Star vs. Delta Connection in Electrical Systems
Star vs. Delta Connection in Electrical Systems
First of all I want to clear you that Star & Delta Connection only possible in 3 phase system, So in our domestic
system it is not possible, because generally all house hold electrical equipment are designed with single phase
supply.
• Star connection is used where we require Neutral terminal to obtain Phase voltage like above image.
• in a star connected system VL=√3Vph,mean Phase voltage is root 3 times less than line voltage.
• In a star Connected system IL=I phase.
• Star connected system require less insulation level.
• Star Connected system is used where low starting current is required.
Shipboard power is generated using a prime mover and an alternator working together. For this an alternating
current generator is used on board. The generator works on the principle that when there is a relative motion
between conductor and magnetic field, emf will be induced. This emf is directly proportional to the rate of flux.
This is also known as Faraday’s law of electromagnetic induction.
A shipboard distribution system consists of different component for distribution and safe operation of the
system. They are:
Emf or the current produced by Faraday’s law, its direction can be find out with
Flemings right hand rule. The right hand is held with the thumb, index finger and
the middle finger mutually perpendicular to each other (at right angles),
as shown in figure.
• The thumb is pointed in the direction of the motion of the conductor relative to the magnetic field.
• The first finger is pointed in the direction of the magnetic field. (north to south)
• Then the second finger represents the direction of the induced or generated current within the conductor
▪ The Thumb represents the direction of Thrust on the conductor (force on the conductor).
▪ The Fore finger represents the direction of the magnetic Field.
▪ The Center finger (middle finger) the direction of the Current.
9. Lenz’s law
Lenz’s law states that when an emf is generated by a change in magnetic flux according to Faraday’s Law,
the polarity of the induced emf is such, that it produces a current and it’s magnetic field opposes the change
which produces it. It is also called Back Emf.
The negative sign used in Faraday’s law of electromagnetic induction, indicates that the induced emf ( ε )
and the change in magnetic flux (δΦB) have opposite signs.
• All safeties same as MSB safeties, but the most important is interlock between ESB and MSB, so that
both breakers do not operate at the same time.
• Should be installed as near as possible to emergency source of electrical power.
• ESB should be supplied during normal operation from MSB with an interconnector.
• No accumulation batteries should be fitted in the same place.
• Should be located in the uppermost continuous deck.
• Easily accessible from an open deck
▪ It is a switchboard which distributes emergency load that power is supplied from emergency generator during the main
power source failure.
▪ It has two sections- one for 440V and another is 220V.
▪ Under normal condition, 440 V supply is taken from E/R Main Switchboard, through a Circuit Breaker
▪ When main power is lost, this Circuit breaker is tripped (opened)
▪ Emergency generator comes into action, and supplies power through another circuit breaker
▪ An interlock is provided, to prevent simultaneous closing of both breaker (both main and emergency generator may be
running, simultaneously)
14. What are the equipment which get supply from emergency generator ?
15. What are the requirements / regulations for emergency power sources on ships ?
▪ All passenger and cargo vessels shall be provided with emergency sources of electrical power, for essential services
under emergency conditions.
▪ Emergency source may be generator or batteries, but must be complied with the rules
▪ Emergency sources must be installed in position such that they are unlikely to be damaged or affected by any incident,
which has caused to main power.
▪ Emergency source of power should be capable of operating with a list of up to 22 ½ ° and a trim of up to 10 °
▪ Emergency generator with its switchboard, is located in a compartment which is outside and away from main and
auxiliary machinery space, above the uppermost continuous deck, and not forward of collision bulkhead
▪ For batteries, the above same rules applied, nut must not be fitted in the same place as emergency switchboard.
16. Earth fault indicator
When “EARTH LAMP” switch (ELS) on a feeder panel is in OFF position, the neutral of the star connected primaries
of three lamp transformers is disconnected from the earth, and the voltage across the primary is the same for each
transformer regardless whether the ship’s feeder system contains an earth fault or not. Therefore, three indicator lamps
(TLs) connected to the respective transformer secondaries are on at the same brightness.
To check the ship’s feeder system’s insulation resistance to earth, put “EARTH LAMP” switch (ELS) to TEST (this
earths the neutral of the star connected primaries of lamp transformers). If there is an earth fault in phase R, for
example, the lamp R would be less bright than other two; or if it is a complete earth fault, the lamp R would be off.
Where there is no earth fault, switching of the ELS from OFF to TEST gives no change in lamps’ brightness.
Reverse Power Relay is a directional protective relay that prevents/protect the generator from motoring effect (going
to reverse direction). It is used where generator runs in parallel with other utility or generator. The relay monitors the
power supply from the generator and in case the generator output falls below a preset value, it quickly activates the trip
and disconnects the generator.
CONSTRUCTION
The relay is made up of lightweight non-magnetic Aluminium disc between two soft laminated iron core
electromagnets. The upper magnet is wound with Voltage Coil (PT) which is supplied from one phase & artificial
neutral of generator output. The other output magnet is wound with Current Coil (CT) connected to the same phase as
the voltage in the upper electromagnet.
WORKING
Since Voltage Coil has more number of turns, so it has move inductive value and more induced current that lag in the
coil by an angle of 90°. The current coil has less number of turns, so it has less inductive valve & less induced current
that lag less.
As we all know that current carrying conductor produces the magnetic field. So both upper and lower section produces
magnetic fields. But Induced current in PT lags more than CT so magnetic field produced in upper section will be
weaker than lower section & both magnetic fields will have a difference of 90°
When both fields pass through the Aluminium disc, it produces eddy current. As a result of the formation of eddy
current torque is generated that tries to rotate the disc. Under normal power flow, the trip contact on the disc are open
and rotation is restricted by stoppers but if a reverse power starts to flow the disc is rotated in opposite direction,
moves away from the stoppers in the direction of trip contact that activates the trip.
Single phase induction motor is not the self starting so, to make it self start we can use capacitor & capacitor also
provides high starting torque.
Here, A1 is connected to A2, B1 to C2 and C1 to B2. The prime mover of the incoming machine is started and brought
up to its rated speed. The excitation of the incoming machine is adjusted in such a way that the incoming machine
induces the voltage EA1, EB2, EC3, which is equal to the Busbar voltages VA1, VB1 and VC1.
