PowerFactorController RVS-RVK
PowerFactorController RVS-RVK
1
Read this first
1. About this Instructions Manual
This Instructions Manual is designed to help you quickly install and operate the RVS - RVK PF Controllers. It is organized as
follows :
• Operation of the user interface : for a description of the principle of use of the user interface .
• Part 1. Easy Start: for a quick and easy installation and operation of the basic PF Controller functions using default values.
2. Safety
Read these instructions before you install and operate this PF Controller.
Installation, maintenance, etc. of the PF Controller must be performed by qualified electricians.
Do not work under voltage.
Do not open the PF Controller’s housing. There are no user serviceable parts inside.
Disconnect the voltage before replacing the fuse.
The PF Controller is connected to a current transformer. Do not unplug the current transformer connections before making sure
it is short-circuited or connected to another parallel load of sufficiently low impedance. Failure to do so can create dangerous
over voltages.
Do not use this product for any purpose other than its original aim.
3. Electromagnetic compatibility
This PF Controller has been verified for compliance with EU (European Union) directives for EMC (electromagnetic
compatibility) for operation at 50Hz and bears the CE marking to this effect.
When an apparatus is used in a system, EU directives may require that the system be verified for EMC compliance.
The following guidelines are helpful in improving the EMC performance of a system:
1. Metallic enclosures generally improves EMC performance.
2. Run cables away from apertures in the enclosure.
3. Run cables close to grounded metallic structures.
4. Use multiple ground straps for doors or other panel parts as required.
5. Avoid common ground impedances.
2
Fig. 1. Front Panel
* RVS only
3
Fig. 2. Rear panel and connection arrangement
M1 M2 1 2 3 4 5 6 7 8 9 10 11 12 A A
(✱)
N-REF MAKE
X.1-X.4
NETWORK SUPPLY LOAD
TEMP IN- = Y.1
IN+ = Y.2
V+ = Y.3
SG = Y.4
Y
L3
RESERVED Y.5 - Y.6 L2
LOCK L1
SET
RJ12(✱) RJ12(✱) AUX(✱)
1 2 1 . . 6 1 . . 6
RUN X Y
UNLOCK 1 2 CT1 CT2 PE NC L2 L3
NOMINAL VOLTAGE
100 - 120 Vrms
O
N 1 2
FUSE 125 mA
1 2
RUN
UNLOCK
O
N 1 2
4
Fig. 4. Wiring diagram
(*) To comply with safety standard, one of the CT’s connections shall be grounded.
5
List of parameters and subparameters with their
corresponding display messages
RVK
NEXT
PARAMETERS SUB-PARAMETERS
VRMS U.r.M.S. SCAL. Min. U.Nom.
ARMS A.r.M.S. SCAL. ASin. SEnS.
KVA _UA_
KVAR _UAr StEP M.UAr M.St.p n._St.
DISPLAY COS ϕ _P.F._ rEF. Min.
OUTPUT Out_ 1. 3. 4. 6. 7. 9. 10.12.
DELAY dEL._ S.oFF rES.t AL.rM. rS.Al. Pr.nt
SEQUENCE SEQ_ Ln.Cr. n_PH d.PHi
SETUP SEtP SCAL. SCAL. rEF. _CT_ SEnS.
RVS
NEXT
PARAMETERS SUB-PARAMETERS
VRMS U.r.M.S. SCAL. MAx. Min. U.Nom.
ARMS A.r.M.S. SCAL. MAx. ASin. SEnS.
KVA _UA_ MAx.
KVAR _UAr MAx. StEP M.UAr M.St.p n._St.
DISPLAY THD V t.H.d.U MAx.
THD A t.H.d.A MAx.
COS ϕ _P.F._ rEF. n.rEF. Min.
OUTPUT Out_ 1. 3. 4. 6. 7. 9. 10.12.
