issue can be rectified by manually moving the actuator to both end positions and checking that the corresponding switches are tripped and reset appropriately. If discrepancies are observed, the limit switches must be reset according to the detailed instructions provided in the operation manual to ensure accurate and reliable stop points in both open and closed positions .
In Ex Zone 22 environments, factors such as ignition protection, material compatibility, and equipment certifications determine the suitability of multi-turn actuators. The actuators must be designed to prevent ignition sources in atmospheres where explosive dust can occur. Certifications confirm conformity with safety regulations. Material choice must resist corrosion and wear due to abrasive dust, ensuring durability and safety without compromising performance .
Remote position transmitters play a crucial role by providing precise operational status feedback, enabling operators to monitor actuator position without direct access. This remote capability enhances operational efficiency and safety, particularly in inaccessible or hazardous environments. The transmitters facilitate integration with broader control systems, allowing for automated adjustments and optimized performance in dynamic operational contexts. They contribute to proactive maintenance and operation monitoring by ensuring timely data transmission about the actuator's position and status .
Tandem switches in multi-turn actuators provide redundancy and reliability by ensuring backup switch operations, which enhance safety and operational continuity. They are configured to work in parallel with primary switches and are critical in applications where switch failure could lead to significant operational disruption or safety hazards. Proper configuration includes ensuring that tandem switches are tested regularly for functionality and are set to operate under the same conditions as their primary counterparts .
Maintaining enclosure protection involves ensuring sealing faces are clean, O-rings are intact, and using non-acidic grease to prevent corrosion. This practice helps maintain the integrity of the actuator against environmental factors such as dust and moisture. Regularly checking and restoring these seals prevents ingress that could lead to internal corrosion and mechanical failures, thereby significantly contributing to the long-term durability and reliable performance of the actuators .
Enclosure protection IP 68 significantly enhances the durability of multi-turn actuators in submerged conditions, allowing for a maximum submersion duration of 72 hours with water head up to 6 meters. However, modulating duty cannot be performed during submersion, and the design must prevent water entry into critical components like the hollow shaft to avoid corrosion. Hence, output drive types A and AF, which are prone to water ingress during submersion, should be avoided to prevent corrosion of thrust bearings .
Adjusting the torque on electric multi-turn actuators is critical because the set torque must match the specifications of the valve it operates. Incorrect torque settings can lead to damage or failure of the valve. As such, alterations to the set torque should only be made with the consent of the valve manufacturer, ensuring that the change is within permissible limits. This careful alignment helps prevent operational failures and potential safety hazards .
A test run involves checking the direction of rotation and verifying limit switching functionality. It ensures the actuator correctly interfaces with the valve, operates in the intended direction, and appropriately stops at both end positions. This procedure involves observing the direction of rotation using an indicator disc or the hollow shaft, ensuring correct phase sequence, and verifying whether appropriate switches are tripped at end positions. Proper execution confirms operational integrity and prepares the actuator for service .