Modbus RTU (EIA-485) Interface for

Samsung air conditioners


Compatible with NASA commercial air conditioners commercialized by Samsung

USER MANUAL
Issue date: 01/2024 r1.4 ENGLISH
IntesisTM INMBSSAM001R100 (Samsung NASA) User’s Manual r1.4 EN

Modbus RTU (EIA-485) Interface for


Samsung air conditioners
Compatible with NASA commercial air conditioners commercialized by Samsung

ORDER CODE LEGACY ORDER CODE


INMBSSAM001R100 SM-RC2-MBS-1

© HMS Industrial Networks S.L.U - All rights reserved


URL [Link]
This information is subject to change without notice

2 / 22
IntesisTM INMBSSAM001R100 (Samsung NASA) User’s Manual r1.4 EN

Important User Information


Disclaimer
The information in this document is for informational purposes only. Please inform HMS Industrial Networks
of any inaccuracies or omissions found in this document. HMS Industrial Networks disclaims any responsibility
or liability for any errors that may appear in this document.

HMS Industrial Networks reserves the right to modify its products in line with its policy of continuous product
development. The information in this document shall therefore not be construed as a commitment on the
part of HMS Industrial Networks and is subject to change without notice. HMS Industrial Networks makes no
commitment to update or keep current the information in this document.

The data, examples and illustrations found in this document are included for illustrative purposes and are only
intended to help improve understanding of the functionality and handling of the product. In view of the wide
range of possible applications of the product, and because of the many variables and requirements associated
with any particular implementation, HMS Industrial Networks cannot assume responsibility or liability for
actual use based on the data, examples or illustrations included in this document nor for any damages incurred
during installation of the product. Those responsible for the use of the product must acquire sufficient
knowledge in order to ensure that the product is used correctly in their specific application and that the
application meets all performance and safety requirements including any applicable laws, regulations, codes
and standards. Further, HMS Industrial Networks will under no circumstances assume liability or responsibility
for any problems that may arise as a result from the use of undocumented features or functional side effects
found outside the documented scope of the product. The effects caused by any direct or indirect use of such
aspects of the product are undefined and may include e.g. compatibility issues and stability issues.

© HMS Industrial Networks S.L.U - All rights reserved


URL [Link]
This information is subject to change without notice

3 / 22
IntesisTM INMBSSAM001R100 (Samsung NASA) User’s Manual r1.4 EN

INDEX

1. Presentation .......................................................................................................... 5

2. Connection ............................................................................................................ 6

2.1 Connect to the AC indoor unit ............................................................................... 6

2.2 Connection to the EIA-485 bus ............................................................................. 7

3. Quick Start Guide ................................................................................................... 7

4. Modbus Interface Specification ................................................................................ 8

4.1 Modbus physical layer.......................................................................................... 8

4.2 Modbus Registers ................................................................................................ 8

4.2.1 Control and status registers ........................................................................... 8

4.2.2 Configuration Registers................................................................................ 10

4.2.3 Considerations on Temperature Registers ...................................................... 12

4.3 DIP-switch Configuration Interface ...................................................................... 14

4.4 Implemented Functions ..................................................................................... 17

4.5 Device LED indicator ......................................................................................... 17

4.6 EIA-485 bus. Termination resistors and Fail-Safe Biasing mechanism ...................... 18

5. Electrical and Mechanical features .......................................................................... 19

6. List of supported AC Unit Types. ............................................................................ 20

7. Error Codes ......................................................................................................... 21

© HMS Industrial Networks S.L.U - All rights reserved


URL [Link]
This information is subject to change without notice

4 / 22
IntesisTM INMBSSAM001R100 (Samsung NASA) User’s Manual r1.4 EN

1. Presentation

The INMBSSAM001R100 interfaces allow a complete and natural


integration of Samsung NASA air conditioners into Modbus RTU (EIA-
485) networks.

Reduced dimensions. 93 x 53 x 58 mm / 3.7” x 2.1” x 2.3”

Quick and easy installation.


Mountable on DIN rail, wall, or even inside the indoor unit of AC.

• External power not required.