DELAY dEL._ S.oFF rES.t AL.rM. rS.Al. Pr.nt
SEQUENCE SEQ_. Ln.Cr. Pr.dr. nM.ln. n_PH d.PHi
TEMP tEmP. Unit SCAL. OF.S.t t.rEF. MAx.
SETUP SEtP SCAL. SCAL. rEF. _CT_ SEnS.
6
Operation of the user interface
See Fig. 1 : Front Panel description for easy location of DISPLAY Menu, MODES Menu, INDICATORS and BUTTONS.
• Buttons + and - allow the user to modify menu settings or start a process by pressing them simultaneously.
• Press and Hold the DISPLAY or NEXT buttons to display prompts for measured values and adjustable settings.
Release the DISPLAY or NEXT buttons to display the parameter’s value.
• A flashing LED indicates that the corresponding parameter is programmable or the corresponding function is
activated.
• Basic parameters are labelled on the front plate_(DISPLAY menu). Subparameters are not labelled but the left
most digit of the display shows a specific sign ( for max., _ for min., ...)
• When a decimal point of the right most digit lights, the displayed value must be multiplied by 1000 (eg. 99.9.).
7
Part 1. Easy Start
See Front panel (Fig.1) and Rear panel (Fig.2) descriptions for easy location of switches, buttons and LED’s.
If you have received your capacitor bank already fitted with a connected RVS/RVK Power Factor Controller go directly
to point 6 of this Easy Start
1. Check the PF Controller supply voltage (see the orange sticker on the back side of the PF Controller).
NOMINAL VOLTAGE NOMINAL VOLTAGE NOMINAL VOLTAGE
100 -120 Vrms 220 - 240 Vrms 380 - 440 Vrms
The working voltage range indicated on the sticker is a nominal voltage. A tolerance of +/- 10% is allowed.
4. Enter :
• The number of active outputs
• The type of switching sequence
by following this programming procedure :
4.1. Put the switch n°2 located on the back side (lower left end) of the controller on SET position (up). Make sure that switch
n°1 is in the UNLOCK position (down). See Fig.2 and Fig.3.
The LOCK position prevents any unauthorized operation of the PF controller. The LOCK status is displayed by the LOCK
LED located on the front panel.
4.2. Select the SET mode by repeatedly pressing the MODE button until the SET mode LED lights up.
4.3. Select the OUTPUT parameter by repeatedly pressing the DISPLAY button until the OUTPUT LED flashes.
4.4. Repeatedly press the – or + buttons to program the required number of active outputs (from 1 to 12 outputs for RVS-12
and RVK-12, from 1 to 6 outputs for RVS-6 and RVK-6).
4.5. Select the SEQUENCE parameter by repeatedly pressing the DISPLAY button until the SEQUENCE LED flashes.
(see appendix B for details about sequence)
4.6. Repeatedly press the – or + buttons until the required sequence is displayed.
8
5. Default settings for switching delay time between steps, type of
switching and network configuration are :
• Switching delay time between steps :default setting = 40 s.
• Type of switching :default setting = linear.
• Network configuration :default setting = three-phase.
6. Enter :
• The scaling of Vrms (voltage), network to control voltage ratio
• The scaling of Arms (current), current transformer ratio
• The target Power factor
& Activate :
• The auto-adaptation to phase rotation
• The automatic computation of C/k (sensitivity)
6.8. Repeatedly press the – or + buttons to modify the default value of the day COS ϕ target until the required value is
displayed.
Caution: Before going to the next step, load has to be passive (not generative).
6.10. Simultaneously press the – and + buttons to activate the auto-adaptation to phase rotation. The message _Ct_ is
displayed for one second. Depending on the actual CT connection either the message GOOd or the message rEU_
(reverse) appears. If the CT is reversed there is no need to make an adjustment.
The PF Controller will make an internal adjustment automatically.
If the current is too small, the PF Controller will display the message I_tS.