The correct moment to close the switch is obtained at the instant when the straight connected lamp is dark, and the
connected cross lamps are equally bright. If the phase sequence is incorrect, no such instant will take place, and all the
lamps will be dark simultaneously.
The direction of rotation of the incoming machine is changed by interchanging the two lines of the machine. Since the
dark range of the lamp extends to a considerable voltage range, a voltmeter V1 is connected across the straight lamp.
The synchronising switch is closed when the voltmeter reading is zero.
Thus, the incoming machine is now floating on the Busbar and is ready to take up the load as a generator. If the prime
mover is disconnected, it behaves as a motor. For paralleling small machines in power stations, three lamps along with
the synchroscope are used. For synchronising very large machine in power stations, the whole procedure is performed
automatically by the computer.
• The synchroscope consists of a small motor with coils on the two poles connected across two phases. Let’s say
it is connected in red and yellow phases of the incoming machine and armature windings supplied from red
and yellow phases from the switchboard bus bars.
• The bus bar circuit consists of an inductance and resistance connected in parallel.
• The inductor circuit has the delaying current effect by 90 degrees relative to current in resistance.
• These dual currents are fed into the synchroscope with the help of slip rings to the armature windings which
produces a rotating magnetic field.
• The polarity of the poles will change alternatively in north/south direction with changes in red and yellow
phases of the incoming machine.
• The rotating field will react with the poles by turning the rotor either in clockwise or anticlockwise direction.
• If the rotor is moving in clockwise direction this means that the incoming machine is running faster than the
bus bar and slower when running in anticlockwise direction.
• Generally, it is preferred to adjust the alternator speed slightly higher, which will move the pointer on
synchroscope is in clockwise direction.
• The breaker is closed just before the pointer reaches 12 o clock position, at which the incoming machine is in
phase with the bus bar.
• Note: Without the aid of synchroscope and lamp method, alternators can be synchronised by using a voltmeter
connected across one pole of the incoming generator circuit breaker. When the voltmeter shoots from 0 to
maximum, close the circuit breaker, on adjusting generator speed passing through zero.
Star-Delta Starter
In star delta starting, the motor is connected in STAR mode throughout the starting period. When the motor reached
the required speed, the motor is connected in DELTA mode.
Auto-transformer starter:
It is provided with a number of tappings. The starter is connected to one particular tapping to obtain the most suitable
starting voltage. A double throw switch S is used to connect the auto transformer in the circuit for starting. When
the handle H of the switch S in the START position. The primary of the auto transformer is connected to the supply
line, and the motor is connected to the secondary of the auto transformer.
When the motor picks up the speed of about 80 percent of its rated value, the handle H is quickly moved to
the RUN position. Thus, the auto transformer is disconnected from the circuit, and the motor is directly connected to
the line and achieve its full rated voltage. The handle is held in the RUN position by the under voltage relay.
If the supply voltage fails or falls below a certain value, the handle is released and returns to the OFF position.
Thermal overload relays provide the overload protection.
ADVANTAGES OF AUTO TRANSFORMER STARTER:
a ) On the 65% tapping the line current is approximately equal tp that of a Star-Delta starter, however, at the time of
switching from reduced voltage to the full supply voltage, the motor is not disconnected so that the second peak is
very much reduced since the transformer is converted into reactance for a short time.
b ) It is possible to vary the tapping from 65% to 80% or even up to 90% of the supply voltage in order to ensure that
the motor starts satisfactorily.
Disadvantages:
a ) One of its great disadvantages is the limitation of its operation frequency. It is always necessary to know the
operation frequency in order to determine a suitably rated auto-transformer.
b ) The compensating switch is much more expensive than a Star-Delta starter due to the auto-transformer.
c ) Due to the size of the auto-transformer starter, much larger control panels are required which increases the price.
Soft Starter
The soft starter operates on a different premise. This principle is that by adjusting the voltage applied to the
motor during starting, the current and torque characteristics can be limited and controlled.
For induction motors, the starting torque (LRT) is approximately proportional to the square of the starting current
(LRA) drawn from the line. LRT ∝ I2. This starting current is proportional to the applied voltage (V). So the
torque can also be considered to be approximately proportional to the applied voltage. LRT ∝ V2.. By
adjusting voltage during starting, the current drawn by the motor and the torque produced by the motor can be
reduced and controlled.
By using six SCR’s in a back to back configuration as shown in figure 2, the soft starter is able to regulate the
voltage applied to the motor during starting from 0 volts up to line voltage. Unlike the VFD, line frequency is
always applied to the motor. Only the voltage changes.
Timing of when to turn on the SCR’s is the key to controlling the voltage output of a soft starter. During the
starting sequence the logic of the soft starter determines when to turn on the SCR’s. It does not turn on the
SCR’s at the point that the voltage goes from negative to positive, but waits for some time after that. This is
known as “phasing back” the SCR’s. The point that the SCR’s are turned on is set or programmed by what is
called either initial torque, initial current or current limit setting.
The input voltage to the soft starter is the same as the VFD shown in figure 3. The result of phasing back the
SCR’s is a non-sinusoidal reduced voltage at the terminals of the motor which is shown in figures 7. Since the
motor is inductive and the current lags the voltage, the SCR stays turned on and conduct until the current goes to
zero. This is after the voltage has gone negative.
Applications:
• In pump applications- a soft start can avoid pressure surges
• In conveyor belt systems- avoids jerk and stress on drive components.
• Fans or other systems with belt drive- to avoid slipping of belt
• In all systems- limits the inrush current and so improves the stability of power supply.
Soft starters do have an advantage over conventional reduced voltage starting.
They are able to adjust voltage, current and therefore torque over a wide range
instead of single or a few fixed values. This can be seen in Figure 10.
When voltage or current is held to a constant value, the speed-torque curve
labelled “Current Limit” is produced. This curve would move up or down
depending on the current limit setting. The upper boundary of this
adjustment is the “Full Voltage” curve.
The winding has at least three taps where electrical connections are made. Since part of the winding does "double
duty", autotransformers have the advantages of often being smaller, lighter, and cheaper than typical dual-winding
transformers, but the disadvantage of not providing electrical isolation between primary and secondary circuits. Other
advantages of autotransformers include lower leakage reactance, lower losses, lower excitation current, and increased
VA rating for a given size and mass.
