Understanding DOL Motor Starters
Understanding DOL Motor Starters
EMTC 127
|PGPM |
2
MODULE 2: ACROSS THE LINE MOTOR STARTERS
INTRODUCTION
This module aims to provide information about the Motor Control Circuits and
Motor Controller. It contains deeper understanding about the direct on line motor
starter and motor controller and circuits for greater familiarization of the topic. This
module is a consolidated information in which the limit switches and how could it
help the students to make and analyze a diagram. The intent of this module the
reader to analyze and construct a diagram by familiarizing the motor controller and
circuits.
OBJECTIVES
To be familiarized with the design of the control circuit diagram and
wiring circuit diagram of the direct on line motor starter.
Learners will able to perform actual board wiring activity on the
reduced voltage motor starter.
Will able to troubleshoot possible defects and circuit faults of the
motor controller.
To be familiarized with the control circuit diagram and wiring circuit
diagram designing of the reduced voltage motor starter.
Learners will able to perform actual board wiring activity about the
manual and magnetic motor starter.
Will able to troubleshoot possible defects and circuit faults of the
motor controller.
To discuss cautions that must be observed in reversing circuits
Will explain how to reverse a three-phase motor
Will discuss interlocking methods
DIRECTIONS
The module contains five (5) lessons. Read carefully the different topics given
in this module. Understand each process if there are, carefully direct on line (DOL)
motor starter, limit switches/contact sensors, manual & magnetic motor starter and
motor controller. Answer carefully the given exercises at the end of the discussion.
If there are something that is hard for a student to understand, you may ask
questions to the faculty. Inquiries and clarification will be given for greater learning
development.
|PGPM |
3
MODULE 2: ACROSS THE LINE MOTOR STARTERS
LESSON 1
|PGPM |
4
MODULE 2: ACROSS THE LINE MOTOR STARTERS
the start cycle, the motor will stops accelerating. If the starting torque with
a DOL starter is insufficient for the load, the motor must be replaced with a
motor which can develop a higher starting torque.
The acceleration torque is the torque developed by the motor minus the load
torque, and will change as the motor accelerates due to the motor speed
torque curve and the load speed torque curve. The start time is dependent
on the acceleration torque and the load inertia.
DOL starting have a maximum start current and maximum start torque
This may cause an electrical problem with the supply, or it may cause a
mechanical problem with the driven load. So this will be inconvenient for
the users of the supply line, always experience a voltage drop when starting
a motor. But if this motor is not a high power one it does not affect much
NO-normally open
NC-normally closed
|PGPM |
5
MODULE 2: ACROSS THE LINE MOTOR STARTERS
|PGPM |
6
MODULE 2: ACROSS THE LINE MOTOR STARTERS
|PGPM |
7
MODULE 2: ACROSS THE LINE MOTOR STARTERS
|PGPM |
8
MODULE 2: ACROSS THE LINE MOTOR STARTERS
|PGPM |
9
MODULE 2: ACROSS THE LINE MOTOR STARTERS
LEARNING ACTIVITY 2. 1
1. How does a Direct On Line Motor Starter work? Prove your answer
in a minimum of 70 words.
2. Explain the Wiring Diagram of Direct On Line Starter based on
your understanding in a minimum of 100 words.
3. As a student, Is it important to memorize the number of the
connection or the contacts? Why? Prove your answer in a minimum
of 70 words.
|PGPM |
10
MODULE 2: ACROSS THE LINE MOTOR STARTERS
LESSON 2
LIMIT SWITCHES
Limit switches consist of an actuator with operating head, the switch body
mechanism, and a series of electrical terminals that are used to connect the
switch to the electrical circuit that it is controlling. The operating head is the
part of the limit switch that comes in contact with the target. The actuator
contains is connected to the operating head, whose linear, perpendicular, or
rotary motion is then translated by the actuator to close or open the switch.
The switch body contains the switch contact mechanism whose state is
controlled by the actuator. The electrical terminals are connected to the
switch contacts and enable wires to be joined to the switch through terminal
screws.
