FORM 201.

28-EG1 (118)

Model YVAA
Air-Cooled Screw Compressor Liquid Chillers
With Variable Speed Drive
Style A
150-500 Tons
525-1750 kW
2 Compressor
50 and 60 Hz
HFC-134a or
HFC-513A
FORM 201.28-EG1 (118)

Nomenclature

YVAA 021 3AXX 46 A A

REFRIGERANT
HFC - 134a
HFC-513A
DEVELOPMENT LEVEL

VOLTAGE CODE
-17 = 208-3-60
-28 = 230-3-60
-40 = 380-3-60
-42 = 400-3-60
CONFIGURATION -46 = 460-3-60
Condenser Code -50 = 380-415-3-50
Evaporator Code -58 = 575-3-60
Compressor Code
Condenser Fan &
Sound Kit Code
FRAME
SIZE

UNIT TYPE
YORK Chiller
Air Cooled Screw
Design Series A

Approvals
• ASME Boiler and Pressure Vessel Code – Section Vlll Division 1.

• AHRI Standard 550/590 and 551/591.

• UL 1995 – Heating and Cooling Equipment

• ASHRAE 15 – Safety Code for Mechanical Refrigeration

• ASHRAE Guideline 3 – Reducing Emission of Halogenated Refrigerants in Refrigeration and Air-Conditioning


Equipment and Systems

• N.E.C. – National Electrical Code

• OSHA – Occupational Safety and Health Act

2 JOHNSON CONTROLS
FORM 201.28-EG1 (118)

Physical Data - Microchannel Coil - English (SI)


The data shown in this table is applicable to selected typical configurations. Other configurations are available
through our configuration/selection software. Please contact your nearest Johnson Controls Sales Office for the
chiller configuration that best matches your specific needs.
UNIT FRAME 15 16 17 18 19 19 20 21 21 21
CONDENSER CODE 3 5 8 3 5 8 0 3 5 8
EVAPORATOR CODE B B C A A B C A C C
GENERAL UNIT DATA
Number of Independent
2
Refrigerant Circuits
Refrigerant Charge, R-134a,
175/175 190/190 225/225 175/155 190/170 220/195 205/205 175/175 225/225 240/240
or R-513A, Circuit.-1/Circuit.-2,
(79/79) (86/86) (102/102) (79/70) (86/77) (100/88) (93/93) (79/79) (102/102) (109/109)
lbs (kg)
Oil Charge, Circuit.-1/Circuit.-2, 2.1/2.0 2.2/2.2 2.5/2.5 2.4/2.0 2.6/2.1 2.7/2.2 2.6/2.6 2.5/2.5 2.8/2.8 2.9/2.9
gal (liters) (8.0/7.7) (8.5/8.5) (9.3/9.3) (9.2/7.7) (9.7/8.0) (10.4/8.5) (10.0/10.0) (9.3/9.3) (10.5/10.5) (10.8/10.8)
Minimum Load % 10%
Chassis Dimensions - Length, 203.3 247.2 291.2 247 291.2 335.2 226 291.2 291.2 335.2
inches (mm) (5163) (6280) (7397) (6274) (7397) (8514) (5741) (7397) (7397) (8514)
Chassis Dimensions - Width, 88.3 88.3 88.3 88.3 88.3 88.3 88.3 88.3 88.3 88.3
inches (mm) (2242) (2242) (2242) (2242) (2242) (2242) (2242) (2242) (2242) (2242)
Chassis Dimensions - Height, 94.6 94.6 94.6 94.6 94.6 94.6 94.6 94.6 94.6 94.6
inches (mm) (2403) (2403) (2403) (2403) (2403) (2403) (2403) (2403) (2403) (2403)
COMPRESSORS, SEMI-HERMETIC SCREW
Quantity per Chiller 2
CONDENSER FANS
Number Circuit-1/Circuit-2 4/4 5/5 6/6 6/4 7/5 8/6 4/4 6/6 6/6 7/7
Air on Condenser (Min/Max), 0°F/131°F
°F (°C) (-17.8°C/55°C)
EVAPORATOR, SHELL AND TUBE HYBRID FALLING FILM 2
58 58 71 48 48 58 71 48 71 71
Water Volume, gal (liters)
(220) (220) (269) (182) (182) (220) (269) (182) (269) (269)
Leaving Water Temperature 40/70
(Min/Max), °F (°C) 2 (4.4/21.1)
Maximum Water Side 150
Pressure, psig (barg) (10.3)
Maximum Refrigerant Side 235
Pressure, psig (barg) (16.2)
Evaporator Drain Connection, 3/4
inches (mm) (19)
NOTES:
1. Shipping and operating weights are not show as selected options may add weight to unit. Contact your nearest Johnson Controls Sales
RI¿FHIRUZHLJKWGDWD
2. )RUOHDYLQJOLTXLGWHPSHUDWXUHEHORZƒ) ƒ& RUDERYHƒ) ƒ& FRQWDFW\RXUQHDUHVW-RKQVRQ&RQWUROV6DOHV2I¿FHIRUDSSOLFD-
tion requirements.