9
Automatic computation of C/k (sensitivity)
6.11. Press the NEXT button once. The SETUP LED flashes.
Press and hold the NEXT button to display the sensitivity prompt : SEnS. Release the NEXT button to display the
message _AU_ (automatic computation of sensitivity).
Note: The C/k computation has better chance to suceed if the power network is stable.
If the process failed several times consecutively, we recommend to wait for a quiet network time or to use
another way to set the C/k (see appendix A).
6.12. Warning : this operation will switch on and off the first capacitor step.
Simultaneously press the – and + buttons to activate the automatic computation of C/k. The message _AU_ flashes until
the end of the computation.
The computation time is equal to 4 times the switching delay time between steps (eg. 2 min 40sec for a delay time of 40
seconds.)
At the end of the computation process, the computed C/k value is displayed. See Appendix A if you want to check the
C/k value yourself.
Note :You can check the above programmed values by repeating steps 6.3. to 6.12.
10
Part 2. Advanced Features
1. The DISPLAY Menu
The DISPLAY Menu allows the user to display all the parameters and subparameters (50 for the RVS and 33 for the RVK).
The DISPLAY button allows the direct display (one at a time) of the basic measurements or basic parameters (8 for RVS and 5
for RVK).
The programming procedure of the parameters is described in point 2.4. SET mode.
The basic measurements directly accessible are :
PROMPT
See table 1 for the list of all parameters and subparameters with their corresponding display indications.
− Voltage transformer ratio (programmable from 0.01 to 650, multiplies voltage input by the selected ratio) SCAL.
− Minimum voltage threshold below which all capacitor steps are switched off Min.
11
− Current transformer ratio (programmable from 0.1 to 65500) SCAL.
− Maximum current threshold above which LOG mode is triggered (not available on RVK). MAx.
+ C/k (PF Controller reaction sensitivity - programmable from 0.050 to 1.00 for a 5 A input device) SEnS.
− Maximum kVA threshold above which LOG mode is triggered (not available on RVK). MAx.
− Maximum kvar threshold above which LOG mode is triggered (not available on RVK) MAx.
− Size of the smallest capacitor step (lowest kvar variation - from 0 to 99.9 Mvar). See Appendix A. StEP
+ Instantaneous missing reactive power to reach the preset minimum COS ϕ M.Uar
+ Instantaneous missing capacitor steps to reach the preset minimum COS ϕ M.St.p
− Maximum threshold of voltage total harmonic distortion above which the LOG mode is triggered. MAx.
− Maximum threshold of current total harmonic distortion above which the LOG mode is triggered. MAx.
− Reference value for Night COS ϕ control (not available on RVK) n.rEF.
N.B. Switching to night COS ϕ is performed through an external make contact connected to the X RJ12 plug
in (see table on the back side of the RVS PF Controller).
The night COS ϕ switching can be disabled by increasing the nrEF value to _dIS (after c O.70).
12
− Activation/deactivation of selected outputs:
• A, outputs 1 to 3 1.3.
• B, outputs 4 to 6 4.6.
• C, outputs 7 to 9 7.9.
• D, outputs 10 to 12 10.12.
Note: The individual state of output is displayed by pressing the NEXT button.
The sign indicates an activated output. The absence of this sign indicates a deactivated output.
Outputs are (de)activated by pressing the - button. The output is selected by pressing the + button.
The sign underscore _ indicates the selected output (eg. _ ).
DELAY: switching on delay time between steps (programmable from 1 to 120 seconds or 1 to 120 minutes dEL_
Eg. : S. xxx = xxx seconds, M. xxx = xxx minutes)
− Delay time after which the LED alarm lights up and alarm relay switches on when the following AL.rM
conditions are present :
• all capacitor steps are switched on and there is a demand for additional capacitor steps.
• the actual COS ϕ is lower than the programmed minimum COS ϕ threshold (not the target COS ϕ).
The alarm delay time is programmable from 1 to 120 seconds or 1 to 120 minutes.