Consider, no current is flowing in the armature conductors and only the field winding is energized (as shown in the
first figure of the above image). In this case, magnetic flux lines of the field poles are uniform and symmetrical to the
polar axis. The 'Magnetic Neutral Axis' (M.N.A.) coincides with the 'Geometric Neutral Axis' (G.N.A.).
The second figure in the above image shows armature flux lines due to the armature current. Field poles are de-
energised.
Now, when a DC machine is running, both the fluxes (flux due to the armature conductors and flux due to the field
winding) will be present at a time. The armature flux superimposes with the main field flux and, hence, disturbs the
main field flux (as shown in third figure the of above image). This effect is called as armature reaction in DC
machines.
Compensating winding: Now we know that the armature reaction is due to the presence of armature flux. Armature
flux is produced due to the current flowing in armature conductors. Now, if we place another winding in close
proximity of the armature winding and if it carries the same current but in the opposite direction as that of the armature
current, then this will nullify the armature field. Such an additional winding is called as compensating winding and it
is placed on the pole faces. Compensating winding is connected in series with the armature winding in such a way that
it carries the current in opposite direction.
Interpoles:Interpoles are the small auxiliary poles placed between the main field poles. Winding on the interpoles is
connected in series with the armature. Each interpole is wound in such a way that its magnetic polarity is same as that
of the main pole ahead of it. Interpoles nullify the quadrature axis armature flux.
It works on the principle of Seebeck effect. It is a phenomenon in which a temperature difference between two
dissimilar electrical conductors or semiconductors produces a voltage difference between the two substances. When
heat is applied to one of the two conductors or semiconductors, heated electrons flow toward the cooler one.
Made of two different alloy or metal joined together.
Two junctions maintained at different temperature, one junction which is cold maintained at constant temperature and
other junction is easily found.
The working principle of an alternator or AC generator is similar to the basic working principle of a DC generator.
Below given figure helps you understanding how an alternator or AC generator works. According to the Faraday's law
of electromagnetic induction, whenever a conductor moves in a magnetic field EMF gets induced across the
conductor. If the close path is provided to the conductor, induced emf causes current to flow in the circuit.
Now, see the above figure. Let the conductor coil ABCD is placed in a magnetic field. The direction of magnetic flux
will be form N pole to S pole. The coil is connected to slip rings, and the load is connected through brushes resting on
the slip rings.
Now, consider the case 1 from above figure. The coil is rotating clockwise, in this case the direction of induced current
can be given by Fleming's right hand rule, and it will be along A-B-C-D.
As the coil is rotating clockwise, after half of the time period, the position of the coil will be as in second case of
above figure. In this case, the direction of the induced current according to Fleming's right hand rule will be along D-
C-B-A. It shows that, the direction of the current changes after half of the time period, that means we get an alternating
current.
It these alternators, slip rings and brushes are eliminated that is the reason behind its name Brushless Alternator.
The components of alternator are as follows. There is a stator body and rotor assembly. Stator body houses the
main stator and the exciter stator. Similarly rotor assembly consists of a main rotor and the exciter rotor along with
the bridge rectifier assembly mounted on a plate attached to the rotor. The exciter stator has residual magnetism
present in it. When the rotor starts rotating AC output, is generated in the exciter rotor coil. This output is passed
through a bridge rectifier and is converted to DC and given to the main rotor. The moving main rotor generates
AC current in the stationary main stator coils. This is the final output of the alternator. The exciter plays a key role
in controlling the output of alternator. Supplies DC magnetising current to the rotor which is the field the main
alternator. Thus if we increase or decrease the amount of current to the stationary exciter field coils, the output of
main alternator can be varied.
Automatic Voltage Regulator
Automatic voltage regulator circuit performs this important operator of controlling the exciter current.
For example lets assume the output voltage is low, AVR senses this and increases excitation current in the exciter
stator. This in turn increases the output from the excitor rotor. This increased output is converted to DC fed to the
main rotor, thus increasing its magnetic field [Link] in increase in the output.
Similarly when the output is high, its works vice versa.
In a process control of voltage regulation by electronic AVR involves the following components
• voltage sensing unit – to check the present value of the voltage
• voltage comparing unit – to check error .i.e. difference in voltage
• amplifying unit – to amplify the error signal
• correcting unit – to apply actions to process control as per error to get desired output voltage
The basic block diagram is shown below:
The direct current derived from the alternator output through the transformer is rectified and filtered. Then it is applied
to a Wheatstone bridge which has fixed resistance on two arms and variable resistances (Zener diode voltage
reference) on the other two.
The Zener operate in the reverse breakdown mode, as these diodes are manufactured with a Zener breakdown voltage
of very low value. Zener diode voltage remains constant once breakdown voltage has occurred despite the change in
the [Link] implies that changes in applied voltage, while not affecting voltage across the diode, will cause a
change in resistance which permits the change in current. As with a Wheatstone bridge, imbalance of the resistance
changes the flow pattern and produces in the voltage measuring bridge an error signal.
The error signal can be amplified and used to control alternator excitation. Thus it can control the firing angle of
thyristors through a triggering circuit to give the desired voltage. It can be used in the statically excited alternator to
correct small errors through a magnetic amplifier arrangement. The error signal has also been amplified through
transistors in series, for excitation control.
34. What is True Power, Apparent Power, Power factor? What is leading and lagging power factor?
Inductive loads: Inductive loads include motors, transformers, and solenoids. In a purely inductive circuit, current
lags behind voltage by 90°. Current and voltage are said to be “out of phase.”
Capacitive loads: Capacitive loads include power factor correction capacitors and filtering capacitors. In a purely
capacitive circuit, current leads voltage by 90°.
Resistive loads: Resistive loads include devices such as heating elements and incandescent lighting. In a purely
resistive circuit, current and voltage rise and fall at the same time. They are said to be “in phase.
True Power: Power drawn by a resistive circuit is converted into useful work. This is known as the true power in a
resistive circuit. True power is measured in watts (W), kilowatts (kW), or megawatts (MW). In a DC circuit or in
a purely resistive AC circuit, true power can easily be determined by measuring voltage and current. True power in a
resistive circuit is equal to system voltage (V) times current (I).
for example, an incandescent light (resistive load) is connected to 120 VAC. The current meter shows the light is
drawing 0.833 amps. In this circuit, 100 watts of work is done (120 VAC x 0.833 amps).