24 JOHNSON CONTROLS
FORM 201.28-EG1 (118)

Physical Data - Microchannel Coil - English (SI) (Cont'd)


The data shown in this table is applicable to selected typical configurations. Other configurations are available
through our configuration/selection software. Please contact your nearest Johnson Controls Sales Office for the
chiller configuration that best matches your specific needs.
UNIT FRAME 23 24 24 26 27 27 27 27 29 30
CONDENSER CODE 3 5 8 3 0 3 5 8 5 3
EVAPORATOR CODE B C C B D D E E E C
GENERAL UNIT DATA
Number of Independent
2
Refrigerant Circuits
Refrigerant Charge, R-134a or
210/190 250/225 250/250 210/210 250/250 265/265 265/265 270/270 310/265 290/245
R-513A, Circuit.-1/Circuit.-2,
(95/86) (113/102) (113/113) (95/95) (114/114) (120/120) (120/120) (122/122) (141/120) (132/111)
lbs (kg)
Oil Charge, Circuit.-1/Circuit.-2, 2.7/2.6 2.9/2.8 2.9/2.9 2.7/2.7 3.0/3.0 3.0/3.0 3.0/3.0 3.1/3.1 4.2/3.1 4.1/3.0
gal (liters) (10.1/9.7) (11.1/10.5) (11.1/11.1) (10.1/10.1) (11.4/11.4) (11.4/11.4) (11.4/11.4) (11.6/11.6) (15.9/11.7) (15.5/11.4)
Minimum Load % 10%
Chassis Dimensions - Length, 291.2 335.2 379.1 335.2 291.2 335.2 335.2 379.2 379.2 379.2
inches (mm) (7397) (8514) (9631) (8514) (7397) (8514) (8514) (9631) (9631) (9631)
Chassis Dimensions - Width, 88.3 88.3 88.3 88.3 88.3 88.3 88.3 88.3 88.3 88.3
inches (mm) (2242) (2242) (2242) (2242) (2242) (2242) (2242) (2242) (2242) (2242)
Chassis Dimensions - Height, 94.6 94.6 94.6 94.6 94.6 94.6 94.6 94.6 94.6 94.6
inches (mm) (2403) (2403) (2403) (2403) (2403) (2403) (2403) (2403) (2403) (2403)
COMPRESSORS, SEMI-HERMETIC SCREW
Quantity per Chiller 2
CONDENSER FANS
Number Circuit-1/Circuit-2 7/5 8/6 8/8 7/7 6/6 7/7 7/7 8/8 9/7 9/7
Air on Condenser (Min/Max), 0°F/131°F
°F (°C) (-17.8°C/55°C)
EVAPORATOR, SHELL AND TUBE HYBRID FALLING FILM 2
58 71 71 58 82 82 113 113 113 71
Water Volume, gal (liters)
(220) (269) (269) (220) (310) (310) (428) (428) (428) (269)
Leaving Water Temperature 40/70
(Min/Max), °F (°C) 2 (4.4/21.1)
Maximum Water Side Pressure, 150
psig (barg) (10.3)
Maximum Refrigerant Side 235
Pressure, psig (barg) (16.2)
Evaporator Drain Connection, 3/4
inches (mm) (19)
NOTES:
1. Shipping and operating weights are not show as selected options may add weight to unit. Contact your nearest Johnson Controls Sales
RI¿FHIRUZHLJKWGDWD
2. )RUOHDYLQJOLTXLGWHPSHUDWXUHEHORZƒ) ƒ& RUDERYHƒ) ƒ& FRQWDFW\RXUQHDUHVW-RKQVRQ&RQWUROV6DOHV2I¿FHIRUDSSOLFD-
tion requirements.

