FOOTING : MOTOR & DB ROOM External Wall

No of floors 2 Steel Design


Pannel size L(ft) B(ft) fc'

Assumed Footing
12 21.4 thickness (d) 8 in fy
Equivalent Width For S/S 14.27 ft Slab Thickness (in) 6 in
Equivalent Width For L/S -1.29 ft Qu 2 ksf ((1.7L.L+1.4D.L)/ bx1)
Width of Projected Slab(ft) 0.00 ft
Wall Width 1.25 ft
Parapet Height 2 ft
Floor Height 21 ft
Ht. of Wall Below Plinth 4 ft
Additional ht. of steps 0 ft (L)
Total Wall Height 27 ft Mu 0 kip-ft. 1/2*Qu*(b-a)/2^2
LOADS
Water Tank Load 0 kips (B)
SLAB LOADING Vc 5 kip/ft .75*(2*(fc')^.5*12*d)
L.L (live load) 30 psf
D.L(dead load imposed) 60 psf Vu 1 kips Qu*((b-a)/2-d)
D.L(self wt. of slab) 75 psf
Water Tank Load on Slab 0.00 psf
Total Load (Ws) 165 psf 210 R 10
Load from Slab L/S (0.21) k/ft -0.27 steel ratio 0.0001
Projected Slab Load - k/ft
Vertical Projection Load - k/ft Load from Slab S/S 2.35 k/ft
Wall Load 4.05 k/ft 4.86 Wall Load 4.05 k/ft min. steel ratio 0.002
Total Load on L/S 3.84 k/ft 4.59 Total Load on S/S 6.40 k/ft Selected Steel Rat 0.002
q net(bearing capacity) 0.75 tsf
1.653 psf As 0.192 in2/sft
Footing width (reqrd.) Footing width (reqrd.)
along L 2.32 ft along B 3.87 ft bar # 3 0.11 in2
selected width 'b' in ft 3.00 ft selected width 'b' in ft 3.00 ft spacing 6.91 in 6.00 in

FOOTING No. : External Wall


No of floors 2 Steel Design
Pannel size L(ft) B(ft) fc'

Assumed Footing
18 18 slab thickness (in) 4.8 in thickness (d) 9 in fy
slab thickness (in) 5 in
contr. Area 162 Qu 5,726 psf ((1.7L.L+1.4D.L)/ bx1)
wall width (ft) 0.75 (L)
wall height.(ft) 27 Mu 5,413 lb-ft. 1/8*Qu*(b-a)^2
LOADS (B)
SLAB LOADING Vc 8873 lbs/ft .75*(2*(fc')^.5*12*d)
L.L (live load) 35 psf
D.L(dead load imposed) 80 psf Vu 3579 lbs Qu*((b-a)/2-d)
D.L(self wt. of slab) 62.5 psf
Total Load (w) 178 psf R 123
Total Load (W-1) 57.51 klf Total Load (W-1) 57.5 klf steel ratio 0.0010
Wall Loading (W-2) 2.53 klf Wall Loading (W-2) 2.53 klf min. steel ratio 0.0018
Wt-L 5.73 klf Wt-B 5.73 Selected Steel Rat 0.0018
q net(bearing capacity) 0.75 tsf
1.653 psf As 0.1944 in2/sft
Footing width (reqrd.) Footing width (reqrd.)
along L 3.46 ft along B 3.46 ft bar # 3 0.11 in2
selected width 'b' in ft 3.50 ft selected width 'b' in ft 3.50 ft spacing 6.82 in 6.00 in
lx/ly 1.783333
2500 psi

60000 psi
D.L
1.7L.L+1.4D.L)/ bx1)

2*Qu*(b-a)/2^2

5*(2*(fc')^.5*12*d)
3000 psi

60000 psi

1.7L.L+1.4D.L)/ bx1)

8*Qu*(b-a)^2

5*(2*(fc')^.5*12*d)
FOOTING : MOTOR & DB ROOM External Wall
No of floors 2 Steel Design
Pannel size L(ft) B(ft) fc'

