VEC Vacuum Contactor Overview
VEC Vacuum Contactor Overview
Vacuum Contactor
7.2kV/12kV,…400A,…4kA
[Link]
▎ Contents
Outline……………………………………………………..…………1
Technical Features………………………………………………....2
Product Models…….………………………………………………..6
[Link] V E C C a tal og
Outline
▍
• VEC vacuum contactor & fuse combination unit is an
indoor switchgear developed by Xiamen Huadian
Switchgear Co., Ltd., with rated voltage of 3.6 ~ 12kV
working in three-phase AC distribution system.
• VEC vacuum contactor & fuse combination unit has
passed the whole set of type testing.
• There are full specification series of VEC vacuum
contactor & fuse combination products, reaching the
internal advanced level.
• Design and manufacture of VEC vacuum contactor &
fuse combination unit is in full conformity with the
standards of GB, DL, IEC, DIN VDE and other
advanced industrialized countries.
• VEC vacuum contactor & fuse combination unit is
mainly used to control and protect high voltage motors,
transformers and capacitor banks, which require
frequent start-up .
• VEC vacuum contactor & fuse combination products
have reasonable structure, compact size, light weight,
long mechanical life, high reliability, low cut-off current
value and long electrical life. It is a high-performance,
maintenance-free vacuum contactor & fuse combination
unit.
▍Application Field
• Power station
• Power distribution network
• Industrial systems (petrochemicals, metallurgy, etc.)
▍Application Area
• VEC vacuum contactor & fuse combination unit is widely used in power
distribution sites which require frequent operation, such as industry, power
plant, oil drilling platform etc., to provide reliable control and protection for
electrical equipment. In combination with a fuse capable of breaking a
wide range of short-circuit fault current and its current limiting effect, VEC
can be used in circuits with short-circuit capacity up to 1000 MVA.
• VEC vacuum contactor & fuse combination unit is equipped with high-
performance vacuum interrupter, which enables VEC to be used with fuse
to control and protect motors, capacitor and transformer banks etc. under
extremely harsh conditions.
▍Structural Features
▍Main Technical Parameters for VEC Vacuum Contactor & Fuse Combination Unit
▍
Note: The high voltage fuse is replaced by an analog fuse with a negligible resistance when measuring the resistance of
main circuit.
Product Model
VEC 07 M
Product Features
Application Area
• High voltage motors, transformers and capacitor banks • High voltage motors, transformers and capacitor
requiring frequent start-up; banks requiring frequent start-up;
• Power plant, power grid, petrochemical, metallurgy and • Spare parts supplement and after-sale maintenance
other new station projects; of previous version products;
• Power transformation of power grids and industrial
projects;
Ordering Instruction
▍Ordering Instruction
• Model, name and quantity of vacuum contactor;
• Closing and opening operation voltage, and whether
mechanical holding is needed;
• Type and current of fuse (to be ordered separately);
• Model, name, specification and quantity of spare parts;
• Please indicate any special circumstances in the order
agreements;
• For the upgrading and replacement of contactor products for
some specific projects, the actual project site situation and
the diversity of secondary electrical connections need to be
considered;
• Please contact the manufacturer for more technical support
before selecting the model;
test position
service position
[Link]
[Link]
Electrical Control Wiring
test position
service position
• JS Counter
•V Rectifier bridge
VEC Catalog | 9
10 | VEC Catalog
Electrical Control Wiring
• SC Closing button
• SO Opening button
Electrical wiring diagram for fixed-type VEC vacuum contactor & fuse combination unit(mechanical holding)
[Link]
[Link]
Electrical Control Wiring
• SO Opening button
• KA1,KA2 Intermediate relay
• JS Counter
•V Rectifier bridge
VEC Catalog | 11
Outline Dimension Drawing
Outline dimension drawing for withdrawable type VEC vacuum contactor & fuse combination unit
201
Φ100.5
205±1.5
φ35
618
630
Fuse indicator
Counter
Closing/Opening indicator
260±1.5
282.5
245.5
212.5
Opening button
150.5
154
76
43.5 50 60 438
609
492
150±1 150±1
(51)
(33)
502 14
530
Outline dimension drawing for withdrawable type VEC vacuum contactor & fuse combination unit (310mm version)
638
201 104
90
Φ100.5
310±1
737
726
φ35
Fuse indication
Counter
282.5
Closing/opening
245.5
260
212.5
Trip
150.5
154
76
43.5 50 60 438
609
490
150±1 150±1
(33)
(51)
14
502
530
230 155
φ35
A section
Counter
312
Closing/Opening Indicator
217
Opening button
385 25 280
450
357
150 150
Φ121 A section
40
557
450
Following factors need to be considered: working voltage, working current, starting time, starting times per hour, full load
current of motor, short circuit current at installation site, application scope of fuse etc. with details as follows:
1. The rated voltage of fuse shall be not less than the working voltage of the system.
2. The rated current of fuse shall be selected according to the following formula and chart
ly=Nlnδ
where:In—full load current of motor
δ—Comprehensive coefficient
N—Ratio of starting current to full load current, usually N=6
ly—Current value during starting time
Draw the point of ly value corresponding to the starting time on the fuse time current characteristic curve provided by the
fuse manufacturer. The fuse with curve corresponding to the point or the curve close to the right of this point is the
optional one. And the rated current of the fuse should be greater than 1.7 times of full load current of motor (20%
capacity reduction in closed environment has been considered).
For example: 12kV system, 1125kw motor, power factor is 0.85, efficiency is 0.9, starting frequency ≤ 2 times / h, starting time ≤ 6S,
motor full load current In = 84.9A, then ly = 866A. For 12kV system, the fuse specification is 160A with point found on fuse time-
current characteristic curve, corresponding to 866A, 6S. It is verified that 160 > 1.7 * 84.9, so the fuse can be selected with
specifications above 160A.
10,000 10,000
1000 1000
Pre arcing time (S)
Pre arcing time (S)
100 100
10 10
1 1
0.1 0.1
0.01 0.01
10 100 1000 10,000 100,000 10 100 1000 10,000 100,000
The selection of fuse for transformer protection shall be coordinated with the protection device of contactor and be able
to withstand high inrush current of transformer. The selection principle of rated current is shown in the following table:
▍
Transformer protection fuse selection table
50
100 20 16
125 20 16
160 25 16
200 31.5 20
250 40 25
300/315 50 31.5
400 71 40
500 80 50
630 100 63
800 140 80
1000 160 100
1250 200 125
1600 250 160
VEC12/Catalog/202106/001/EN
We reserve the right to make technical changes or modify the contents of this document without prior notice. All the
agreed particulars shall prevail . All rights reserved.