METHOD STATEMENT ELECTRICAL ACCESS CONTROL SYSTEM

METHOD STATEMENT FOR


INSTALLATION OF ACCESS
CONTROL SYSTEM

Page 1|5
METHOD STATEMENT ELECTRICAL ACCESS CONTROL SYSTEM

1.0 Scope

This method statement details the method of installation of Access Control System.

Note
A separate Method Statement Ref. ETA/MS/E- 038 shall be submitted for testing and
commissioning of the Door Entry System (CCTV System, Access Control System,
Audio Intercom, Video Intercom)

2.0 Material

2.1 All materials shall be as per approved material submittals.

2.2 Type of cable shall be as per approved shop drawings / system manufacturer’s
recommendation.

2.3 Type and location of Card readers, Door contacts, Magentic locks, Exit Push
button shall be as per approved shop drawing.

3.0 Applicable Location

3.1 Tower E1, E2, E3, W1, W2, W3 (Entry to the Building from the Podium Areas
upto Level 2)

4.0 Method

4.1 Storage

4.1.1 All materials received at site shall be inspected and ensured against
approved material submittal.

4.1.2 Any discrepancies, damages etc. shall be notified immediately for


further action.

4.1.3 Material found not suitable for the project are to be removed from site
immediately.

4.1.4 Cables shall be stored with the factory packing on the flat surface.

4.1.5 Materials shall be stacked properly as per manufacturer’s


recommendation and covered to prevent dust and water / moisture.

4.1.6 Access Control System Equipment to be stored as per manufactures


recommendation mentioned / marked in the packing.

4.1.8 Ambient condition of the storage place to be as per manufacturer’s


recommendation.

Page 2|5
METHOD STATEMENT ELECTRICAL ACCESS CONTROL SYSTEM

4.2 Installation

4.2.1 Control Cable

[Link] Ensure the relevant current / approved shop drawings are


available with installation team.

[Link] Transfer the cable to the work place with the help
manpower..

[Link] Check the cable drum for any external damage during
transportation and ensure the type of cable against area of
usage / application.

[Link] Type and size of the cable is as per approved shop


drawings.

[Link] In concealed application pull cables manually through


conduit installed as per approved shop drawings and
approved method statements.

[Link] Leave enough length of cable at both ends of panel and


devices for termination.

[Link] No through joints is allowed without the sanction of the


Consultants.
.
4.2.2 Access Control Equipments.

[Link] Ensure the relevant current / approved shop drawings are


available with installation team.

[Link] Transfer the equipment to the work place with the help of
manpower.

[Link] Location of the panel to be as per approved shop


drawing after coordinating with other services.

[Link] Fixing holes will be marked properly keeping back box


of the panel in place.

[Link] Fix back box properly and fix remaining panel


accessories.

4.2.3 Card Readers

[Link] Ensure the relevant current / approved shop drawings are


available with installation team.

Page 3|5
METHOD STATEMENT ELECTRICAL ACCESS CONTROL SYSTEM

[Link] Exact location of the Card Readers to be as per approved


Shop drawing.

[Link] For the Card readers, which needs to be fixed on the


wall, fix appropriate [Link] box.

[Link] Install the Card readers and terminate the cable properly.

4.2.4 Door Contacts

[Link] Ensure the relevant current / approved shop drawings are


available with installation team.

[Link] Exact location of the Door Contacts to be as per approved


Shop drawing.

[Link] Type of Door Contacts to be as per the location and type


of door i.e., either recessed or surface mounted

[Link] For the Door Contacts, which needs to be fixed on the


door, door supplier to provide appropriate provisions.

[Link] Install the Door Contacts and terminate the cable


Properly.

4.2.5 Locks

[Link] Ensure the relevant current / approved shop drawings are


available with installation team.

[Link] Exact location of the Locks to be as per approved


Shop drawing.

[Link] Type of Locks Contacts to be as per the location and type


of door i.e., either recessed or surface mounted

[Link] For the Locks, which needs to be fixed on the door, door
supplier to provide appropriate provisions.

[Link] Install the locks and terminate the cable Properly.

4.2.6 Exit Push Button

[Link] Ensure the relevant current / approved shop drawings are


available with installation team.

[Link] Exact location of the Push Button to be as per approved


Shop drawing.

Page 4|5
METHOD STATEMENT ELECTRICAL ACCESS CONTROL SYSTEM

[Link] For the Push Buttons, which needs to be fixed on the


wall, fix appropriate [Link] box.

[Link] Install the Push Buttons and terminate the cable properly.

5.0 Records

5.1 QC Installation Check List

5.2 Inspection request duly signed-off by NMX and Consultant.

6.0 Attachment

6.1 QC installation checklist of Access Control System.