The alarm function resets after the alarm reset delay when one of the two above conditions disappears. rS.AL.
The alarm reset delay time is programmable from 1 to 120 seconds or 1 to 120 minutes.
– Printing time period of parameters Pr.nt
− Phase shift programmable from -179° to +179°, useful in case of particular configuration of voltage and
current measurement devices (i.e. when CT is set in one of the voltage lines PT). d.PHi
TEMP
− Temperature unit: C° or F° Unit
13
SETUP: setup utility (see part 1. ‘Easy Start’) SEtP
• Number of active outputs (1 to 6 for RVS-6 and RVK-6, 1 to 12 for RVS-12 and RVK-12)
• OUTPUT: number of activated outputs when capacitor step has just switched.
• SEQUENCE: logged information (report) printed once per hour if a log condition occurs. It is not related to the preset
printing delay (not available on RVK).
• SETUP: full settings report printed only once and not related to the pre-set printing delay.
1. Select the SET mode by repeatedly pressing the MODE button until the SET mode LED lights up.
2. Select the DELAY parameter by repeatedly pressing the DISPLAY button until the DELAY LED flashes.
3. Select the print delay by pressing the button NEXT until the message Pr.nt is displayed.
4. Press the – or + buttons until the display indicates the required delay time between printings.
5. Select the PRINT mode by repeatedly pressing the MODE button until the PRINT mode LED lights up.
6. Select the parameter you want to print by pressing the DISPLAY button.
7. Enable printing of the parameter by pressing the + button (pressing the - button disables the parameter to print).
The LED corresponding to the enabled parameter flashes.
8. To enable other parameters repeat steps 6 and 7.
14
9. Install the IR printer in the IR emitting area (up to 2 m when printer faces the front panel of the PF Controller, less than 10
cm when printer is in the same plane as the PF Controller’s front panel).
Note: If the IR printer is magnetically fixed to the metallic cabinet door where the PF Controller is installed it must be
mounted within 10 cm of the controller.
10. Energize the printer (see IR printer Instructions Manual).
11. Press the NEXT button to start the printing session. The PRINT LED flashes.
12. Press the NEXT button again to stop the printing session. The PRINT LED stops flashing.
(The printer may continue to print until its buffer is empty.)
7. Press the + button to enable printing of COS ϕ. The COS ϕ LED is flashing.
8. Press the NEXT button to start printing of the enabled parameters (pressing the NEXT button again stops the printing).
1. Put the switch n°2 located on the back side (lower left end) of the controller on SET position (up). Make sure that switch
n°1 is on UNLOCK (down) position (See Fig. 2 ).
2. Select the SET mode by repeatedly pressing the MODE button until the SET mode LED lights up.
3. Select the required parameter by repeatedly pressing the DISPLAY button until the corresponding LED flashes.
4. Select the required subparameter by pressing the NEXT button.
15
The following measurements can be plotted:
• KVAR: reactive power consumed from the network. (-5 kvar to +5 kvar - 1 bit = 100 Var)
1. Select the PLOT mode by repeatedly pressing the MODE button until the PLOT mode LED lights up.
2. Select the parameter you want to plot.
3. Enable plotting of the parameter by pressing the + button (pressing the - button disables the parameter to plot). The LED
corresponding to the enabled parameter flashes.
− Accumulated time during which voltage has been above the programmed maximum voltage threshold. U.tiM.
16
ARMS
− Maximum current value above the programmed current threshold A.LoG.
− Accumulated time during which current has been above the programmed maximum current threshold A.tiM.
KVA
− Maximum kVA value above the programmed kVA threshold UA_L.
− Accumulated time during which the kVA value has been higher than the programmed maximum kVA
threshold UA_t.
KVAR
− Maximum kvar value above the programmed kvar threshold UAr.L.
− Accumulated time during which the kVAR has been higher than the programmed maximum kVAR
threshold UAr.t.