• Direct connection to Modbus RTU (EIA-485) networks. Up to 63 INMBSSAM001R100 devices


can be connected in the same network.
INMBSSAM001R100 is a Modbus slave device.

• Direct connection to the AC unit.

• Configuration from both on-board DIP-switches and Modbus RTU.

• Total Control and Supervision.

• Real states of the AC unit's internal variables.

• Allows simultaneous use of the AC’s remote controls and Modbus RTU.

Modbus RTU
EIA-485 network Modbus RTU
Master
device
INMBSSAM001R100

Up to 63
AC indoor INMBSSAM001R100
• SCADA
units*
• PLC
• DDC
• BMS
• HMI
• Controller
• etc

INMBSSAM001R100

* Up to 63 Intesis devices can be installed in the same Modbus RTU bus. However, depending on the configured speed, the installation
of Modbus Repeaters may be required.

© HMS Industrial Networks S.L.U - All rights reserved


URL [Link]
This information is subject to change without notice

5 / 22
IntesisTM INMBSSAM001R100 (Samsung NASA) User’s Manual r1.4 EN

2. Connection

The interface comes with 1 plug-in terminal block of 2 poles to establish direct connection with
the AC indoor unit. It comes as well with a plug-in terminal block of 2 poles to establish direct
connection with the Modbus RTU EIA-485 network.

2.1 Connect to the AC indoor unit

The INMBSSAM001R100 connects directly to the Samsung Remote Controller Bus (F3F4
Connector). Depending on which controllers are available, the recommended connection
methods are the following ones (details in Figure 2. 1):

• Wired remote control available. Connect the gateway in parallel with the wired
Remote Controller (wired remote controller acts as Main).

• No remote control available Connect the gateway directly to the F3F4 bus of the
indoor unit. There’s no Samsung remote controller.

Maximum F3F4 bus length is 100 m (328.08 ft). The communication F3F4 bus has polarity
sensitivity.

Important: Communication may shut down if an AC manufacturer’s wired remote controller is


connected to the same bus. Wired remote controllers have a Main/Sub setting to define their
roles and must be set up accordingly when two wired remote controllers are installed. For more
information, check the wired remote controller’s installation manual.

For wall mounting


(It is not mandatory to have it in the network) extract the upper
and down staples
Remote Controller 53 mm / 2.1” until you hear the
Samsung
"click".
Connection to F3F4 bus.
Two wire cable.

F3 F4
AC Unit
F4 F3

AC Indoor Unit 90 mm / 3.5”


EIA485
A+ B-

Internal
Electronic
control board F4
F3
Max. 100 m / 328.08 ft
MODBUS RTU
EIA-485
Bus

For wall mounting


extract the upper
and down staples
53 mm / 2.1” until you hear the
"click".

F3 F4
AC Unit

AC Indoor Unit 90 mm / 3.5”


Connection to F3F4 bus.
EIA485
Two wire cable. A+ B-

Internal
Electronic
control board F4
F3
Max. 100 m / 328.08 ft
MODBUS RTU
EIA-485
Bus

Figure 2. 1 INMBSSAM001R100 connection diagram

© HMS Industrial Networks S.L.U - All rights reserved


URL [Link]
This information is subject to change without notice

6 / 22
IntesisTM INMBSSAM001R100 (Samsung NASA) User’s Manual r1.4 EN

2.2 Connection to the EIA-485 bus

Connect the EIA-485 bus wires to the plug-in terminal block (the one labeled as EIA485) of
INMBSSAM001R100 and keep the polarity on this connection (A+ and B-). Make sure that the
maximum distance to the bus is 1,200 meters (3,937 ft). Loop or star typologies are not
allowed in the case of the EIA-485 bus. A terminator resistor of 120Ω must be present at each
end of the bus to avoid signal reflections. The bus needs a fail-safe biasing mechanism (see
section 4.6 for more details).

3. Quick Start Guide

1. Disconnect the air conditioning from the Mains Power.

2. Attach the interface next to the AC indoor unit (wall mounting) following the instructions
of the diagram below or install it inside the AC indoor unit (respect the safety
instructions given).