Reactive Power: Reactive power is measured in volt-amps reactive (VAR). Reactive power represents the energy
alternately stored and returned to the system by capacitors and/or inductors. Although reactive power does not produce
useful work, it still needs to be generated and distributed to provide sufficient true power to enable electrical processes
to run.
Apparent Power: Apparent power is the vector sum of true power, which represents a purely resistive load, and
reactive power, which represents a purely reactive load.
Power Factor
Power factor (PF) is the ratio of true power (PT) to apparent power (PA) or a measurement of how much power is
consumed and how much power is returned to the source. Power factor is equal to the cosine of the angle theta in the
above diagram.
35. What will be the effect of reduced Power factor on Diesel Engines? How to improve Power factor?
It won’t effect much as True power (KW) is taken care by governor and Reactive Power (KVar) is taken care by
alternator. But still if power factor is not improved, the results are high cost of production of electricity, low efficiency,
High fuel consumption.
The ways to improve power factor are nothing but the ways to generate reactive power.
Capacitor or capacitor banks: Capacitors: Improving power factor means reducing the phase difference between
voltage and current. Since majority of loads are of inductive nature, they require some amount of reactive power for
them to function. This reactive power is provided by the capacitor or bank of capacitors installed parallel to the load.
Synchronous motors: When a Synchronous motor operates at No-Load and over-exited then it’s called a synchronous
Condenser. Whenever a Synchronous motor is over-exited then it provides leading current and works like a capacitor.
When a synchronous condenser is connected across supply voltage (in parallel) then it draws leading current and
partially eliminates the re-active component and this way, power factor is improved. Generally, synchronous
condenser is used to improve the power factor in large industries.
37. What is ICCP?
Cathodic protection is a method of corrosion control that can be applied to buried and submerged metallic structures.
The material to be protected is supplied with an external cathodic current. The electrochemical potential of the
protected material is moved in a negative direction to the immune area. The material is completely protected when it
reaches the protection potential.
There are two ways of cathodic protection:
1. Sacrificial anode
2. Impressed current
For larger structures, galvanic anodes can’t economically deliver enough current to provide complete
protection. In this method, the metal to be protected is connected to an insoluble anode and current is passed
using DC power source (or AC powered transformer rectifier) opposite to the corrosion current, so that the
corroding metal gets converted from anode to cathode and is protected from corrosion.
Insoluble anodes are like graphite, platinum, stainless steel, platinised titanium etc.
In this method, we impress a direct current between an inert anode and the structure to be protected. Since electrons
flow to the structure, it is protected from becoming the source of electrons (anode).The impressed current cathodic
protection system usually provides electrodes of a much longer lifespan than a sacrificial anode.
Impressed current cathodic protection systems are the ultimate state-of-the-art, long-term solution to corrosion
problems, and are recognized as a superior alternative to sacrificial anode systems, which require frequent
replacement. Impressed current cathodic protection systems are preferred by ship owners because they reduce fuel cost
and maintenance.
Our systems work by supplying a controlled amount of DC current to submerged surfaces using highly reliable mixed
metal oxide anodes and zinc reference electrodes. This electrical current constantly monitored and regulated by the
system itself to prevent the electrochemical action of galvanic corrosion before it begins.
For more than 25 years, sea-going vessels of every type and size – oil tankers, LNG carriers, cruise ships, pleasure
craft, workboats, semi-submersibles, and more – have benefited from the 24-hour protection provided by Impressed
current cathodic protection systems against the costly, corrosive effects of electrolysis
System Advantage
Increased life of rudders, shafts, struts, and propellers as well as any other underwater parts affected by electrolysis
Anodes are light, sturdy and compact for easy shipping, storage, and installation
Anodes, reference cells, and automatic control systems maintain just the right amount of protection for underwater
hulls and fittings, unlike standard zinc anodes, which can’t adjust to changes in salinity or compensate for extreme
paint loss
Automatic control equipment ensures reliable, simple operation
Optimum documented corrosion protection at a minimum overall cost
Only one installation required for the life of the vessel or structure
Increased dry-dock interval
Reference Cell / Electrode
The correct value of protection correct can be determined by the reference cell. It measures the voltage between the
hull & seawater. These are either Zinc (Zn) or Silver (Ag) attached to the hull, but insulated from it, below the water
line.
Power Supply Unit / Control Panel
Each standard ICCP system utilizes a solid-state controller which monitors and controls the protection as measured by
the Zinc Reference electrode. Anode current automatically increases when the electrode potential falls below the
designated control value. An over- and an under-potential alarm is provided with the system package.
Any Voltage used on board a ship if less than 1kV(1000 V) then it is called as LV (Low Voltage) system and any
voltage above 1kV is termed as High Voltage.
Typical Marine HV systems operate usually at 3.3kV or 6.6kV. Passenger Liners like QE2 operate at 10kV.
The design benefits relate to the simple ohms law relationship that current (for a given power) is reduced as the
voltage is increased. Working at high voltage significantly reduces the relative overall size and weight of electrical
power equipment.
Insulation is to be tested by 5000V DC.
AS PER OHMS LAW
POWER = VOLTAGE x CURRENT
For a given Power,
Higher the Voltage, Lesser is the Current
440 KW = 440,000 Watts
= 440 Volts x 1000 Amps
=1100 Volts x 400 Amps
=11000 Volts x 40 Amps
– When large loads are connected to the LV system the magnitude of current flow becomes too large resulting in
overheating due to high iron and copper losses.
P = VI CosФ
Copper loss =I² R [kW]
THE MAJOR DIFFERENCES BETWEEN HIGH VOLTAGE SUPPLY AND LOW VOLTAGE SUPPLY ON
BOARD SHIPS ARE:
1. High voltage systems are more extensive with complex networks and connections,
2. Isolated equipment MUST BE earthed down
3. Access to high voltage areas should be strictly limited and controlled
4. Isolation procedures are more involved
5. Switching strategies should be formulated and recorded
6. Specific high voltage test probes and instruments must be used
7. Diagnostic insulation resistance testing is necessary
8. High voltage systems are usually earthed neutral and use current limiting resistors
9. Special high voltage circuit breakers have to be installed
Advantages:
For a given power, Higher voltage means Lower current, resulting in:
– Reduction in size of generators, motors, cables etc.