Industrial machinery that undergoes automatic operations usually requires
control switches that activate according to the movements involved in a
machine’s performance. For repeat usage, the accuracy of the electrical
switches needs to be reliable and their response rate should be prompt. Due
to the mechanical specifications and performance parameters of different
|PGPM |
11
MODULE 2: ACROSS THE LINE MOTOR STARTERS
Control schematics for limit switches usually display a limit switch symbol to
indicate the state of the switch contacts. The most common contact symbols
show whether the device has normally open or normally closed limit switch
contacts. The symbol for a “normally open held closed” state indicates that
the contact has been wired as a normally open contact, but when the circuit
is put into its normal off state, part of the machine keeps the contact closed.
Likewise, a limit switch that is designated as “normally closed held open” will
have a closed wiring design but be held open. Other types of contacts, such
as those used in pressure and flow switches, can be configured in a similar
way.
|PGPM |
12
MODULE 2: ACROSS THE LINE MOTOR STARTERS
Limit switches also have several limitations, which means they may not be suited
for every application:
Because they rely on mechanical action, they generally are used in equipment
that operates at relatively low speeds
They are contact sensors, meaning they must make physical contact with the
target for them to operate
The nature of their mechanical design means that the devices are subject to
mechanical wear or fatigue over time and will need eventual replacement
There are several key terms that are associated with the design of limit switches.
Here is a brief summary of those terms for reference:
|PGPM |
13
MODULE 2: ACROSS THE LINE MOTOR STARTERS
In the case of the lever type limit switch, the actuating arm is a rod connected
to a lever shaft which is free to rotate when the rod is dislocated.
When the forces displaying rod are removed, the lever shaft is returned to its
normal state by a return spring.
The lever shaft has a roller mounted on its bottom, which rotates a rocker as
it changes its position from right side to left side.
The mechanical action operates one are more contacts which are mounted on
the other side of the limit switch as shown in the above figure.
The electrical contact may be open or close initially. The action of the
actuator and lever arms takes it from one state to the other state.
Hence normally open limit switch will be closed and when activated and the
closed switch will be open when actuated.
|PGPM |
14
MODULE 2: ACROSS THE LINE MOTOR STARTERS
In the push type limit switch in the above figure, the contact gets operated
from the depression of the contact lever arm.
Rotary limit switches are preferred where the adjustment of limits of travel
is required frequently.
In this case the once the limit switch is fixed, only very little adjustment is
possible by adjusting the lever position.
Momentary contact
Maintained contact
|PGPM |
15
MODULE 2: ACROSS THE LINE MOTOR STARTERS
Momentary Contact
When the target comes in contact with the actuator arm, it makes to move
the actuator from the free position to the operating position.
At this point, the electrical contacts also change the state. When the target
moves away, the actuating arm and also the contacts become normal.
Maintained Contact
|PGPM |
16
MODULE 2: ACROSS THE LINE MOTOR STARTERS
Advantages
Disadvantages
Applications
LEARNING ACTIVITY 2. 2
|PGPM |
17
MODULE 2: ACROSS THE LINE MOTOR STARTERS
LESSON 3
Manual motor starters are electromechanical protection devices for the main
circuit. They are used mainly to switch motors manually ON/OFF and to
provide fuse less protection against short-circuit, overload and phase failures.
Fuse less protection saves costs, space and ensures a quick reaction under
short-circuit condition by switching off the motor within milliseconds. Starter
combinations are setup together with contactors.
A manual motor starter is package consisting of a horsepower rated switch
with one set of contacts for each phase and corresponding thermal overload
devices to provide motor overload protection.
The main advantage of a manual motor starter is lower cost than a magnetic
motor starter with equivalent motor protection but less motor control
capability.
Manual motor starters are often used for smaller motors - typically fractional
horsepower motors but the National Electrical Code allows their use up to 10
Horsepower.
Since the switch contacts remain closed if power is removed from the circuit
without operating the switch, the motor restarts when power is reapplied
which can be a safety concern.