3. Connect the F3F4 bus between the interface and the AC indoor unit following the
instructions of the diagram. Screw each bare cable end in the corresponding F3F4
terminals.

4. Connect the EIA-485 bus to the connector EIA485 of the interface.

5. Close the AC indoor unit.

6. Check the DIP-Switch configuration of the Intesis interface and make sure it matches the
current installation’s parameters (see section 4.3).

By default, the interface is set to:


SW3 SW4
▪ Modbus Slave Address ➔ 1 ON ON

▪ Modbus baud rate ➔ 9600 bps

These parameters can be modified from SW4 and SW3 DIP-Switches.

All other switch positions are set at low level (Off position ) by default.

NOTE: All changes on the DIP-Switch configuration require a system power cycle to be
applied.

7. Connect the AC system to Mains Power.

IMPORTANT: The Intesis interface requires to be connected to the AC unit (powered) to


start communicating.

© HMS Industrial Networks S.L.U - All rights reserved


URL [Link]
This information is subject to change without notice

7 / 22
IntesisTM INMBSSAM001R100 (Samsung NASA) User’s Manual r1.4 EN

4. Modbus Interface Specification

4.1 Modbus physical layer

INMBSSAM001R100 implements a Modbus RTU (Slave) interface, to be connected to an EIA-


485 line. It performs 8N2 communication (8 data bits, no parity and 2 stop bit) with several
available baud rates (2400 bps, 4800 bps, 9600 bps -default-, 19200 bps, 38400 bps, 57600
bps, 76800 bps and 115200 bps). It also supports 8N1 communication (8 data bits, no parity
and 1 stop bit).

NOTE: The gateway automatically detects the communication type (8N2 or 8N1) and sets itself
accordingly. No action is needed.

4.2 Modbus Registers

All registers are type “16-bit unsigned Holding Register” and they use the Modbus big endian
notation.

4.2.1 Control and status registers

Register Address Register Address


R/W Description
(protocol address) (PLC address)
AC unit On/Off
0 1 R/W ▪ 0: Off
▪ 1: On
AC unit Mode 1

▪ 0: Auto
▪ 1: Heat
1 2 R/W
▪ 2: Dry
▪ 3: Fan
▪ 4: Cool
AC unit Fan Speed 1

▪ 0: Auto
▪ 1: Low
2 3 R/W
▪ 2: Mid
▪ 3: High
▪ 4: Turbo
AC unit Vane UD Position 1

3 4 R/W ▪ 0: Swing Off (Auto)


▪ 10: Swing On
AC unit Temperature setpoint 1,2,3

▪ -32768 (Initialization value)


4 5 R/W
▪ Cool: 18..30ºC (ºC/x10ºC) / 65..86ºF
▪ Heat: 16..30ºC (ºC/x10ºC) / 63..86ºF
AC unit Temperature reference 1,2,3

▪ -32768 (Initialization value)


5 6 R
▪ -41..38ºC (ºC/x10ºC)
▪ -106..212ºF

1
Available values will depend on the AC unit mode. Check the AC unit model functions in its user manual to know the possible values for
this register.
2
Magnitude for this register can be adjusted to Celsius x 1ºC, Celsius x 10ºC (default) or Fahrenheit. See section 4.2.3 for more
information.
3
It is not possible turn to x10 the value shown in Fahrenheit.