– Saving of Space and weight
– Ease of Installation
– Reduction in cost of Installation
– Lower losses – more efficient utilization of generated power
– Reduction in short circuit levels in the system which decides the design and application of the electrical equipment
used in the power system.
Disadvantages:
1. Higher Insulation Requirements for cables and equipment used in the system.
2. Higher risk factor and the necessity for strict adherence to stringent safety procedures.
The HV system has separate device called negative phase sequence (NPS) relay. It is used to measure the amount of
unbalance in the motor current.
Arcing:
An unintentional electric arc occurs during opening of a breaker, contactor or switch, when the circuit tries to maintain
itself in the form of an arc.
During an insulation failure, when current flows to ground or any other short circuit path in the form of accidental tool
slipping between conducting surfaces, causing a short circuit.
Results of an electric arc:
Temperatures at the arc terminals can reach or exceed 35,000° f or 20,000˚c or four times the temperature of sun’s
surface. The heat and intense light at the point of arc is called the arc flash.
Air surrounding the arc is instantly heated and the conductors are vaporised causing a pressure wave termed as ARC
BLAST.
Harmonic filters:
Three-phase harmonic filters are shunt elements that are used in power systems for decreasing voltage distortion and
for power factor correction. Nonlinear elements such as power electronic converters generate harmonic currents
or harmonicvoltages, which are injected into the power system.
39. What is earthed neutral and isolated neutral system and neutral earthing resistor?
In neutral insulated system, the star point of the source is not connected to earth. Hence there happens to be only 3
leads (3 phase wires R,Y,B) emanating from the source.
In neutral earthed system, the star point is earthed to ground. So 4 wires emanating from source (3 phase and 1
neutral).
• Open circuit fault (A) : due to break in the conductor so that current cannot flow.
• Short circuit fault (C) : due to break in insulation so that two conductor touches each other giving a short
path to current and allowing a very large current to bypass the load.
• Earth Fault (B) : This is also due to break in insulation, but the conductor touches the metal enclosure or the
hull indirectly.
The discussion of the two types of electrical system(Insulated or earthed neutral) depends on a large extent to the earth
fault occurring in the circuit.
If a single earth fault occurs in the line of an earthed neutral system, then it would be equivalent to a short circuit fault.
The reason being, the earthed neutral creates a closed path for the earth current to flow through the hull of the
[Link] this path has a minimal resistance, the earth current can increase to a very large extent.
Onboard ship, if the earth current increases beyond the current rating of the generator, the entire system may collapse
causing irreparable damage. To limit this earth current, a Neutral Earthing Resistor is connected to the earthed
neutral of the source. This resistor is of sufficient ohmic value to limit the earth current within rating of the generator.
However, the magnitude of earth current is sufficiently large to operate the tripping mechanism of the faulted
equipment immediately isolating it from supply and rendering it safe.
Onboard a ship, the priority requirement is to maintain continuity of the electrical supply to essential equipment in
event of a single earth fault [Link] this in mind, it is well understood that onboard a ship, a neutral
insulated system is to be used. And, in shore installations neutral earthed system is used.
Shipboard main LV systems at 440 V are normally provided with neutral insulated system. On the other hand HV
system (1000 V to 3.3 KV) are usually provided with neutral earthed system via a neutral earthing resistor.
Both the Insulated neutral and Earthed neutral system have got their own advantages and disadvantages. Where it is
easier in the earthed neutral system to detect any earth faults in system, it is easier in isolated neutral system to
maintain the continuity of service.
As it can be seen in the diagram, the batteries are in standby mode with the charging switches C closed and the load
switches L open. The positions of these switches are held with the help of an electromagnetic coil against the spring
tension. The electromagnetic coil gets its supply from the main power source available on the ship. As soon as there is
a loss of main power, the electromagnetic coil loses its power and the batteries are connected to load switch L which
gets disconnected from the charging switch C.
Once the power is available from the main system, the batteries are connected back to the charging circuit again
manually. Also, there is a test switch provided to test the system as a part of the routine tests.
To measure the condition of a battery, generally two parameters are taken, specific gravity and voltage. The specific
gravity is measured using a hydrometer while the latter is measured using a voltage meter.
Ni-Cd Battery
Charged→ Voltage=1.2V Specific gravity=1.21
Discharged→ Voltage=1.1V Specific gravity=1.17
Operation
Referring to Figure 22.11, when the double pole switch is closed the navigation light is illuminated. Current in the
relay circuit causes the relay coil to energise, which pulls the NC (normally closed) contact open so that the audio
alarm (buzzer) circuit is now open. Only a low voltage lamp is needed for the indicating lamp. This ensures a small
voltage drop across that part of the circuit. Keeping regulatory requirements in mind, if the indicating lamp fails, the
circuit is completed through the back-up resistor, so the navigation light does not fail.
If the navigation light fails, or if a fuse blows, the current in the circuit ceases and the relay is de-energised. The NC
contact springs back to activate the buzzer circuit. In case of failure of the ship's mains, the double pole switch may be
changed over to emergency supply.
• Air Circuit breaker: This uses air as interrupting and insulating medium. These are further classified as Air
magnetic circuit breakers and Air blast circuit breakers.
• Moulded case circuit breaker (MCCB’s): These current ratings are higher at 1000A. This has earth fault
protection in addition to over current protection. The trip settings of the breaker can vary easily.
• Miniature Circuit Breaker (MCB’s): These current ratings are less than 100A with only one over current
protection in built within it. The trip settings are not adjustable in MCB.
• Vaccum type breakers: This uses vacuum as the interrupting medium because of its high dielectric and
diffusive properties as interrupting medium.
• Incoming power has to be removed, lock out tag out has to be done.
• Manually operate operating mechanism to check if it is working properly.
• Inspection of contacts caused by arcing or corrosion.
• Lubrication of mechanical contacts.
• Arc chutes are removed, inspected for broken parts and erosion of the steel splitter plates.
49. What is Zener diode?
A heavily doped semiconductor diode which is designed to operate in reverse direction is known as the Zener diode.