Assumed Footing
21.4 12 thickness (d) 6 in fy
Equivalent Width For S/S 8.00 ft Slab Thickness (in) 6 in
Equivalent Width For L/S 10.74 ft Qu 2 ksf ((1.7L.L+1.4D.L)/ bx1)
Width of Projected Slab(ft) 0.00 ft
Wall Width 1.25 ft
Parapet Height 2 ft
Floor Height 11 ft
Ht. of Wall Below Plinth 8 ft
Additional ht. of steps 0 ft (L)
Total Wall Height 32 ft Mu 2 kip-ft. 1/2*Qu*(b-a)/2^2
LOADS
Water Tank Load 0 kips (B)
SLAB LOADING Vc 4 kip/ft .75*(2*(fc')^.5*12*d)
L.L (live load) 40 psf
D.L(dead load imposed) 65 psf Vu 2 kips Qu*((b-a)/2-d)
D.L(self wt. of slab) 75 psf
Water Tank Load on Slab 0.00 psf
Total Load (Ws) 180 psf 219 R 133
Load from Slab L/S 1.93 k/ft 2.3526 steel ratio 0.0011
Projected Slab Load - k/ft
Vertical Projection Load - k/ft Load from Slab S/S 1.44 k/ft
Wall Load 4.80 k/ft 5.76 Wall Load 4.80 k/ft min. steel ratio 0.002
Total Load on L/S 6.73 k/ft 8.11 Total Load on S/S 6.24 k/ft Selected Steel Rat 0.002
q net(bearing capacity) 0.75 tsf
1.653 psf As 0.144 in2/sft
Footing width (reqrd.) Footing width (reqrd.)
along L 4.07 ft along B 3.77 ft bar # 3 0.11 in2
selected width 'b' in ft 4.00 ft selected width 'b' in ft 4.00 ft spacing 9.21 in 6.00 in

FOOTING No. : External Wall


No of floors 2 Steel Design
Pannel size L(ft) B(ft) fc'

Assumed Footing
18 18 slab thickness (in) 4.8 in thickness (d) 9 in fy
slab thickness (in) 5 in
contr. Area 162 Qu 5,726 psf ((1.7L.L+1.4D.L)/ bx1)
wall width (ft) 0.75 (L)
wall height.(ft) 27 Mu 5,413 lb-ft. 1/8*Qu*(b-a)^2
LOADS (B)
SLAB LOADING Vc 8873 lbs/ft .75*(2*(fc')^.5*12*d)
L.L (live load) 35 psf
D.L(dead load imposed) 80 psf Vu 3579 lbs Qu*((b-a)/2-d)
D.L(self wt. of slab) 62.5 psf
Total Load (w) 178 psf R 123
Total Load (W-1) 57.51 klf Total Load (W-1) 57.5 klf steel ratio 0.0010
Wall Loading (W-2) 2.53 klf Wall Loading (W-2) 2.53 klf min. steel ratio 0.0018
Wt-L 5.73 klf Wt-B 5.73 Selected Steel Rat 0.0018
q net(bearing capacity) 0.75 tsf
1.653 psf As 0.1944 in2/sft
Footing width (reqrd.) Footing width (reqrd.)
along L 3.46 ft along B 3.46 ft bar # 3 0.11 in2
selected width 'b' in ft 3.50 ft selected width 'b' in ft 3.50 ft spacing 6.82 in 6.00 in
lx/ly 0.560748
2500 psi

60000 psi
D.L
1.7L.L+1.4D.L)/ bx1)

2*Qu*(b-a)/2^2

5*(2*(fc')^.5*12*d)
3000 psi

60000 psi

1.7L.L+1.4D.L)/ bx1)

8*Qu*(b-a)^2

5*(2*(fc')^.5*12*d)
Project: SAFE CITY
Structure: PPIC3 Residences
Reference: Drawing No.
Designed by: ABC
Engineering Consultancy Checked by: ABC
Services Punjab Pvt Ltd. Date: 30/11/2017

1. Input Data: Hp
n = 1 nos. (No. of floors) Icant
h
lx = 16 ft. (Short side of panel)
ly = 31.25 ft. (Long side of panel)
lcant. = 0 ft. (Cantilever width)
tp
tw = 9 in. (Masonry thickness) Hf
tp = 0 in. (Plaster thickness)
Hbp = 6 ft. (Height below plinth, see figure)
Hf = 15 ft. (Floor height)
h
Hp = 0 ft. (Height of parapet)
st1 = 6 in. (Height of step 1)
tw
st2 = 6 in. (Height of step 2)
w1 = 22.5 in. (Width of step 1) Hf
w2 = 18 in. (Width of step 2)
γc = 150 pcf (Unit weight of concrete)
γm = 120 pcf (Unit weight of masonry) FFL
st2 w2
γfinishes = 120 pcf (Unit weight of finishes) st1 w1 Hbp
qall = 0.5 tsf (Allowable Bearing Capacity of Soil) Hfoun
= 1.102 ksf
Wpro
2. Floor Service Loads: Figure 1: Wall Foundation Section
[Link]. Floor h DL hff SDL LL
(in) (psf) (in) (psf) (psf)
1 GF 6 75 6 60 20
2 Roof 0 0 0 0 0
3 First Floor 0 0 0 0 0
4 0 0 0 0 0

3. Equivalent Slab Widths: 18 20


B1 = 10.33 ft.
B2
B3
B4
=
=
=
5.17
13.20
6.60
ft.
ft.
ft.
13
C
Where,
14

Figure 2: Enter letter "C" in panel to be analyzed.

