ENGLISH
Isolation transformer
3600W Auto 115/230V
Rev 11 - 02/2023
This manual is also available in HTML5.
Isolation transformer
Table of Contents
1. Safety Instructions ................................................................................................................... 1
2. Features ................................................................................................................................ 2
2.1. Electrical safety .............................................................................................................. 2
2.2. Galvanic corrosion prevention ............................................................................................. 2
2.3. Converting voltages ......................................................................................................... 3
2.4. Automatic AC input voltage detection ..................................................................................... 3
2.5. Soft start ...................................................................................................................... 3
2.6. Internal wiring diagram ...................................................................................................... 4
2.7. Safety when the vessel is out of the water ............................................................................... 4
3. Installation ............................................................................................................................. 5
3.1. What's in the box ............................................................................................................ 5
3.2. Connections overview ...................................................................................................... 5
3.3. AC output configuration ..................................................................................................... 5
3.4. Connecting AC input and AC output ...................................................................................... 6
3.5. AC output neutral to earth link ............................................................................................. 7
3.6. Cable cross-section requirements ......................................................................................... 7
3.7. Wiring example .............................................................................................................. 8
3.8. Linking input and output earth when the vessel is out of the water. ................................................... 8
4. Operation .............................................................................................................................. 9
4.1. Automatic input voltage detection ......................................................................................... 9
4.2. LED indications .............................................................................................................. 9
4.3. Inrush current limiter ........................................................................................................ 9
4.4. Temperature protection ..................................................................................................... 9
5. Technical specifications .......................................................................................................... 10
6. Dimensions .......................................................................................................................... 11
Isolation transformer
1. Safety Instructions
WARNING: Before installing, using, storing or transporting this product, read and save the safety instructions
below.
General:
• Review the related documentation of this product to familiarise yourself with safety markings and
instructions before operating the equipment. This product has been designed and tested in accordance with
international standards. Only use the equipment for the intended purpose of application and in accordance
with the specifications as stated in the Technical specification chapter.
• WARNING: RISK OF ELECTRIC SHOCK.
• Do not open the enclosure if the product is still connected to an electrical power source.
• Do not remove the front panel or operate the product without all panels fitted. Refer all servicing to qualified
personnel.
• Caution: never carry heavy loads without assistance.
• Do not expose the product to water, mist, snow, spray, or dust.
• Do not use the product in locations where there is a risk of gas or dust explosions. This product is not
ignition protected.
Installation:
• Always refer to the installation section in the manual before applying power to the equipment.
• Connections, cable sizes and safety features must be according to the locally applicable regulations.
• This is a safety class I product (provided with a protective earthing terminal). An uninterruptible safety
earth ground must be provided at the AC-in and AC-out terminals. An additional grounding point is located
at the outside of the product. Whenever it is likely that the grounding protection has been impaired, the
product must be made inoperative and secured against any unintended operation; refer to qualified service
personnel.
• Make sure that circuit breakers are provided in the connecting wires. Never replace a safety component
with a different type. Consult the manual to determine the correct component.
• Before applying power, verify that the available power source matches the configuration settings of the
product as described in the manual.
• Ensure that the environmental conditions are suitable for the operation of the equipment. Never operate
the product in the rain or a dusty environment. Allow at least 10cm of free space around the product for
ventilation, and ensure that ventilation fans are not blocked. Install in a well-ventilated and heat-resistant
environment. Avoid the presence of, e.g. chemicals, synthetic components, curtains or other textiles in the
immediate vicinity of the product.
• Be sure that the demanded power does not exceed the product's power rating.
Transport and storage:
• When storing or transporting the product, make sure that all mains power leads are disconnected.
• No liability can be accepted for any transport damage when equipment is shipped in non-original packaging.
• Store the product in a dry location. Storage temperature must be between -20°C and 60°C.
Page 1 Safety Instructions
Isolation transformer
2. Features
The isolation transformer eliminates any electrical continuity between AC shore power and the vessel. It is essential for safety and
eliminates the need for galvanic isolators and polarity alarms.
2.1. Electrical safety
Electrical safety is taken for granted in the case of a standard on-shore installation. A circuit breaker will trip, or a GFCI (Ground
Fault Circuit Interrupter) will trip in case of a short circuit or a current leakage to ground. Connecting the ground wire of the
shore-side supply to a vessel's metal parts will result in galvanic corrosion.
Bringing only the live and neutral wire onboard results in an unsafe situation because GFCIs will not work, nor will a breaker trip in
case of a short circuit to a metal part on the vessel.
2.2. Galvanic corrosion prevention
Galvanic corrosion occurs when two dissimilar metals in electrical contact are simultaneously exposed to an electrically
conducting fluid. Seawater and, to a lesser extent, freshwater are such fluids. In general, the more active alloy of the couple
corrodes preferentially, while the less active (more noble) material is cathodically protected. The rate of galvanic corrosion is a
function of several variables, including area ratios, the conductivity of the fluid, temperature, the nature of the materials, etc.
