Electrical Date: 1/2008
Author: Jim Pauley
Shortz Document Number: 0100DB0705
Cedar Rapids, Iowa, USA
www.us.schneider-electric.com/codes
Keywords: Termination, Neutral,
Panelboard, Conductor,
Ground, Load Center,
Can Multiple Neutral Conductors be Multiple Ground
Terminated in a Panelboard Termination?
Can I install more than one neutral Multiple neutral conductors from separate branch or separate feeder circuits
conductor in a panelboard termination? cannot be installed in the same neutral terminal.
Does the NEC address this issue? The requirement has generally been enforced in the past by a close review
of the manufacturer markings and by NEC® 110.3(B). Clause 12.3.10 of
UL 67 (Panelboards) states, “An individual terminal shall be provided for the
connection of each branch-circuit neutral conductor.”
A code change was accepted for the 2002 NEC that made it clear that each
grounded conductor (neutral) must have its own terminal. The 2008 NEC
408.41 is the location of the rule.
Why does the UL standard place this Solid rationale exists for individual termination requirements in the product
restriction on the panelboard? standards. Multiple neutral conductors in a single termination create a
significant problem when the circuit needs to be isolated. In order to isolate
the circuit, the branch breaker is turned off and the neutral is disconnected
by removing it from the terminal. If the terminal is shared with another
circuit, the connection on the other (still energized) circuit will be loosened
as well. Loosening of the second neutral (loss of neutral) under load is a
safety hazard, and may establish an overvoltage condition on lighting and
appliances if the neutral is part of a 120/240 Vac multi-wire branch circuit.
Also, the neutral assemblies are not evaluated with multiple neutral
conductors in the same terminal.
Since I can’t place two neutrals in a The connection of a neutral and equipment-grounding conductor in the
single termination, can I install the same termination creates a similar issue. One of the objectives of the
neutral and ground conductor in the particular arrangement of bonding jumpers, neutrals and equipment
same termination? grounds is to allow circuit isolation while keeping the equipment grounding
conductor still connected to the grounding electrode (see UL 869A -
Reference Standard for Service Equipment). When the neutral is
disconnected, the objective is to still have the equipment ground solidly
connected to the grounding electrode. If both the neutral and grounded
conductor is under the same terminal, this cannot be accomplished.
For More Information: For more information on installing multiple conductors in a single
termination see the following references:
NEC® Section 110.14(A), 408.41
UL White Book—Electrical Equipment for use in Ordinary Locations
(AALZ)
Visit the Schneider Electric North America
Codes and Standards Electrical Shortz website: www.us.schneider-electric.com/codes/industrystandards/publications/electricalshortz
Schneider Electric USA
3700 6th Street S.W. “Electrical Shortz” are produced by the Schneider Electric North America Codes and
Cedar Rapids, Iowa 52404 USA Standards Group. These documents provide general guidance on a specific issue.
1-888-SquareD (1-888-778-2733) Circumstances regarding particular installation issues may need furter consideration.
www.us.SquareD.com © 2007 Schneider Electric All Rights Reserved