THD V
− Maximum value of voltage total harmonic distortion above the programmed threshold of voltage total
harmonic distortion h.d.U.L.
− Accumulated time during which the voltage total harmonic distortion has been higher than the maximum
(programmed) threshold of voltage total harmonic distortion h.d.U.t.
THD A
− Maximum value of current total harmonic distortion above the programmed threshold of current total
harmonic distortion h.d.A.L.
− Accumulated time during which the current total harmonic distortion has been higher than the maximum
(programmed) threshold of current total harmonic distortion h.d.A.t.
COS ϕ
− Missing reactive power to be delivered by the capacitor bank to reach the pre-set minimum COS ϕ. M.Ur.L.
− Missing steps of capacitor to be switched on to reach the preset minimum COS ϕ. M.St.L.
− Accumulated time during which missing reactive power to reach the preset minimum COS ϕ has been
measured. M.Ur.t.
TEMP
− Maximum temperature value above the programmed maximum temperature threshold t.LoG.
− Accumulated time during which the temperature value has been higher than the maximum temperature
threshold t.tiM.
Logging measurements
1. Select the SET mode by repeatedly pressing the MODE button until the SET mode LED lights up.
2. Select the basic parameter you want to log by repeatedly pressing the DISPLAY button until the corresponding LED
flashes.
3. Select the threshold by pressing the NEXT button.
4. Press the – or + buttons until the display indicates the required threshold value.
5. Repeat steps 2 to 4 for each parameter to log.
6. Once all required thresholds are set quit the SET mode.
17
Note:Access to the LOG mode is only possible when logged data is already recorded.
7. Select the LOG mode by repeatedly pressing the MODE button until the LOG mode LED lights up. Once in the LOG
mode, flashing LED’s indicate logged measurements.
8. Select the logged measurement by repeatedly pressing the DISPLAY button until the corresponding LED flashes.
Note: At least one alarm condition must be valid to enter the LOG mode
9. Display Max. values and durations (display format : hh.mm) via the NEXT button.
Note:Minimum duration time is 1 min.
10. Deleting logged data is achieved by simultaneously pressing + and - buttons. Once + and - buttons are released,
the,message n__y (no - yes) is displayed. Enable deleting by pressing the + button (message y disappears).
11. Quit the LOG mode to delete.
Caution : to clear all logged information check that there is no valid LOG condition before deleting.
1. Select the SET mode by repeatedly pressing the MODE button until the SET mode LED lights up.
2. Select the VRMS parameter by repeatedly pressing the DISPLAY button until the corresponding LED flashes.
3. Select the subparameter MAx. by pressing the NEXT button.
5. Press the – or + buttons until the display indicates 250.
6. Quit the SET mode to store the threshold value entered.
7. If overvoltage conditions have occurred the LOG LED starts flashing.
8. Select the VRMS parameter by repeatedly pressing the DISPLAY button until the corresponding LED flashes. U. Log is
displayed.
9. Press Next button to display U.tim.
3. The INDICATORS
The following INDICATORS are displayed:
• The LOCK status (front panel deactivation when the switch n°1 is in LOCK position)
See Fig. 1 : Front panel for easy location of the above indicators
18
4. Remote Control & Serial Port
The RVS can be connected to a Personal Computer . The RVS-Link software is required for this operation.
− Process measurements :
The RVS-Link processes the acquired signals (harmonic analysis, FFT, back up files, etc.) and displays them graphically.
− Download any batch files of macro commands from the PC to the RVS :
The RVS-Link software allows the user to create customized batches of commands and download them to the RVS.
19
Part 3. Testing & Troubleshooting
1. Testing
After installation of the automatic capacitor bank and programming of the switching parameters, the following tests can be
performed depending on load situation.
B. Inductive load.
Capacitor steps will now be automatically switched on to compensate the inductive load (the controller will not react if the
inductive current is lower than the preset C/k value. In such a case, test according to A. above).
