Download as PDF, TXT or read online on Scribd

InteliATS2 50

Order code: IA250XXXBAA

Automatic Transfer Switch Controller


Datasheet
Product description

Automatic Transfer Switch (ATS) controller for Remote display support


stand-by and prime-power applications Detailed history log with up to 150 records
All-in-one intuitive & powerful PC tool for User setpoints and protections
configuration, monitoring and control locally or True RMS measurement
remotely
Multi-purpose scheduler
Easy to install, configure and use
User Access Management
Key features 5 languages in the controller & Translator
Mains-To-Mains or Mains-To-Gen application functionality
6 binary outputs, 6 binary inputs Cut-out: 172 × 112 mm
Connection and configuration in PC tool
Application overview
InteliConfig
Power over USB for controller configuration
RTC with battery back-up (full calendar)
Slot for extension plug-in module (support of 4G,
BI/BO, Ethernet)
Full remote communications support (AirGate 2.0,
WSV, InteliSCADA)
Internet access using Ethernet/4G
Modbus TCP/RTU, SNMP v1/v2c
Active SMS and emails
Cyber security improvement, Firewall
Modbus register mapping possibility
Elevator switch, Geo-Fencing

| InteliATS2 50 Datasheet | Related HW ver: 1.0.0 | Related SW ver: 1.0.0 | Date of issue: 2/23/2022
Dimensions, terminals and mounting

Plug-in module

Note: Dimension "X" depends on plug-in module

Note: Dimensions are in millimeters.

Note: The final depth of the controller depends on the selected plug-in module – it can vary between 47 mm and "X" mm.
Mind also the size of connectors and cables (e.g. in case of RS232 connector, add about 60 mm more for standard
RS232 connector and cable).

Note: The controller is to be mounted into panel doors as a standalone unit using provided holders. The requested cutout
size is 172 × 112 mm. Use the screw holders delivered with the controller to fix the controller into the door.

InteliATS2 50 Datasheet 2
Technical data

Power supply
Power supply range 8-36 VDC

Power consumption
2.0 W
(without modules)
RTC battery Replaceable (3 V)

Fusing power 4 A w/o BOUT consumption

Max. Power Dissipation 4.5 W

Operating conditions
Protection degree (front
IP 65
panel)
Operating temperature -20 ˚C to +70 ˚C

Storage temperature -30 ˚C to +80 ˚C


95 % non-condensing
Operating humidity
(EN 60068-2-30)
5-25 Hz, ± 1.6 mm
Vibration
25-100 Hz, a = 4 g
2
Shocks a = 500 m/s

Surrounding air temperature rating 70 °C


Suitable for pollution degree 2

Voltage measurement
Measurement inputs 3ph-n S1 voltage, S2 voltage
10-277 V AC / 10-480 V AC (EU)
Measurement range 10-346 V AC / 10-600 V AC
(US/Canada)

Linear measurement 350 V AC Ph-N


and protection range 660 V AC Ph-Ph

Accuracy 1%

Frequency range 30-70 Hz (accuracy 0.1 Hz)

Input impedance 0.72 MΩ ph-ph , 0.36 MΩ ph-n

Display
Type Build-in monochromatic 3.2"

Resolution 132 × 64 px

Communications
USB Device Non-isolated type B connector

Binary inputs
Number 6
0-2 VDC close contact
Close/Open indication
6-36 VDC open contact

Binary outputs
Number 6

Max. current BO1-6 = 0.5 A

Switching to positive supply terminal

InteliATS2 50 Datasheet 3
Available plug-in modules
Product Description Order code

CM-RS232-485 Dual port interface CM223248XBX


CM2-4G-GPS 4G & GPS plug-in communication module CM24GGPSXBX
CM3-Ethernet Internet / Ethernet plug-in communication module CM3ETHERXBX
EM-BIO8-EFCP 8 additional binary inputs/outputs EM2BIO8EXBX

Note: Controller has 1 slot for plug-in modules.

Functions and protections


Support of functions and protections as defined by ANSI (American National Standards Institute):

Description ANSI code Description ANSI code


Master unit 1 Incomplete sequence relay 48
Stopping device 5 Breaker failure 50BF
Multi-function device 11 AC circuit breaker 52
Starting-to-running transition contactor 19 Overvoltage 59
Undervoltage 27 Aux Over Voltage 59X
Aux Battery Under Voltage 27X Reclosing relay 79
Annunciator 30 Overfrequency 81O
Master sequence device 34 Underfrequency 81U
Voltage unbalance/Negative sequence voltage 47 Auto selective control/transfer 83

Certifications and standards


EN 61000-6-2 EN 60068-2-6 (2÷25 Hz / ±1,6 mm; 25÷100 Hz / 4.0 g)
2
EN 61000-6-4 EN 60068-2-27 (a=500 m/s ; T=6 ms)

EN 61010-1 EN 60068-2-30:2005 25/55°C, RH 95%, 48hours

EN 60068-2-1 (-20 °C/16 h) EN 60529 (front panel IP65, back side IP20)

EN 60068-2-2 (70 °C/16 h) UL 1008 (pending)

E-mail: info@[Link]
Web: [Link]

© ComAp. Features and specification are subject to change without prior notice.