(Reference. Concrete Structures,


Part-I by Zahid Ahmad Siddique, pg. 90 - 92)

4. Total Service (ws) & Factored (wu) Line Loads:


4a. Service Loads:
[Link]. Wall DL SDL LL ws
Wall Plaster Slab D+L
(kip/ft) (kip/ft) (kip/ft) (kip/ft) (kip/ft) (kip/ft)
1 B1 2.09 0 0.77 0.62 0.21 3.69
2 B2 2.09 0 0.39 0.31 0.10 2.89
3 B3 2.09 0 0.99 0.79 0.26 4.14
4 B4 2.09 0 0.50 0.40 0.13 3.12

4b. Factored Loads:


[Link]. Wall 1.2 DL 1.2SDL 1.6LL wu
Wall Plaster Slab 1.2D+1.6L
(kip/ft) (kip/ft) (kip/ft) (kip/ft) (kip/ft) (kip/ft)
1 B1 2.51 0.00 0.93 0.74 0.33 4.52
2 B2 2.51 0.00 0.47 0.37 0.17 3.51
3 B3 2.51 0.00 1.19 0.95 0.42 5.07
4 B4 2.51 0.00 0.59 0.48 0.21 3.79
Project: SAFE CITY
Structure: PPIC3 Residences
Reference: Drawing No.
Designed by: ABC
Engineering Consultancy Checked by: ABC
Services Punjab Pvt Ltd. Date: 30/11/2017

5. Required footing Width:

[Link]. Wall Wreq Wpro


(ft) (ft)
1 B1 3.35 3.5
2 B2 2.63 3.5
3 B3 3.76 3.5
4 B4 2.83 3.5

6. Steel Design:
6a. Footing Material:
fc' = 2500 psi
fy = 60000 psi

6b. Footing Thickness:


[Link]. Wall Hfoun Cover
(in.) (in)
1 B1 5 2
2 B2 5 2
3 B3 5 2
4 B4 5 2

6c. Ultimate Soil Pressure (qu), ultimate moment (Mu) and ultimate shear (Vu):
qu = wu/ Wpro
Mu=(1/32)*qu*(2Wpro-tw)^2 (moment on section at distance tw/4 from face inside masonry)
Vu=qu*{0.5(Wpro-tw)-d}
[Link]. Wall qu Mu Vu
(ksf) (kip-ft/ft) (kip/ft)
1 B1 1.29 1.57 1.45
2 B2 1.00 1.54 1.13
3 B3 1.45 1.91 1.63
4 B4 1.08 1.12 1.22

6d. Design for Shear and Moment:

[Link]. Wall Vu φVc Check Mu φMnmin As Bar s Bar strans


(kip/ft) (kip/ft) (kip-in/ft) (kip-in/ft) in2/ft (in. c/c) (in. c/c)
1 B1 1.45 2.7 OK 18.90 15.75 0.1296 #3 10.0 #3 10
2 B2 1.13 2.7 OK 18.45 15.75 0.1265 #3 10.0 #3 10
3 B3 1.63 2.7 OK 22.96 15.75 0.1575 #3 8.4 #3 10
4 B4 1.22 2.7 OK 13.43 15.75 0.1080 #3 10.0 #3 10

7. Summary:

[Link]. Wall fc' fy Hf Wpro Reinforcement


(psi) (psi) (in.) (ft.) Main Transverse
1 B1 5 3.5 #3 @ 10 in. c/c #3 @ 10 in. c/c
2 B2 5 3.5 #3 @ 10 in. c/c #3 @ 10 in. c/c
2500 60000
3 B3 5 3.5 #3 @ 8 in. c/c #3 @ 10 in. c/c
4 B4 5 3.5 #3 @ 10 in. c/c #3 @ 10 in. c/c

Wall

FFL

Secondary
Rebar

Hfound

Cover Main rebar

Wpro
Hfound

Cover Main rebar

Wpro
Material
1- or 2-component
SelfLeveling or Nonsag
Primer Required
Backer Rod Required
Joint Type
Silicone or Polyurethane
1
SL
No
Yes
Concrete to Concrete
Property Test Method Min. Max.
Flow at room temperature, mm - -
Tex-525-C
Nonvolatile content, % 93 -
Tack-free time, minutes ASTM C679 - 180
Extrusion Rate, g/ min ASTM C1183 - -
Tensile Strength and 24 hr. Extension Test Tex-525-C
Initial cure time, days - 6
Strength after air curing only, psi - 4 30
Strength after water immersion, psi - 4 30
Strength after over aging, psi - 4 30
Strength after bond test, psi - 4 30
24 hr. extension test, all specimens - Pass