If all steps are switched on and there is still a demand for additional steps, then check the setting of C/k. If it is correct, then the
bank is too small to compensate to COS ϕ = 1. Select a lower value for COS ϕ.
When one stage repeatedly switches on and off, it means the C/k is set too low (unless the load actually fluctuates periodically
with a time period equal to the switching delay time).
2. Troubleshooting
Fault
The controller does not switch on or off steps although there is a considerable variable inductive load.
Solution
– Check that the controller is in automatic mode.
– Check that the CT connection (i.e. “R” phase) and the voltage connections (i.e. “S-T” phases) are connected in different
phases.
– Check setting of C/k.
Fault
The controller does not seem to activate any steps.
Solution
Wait for the delay time between switching or a power outage delay time.
20
Fault
The preset power factor is not achieved.
Solution
• At low or no load, a low power factor can correspond to a very small inductive current. The corresponding capacitor
steps are too large for compensation.
• If the average COS ϕ over a period of time is too low, the preset COS ϕ may be increased.
Fault
Solution
Normal situation when the actual inductive current varies around the set sensitivity (C/k).
Fault
The controller indicates capacitor steps switched on, but the contactors are not activated.
Solution
Check the wiring diagram of the power contactors and the controller outputs.
Fault
The alarm function is activated although everything seems normal.
Solution
A very high demand of reactive power during a few minutes may make the bank insufficient to compensate the required
amount of reactive power. It shall therefore indicate an alarm.
Fault
All capacitors are switched on although the required reactive power is relatively low.
Solution
The CT has been placed on the load side of the capacitors.
Fault
The controller is connected but does not work (no LED on).
Solution
Check the voltage setting and the fuse (0.1A/250 V) located on the back side of the controller.
21
Part 4. Technical Specifications
Measuring system: micro-processor system for balanced three-phase networks or single-phase networks.
Operating voltage: 100 to 120 V, 220 V to 240 V, 380 V to 440 V depending on type of controller.
Voltage tolerance: +/- 10% on indicated operating voltages.
Note: a controller may work with a voltage supply out of the above mentioned specified
range. Should it be the case, ABB does not give any guarantee that technical specifications
will be respected.
Frequency range: 50 or 60 Hz +/- 5% (automatic adjustment to network frequency).
Current input: 5A (RMS). 1A on request.
Current input impedance: < 0.1 Ohm.
Fuse rating: 125 mA / 250 Vmin. (T-type).
Primary transformer fuse: a primary transformer fuse is included (for UL approval). This fuse is a safety device under
250 VAC. An external fuse (rated 500 V) must be added for a higher voltage.
Consumption: 15 VA max.
Switching sequences: 1:1:1:1:......1 linear
1:1:1:1:......1 circular
1:1:2:2:......2 linear (1:1 steps circular)
1:1:2:2:......2 circular on outputs of value “2” (1:1 steps circular)
1:2:2:2:......2 linear
1:2:2:2:......2 circular on outputs of value “2”
1:2:4:4:......4 linear
1:2:4:4:......4 circular on outputs of value “4”
1:1:2:4:......4 linear (1:1 steps circular)
1:1:2:4:......4 circular on outputs of value “4” (1:1 steps circular)
1:2:4:8:......8 linear
1:2:4:8:......8 circular on outputs of value “8”
1:1:2:4:8:...8 linear (1:1 steps circular)
1:1:2:4:8:...8 circular on outputs of value “8” (1:1 steps circular)
Output contact rating: Max. continuous current: 1.5A.
Max. peak current: 5A.
Max. voltage: 440 V.
Terminal A-A are rated for a continuous current of 18A (9A/terminal).
Power factor setting: 0.7 inductive to 0.7 capacitive.
Starting current setting (C/k): - 0.05 to 1A (0.01 to 0.2 for a “1A input” controller).
- automatic measurement of C/k.
