SERVICE ENTRANCE CAP
SERVICE ENTRANCE
INCANDESCENT LIGHTING FIXTURE / DOWNLIGHT
PIN LIGHT
ELECTRICAL NOTES &
WALL MOUNTED LIGHT (WEATHER PROOF) SPECIFICATIONS:
DECORATIVE CIRCULAR LAMP
CHANDELIER LIGHTING FIXTURE
· ALL ELECTRICAL WORKS CONTAINED
DOUBLE CONVENIENCE OUTLET HEREIN SHALL CONFORMED WITH THE
ACU
AIR CONDITIONING UNIT OUTLET LATEST PROVISIONS OF THE PHILIPPINE
60 A WP ELECTRICAL CODE, THE RULES AND
DOUBLE CONVENIENCE OUTLET (WEATHER PROOF)
RANGE
REGULATIONS OF THE LOCAL POWER
20A 20A RANGE HOOD OUTLET UTILITIES AND THE LOCAL TELEPHONE
L.O. ckt 1 ckt 2 L.O. REF
REFRIGERATOR OUTLET COMPANY.
WH
20A 20A WATER HEATER UNIT OUTLET
· TYPES OF WIRING TO BE USED SHALL
C.O.ckt 3 ckt 4 C.O. S1
SINGLE GANG SWITCH BE RIGID STEEL CONDUIT (RSC )
S2
DOUBLE GANG SWITCH
AND POLYVINYL CHLORIDE
30A 30A
( PVC ) CONDUIT PIPE.
SPARE ckt 5 6 SPARE S3
TRIPLE GANG SWITCH
ckt
S3W
THREE WAY SWITCH · ELECTRICAL EQUIPMENTS, DEVICE,
. # CIRCUIT HOMERUN TO PANEL BOARD
FIXTURES TO BE USED SHALL BE NEW
CKT
AND HIGH QUALITY AND APPROVED
DB DISTRIBUTION BOARD/PANEL BOARD TYPES FOR THE LOCATION AND
GROUND M KILOWATT HOUR METER
PURPOSED.
· WATER PUMPS SHALL BE PROVIDED
RISER DIAGRAM LEGENDS AND SYMBOL WITH APPROVED TYPE AND BRAND OF
MAGNETIC STARTER AND ON/OFF
scale: NTS
scale: 1:100m PUSH BOTTON SWITCH.
· CONDUITS RUN ARE ONLY SCHEMATIC,
ACTUAL RUN SHALL BE DETERMINED IN
THE FIELD.
SCHEDULE OF LOADS PER UNIT:
· CONDUITS SHALL BE EMBEDDED AT 2"
CIRCUIT SOCKET OVER CURRENT SIZE OF WIRE CONDUIT TOTAL: COMPUTATIONS PER UNIT: FROM THE CONCRETE FLOORS, WALLS
DESCRIPTION V/A VOLT AMP OR COLUMNS FINISH EXCEPT THOSE RUN
NO. OUTLET PROTECTIVE DEV. THHN/THWN SIZE SOCKET I = P / V (80%) D.F.
OUTLET TERMINATING AT BOXES OR ENCLOSURES.
1 LIGHTING OUTLETS 12 200 220 0.90 2P, 15AT, 220V CB 2.0 mm² 20 mmØ I = (560 / 220V (0.8)
2 CONVENIENCE OUTLETS 8 360 220 1.63 2P, 30AT, 220V CB 3.5 mm² 20 mmØ V/A 560 I =2.03 AMPS. · ALL CONDUITS AND METAL FRAMES OR
AMP 2.53 EQUIPMENT SHALL BE PROPERLY GROUNDED
AND BONDED TOGETHER BY MEANS OF
FOR SUB MAIN WIRE USE: COPPER STRAPS AND SHALL BE CONNECTED
TO THE MAIN WATER PIPE LINE.
2 - 38mm² THHN/THWN CU.WIRE IN
#8 dia RSC/16mm dia IMC
· THERE SHALL BE ONLY ONE SERVICE DROP
TO A BUILDING.
FOR SUB MAIN BREAKER USE:
· THE WORK HEREUNDER SHALL BE UNDER
2P, 40AT, PLUG-IN TYPE, 10 KAIC, 220V C.B.
THE DIRECT SUPERVISION OF A LICENSED
ELECTRICAL ENGINEER OR MASTER
ELECTRICIAN
ALL WORKS SHALL BE DONE IN NEAT &
WORKMANLIKE MANNER.
SCHEDULE OF LOADS AND COMPUTATION
scale: 1:100m
PREPARED FROM THE OFFICE OF : R.A. 9266 PROFESSIONAL ELECTRICAL ENGINEER OWNER : PROJECT TITLE : SHEET CONTENTS : REVISIONS : SHEET NO . :
DRAWING SPECIFICATIONS DULY SIGNED, SYMBOL DESCRIPTION DATE
STAMPED OR SEALED AS INSTRUMENT OF SERVICE,
ARE INTELLECTUAL PROPERTIES AND DOCUMENTS
E
OF THE ARCHITECT WHETHER THE OBJECT FOR
WHICH
THEY ARE MADE IS EXECUTED FOR ANY PERSON
# 179 Alejo St. Poblacion East, Asingan, Pangasinan WITHOUT THE CONSENT OF THE ARCHITECT OR
2 2
[email protected]. AUTHOR OF SAID DOCUMENTS, TO DUPLICATE OR
TO PRC. NO. : VALIDITY.
MAKE COPIES OF SAID DOCUMENTS FOR USE
IN THE REPETITION OF AND FOR OTHER PROJECTS PTR NO. : DATE ISSUED :
OR BUILDING ADDRESS : ADDRESS :
WHETHER PARTLY OR IN WHOLE. TIN :