They do not allow the use of remote control or auxiliary control equipment
like a magnetic starter does.
Main Benefits:
|PGPM |
18
MODULE 2: ACROSS THE LINE MOTOR STARTERS
Main Features:
These devices are mainly used to switch motors manually on/ off and protect
them against short-circuit, overload and phase failures. Fuse less protection
with a manual motor starter saves costs, space and ensures a quick reaction
under short-circuit condition, by switching off the motor within milliseconds.
|PGPM |
19
MODULE 2: ACROSS THE LINE MOTOR STARTERS
Customer benefit
Compact design / space saving
Various functions in one device
Quick reaction / fast current limitation
Motor protection concept for the world market (IEC, UL)
Safe and cost-saving solution
How Does a Manual Motor Starter Work?
Manual motor starters are the simplest kind of motor starter and consist of an
on/off switch and an overload relay. They are, as their name suggests,
operated manually. A button, toggle, or rotary switch mounted directly on
the starter is pressed to start or stop the connected electrical equipment.
Mechanical linkages from the buttons or toggle force the contacts to open and
close, starting and stopping the motor.
In the manual motor starter, the capacitor and coils present in the motor will
control the direction on a single-phase induction motor. If the motor reaches
a specific speed, the built-in starter winding starts to produce a click sound.
Manual motor starters give motors overload protection. They make sure that
the required amount of current passes to the motor and help with the
temperature control in the motor.
All motor starters share certain power control functions. They are rated by
current (amperes) or power (horsepower) and have remote on/off control and
motor overload protection. They have plugging and jogging functions that
rapidly make or break a current.
A self-protected starter is a variation of the manual starter and is often used
in multiple-motor control panels. The control panels have low-level,
instantaneous overcurrent protection which lets a single upstream short-
circuit-protection device protect several starters. This means the motors
don’t need individual short-circuit protection. These manual starters can be
used on both single and three-phase motor loads.
|PGPM |
20
MODULE 2: ACROSS THE LINE MOTOR STARTERS
Considerations
Manual motor starters are limited to the size motor they can start, starting
at the fractional HP levels and usually extending up to a maximum of 10-15
HP, depending on voltage. They tend to be used with equipment that is
started infrequently or which run continuously with few stops. Beyond there,
specifiers need to consider magnetic starters or even soft starters. Special
cases such as reversing or multi-speed service are addressed by application-
specific styles. Other considerations beyond motor size and voltage include
what looking at the applications and looking into options such as explosion-
proof, enclosure ratings, and fuse or breaker protected.
LEARNING ACTIVITY 2. 3
1. Can I use the Manual Motor Starter on a single phase motor? Why?
2. Can the Manual Motor Starter be used alone or only with a contactor?
3. Explain the difference between manual motor starters that provide
low voltage release and those that do not.
|PGPM |
21
MODULE 2: ACROSS THE LINE MOTOR STARTERS
LESSON 4
1. Power Circuit: The power circuit connects the line to the motor. It provides
transmission of electricity through the starter contacts, overload relay, and then to
the motor. The motor current is carried by the power (main) contacts of the
contactor.
2. Control Circuit: This is the other motor starter circuit, which operates the contactor
to turn it on or off. The contactor main contacts are responsible for allowing or
interrupting the flow of current to the motor. To do this, the contacts in the control
circuit are either opened or closed. The control circuit energizes the contactor coil,
which creates an electromagnetic field. The power contacts are pulled by this
electromagnetic field to a closed position. This completes the circuit between the
motor and the line. This way, remote operations are made possible by the control
circuit.
|PGPM |
22
MODULE 2: ACROSS THE LINE MOTOR STARTERS
1. Method 1: One of the most widely used methods employed for wiring the control
circuit is referred to as the “Two-wire method”. A maintained contact type of pilot
device like presence sensor, thermostat, or float switch is used in the two-wire
method of wiring the control circuit.
2. Method 2: Unlike the two-wire method, the “Three-wire method” of wiring the
control circuit uses a holding circuit contact and the momentary contact pilot
devices.