© HMS Industrial Networks S.L.U - All rights reserved


URL [Link]
This information is subject to change without notice

8 / 22
IntesisTM INMBSSAM001R100 (Samsung NASA) User’s Manual r1.4 EN

Register Address Register Address


R/W Description
(protocol address) (PLC address)
Window Contact
6 7 R/W ▪ 0: Closed (Default)
▪ 1: Open
INMBSSAM001R100 Disablement 4
▪ 0: INMBSSAM001R100 enabled
7 8 R/W
(Default)
▪ 1: INMBSSAM001R100 disabled
AC Remote Control Disablement 4
▪ 0: Remote Controller enabled
8 9 R/W
(Default)
▪ 1: Remote Controller disabled
AC unit Operation Time 4
9 10 R/W ▪ 0..65535 (hours). Counts the time
the AC unit is in “On” state.
AC unit Alarm Status
10 11 R ▪ 0: No alarm condition
▪ 1: Alarm condition
Error Code 5
▪ 0: No error present
▪ 65535(-1 if it is read as signed
value): Error in the communication
11 12 R
of INMBSSAM001R100 with the AC
indoor unit.
▪ Any other error present, see the
table at the end of this document.
Indoor unit´s ambient temperature from
external sensor (at Modbus side) 1,2,3,6
▪ -32768: (Initialization value). No
22 23 R/W
temperature is being provided from
an external sensor.
▪ Any other: (ºC/x10ºC/ºF)
AC Real temperature setpoint 1,2,3,6
▪ When no external temperature is
provided, this read-only register will
have the same value as register 5
23 24 R (PLC addressing). In all cases, it will
show the current setpoint in the
indoor unit.
▪ 16..31ºC (ºC/x10ºC)
▪ 60..92ºF
AC unit Left/Right Vane Position
26 27 R/W ▪ 0: Swing Off (Auto)
▪ 10: Swing On

4
This value is stored in non-volatile memory.
5
See section 7 for possible error codes and their explanation.
6
See section 4.2.3 for more information.

© HMS Industrial Networks S.L.U - All rights reserved


URL [Link]
This information is subject to change without notice

9 / 22
IntesisTM INMBSSAM001R100 (Samsung NASA) User’s Manual r1.4 EN

Register Address Register Address


R/W Description
(protocol address) (PLC address)
Window contact ON/OFF Disablement
▪ 0: Window contact is not disabling
option On/Off at this moment
40 41 R
(Default value)
▪ 1: Window contact is disabling
option On/Off at this moment
Filter status
44 45 R ▪ 0: OK
▪ 1: Filter cleaning
Return path Temperature 1,2,3
▪ -32768 (Initialization value)
66 67 R ▪ Ranges determined by the
Manufacturer of the AC indoor unit:
(ºC/x10ºC/ºF)
Block Periodic Sendings 4,7,8
97 98 R/W ▪ 0: Non-blocked (Default value)
▪ 1: Blocked

4.2.2 Configuration Registers

Register Address Register Address


R/W Description
(protocol address) (PLC address)
“Open Window” switch-off timeout 9

13 14 R/W ▪ 0..30 (minutes)


▪ Factory setting: 30 (minutes)
Modbus RTU baud-rate
▪ 2400bps
▪ 4800bps
▪ 9600bps (Default)
14 15 R ▪ 19200bps
▪ 38400bps
▪ 57600bps
▪ 76800bps
▪ 115200bps
Modbus Slave Address
15 16 R
▪ 1..63
Filter reset
43 44 W
▪ 1: Filter reset
49 50 R Device ID: 0x2E00
50 51 R Software version
Number of IUs connected
67 68 R ▪ Indicates the number of indoor units
connected to the same RC bus.

7
If the register is configured as “0: Non-blocked”, all commands received from Modbus will be sent to the AC system. If “1: Blocked”,
commands from Modbus will only be sent to the AC system if they differ from the previous value (values sent on change).
8
This register applies to firmware version 0.1 onwards.
9
Once window contact is open, a count-down to switch off the AC Unit will start from this configured value.

© HMS Industrial Networks S.L.U - All rights reserved


URL [Link]
This information is subject to change without notice

10 / 22
IntesisTM INMBSSAM001R100 (Samsung NASA) User’s Manual r1.4 EN

Internal IU address
▪ All indoor units connected in the RC bus are
68 69 R/W listed in an Internal array in address
ascending order. This register indicates the
position in the array of the current indoor
unit status reported.
IU Address status reported
69 70 R ▪ Address of the indoor unit that reports the
status in case there is more than one
indoor unit connected in the RC bus.
Reset/Reboot device
99 100 W
▪ 1: Reset

© HMS Industrial Networks S.L.U - All rights reserved


URL [Link]
This information is subject to change without notice

11 / 22
IntesisTM INMBSSAM001R100 (Samsung NASA) User’s Manual r1.4 EN

4.2.3 Considerations on Temperature Registers

• AC unit temperature setpoint (R/W)


(register 4 – in Protocol address / register 5 – in PLC address):
This is the adjustable temperature setpoint value that must be required by the user. This
register can be read (Modbus function 3 or 4) or written (Modbus functions 6 or 16). A
remote controller connected to the Samsung indoor unit will report the same
temperature setpoint value as this register.

