NOTICE: See Installation and Maintenance Instructions, I&M No. V6844R3 - Section 2 of 2 for exploded isometric views.
DESCRIPTION OPERATION
Series 8401 valves are solenoid piloted, adapter base S 3-Way Function
mounted 3-way and 4-way function valves designed for air Solenoid De-energized: Flow is from Port 4 to Port 5. Ports
actuator service. These valves are designed with a special 1 and 3 are closed.
flow gasket which allows valve to function in a 3-way or
Solenoid Energized: Flow is from Port 1 to Port 4 and from
4-way mode depending upon requirements. When
Port 2 to Port 5.
installed, the flow gasket is indexed to the desired function
(3 or 4 way) by locating the long tab on the flow gasket in the
appropriate slot in the adapter base. The adapter base, 3-Way Flow Diagrams
valve body, and pilot valve body are made of nylon. Internal
valve parts are designed for low friction, high strength, and De-Energized Energized
long life. A built-in manual operator allows manual
operation when desired or during an electrical power 4 2 4 2
outage.
Series 8401 valves may be provided with the following
solenoids: 513 513
S Open-Frame
S General Purpose/Raintight/Watertight
S Raintight/Watertight/Explosionproof S 4-Way Function
Solenoid De-energized: Flow is from Port 4 to Port 5 and
NOTE: See separate installation and maintenance from Port 1 to Port 2. Port 3 is closed.
instructions for General Purpose/Raintight/Watertight or Solenoid Energized: Flow is from Port 1 to Port 4 and from
Raintight/Watertight/ Explosionproof Solenoids. Port 2 to Port 3. Port 5 is closed.
Conduit Connector Kit No. K224735: The open-frame NOTE: A loss of main line pressure will not cause the valve
solenoid with lead wires may be provided with a gasket to shift in either the energized or de-energized solenoid
threaded conduit hub for watertight construction (see mode.
Figure 6 on page 3). IMPORTANT: Main inlet pressure must be a minimum of
20 psig. Maximum pressure 150 psig.
e
Page 1 of 8 (Section 1 of 2)
50 Hanover Road, Florham Park, New Jersey 07932 www.ascovalve.com E179189 All Rights Reserved.
Manual Operation Adjustment
Manual operator provides manual operation when desired or When the valve leaves the factory, the
during an electrical power outage. To operate valve manually, metering stem is backed out
insert a screwdriver into stem slot and push in, then release. counterclockwise (toward plus +) as
This action will operate the valve momentarily. To maintain far as possible to give full unrestricted
this position, push in stem and rotate it clockwise 90_; stem will flow. Before starting, check this
remain in the engaged position. Valve will now be in the same adjustment to verify that the
position as when the solenoid is energized. To disengage metering stem is backed out fully
manual operator, rotate operator stem counterclockwise 90_; counterclockwise.
stem will return upward.
INSTALLATION
Figure 1. Partial view of pilot valve (top) to
show location of manual operator. Check nameplate for correct catalog number, pressure,
voltage, frequency, and service. Never apply incompatible
fluids or exceed pressure rating of the valve. Installation and
Flow Controls (metering) valve maintenance to be performed by qualified personnel.
Each valve is provided with two independent metering
devices. Each device meters the flow of two valve ports. The
side of the valve with the solenoid meters flow from Port 1 to Future Service Considerations
Port 2 and from Port 4 to Port 5. The side of the valve without Provision should be made for performing seat leakage,
the solenoid meters flow from Port 2 to Port 3, and from Port external leakage, and operational tests on the valve with a
1 to Port 4. nonhazardous, noncombustible fluid after disassembly and
reassembly.
1.338
34,0 1.260
32,0
conduit
connector connector
gasket Note:
The DIN connector is not
included under the Underwriters
Note: Laboratories, Inc. Component Indicates parts supplied
The conduit hub is not center screw Recognition of Series 8401 valves.
included under the Underwriters
Laboratories, Inc. Component
Recognition of Series 8401 valves.
Figure 7. DIN Plug Connector Kit No. K226061
Continued on I&M No. V6844R3 - Section 2 of 2
Figure 6. Conduit Connector Kit No. K224735.
*DuPont's Registered Trademark