The control circuit can derive the power from either of the following three ways:
Common Control: This type of control is when the power source of the
control circuit is the same as the motor.
Separate Control: This is the most popular type of control. As the name
suggests, the control circuit derives power from a
separate source in this arrangement. Generally, the power
derived is lower in voltage as compared to the motor’s
power source.
Transformer Control: As the name suggests, the control circuit derives power
from a control circuit transformer. Generally, the power
derived is lower in voltage as compared to the motor’s
power source.
Depending on how they are connected in a circuit, there are many types of magnetic
motor starters, such as:
1. Direct-On-Line Starter
The direct-on-line starter is the simplest form of motor starter, other than a
manual starter. The controller of this starter is typically a simple push button
(but could be a selector switch, limit switch, float switch, etc.). Pressing the
start button closes the contactor (by energizing the contactor coil) connected
to the main supply and motor. This provides the supply current to the motor.
To turn the motor off, a stop button is provided. To protect it from over
current, the control circuit is wired through a normally closed auxiliary
contact of the overload relay. When the overload relay trips, the normally
closed auxiliary contact opens, and de-energizes the contactor coil, and the
contactor main contacts open.
|PGPM |
23
MODULE 2: ACROSS THE LINE MOTOR STARTERS
In the rotor resistance starter, the three resistances are connected such that
they are in series with the rotor windings. This helps reduce the rotor current
considerably, as well as increases the motor torque.
|PGPM |
24
MODULE 2: ACROSS THE LINE MOTOR STARTERS
|PGPM |
25
MODULE 2: ACROSS THE LINE MOTOR STARTERS
Compared to the other types of starters, the star delta starter is used on a
large scale. As the name suggests, the three windings are connected in a star
connection in the star delta starters. A certain time is set by the timer or any
other controller circuit. After this time is passed, the windings are then
connected in the delta connection. The phase voltage in the star connection
is reduced to 58%, and the total current drawn is 58% of normal current. This
results in a reduced torque.
|PGPM |
26
MODULE 2: ACROSS THE LINE MOTOR STARTERS
The power rating of the motor starter is based on the type of motor used. DC
motor starters have ratings for DC horsepower. On the other hand, AC motor
starters have a single-phase power and three-phase power rating.
|PGPM |
27
MODULE 2: ACROSS THE LINE MOTOR STARTERS
The rating of the motor starter is based on the size and type of load for which
it was designed. Starters conform to the standards and ratings from
Underwriters Laboratories (UL), Canadian Standards Association (CSA),
International Electrotechnical Commission (IEC) and National Electrical
Manufacturers Association (NEMA).
NEMA Rating
The NEMA ratings of a starter depends largely on the maximum horsepower
ratings given in the National Electrical Manufacturers Association ISCS2
standard. The selection of the NEMA starters is done on the basis of their
NEMA size, which varies from Size 00 to Size 9.
The NEMA starter, at its stated rating, can be used for a wide range of applications,
ranging from simple on and off applications to plugging and jogging applications,
which are more demanding. It is necessary to know the voltage and horsepower of
the motor when selecting the proper NEMA motor starter. In the case where there
is a considerable amount of plugging and jogging involved, then derating a NEMA-
rated device will be required.
IEC Rating
The International Electrotechnical Commission (IEC) has specified the
operational and performance characteristics for IEC devices in the publication
IEC 60947. Standard sizes are not specified by the IEC. The typical duty cycle
of IEC devices are defined by utilization categories. As far as general motor
starting applications are concerned, the AC3 and AC4 are the most common
utilization categories.
Unlike NEMA sizes, they are typically rated by their maximum operating
current, thermal current, HP and/or kW rating.
There are other parameters that are important to consider, while selecting
motor starters, such as time-limit acceleration, current-line acceleration,
control voltage, number of poles, and operating temperature. We will cover
those in a future white paper.
|PGPM |
28
MODULE 2: ACROSS THE LINE MOTOR STARTERS
LEARNING ACTIVITY 2. 4
1. If magnetic coils are powered by AC, why don’t their contacts open
and close 120 times per second?