• AC unit temperature reference (R)


(register 5 – in Protocol address / register 6 – in PLC address):
This register reports the temperature that is currently used by the Samsung indoor unit
as the reference of its own control loop. Depending on the configuration of the indoor
unit, this value can be: the temperature reported by the sensor of the return path of the
Samsung indoor unit, the temperature provided by the sensor of its remote controller or
the temperature provided by Modbus (external temperature). It is a read-only register
(Modbus functions 3 or 4).

• AC unit external temperature reference (Modbus) (R/W)


(register 22 – in Protocol address / register 23 – in PLC address):
This register allows us to provide an external temperature’s sensor from the Modbus
side. If a valid value is written in this register, this will be sent to the Samsung Remote
Controller bus (RC). Notice that in order to apply this setting, the system shall be set so
that the Indoor Unit is configured to use the ambient temperature from the Remote
Controller as the reference of its own control loop.

Please, check Samsung’s User Manual or Samsung’s Installation Manual to see how the
reference temperature source can be changed from the own return path to the reference
temperature.

After the startup, the value for “external temperature’s reference” (register 22/23) has a
value -32768 (0x8000). This value means that no external temperature reference is
being provided through INMBSSAM001R100. In this scenario, the AC indoor unit will use
its own return path temperature sensor as reference for its control loop or the remote
controller’s one (if connected and configured to do so).

This register can be read (Modbus function 3 or 4) or written (Modbus functions 6 or 16)

• AC temperature Real setpoint (R)


(register 23 – In Protocol address / register 24 – in PLC address):
As it has been detailed on the previous point, the real temperature setpoint in the indoor
unit and the temperature setpoint requested from INMBSSAM001R100 might differ
(when a value in register 22/23 – “external temperature reference” is entered). This
register always informs about the current temperature setpoint which is being used by
the indoor unit – it is also includes the temperature setpoint that will be shown by an
additional remote controller from Samsung connected to the indoor unit, if it is present
on the system.

This register can be read (Modbus function 3 or 4)

© HMS Industrial Networks S.L.U - All rights reserved


URL [Link]
This information is subject to change without notice

12 / 22
IntesisTM INMBSSAM001R100 (Samsung NASA) User’s Manual r1.4 EN

• Return path Temperature (R)


(register 66 – in Protocol address / register 67 – in PLC address):
This register shows the temperature value reported by the sensor of the own return path
of the Samsung indoor unit. It is a read-only register (Modbus functions 3 or 4).

Moreover, notice that temperature’s values of all these four registers are expressed according to
the temperature´s format configured through its onboard DIP-Switches (See section 4.3).
These following formats are possible:

• Celsius value: Value in Modbus register is the temperature value in Celsius (i.e. a
value “22” in the Modbus register must be interpreted as 22ºC).
• Decicelsius value: Value in Modbus register is the temperature value in
decicelsius (i.e. a value “220” in the Modbus register must be interpreted as
22.0ºC).
• Fahrenheit value: Value in Modbus register is the temperature value in
Fahrenheit (i.e. a value “72” in the Modbus register must be interpreted as 72ºF
(~22ºC).

© HMS Industrial Networks S.L.U - All rights reserved


URL [Link]
This information is subject to change without notice

13 / 22
IntesisTM INMBSSAM001R100 (Samsung NASA) User’s Manual r1.4 EN

4.3 DIP-switch Configuration Interface

All the configuration values on INMBSSAM001R100 can be written and read from Modbus
interface. Otherwise, some of them can also be setup from its on-board DIP-switch interface.
The device has DIP-switches SW1, SW3 and SW4 on the following locations:

ON
SW1*
1234
SW1*
F3 F4
AC Unit * DIP-Switch SW1 is
not used by the
current version of
INMBSSAM001R100