It is a misunderstanding that galvanic corrosion occurs only in metal and aluminium hulls. In fact, it can occur on any vessel as
soon as a metallic part (the shaft and propeller) is in contact with water. Galvanic corrosion will quickly dissolve your sacrificial
anodes and attack the shaft, propeller and other metal parts in contact with water when the vessel is connected to the shore-side
supply. It might therefore be tempting not to connect the ground conductor: this is, however, extremely dangerous because a
GFCI will not work, nor will a circuit breaker trip in case of a short circuit to a metal part on the vessel.
The best solution to avoid galvanic corrosion and, at the same time, prevent any unsafe situation is to install an isolation
transformer to connect to the shore-side supply. The isolation transformer eliminates any electrical continuity between shore
power and the vessel. The shore power is fed to the transformer's primary side, and the vessel is connected to the secondary.
The isolation transformer completely isolates the vessel from the shore ground. By connecting all metal parts to the neutral output
on the secondary side of the transformer, a GFCI or a breaker will trip in case of a short circuit.
ID Description
A Shore AC supply
B Shore AC distribution
C GFCI (ground fault circuit interrupter)
D Vessel AC supply
E Galvanic corrosion
The shore ground connected to immersed metals of the vessel causes
galvanic corrosion.
Page 2 Features
Isolation transformer
ID Description
A Shore AC supply
B Shore AC distribution
C Isolation transformer
D GFCI (ground fault circuit interrupter)
E Vessel AC supply
The shore ground is isolated from the vessel ground, and galvanic
corrosion originating from the shore connection is blocked.
2.3. Converting voltages
The isolation transformer converts the input voltage with a 1:1.05 ratio. The 1:1.05 transformer ratio boosts the output voltage of
the isolation transformer by 5%. This is to compensate for shore power voltage drops that are a common occurrence in marinas.
The isolation transformer can be used in 115V or 230V systems and also be used to convert 230V to 120V and 115V to 240V.
Depending on the isolation transformer configuration:
• A 230V input becomes 240V.
• A 230V input becomes 120V.
• A 115V input becomes 240V.
• A 115V input becomes 120V.
The isolation transformer can be used in 50Hz or 60Hz systems. However, the isolation transformer cannot convert frequencies
from 50Hz to 60Hz or vice versa.
2.4. Automatic AC input voltage detection
The isolation transformer will automatically detect the incoming voltage and will switch to a 115 or 230V AC input configuration,
depending on the input voltage:
• If the incoming voltage is between 88 and 130V, the transformer switches to 115V input mode.
• If the incoming voltage is between 185 and 250V, the transformer switches to 230V input mode.
2.5. Soft start
Soft start is a standard feature of a Victron Energy isolation transformer. It will prevent the shore power circuit breaker from
tripping due to the transformer inrush current.
Page 3 Features
Isolation transformer
2.6. Internal wiring diagram
ID Description
A Shore AC connection
B Soft start
C Transformer
D Vessel AC connection
E Neutral - Earth link (removable)
F Shore Earth
G Vessel Earth
Internal wiring diagram of the isolation transformer.
2.7. Safety when the vessel is out of the water
It is recommended, for optimal safety, to connect the shore earth to the vessel's earth when the vessel is out of the water, in
winter or for maintenance. The isolation transformer has a facility for this.
Page 4 Features
Isolation transformer
3. Installation
3.1. What's in the box
The isolation transformer ships with the following items:
Description
1x hanging bracket, used for mounting the isolation transformer inside a vessel.
1x isolation transformer.
1x long yellow/green jumper wire with female 6.35 mm spade connectors, used to connect AC input earth (PE) to AC output
earth (PE) when the vessel is out of the water for maintenance or winter storage.
1x long yellow/green wire with eye terminals, used for case grounding.
1x short yellow/green jumper wire with female 6.35 mm spade connectors, used to make AC output neutral (N) to earth (PE)
link.
7x mounting screws.
3.2. Connections overview
I Description
D
AC input screw terminals (shore power):
1
Phase (Lin) neutral (Nin) and earth (PEin).
Male spade terminals to establish an AC output neutral to earth connection link for a correct operation of an AC output
2 GFCI:
Connect J21 to J33 to cabinet.
Male spade terminals to configure the AC output voltage:
3 For 115V, connect J29 to J32 and connect J31 to J25.
For 230V, connect J31 to J32.
AC output screw terminal (AC loads or AC installation):
4
Phase (Lout) neutral (Nout) and earth (PEout).
Male spade terminals to bridge AC input earth to AC output earth when the vessel is out of the water:
5
Connect PEin (J34A and/or J34A1) to J34.
3.3. AC output configuration
The AC output needs to be configured for 115 or 230V use. This is done by connecting male spade terminals using the black
jumper wires (included). These terminals are located above the AC output connector.