Diodes generally are known as a device that allows the flow of current in one direction (forward biased) and offers
resistance to the flow of current when used in reverse bias. Whereas Zener Diode not only allow the flow of current
when used in forward bias, but they also allow the flow of current when used in the reversed bias so far the applied
voltage is above the breakdown voltage known as the Zener Breakdown Voltage. Or in other words Breakdown
voltage is the voltage, on which Zener Diode starts conducting in reverse direction.
As the reverse voltage applied to the Zener diode increases towards the specified Breakdown Voltage (Vz), a current
starts flowing through the diode and this current is known as the Zener Current and this process is known as Avalanche
Breakdown.
.
In Experiment A, a 12V zener diode is connected in reversed biased as shown in the image and it can be seen that the
zener diode blocked the voltage effectively because it was less/equal to the breakdown voltage of the particular zener
diode and the lamp thus stayed off.
In Experiment B, a 6v Zener Diode used is conducting (the bulb comes on) in reverse biased because the applied
voltage is greater than its breakdown voltage and thus shows that the breakdown region is the region of operation of
the zener diode.
The VI characteristic graph of the Zener diode is shown in the figure below.
This curve shows that the Zener diode, when connected in forwarding bias,
behaves like an ordinary diode. But when the reverse voltage applies across
it and the reverse voltage rises beyond the predetermined rating, the
Zener breakdown occurs in the diode. At Zener breakdown voltage the
current starts flowing in the reverse direction.
50. Transformer?
It is an static apparatus in which electric power in
one circuit is transformed into electric power
of same frequency in other circuit. It can raise
or lower the voltage in a circuit but with
corresponding raise or decrease in current.
Its done by mutual induction, two circuits are
linked by magnetic flux.
Step up transformers:
Secondary coil has more number of turns than primary.
Step down transformers:
Primary coil has more number of turns than secondary.
The HV side of the transformer is kept open. Now with the help of variac, applied voltage gets slowly increased until
the voltmeter gives reading equal to the rated voltage of the LV side. After reaching rated LV side voltage, we record
all the three instruments reading (Voltmeter, Ammeter and Wattmeter readings).
The ammeter reading gives the no load current Ie. As no load current Ie is quite small compared to rated current of the
transformer, the voltage drops due to this current that can be taken as negligible.
Since voltmeter reading V1 can be considered equal to the secondary induced voltage of the transformer, wattmeter
reading indicates the input power during the test. As the transformer is open circuited, there is no output, hence the
input power here consists of core losses in transformer and copper loss in transformer during no load condition. But as
said earlier, the no-load current in the transformer is quite small compared to the full load current so, we can neglect
the copper loss due to the no-load current. Hence, can take the wattmeter reading as equal to the core losses in the
transformer.
Therefore it is seen that the open circuit test on transformer is used to determine core losses in transformer
Short Circuit Test on Transformer
The connection diagram for short circuit test on transformer is shown in the figure. A voltmeter, wattmeter, and an
ammeter are connected in HV side of the transformer as shown. The voltage at rated frequency is applied to that HV
side with the help of a variac of variable ratio auto transformer. We short-circuit the LV side of the transformer. Now
with the help of variac applied voltage is slowly increased until the wattmeter, and an ammeter gives reading equal to
the rated current of the HV side.
.After reaching rated current of HV side, we record all the three instruments reading (Voltmeter, Ammeter and Watt-
meter readings). The ammeter reading gives the primary equivalent of full load current IL. As the voltage applied for
full load current in short circuit test on transformer is quite small compared to the rated primary voltage of the
transformer, the core losses in transformer can be taken as negligible here.
Let’s say, voltmeter reading is Vsc. The watt-meter reading indicates the input power during the test. As we have short-
circuited the transformer, there is no output; hence the input power here consists of copper losses in the transformer.
Since the applied voltage Vscis short circuit voltage in the transformer and hence it is quite small compared to the rated
voltage, so, we can neglect the core loss due to the small applied voltage. Hence the wattmeter reading can be taken as
equal to copper losses in the transformer.
Hence the short-circuit test of a transformer is used to determine copper losses in the transformer at full load.
It is done only by 5000 V DC megger test. It is used to determine the fitness of a motor or generator for use. This
index gives an indication of build up of dirt or moisture, deterioration of insulation.
Before measuring IR, we should remove all connections to the machine and discharge windings to ground
machine frame. Using meghometer, an electric current of either 500 or 1000 Volts DC should be applied between
winding and ground. Voltage that is applied should be kept constant for 10 minutes. An initial reading of IR is
recorded at 1 minute and second reading is recorded at 10 minutes. The ratio between 10 minute and 1 minute
measurements gives polarization index. The polarization index should be atleast 2.0
• Unsealed batteries contains a liquid combination of water and sulphuric acid while sealed batteries hold
only enough liquid to allow the electrolyte to flow.
• Unsealed batteries needs more maintenance while sealed batteries are maintenance free.
• Unsealed batteries need regular care to maintain correct level of liquid while sealed batteries do not need
as electrolyte is completely absorbed in the separator and do not need water to add.
• Unsealed batteries lasts longer as compared to sealed ones.
• Unsealed batteries takes more time to get charged.
• Unsealed batteries cannot withstand with too much varying climates.
• Unsealed batteries used for power backup, telecom and utility etc. While sealed batteries are used in
robotics and uninterrupted power system.
Consider the typical control system shown in above figure in which the process variable of a process has to be
maintained at a particular level. Assume that the process variable is temperature (in centigrade). In order to measure
the process variable (i.e., temperature), a sensor is used (let us say an RTD).
A set point is the desired response of the process. Suppose the process has to be maintained at 80 degree centigrade,
and then the set point is 80 degree centigrade. Assume that the measured temperature from the sensor is 50 degree
centigrade, (which is nothing but a process variable) but the temperature set point is 80 degree centigrade.
This deviation of actual value from the desired value in the PID control algorithm causes to produce the output to the
actuator (here it is a heater) depending on the combination of proportional, integral and derivative responses. So the
PID controller continuously varies the output to the actuator till the process variable settle down to the set value. This
is also called as closed loop feedback control system.
Programmable Logic Controller (PLC) is a digital computer used for the automation of various electro-mechanical
processes in industries. These controllers are specially designed to survive in harsh situations and shielded from heat,
cold, dust, and moisture etc. PLC consists of a microprocessor which is programmed using the computer language.