EIA485 ON ON
A+ B-

12345678 1234
SW3 SW4

SW3 SW4
The following tables apply to the interface´s configuration through DIP-switches:

SW3/SW4 – Baud rate configuration

SW3-P7..8 SW4-P3 Description

ON ON

2400bps

ON ON
4800bps

ON ON
9600bps (Default value)

ON ON

19200bps

ON ON

38400bps

ON ON
57600bps

ON ON

76800bps

ON ON

115200bps

Table 4.1 SW3-SW4: Modbus baud rate

© HMS Industrial Networks S.L.U - All rights reserved


URL [Link]
This information is subject to change without notice

14 / 22
IntesisTM INMBSSAM001R100 (Samsung NASA) User’s Manual r1.4 EN

SW4 – Degrees/Decidegrees (x10), temperature magnitude (ºC/ºF) and EIA-485 termination


resistor.

SW4-P1..2-4 Description

ON

Temperature values in Modbus register are represented in degrees (x1) (Default value)

ON

Temperature values in Modbus register are represented in decidegrees (x10)

ON

Temperature values in Modbus register are represented in Celsius degrees (Default value)

ON

Temperature values in Modbus register are represented in Fahrenheit degrees

ON

EIA-485 bus without termination resistor (Default value)

ON

Internal termination resistor of 120Ω connected to EIA-485 bus

Table 4.2 SW4: Temperature and termination resistor configuration

© HMS Industrial Networks S.L.U - All rights reserved


URL [Link]
This information is subject to change without notice

15 / 22
IntesisTM INMBSSAM001R100 (Samsung NASA) User’s Manual r1.4 EN

SW3 – Modbus Slave address

Add SW3-P1..6 Add SW3-P1..6 Add SW3-P1..6 Add SW3-P1..6 Add SW3-P1..6

ON ON ON ON ON

0 13 26 39 52

ON ON ON ON ON

1 14 27 40 53

ON ON ON ON ON

2 15 28 41 54

ON ON ON ON ON

3 16 29 42 55

ON ON ON ON ON

4 17 30 43 56

ON ON ON ON ON

5 18 31 44 57

ON ON ON ON ON

6 19 32 58
45
ON ON ON ON ON

7 20 33 59
46
ON ON ON ON ON

8 21 34 47 60

ON ON ON ON ON

9 22 35 48 61

ON ON ON ON ON

10 23 36 62
49
ON ON ON ON ON

11 24 37 50 63
ON ON ON ON

12 25 38 51

Table 4.3 SW3: Modbus slave address

© HMS Industrial Networks S.L.U - All rights reserved


URL [Link]
This information is subject to change without notice

16 / 22
IntesisTM INMBSSAM001R100 (Samsung NASA) User’s Manual r1.4 EN

4.4 Implemented Functions

INMBSSAM001R100 implements the following standard Modbus functions:

▪ 3: Read Holding Registers

▪ 4: Read Input Registers

▪ 6: Write Single Register

▪ 16: Write Multiple Registers (Despite this function is allowed, the interface does not
allow to write operations on more than 1 register with the same request, this means that
length field should be always be 1 when this function is being used in case of writing).

The maximum of registers that can be read in a single request is 100.

4.5 Device LED indicator

The device includes two LED indicators to show all the possible operational states. In the
following table there are written the indicators which can be performed and their meaning.

L1 (green LED)

Device status LED indication ON / OFF Period Description

During not normal


LED blinking 500ms ON / 500ms OFF Communication error
operation

During normal Normal operation (configured and


LED flashing 100ms ON / 1900ms OFF
operation working properly)

L2 (red LED)

Device status LED indication ON / OFF Period Description

During not normal


LED Pulse 3sec ON / --- OFF Under voltage
operation

L1 (green LED) & L2 (red LED)

Device status LED indication ON / OFF Period Description

During normal
LED Pulse 5sec ON / --- OFF Device Start-up
operation

During not normal LED alternatively


500ms ON / 500ms OFF Flash checksum not OK
operation blinking

© HMS Industrial Networks S.L.U - All rights reserved


URL [Link]
This information is subject to change without notice

17 / 22
IntesisTM INMBSSAM001R100 (Samsung NASA) User’s Manual r1.4 EN

4.6 EIA-485 bus. Termination resistors and Fail-Safe Biasing


mechanism

EIA-485 bus requires a 120Ω terminator resistor at each end of the bus to avoid signal
reflections.