Page 5 Installation
Isolation transformer
Connect Connections
AC output
jumper cable
voltage
between
J29 and J32
115V
J31 and J25
230V J31 and J32
3.4. Connecting AC input and AC output
Shock hazard. Do not work on the isolation transformer or the electrical system if still connected to an
electrical power source.
Connection sequence:
1. Pass the AC cables through the cable glands at the bottom of the cabinet in the following way:
a. Pass the AC input (shore power) cable through the left side cable gland.
b. Pass the AC output (AC loads) cable through the right side cable gland.
2. Connect the AC input cable to the INPUT terminal block in the following way:
a. Connect the earth wire to the PE terminal.
b. Connect the neutral wire to the N terminal.
c. Connect the phase wire to the L terminal.
3. Connect the AC output cable to the OUTPUT terminal block in the following way:
a. Connect the earth wire to the PE terminal.
b. Connect the neutral wire to the N terminal.
c. Connect the phase wire to the L terminal.
4. Connect the enclosure to the ground (=all the metal parts in the vessel) in the following way:
a. Connect the M6 bolt underneath the enclosure to the vessel ground. See the below drawing for the location of the chassis
earth bolt.
Page 6 Installation
Isolation transformer
Location of the chassis earth bolt.
3.5. AC output neutral to earth link
A GFCI must be installed in the AC output of the isolation transformer. For the GFCI to operate correctly, the AC output neutral
must be connected to the AC output earth and ground (= all the metal parts in the vessel).
To link the AC output neutral (N) to earth (PE), place a green/yellow jumper wire (included) between the J33 and J21 male spade
connectors.
AC output neutral (N) to earth (PE) link.
3.6. Cable cross-section requirements
Use the following minimal cable cross-sections:
Isolation transformer power rating Voltage Metric AWG
3600W 115V 6mm² AWG 10
3600W 230V 2.5mm² AWG 13
Page 7 Installation
Isolation transformer
3.7. Wiring example
Wiring example isolation transformer installed on a vessel connected to shore power.
I Description
D
A Shore power.
B Circuit breaker.
C GFCI (Ground Fault Circuit Interrupter).
D Shore cable.
E Isolation transformer.
F AC loads.
3.8. Linking input and output earth when the vessel is out of the water.
For safety reasons, when the vessel is out of the water (on land) during winter or for maintenance, the vessel's earth (PE)
conductor must be connected directly to the shore power earth (PE) conductor.
This can be achieved inside the isolation transformer by connecting the yellow/green jumper wire (included) between male spade
terminals J34A and J34, as indicated below.
AC input earth is connected to AC output earth when the vessel is out of the water (on land) during winter or for maintenance.
Page 8 Installation
Isolation transformer
4. Operation
Check the input and output voltage configuration before operating the isolation transformer.
4.1. Automatic input voltage detection
The isolation transformer automatically detects the incoming voltage and will set its input voltage mode according to the below
table.
Green Yellow Yellow
Input voltage range “on” “115V" “230V” Behaviour
LED LED LED
0 - 87V On Off Off Both the input and output are switched off.
88V - 130V On On Off Operating in 115V input mode.
130V - 185V On Off Off Both the input and output are switched off.
185V - 250V On Off On Operating in 230V input mode.
4.2. LED indications
The isolation transformer has the following LED indications:
LED Colour Description
on Green Lights when the isolation transformer is operational.
230V Yellow Lights when the isolation transformer is operating in 230Vac input mode.
115V Yellow Lights when the isolation transformer is operating in 115Vac input mode.
Temperature Red Lights when the fan is on.
4.3. Inrush current limiter
The inrush current limiter prevents upstream circuit breakers from tripping when switching on the isolation transformer.
4.4. Temperature protection
The isolation transformer is fan cooled. The fan speed is temperature-controlled. Its speed (rpm) will increase if the temperature
increases.
The isolation transformer is protected against overtemperature and will switch off in case of overheating.
Page 9 Operation
Isolation transformer
5. Technical specifications
Isolation Transformer 3600 Watt auto
AC input voltage * 115 or 230V, automatic detection
AC output voltage * 120 or 240V
Frequency 50/60Hz
32A (115V)
Output current rating
16A (230V)
Soft start Yes
Operating temperature range -20°C to 40°C
Humidity Max 95%, non-condensing
Transformer type Toroidal (low noise, low weight), 1:1.05 ratio
Enclosure Aluminium (blue RAL 5012)
Protection category IP21
Safety EN 60076
Weight 23kg
Dimensions (h x w x d), mm 362 x 258 x218
*) The isolation transformer can be used as:
• 115V to 120V isolation transformer
• 230V to 240V isolation transformer
• 115V to 240V isolation transformer
• 230V to 120V isolation transformer
Page 10 Technical specifications
Isolation transformer
6. Dimensions
Page 11 Dimensions