The program is written on a computer and is downloaded to the PLC via cable. These loaded programs are stored in
non – volatile memory of the PLC. During the transition of relay control panels to PLC, the hard wired relay logic was
exchanged for the program fed by the user. A visual programming language known as the Ladder Logic was created to
program the PLC.
Components of a PLC system are CPU, Memory, Input /Output, Power supply unit, and programming device. Below
is a diagram of the system overview of PLC.
• CPU – Keeps checking the PLC controller to avoid errors. They perform functions including logic operations,
arithmetic operations, computer interface and many more.
• Memory – Fixed data is used by the CPU. System (ROM) stores the data permanently for the operating
system. RAM stores the information of the status of input and output devices, and the values of timers,
counters and other internal devices.
• I/O section – Input keeps a track on field devices which includes sensors, switches.
• O/P Section - Output has a control over the other devices which includes motors, pumps, lights and solenoids.
The I/O ports are based on Reduced Instruction Set Computer (RISC).
• Power supply – Certain PLCs have an isolated power supply. But, most of the PLCs work at 220VAC or
24VDC.
• Programming device – This device is used to feed the program into the memory of the processor. The
program is first fed to the programming device and later it is transmitted to the PLC’s memory.
• System Buses – Buses are the paths through which the digital signal flows internally of the PLC. The four
system buses are:
· Data bus is used by the CPU to transfer data among different elements.
· Control bus transfers signals related to the action that are controlled internally.
· Address bus sends the location’s addresses to access the data.
· System bus helps the I/O port and I/O unit to communicate with each other.
The IGBT (insulated gate bipolar transistor) is a three-terminal electronic component, and these terminals are termed
as emitter, collector and gate. Two of its terminals namely collector and emitter are associated with a conductance path
and the remaining terminal ‘G’ is associated with its [Link] sum of amplification is achieved by the IGBT is a
radio between its input and output signal.
An IGBT is simply switched “ON” and “OFF” by triggering and disabling its Gate terminal. A constant +Ve voltage
i/p signal across the ‘G’ and the ‘E’ will retain the device in its “ON” state, while deduction of the i/p signal will cause
it to turn “OFF”
IGBT Characteristics
The induction gate bipolar transistor is a voltage controlled device, it only needs a small amount of voltage on the gate
terminal to continue conduction through the device
IGBT can switch current in the unidirectional that is in the forward direction( Collector to Emitter)
The main advantages of IGBT compared with various kinds of transistors are low ON resistance, high voltage -
capacity, fast switching speed, ease of drive and joined with zero gate drive current creates a good option for sensible
speed, and various high voltage applications like PWM, SMPS, variable speed control, AC to DC converter powered
by solar and frequency converter applications which operates with a hundred’s of KHz.
The main disadvantages are: The speed of the Switching is lower to a Power MOSFET and higher to a BJT. The
collector current following due to the minority charge carriers roots the turnoff speed to be slow. 2. There is a chance
of latch up due to the internal structure of PNPN thyristor.
The two main features of variable frequency drive are adjustable speeds and soft start/stop capabilities. These two
features make VFD’s a powerful controller to control the AC motors. VFD consists of mainly four sections; those are
rectifier, intermediate DC link, inverter and controlling circuit.
Rectifier:
It is the first stage of variable frequency drive. It converts AC power fed from mains to DC power. This section can be
unidirectional or bidirectional based on the application used like four quadrant operation of the motor. It utilizes
diodes, SCR’s, transistors and other electronic switching devices.
If it uses diodes, converted DC power is uncontrolled output while using SCR, DC output power is varied by gate
control. A minimum of six diodes are required for the three phase conversion, so the rectifier unit is considered as six
pulse converter.
DC bus:
DC power from the rectifier section is fed to DC link. This section consists of capacitors and inductors to smooth
against ripples and store the DC power. The main function of DC link is to receive, store and deliver DC power.
Inverter:
This section comprises of electronic switches like transistors, thyristors, IGBT, etc. It receives DC power from DC
link and converts into AC which is delivered to the motor. It uses modulation techniques like pulse width
modulation by to vary output frequency for controlling the speed of induction motor.
Control circuit:
It consists of microprocessor unit and performs various functions like controlling, configuring drive settings, fault
conditions and interfacing communication protocols. It receives feedback signal from motor as current speed reference
and accordingly regulates the ratio of voltage to frequency to control motor speed.
Advantages of VFD
• Energy saving
• Limits starting current
• Smooth operation
• High power factor
• Easy installation.
59. How welding transformer works
More number of turns on primary and less number of turns on secondary, which produces high current and
low voltage. One end connected to the secondary electrode and other to work piece and other to work piece to
be welded. Due to high contact resistance, very high current flows. Therefore more I2R heat produces and
electrode melts and fills the gap between the pieces.
60. What happen if one diode in exciter gets (a) open circuit (b) short circuit?
(a) Open circuit: This will not have much problem because other diode will supply at main field. In
manual mode, generator voltage will slightly reduced whereas in AVR, it will automatically maintain
the exciter field current and hence generator voltage and hence exciter will gradually overheat.
The ship has variable frequency drive (VFD) to convert it to 440 Volt and 60 Hz.
To avoid mechanical contact between rotor and stator, and to determine the condition of bearings.
64. Motor is not starting, What are the checks can be done?
• Single phasing
• Overload
• Bearing damage
• Fan not working.
Synchronous motor:
Synchronous motors are not self starting motors
Connection of 3 phase supply to stator will produce a rotating magnetic
field. Effect of rotating magnetic field on rotor is attractive and repulsive,
hence rotor inertia will prevent rotation.
So the rotor has to be brought to synchronous speed and the rotor poles
and rotating magnetic field will get locked together.
One method of starting synchronous motor is by having solid copper bars
permanently embedded in the rotor pole lips and short circuited by rings to
make it as a temporary induction motor. When machine runs at around 95%
synchronous speed, DC excitation is switched on and rotor is pulled into
synchronisation. Use onboard in Gyro compass, Viscotherm etc.
Induction motors:
Three phase AC supply voltage are connected to the three stator phase
windings, the resulting phase currents to produce a magnetic field
which rotates at a speed known as synchronous speed around the
stator core.