To prevent fail status detected by the receivers, which are “listening” the bus, when all the
transmitters’ outputs are in three-state (high impedance), a fail-safe biasing mechanism is also
required. This mechanism provides a safe status (a correct voltage level) in the bus when all the
transmitters’ outputs are in three-state. This mechanism must be supplied by the Modbus
Master.

The INMBSSAM001R100 device includes an on-board terminator resistor of 120Ω that can be
connected to the EIA-485 bus by using DIP-switch SW4.

Some Modbus RTU EIA-485 Master devices can provide also internal 120Ω terminator resistor
and/or fail-safe biasing mechanism (Check the technical documentation of the Master device
connected to the EIA-485 network in each case).

© HMS Industrial Networks S.L.U - All rights reserved


URL [Link]
This information is subject to change without notice

18 / 22
IntesisTM INMBSSAM001R100 (Samsung NASA) User’s Manual r1.4 EN

5. Electrical and Mechanical features

Plastic, type PC (UL 94 V-0)


Net dimensions (dxwxh): Operation
Enclosure 0ºC to +60ºC
93 x 53 x 58 mm / 3.7” x 2.1” x 2.3” Temperature
Color: Light Grey. RAL 7035

Stock
Weight 85 g. -20ºC to +85ºC
Temperature

Wall Operational
Mounting <95% RH, non-condensing
DIN rail EN60715 TH35. Humidity

For terminal: solid wires or stranded wires


Terminal Wiring (twisted or with ferrule)
(for low-voltage 1 core: 0.5mm2… 2.5mm2 Stock Humidity <95% RH, non-condensing
signals) 2 cores: 0.5mm2… 1.5mm2
3 cores: not permitted

1 x Serial EIA485 Plug-in screw terminal


block (2 poles):
Modbus RTU
A, B Isolation voltage 1500 VDC
port
Compatible with Modbus RTU EIA-485
networks
1 x F3F4 bus Plug-in screw terminal block
Isolation
AC unit port (2 poles): 1000 MΩ
resistance
F3, F4

Switch 1
1 x DIP-Switch Protection IP20 (IEC60529)
(SW1)

Switch 3 2 x Onboard LED - Operational


1 x DIP-Switch for Modbus RTU settings LED indicators
(SW3) status

Switch 4
1 x DIP-Switch for extra functions
(SW4)

AC Unit LED DIP


connection Indicators Switch SW1

DIP DIP EIA-485


Switch SW3 Switch SW4 Port

© HMS Industrial Networks S.L.U - All rights reserved


URL [Link]
This information is subject to change without notice

19 / 22
IntesisTM INMBSSAM001R100 (Samsung NASA) User’s Manual r1.4 EN

6. List of supported AC Unit Types.


A list of Samsung indoor unit model’s references compatible with INMBSSAM001R100 and its
available features can be found on this link:

[Link]