2. Based on your own understanding, differentiate the five (5) types
of Magnetic Motor Starter in a minimum of 150 words.
|PGPM |
29
MODULE 2: ACROSS THE LINE MOTOR STARTERS
LESSON 5
CONTROL CIRCUIT
A control circuit is a special type of circuit used to control the operation of a
completely separate power circuit. Consider a 1,000 horsepower, large
industrial motor driving a water pump. The motor is connected to a high
voltage electrical supply of 2,400 volts.
When this motor is energized, it must draw enough current to get the water
moving and it is common for a motor to draw about six times its normal
operating current for a short period of time. When we were talking about
controlling light bulbs, it was safe to operate a simple switch on the wall. But
now this large amount of current flowing when the motor starts can be
troublesome. The first concern is the operator's ability to safely close the
switch. The second concern is that when the operator opens the switch to
turn the motor off, the electricity will continue to try to complete the path.
This will tend to arc between the contacts of the switch as it is opened. This
arcing is not only dangerous but also damages the switch by severely burning
the contact points. A control circuit is used to ensure that the motor is started
and stopped in a safe manner for both the operator and the equipment.
POWER CIRCUIT
A power circuit is defined as any circuit used to carry electricity that operates
a load. This may seem like a simplistic definition but it is important to
distinguish power circuits from control circuits since they serve different
purposes.
A circuit with an outlet for the source, two wires for the path, a switch for
the control device and a motor for a load is a good illustration of a power
circuit. When the switch is closed, the electrons flow through the path and
the electrons go directly through the motor windings and cause the motor to
operate. The only circuit control in this circuit is the switch wired directly in
series with the motor. There is no separate control circuit associated with
this power circuit. Most lighting and receptacle outlet circuits in a house are
power circuits since they only provide power to devices when the devices
operate, and the circuit control is part of the power circuit.
Start-Stop Motor Control
The most common use of 3 wire control is a Start/Stop control. See
image below for an example of 3 wire contro l being used to pull in
a contactor to start a 3 phase motor. When you press the start
button and the stop button is not pressed, the 24VDC relay energizes
|PGPM |
30
MODULE 2: ACROSS THE LINE MOTOR STARTERS
and it pulls in the R1 contactor that feeds three phase power to the
motor. It also pulls in a conta ct that is tied in parallel with the start
button giving it another path for current flow once your release the
start button. This "latches" the relay until the stop button is
pressed.
|PGPM |
31
MODULE 2: ACROSS THE LINE MOTOR STARTERS
The term jogging is often used when referring to full voltage starting of loads;
the term inching can be used to refer to reduced voltage starters. Generally,
the terms are used interchangeably because they both prevent a seal-in
circuit from being used.
|PGPM |
32
MODULE 2: ACROSS THE LINE MOTOR STARTERS
There are many ways to develop a jog control circuit. In designing a jog it is
important to remember the overall outcome is to make a load operate during
the duration of the start button being activated. This means the control
circuit is designed so there is no way for the load to become energized and
stay energized through the memory/seal-in contact.
One of the jog circuit designs is the two-circuit pushbutton. The circuit will
operate as a normal three wire circuit if the start /stop pushbuttons are used.
Pressing the jog button creates a current path directly to the load bypassing
the seal-in of the control circuit. However, the potential danger can exist
because the jog button can potentially become the active seal-in causing the
load to stay on without the assistance of someone pressing the pushbutton. If
it is possible to eliminate using pushbuttons that make and break the control
circuit at the same time in the same circuit.
|PGPM |
33
MODULE 2: ACROSS THE LINE MOTOR STARTERS
|PGPM |
34
MODULE 2: ACROSS THE LINE MOTOR STARTERS
Fig. 2 Magnetic reversing starters generally change T leads 1 and 3 to reverse the
motor
|PGPM |
35
MODULE 2: ACROSS THE LINE MOTOR STARTERS
Interlocking
Interlocking prevents some action from taking place until some other action
has been performed. In the case of reversing starters, interlocking is used to
prevent both contactors from being energized at the same time.