The stator magnetic flux cuts through the rotor copper bars conductors
To induce alternating emf, as the conductors are connected, so it
produces rotor currents.
As the current flows through the conductor, the flux induces on it. The
direction of rotor flux is same as that of the rotor current.
Now we have two fluxes one because of the rotor and another because
of the stator. These fluxes interact each other. On one end of the conductor
the fluxes cancel each other, and on the other end, the density of the flux is
very high. Thus, the high-density flux tries to push the conductor of rotor
towards the low-density flux region. This phenomenon induces the torque on
the conductor, and this torque is known as the electromagnetic torque.
Applications: Lifts, cranes, hoists, large capacity exhaust fans, driving lathe machines, Crushers etc.
• Applications: Pumps Compressors, Small fans, Mixers, Toys, High speed vaccum cleaners,
Electric shavers, Drilling machines
Preferential trip is a kind of electrical arrangement on ship which is designed to disconnect the non-essential circuit i.e.
non-essential load from the main bus bar in case of partial failure or overload of the main supply. The non-essential
circuits or loads on ships are air conditioning, exhaust and ventilation fans, and galley equipments which can be
disconnected momentarily and can be connected again after fault finding. The main advantage of preferential trip is
that it helps in preventing the operation of main circuit breaker trip and loss of power on essential services and thus
prevents blackout and overloading of generator. It is always set at 110% of load.
Construction:
The preferential trip circuit consists of an electromagnetic coil and a dashpot arrangement to provide some delay to
disconnect the non-essential circuits. Along with this, there is also an alarm system provided, which functions as soon
as an overload is detected and trips start operating. There are some mechanical linkages also in the circuit which
instantaneously operates the circuit and completes the circuit for preferential trips.
The dashpot arrangement consists of a small piston with a small orifice and which is placed inside a small cylinder
assembly. This piston moves up against the fluid silicon and the time delay is governed by the orifice in the piston.
Working:
The current passes through the electromagnetic coil and the linkages are kept from contacting using a spring
arrangement. As soon as the current value increases the limit, the electromagnetic coil pulls the linkage up against the
spring force and operates the instantaneous circuit and the alarm system. The lower linkage completes the circuit for
the preferential trip circuit.
The current passes through the coil in the preferential trip circuit which pulls the piston in the dashpot arrangement.
The movement of this piston is governed by the diameter of the orifice and the time delay made by the same. The
preferential trip operates at 5, 10 and 15 seconds and the load is removed accordingly. If the overload still persists,
then an audible and visual alarm is sounded.
The preferential trip is one of those important electrical circuit diagrams which help in removing the excessive load
from the main bus bar, thus preventing situation like blackout which is a dangerous incident to ship, especially when
the ship is sailing in restricted or congested waters.
Order of tripping varies in each vessel, most of the ships have the following order:
5 seconds = Air condition and ventilation
10 seconds = Refrigerated cargo plant
15 seconds = Deck equipment
If over current still exist after tripping of non-essential services, then overload trip gets activated after 20 seconds
and trips the whole circuit.
Voltage and frequency of the inverter supply to the a.c. system must be kept constant within limits. These
characteristics are controlled for a normal alternator by the automatic voltage regulator and the governor of the prime
mover, respectively. They could be controlled for the shaft alternator inverter by a separate diesel-driven synchronous
alternator running in parallel. The extra alternator could also supply other effects necessary to the proper functioning
of an inverter, but the objective of gaining fuel and maintenance economy with a shaft alternator would be lost.
Fortunately the benefits can be obtained from a synchronous compensator (sometimes termed a synchronous
condenser), Which does not require a prime mover or driving motor except for starting. The compensator may be an
exclusive device with its own starter motor or it may be an ordinary alternator with a clutch on the drive shaft from the
prime mover.
The a.c. generator set that fulfils the role of synchronous compensator for the system shown is at the top right of the
sketch. The diesel prime mover for the compensator is started and used to bring it up to speed for connection to the
switchboard. The excitation is then set to provide the reactive power, and finally the clutch is opened, the diesel shut
down and the synchronous machine then continues to rotate independently like a synchronous motor, at a speed
corresponding to the frequency of the a.c. system.
A synchronous compensator is used with the monitoring and controlling system, to dictate or define the frequency. It
also maintains constant a.c. system Voltage, damps any harmonics and meets the reactive power requirements of the
system and converter, as well as supplying, in the event of a short circuit, the current necessary to operate trips. The
cooling arrangements for static frequency converters included . The provision of fans as well as the necessary heat
sinks for thyristors.
• The biggest advantage- it dose not cause air pollution unlike other traditional methods of power production in
ship. Moreover, noise level is also low.
• It is more cost effective as it dose not requires expensive fuel for power generation as main engine itself is a
prime mover.
• The wear and tear and hence the maintenance schedule and costs for the same reduces for independent driven
generator.
• Installation space is less as it is installed close or in line with the shaft of the main engine.
• The investment cost depends on the type and system of the shaft generator but for a basic designed shaft
generator it is low.
• The installation cost for shaft generator is also low as it doesn’t require separate foundation, prime mover or
exhaust system. Even time for installation is also less.
• Low spare parts cost and man – hour cost as the schedule maintenance period for shaft generator has larger
time gap as compared to diesel generator.
o Regular cleaning of dust, dirt, oil and grease from inside and outside of motor.
o The insulation is cleaned by brushing and spraying de-greasant liquids.
o Replacement of worn bearings.
o Ensuring air gap between rotor and stator.
o Finding IR between phases and between phase and earth.
o On the contactors and relays,
▪ Check for signs of overheating, loose connections.
▪ Remove any dust and grease from magnet faces.
▪ Ensuring magnet armature of contactors moves freely.
o On the contacts,
▪ Check for excessive pitting and roughness due to burning
▪ Checks on contact spring pressure.
74. What are the tests to be done on motor opened for overhaul?
The circuit (or instrument) in the hazardous area operates normally until a fault condition occurs. In the
illustration above, a fault voltage is applied to the terminals of the intrinsic safety barrier thus causing the
zener diodes to “operate” and safely pass fault current to ground (rather than into the hazardous area). As a
result of the fault current, the fuse will open and the complete loop maintains safety.
77. What are the electrical maintenance carried out in Dry Dock?