Column Designs Calculation Excel File
Column Designs Calculation Excel File
info
Capacity of the Rectangular Column is: 478.0152 Kip USD Tie Design
272.34 Kip WSD
Rect. Col: WSD: use: # 3 bar @ 10 in C/C Square. Col: WSD: use: # 3 bar @ 10 in C/C
Capacity of the Circular Column is : 218.5695525
Kip USD Rect. Col: USD: use: # 3 bar @ 10 in C/C Square. Col: USD : use: # 3 bar @ 10 in C/C
129.2775 Kip WSD
Calculations
Factored Load: P 300 Kip
Calculation for Square Tied Column: (WSD) Calculation for Square Tied Column: (USD)
We know,
For Spiral Column,
Rectangular Tied Column ( WSD)
Pu= Ø0.85Ag[.85f'c(1-ρg)+fyρg]
Breath: 14.125 in 15 in
Ag 82.49974219
in2 83 in2
Area of the Column: 230 in2
Area of Column = πr2
So, The dimension of the column is:
Radius : r 5.140005717
in 5.2 in
16 X 15 240 in2
Ag 84.948864 in2 85 in2
So, ρg 0.01570855615 0.016
Area of Steel Ast: 3.417195896
in2
So, Ast : 3.84 in2
P= Ag [0.25f'c + fsρg
78.54
Ag 191.6932907
in2 192 in2 0.01637038704
129277.5 lb
so, r is 7.81763105in 8 in 129.2775 Kip
ρg 0.01637038704 0.017
0.017
www.civilsite.info
www.civilsite.info
boloram
Check
If you put values in the main sheet of "Column Design" same as the given values of the pictures bellow then you will find all other content and values same as the main sheet.
Ultimately if it becomes Main sheet, that means " Column Design" = Check (1, 2) Then this sheet should work properly.
Check 01
Check 02
Column Design by USD Method
Column: Columns are defined as members that carry loads chiefly in compression. Columns are generally referred as compression
member because compression force or stress dominates their behavior. Compression member includes
· Arch ribs
· Rigid frame member
· Compression member in trusses
· Shells
· Portion that carry axial compression
Fig: Column
Type-3
Fig: Compression member in trusses
· Short column – fail by crushing of concrete, lateral bucking need not to be considered.
· Long / Slender column – fail by lateral bucking
Reinforcement ratio is defined by, ρ = As/Ag and the its range is 0.01≤ρ≤0.08
According to this minimum steel ration in column is 1% of gross concrete area of column
To avoid congestion most column are designed with a ratio below 0.04.
· A minimum four longitudinal bar is required when the bar s are enclosed by spaced rectangular or circular ties.
· A minimum six longitudinal bar is required when the bar s are enclosed by a continuous spiral.
Clear distance between longitudinal bars shall not be less than 1.5db nor less than 1.5”.
ACI 7.10.4: Spacing may not be less than 1” and may not be larger than 3”
Example 1
Design a square tied column to support an axial dead load of 400 K and a live lode of 210 K using f’c = 5 Ksi, and fy = 60 Ksi, and a steel ratio of about 5%. Design the necessary ties.
Solution:
1.
Column side =
2. Because larger section is adopted, the steel percentage may be reduced by using
11
(1)
(2)
(3)
Assignment:
Design a circular spiral column to support an axial dead load of 400 K and a live load of 250 K using f’c = 4 Ksi, fy = 60 Ksi,
and a steel ratio of about 2.0%. Also, design the necessary spirals.
Columns loaded with axial load and uniaxial moment is designed based on factored load, which must not exceed the design strength, i.e.
øMn ≥ Mu
øPn ≥ Pu
A column can be designed by solving the above two equations for a specific column section.
A better approach, providing the basis for practical design, is to construct a strength interaction diagram defining failure load and
failure moment for a given column for the full range of eccentricities from zero to infinity.
Design Aid: With a representative column design chart column can be designed easily. And this can de done by two methods
1.
a) Select trial cross section dimensions b and h
b) Calculate the ratio γ based on required cover distances to the bar centroid, and select the corresponding column design chart.
d) From the graph, for the values found in (c), read the required reinforcement ratio
2.
a. Select the reinforcement ratio
d. Calculate
Selection of reinforcement for column of given size : In a three-story structure, an exterior column is to be designed for a service dead
load of 222 kips, maximum live load of 297 kips, dead load moment of 136 ft-kips, and live load moment of 194 ft-kips. The minimum live
load compatible with the full live load moment is 166 kips, obtained when no live load is placed on the roof but a full live load is placed on
the second floor. Architectural considerations require that a rectangular column be used, with dimensions b = 20 in. and h = 25 in.
(a) Find the required column reinforcement for the condition that full live load acts.
(b) Check to ensure that the column is adequate for the condition of no live load on the roof.
Solution:
(a) The column will be designed initially for full load, then checked for adequacy when live load is partially removed.
According to the ACI safety provisions, the column must be designed for a factored load kips and
a factored moment A column is specified, and reinforcement distributed around
the column perimeter will be used. Bar cover is estimated to be 2.5 in. from the column face to the steel centerline for each bar. The column parameters
(assuming bending about the strong axis) are
and as before. From Graph A.7 it is found that a reinforcement ratio of is sufficient for this condition,
less than that required in part (a), so no modification is required.
Selecting No. 3 (No. 10) ties for trial, the maximum tie spacing must not exceed, or
20 in. Spacing is controlled by the diameter of the ties, and No. 3 (No. 10) ties will be used at 18 in. spacing.
Example 4 [example 8.4, Nilson 13th edition]
Selection of column size for a given reinforcement ratio: A column is to be designed to carry a factored load
and factored moment ft-kips. Material strengths and are specified.
Cost studies for the particular location indicate that a reinforcement ratio of about 0.03 is optimum. Find the
required dimensions b and h of the column. Bending will be about the strong axis, and an arrangement of steel with bars
concentrated in two layers, adjacent to the outer faces of the column and parallel to the axis of bending, will be used.
Solution:
It is convenient to select a trial column dimension h, perpendicular to the axis of bending; a value of h = 25 in. will be selected,
and assuming a concrete cover of 2.5 in. to the bar centers, the parameter Graph A. 11 of Appendix A applies. For
the stated loads the eccentricity is and From Graph A. 11 with
and from the trial dimension the required column width is
Approximate method:
Design of column for biaxial bending: The column shown below is reinforced
with eight No. 9 (No. 29) bars arranged around the column perimeter, providing an area .
A factored load of 255 kips is to be applied with eccentricities in. and ,
as shown. Material strengths are and . Check Ihe adequacy of
the trial design using the reciprocal load method.
Solution:
By the reciprocal load method, first considering bending about the Y axis, , and
With the reinforcement ratio , using the average of Graphs A.6 ( ) and A.7 ( ),
Then the bending about the X axis, , and Graph A.5 of the Appendix A gives
From which Thus, according to the Bresler method, the design load of
can be applied safely.
[In general biaxial bending should be taken into account when the estimated eccentricity ratio approaches or exceeds 0.2]
Disclaimer
This Microsoft Excel spread sheet will be able to Design rectangular, square and circular column both in USD and WSD method.
This three types of axially loaded short column can be designed by this spread sheet. This sheet is following the ACI and BNBC code and it's prepared by
the recent experience of the owner. If any one wants to implement the result of this sheet in the practical field, it is their own liability.
E-mail: [email protected]
Cell: +88 01771123050
Watch the Tutorial of "Column Design with Excel" at: http://youtu.be/Jh9uz1F-u3Q