© HMS Industrial Networks S.L.U - All rights reserved


URL [Link]
This information is subject to change without notice

20 / 22
IntesisTM INMBSSAM001R100 (Samsung NASA) User’s Manual r1.4 EN

7. Error Codes

Error in
Error Code
Remote Error category Error Description
Modbus
Controller
0 N/A INMBSSAM001R100 No active error
101 101 Communication error Indoor unit communication error
Indoor unit/outdoor unit communication time-out
102 102 Communication error
error; errors in more than 6 packets.
121 121 Indoor sensor error Indoor temperature sensor (open/short).
122 122 Indoor sensor error Indoor unit evaporator-in sensor (open/short)
Indoor unit evaporator-in disconnection. (sensor
128 128 Indoor sensor error
displacement)
129 129 Indoor sensor error Indoor unit evaporator-out separation.
153 153 Drain diagnostic error Indoor floating switch secondary detection
201 201 Configuration error Unit Miss Match indoor/outdoor
202 202 Communication error Indoor/outdoor communication error (1 min)
Comm. error between indoor/outdoor
203 203 Communication error
INV<>MAIN MICOM (1 min)
221 221 Outdoor sensor error Outdoor temperature sensor error
231 231 Outdoor sensor error Condenser temperature sensor error
237 237 Outdoor sensor error Condenser temperature error
251 251 Outdoor sensor error Inverter Emission temperature sensor error
320 320 Outdoor sensor error OPL sensor error
Detection of outdoor freezing when compressor
402 402 Outdoor sensor error
stop
Overload Protection of Outdoor when compressor
404 404 Outdoor unit error
stop
419 419 Control error EEV Open error (Electronic Evaporation Valve)
422 422 Control error EEV Close error
425 425 Installation error Power Cable Miss connection
440 440 Self-diagnostic error Heating operation blocked
441 441 Self-diagnostic error Cooling operation blocked
461 461 ODU protection error Inverter Compressor startup error
Inverter total current error / PFC over current
462 462 ODU protection error
error
463 463 ODU protection error OLP Heat Sink error
464 464 ODU protection error Inverter IPM over current error
465 465 ODU protection error Compressor V limit error
466 466 ODU protection error DC LINK over/low voltage error
467 467 ODU protection error Inverter compressor rotation error
468 468 ODU protection error Inverter current sensor error
469 469 ODU protection error Inverter DC LINK voltage sensor error
Inverter OTP error / Inverter EEPROM read/write
471 471 ODU protection error
error
472 472 ODU protection error AC Zero crossing signal out error
473 473 ODU protection error Compressor Lock error
474 474 ODU protection error Heat Sink sensor error
475 475 Self-diagnostic error Outdoor Fan 2 error
484 484 ODU protection error PFC Overload error
485 485 ODU protection error Input current sensor error
500 500 ODU protection error Heat Sink Overheat error
554 554 Self-diagnostic error Gas leak detector
556 556 Configuration error Outdoor unit Capacity Setup option error
557 557 Configuration error Option Code Miss match indoor units

© HMS Industrial Networks S.L.U - All rights reserved


URL [Link]
This information is subject to change without notice

21 / 22
IntesisTM INMBSSAM001R100 (Samsung NASA) User’s Manual r1.4 EN

Communication error between wired remote and


indoor unit. (When communication has stopped
601 601 Communication error
for 3 minutes after detecting indoor unit and
wired remote control)
Communication error between the Main and Sub
602 602 Communication error wired remote controller. (Only one Main and one
Sub can exist).
Tracking 10 or more errors between wired
604 604 Communication error
remote control and indoor unit.
-COM1, COM2 crossing connection error.
606 606 Installation error -When wired remote is connected to indoor unit
COM1 (F1, F2) terminals.
-Multiple Main error. (When using Main wired
remote control).
607 607 Configuration error
-Error occurs when two wired remotes are both
set as Main in one COM line.
Indoor unit is not installed. (When the indoor
unit is not detected after outside gearing option
609 609 Configuration error
setting and tracking are finished). In case of
using outside gear control.
-Exceeded maximum no. of installation for indoor
units.
618 618 Configuration error
-A reset is required after checking the number of
indoor units.
-Mixed installations for °C/F° indoor unit. (Only
detected on Main wired remote control).
619 619 Configuration error
-Error occurs when mixed indoor units of °C and
°F settings are installed.
-Wired remote control °C/°F setting error.
620 620 Configuration error -This error occurs if the indoor unit is set in °C
while the wired remote is set in °F or vice versa.
This error occurs when the option settings of the
621 621 Configuration error Main and Sub wired remote controllers are
different from each other.
Sub wired remote controller installation error
627 627 Configuration error (when two Sub wired remote controls are
installed).
Wired remote controller COM2 option setting
EA EA Configuration error
error.
65535 Error in the communication of
N/A INMBSSAM001R100
(-1) INMBSSAM001R100 with the AC unit.

In case to detect an error code not listed, contact your closest Samsung technical support
service.

© HMS Industrial Networks S.L.U - All rights reserved


URL [Link]
This information is subject to change without notice

22 / 22