Variable number of active outputs: - RVS/K - 6: 1 to 6.
- RVS/K -12: 1 to 12.
Switching time between steps: programmable from 1 s to 120 s or 1 min to 120 min (independent of reactive load).
Switching off and on delay times are separately programmable (unsymetrical switching
times).
Saving-function of all programmed parameters in case of power outage longer than 40 ms.
Power outage release: automatic disconnection of all capacitors in case of power outage.
Power outage reset delay time: programmable from 1 s to 120 s or 1 min to 120 min.
Autoadaptation to the phase-rotation of the network and the CT-terminals.
Insensibility to harmonics.
Operating temperature : - 10° C to 70° C.
Storage temperature: - 30° C to 80° C.
Mounting position: vertical panel mounting
Dimensions: 144 x 144 x 85 mm (H x W x D)
Weight: 1500 gr. (unpacked).
Connector: WAGO (PHOENIX compatible).
Protection: IP 20.
22
Appendix A. C/k - Sensitivity of the PF Controller
N.B. The " 5 A input" Controller can be set with a C/k in the range (0.05 - 1).
The "1 A input" Controller can be set with a C/k in the range (0.01 - 0.200).
23
Appendix B. Sequences and modes of switching
Examples
demand for adding a step.
Demand
demand for removing a step.
1:1:1:1:1:.... linear
1 1 1 1 ... 1 1 Steps
... 1
... 2
... 3
... 2
... 1
1:1:1:1:1:.... circular
1 1 1 1 ... 1 1 Steps
... 2
... 3
... 4
... 3
... 2
1:2:2:2:2:.... linear
1 2 2 2 ... 2 2 Steps
... 1
... 2
... 3
... 4
... 3
... 2
24
1:2:4:4:4:....
1 2 4 4 ... 4 4 Steps
... 4
... 5
... 6
... 7
... 8
... 7
... 6
1:2:4:8:8:....
1 2 4 8 ... 8 8 Steps
... 13
... 14
... 15
... 14
... 13
... 12
... 11
Example :
− type of sequence : 1:2:4:8:8:8:8
− number of steps to be switched on after the programmed delay time : 17 steps
− procedure :
• programmed delay time (ex : 60 seconds )
• switching on of a step 8
• fixed delay of 12 seconds
• switching on of a step 8
• fixed delay of 12 seconds
• switching on of a step 1
Note : With the INTEGRAL mode, the switching off delay time is equal to the switching on delay time, which is the period of
integration. The alarm will work as in NORMAL mode.
25
Advantage of “double first step” switching sequences
“Double first step” switching sequences are :
• 1:1:2:2:2:2...
• 1:1:2:4:4:4...
• 1:1:2:4:8:8...
This type of switching sequence increases the life time of the most solicitated smaller step by alternately switching the two first
outputs.
This type of switching sequence is implemented both in circular and linear modes. In circular mode the circularity is also applied
on the steps of higher value.
26
Appendix C. Optional accessories
The following optional accessories are available :
RVS-Link software
The RVS-Link software is intended to communicate with the RVS Power Factor Controller through the RS-232 serial port.
The RVS-Link software allows:
Infrared printer
Type HP 82240B
Supplied with magnetic fixation
Max. print speed : 24 character line/second.
Thermal printing.
Length : 3 m.
Fitted with two RJ12 modular plug-in.
Fitted with DB9 - RJ12 adapter.
Temperature probe
-25°C / +100°C.
Wire length : 1.5 m.
Fitted with RJ-12 modular plug-in.
Communication module
27
While all care has been taken to ensure that the information contained
in this publication is correct, no responsibility can be accepted for any
inaccuracy. We reserve the right to alter or modify the information
contained herein at any time in the light of technical or other
developments. Technical specifications are valid under normal
operating conditions only. We do not accept any responsibility for any
misuse of the product and cannot be held liable for indirect or
consequential damages.