This would result in two of the three phase lines being shorted together.
Interlocking forces one contactor to be de-energized before the other one can
be energized.
There are three methods that can be employed to assure interlocking. Many
reversing controls use all three.
Mechanical Interlocking
Most reversing controllers contain mechanical interlocks as well as electrical
interlocks. Mechanical interlocking is accomplished by using the contactors to
operate a mechanical lever that prevents the other contactor from closing
while one is energized. Mechanical interlocks are supplied by the
manufacturer and are built into reversing starters. In a schematic diagram,
mechanical interlocks are shown as dashed lines from each coil joining at a
solid line.
Electrical Interlocking
Two methods of electrical interlocking are available. One method is
accomplished with the use of double acting push buttons (Ill. 6). The dashed
lines drawn between the push buttons indicate that they are mechanically
connected. Both push buttons will pushed at the same time. The normally
closed part of the FORWARD push button is connected in series with R coil,
and the normally closed part of the REVERSE push button is connected in
series with F coil. If the motor should be running in the forward direction and
the REVERSE push button is pressed, the normally closed part of the push
button will open and disconnect F coil from the line before the normally open
part closes to energize R coil. The normally closed section of either push
button has the same effect on the circuit as pressing the STOP button.
|PGPM |
36
MODULE 2: ACROSS THE LINE MOTOR STARTERS
|PGPM |
37
MODULE 2: ACROSS THE LINE MOTOR STARTERS
LEARNING ACTIVITY 2. 5
|PGPM |
38
MODULE 2: ACROSS THE LINE MOTOR STARTERS
SUMMATIVE TEST
SUMMARY
In this module, the Across the line motor starters were discussed. As a brief
information about this, a direct on line (DOL) or across the line starter applies the
full line voltage to the motor terminals. This is the simplest type of motor starter.
A DOL motor starter also contains protection devices, and in some cases, condition
monitoring. The module indicates the different fundamentals of the following Across
the line motor starters that will give idea to students before proceeding to the
deeper knowledge.
Switches/ Contact Sensors are also discussed in module to that aimed to give greater
understanding in schematic diagrams. This will also help students to conceptualize
their own flow and brainstorm on how these contact be interrelated to each other.
This handout also modulates the difference between the manual motor starters and
the magnetic motor starters that involves a brief description of their usage,
importance and to know the things that necessitates them. Motor Control Circuits
are those the ones being described here and will give you emphasize every area of
the lesson.
|PGPM |
39
MODULE 2: ACROSS THE LINE MOTOR STARTERS
A motor starter turns an electric motor on or off while providing overload protection.
There are two main types of starters manual and magnetic. In smaller sizes, a motor
starter is a manually operated switch. Low-voltage protection (LVP), which prevents
automatic restarting after a power failure, is usually not possible with a manual
starter. Larger motors, or those requiring remote or automatic control, use magnetic
contactors. Very large motors running on medium voltage power supplies may use
power circuit breakers
REFERENCES
[Link] (2021). Industrial Control Basics: Motor Control Starters & Magnetic
Motor Starter. Retrieved from: [Link]
paper/industrial-control-basics-motor-starters/
TW [Link] (2020). Control, Wiring – 3 Wire control – Start Stop Circuit.
Retrieved from: [Link]
start-stop-circuit
Apogee Interactive Incorporated (2021). Types of Circuit – Power Circuit. Retrieved
from:[Link]
spc=foe&id=4704
Electrical [Link] (2020). Start Stop Jog Circuit | Motor Control Circuit Diagram.
Retrieved from: [Link]
motor-control-circuit-diagram/
[Link] (2005). Electrical Engineering and Science for
Manufacturing Applications. Retrieved from: [Link]
[Link]/ind-mtr-cntrl_029.html
All About Circuits (2021). Motor Control Circuits. Rohde and Schwarz Technology
Symposium 2021. Retrieved from:
[Link]
circuits/
[Link] (2021). Limit Switch Characteristics. Retrieved from:
[Link]
|PGPM |