JOHNSON CONTROLS 25
FORM 201.28-EG1 (118)

Physical Data - Microchannel Coil - English (SI) (Cont'd)


The data shown in this table is applicable to selected typical configurations. Other configurations are available
through our configuration/selection software. Please contact your nearest Johnson Controls Sales Office for the
chiller configuration that best matches your specific needs.
UNIT FRAME 30 30 31 32 33 34 34 36 37 37
CONDENSER CODE 5 8 8 3 3 3 5 8 3 5
EVAPORATOR CODE C E E E C E E J F J
GENERAL UNIT DATA
Number of Independent
2
Refrigerant Circuits
Refrigerant Charge, R-134a
295/250 315/275 315/295 295/295 290/290 310/310 315/315 475/320 420/245 470/310
or R-513A, Circuit.-1/
(134/114) (143/125) (143/134) (134/134) (132/132) (141/141) (143/143) (216/145) (191/111) (213/141)
Circuit.-2, lbs (kg)
Oil Charge, Circuit.-1/ 4.1/3.0 4.3/3.2 4.3/3.3 4.1/4.1 4.1/4.1 4.2/4.2 4.3/4.3 5.6/5.0 5.3/2.9 5.6/4.3
Circuit.-2, gal (liters) (15.5/11.4) (16.3/12.1) (16.3/12.5) (15.5/15.5) (15.5/15.5) (15.9/15.9) (16.3/16.3) (21.2/19.0) (20.1/11.0) (21.2/16.3)
Minimum Load % 10%
Chassis Dimensions - 423.1 423.1 467.1 379.2 423.1 423.1 467.1 511 467.1 467.1
Length, inches (mm) (10748) (10748) (11865) (9631) (10748) (10748) (11865) (12979) (11864) (11864)
Chassis Dimensions - 88.3 88.3 88.3 88.3 88.3 88.3 88.3 88.3 88.3 88.3
Width, inches (mm) (2242) (2242) (2242) (2242) (2242) (2242) (2242) (2243) (2243) (2243)
Chassis Dimensions - 94.6 94.6 94.6 94.6 94.6 94.6 94.6 94.7 94.7 94.7
Height, inches (mm) (2403) (2403) (2403) (2403) (2403) (2403) (2403) (2405) (2405) (2405)
COMPRESSORS, SEMI-HERMETIC SCREW
Quantity per Chiller 2
CONDENSER FANS
Number Circuit-1/Circuit-2 10/8 10/8 8/8 8/8 9/9 9/9 10/10 14/8 13/7 13/7
Air on Condenser (Min/ 0°F/131°F
Max), °F (°C) (-17.8°C/55°C)
EVAPORATOR, SHELL AND TUBE HYBRID FALLING FILM 2
71 113 113 113 71 113 113 147 96 147
Water Volume, gal (liters)
(269) (428) (428) (428) (269) (428) (428) (556) (363) (556)
Leaving Water Temperature 40/70
(Min/Max), °F (°C) 2 (4.4/21.1)
Maximum Water Side 150
Pressure, psig (barg) (10.3)
Maximum Refrigerant Side 235
Pressure, psig (barg) (16.2)
Evaporator Drain 3/4
Connection, inches (mm) (19)
NOTES:
1. Shipping and operating weights are not show as selected options may add weight to unit. Contact your nearest Johnson Controls Sales
RI¿FHIRUZHLJKWGDWD
2. )RUOHDYLQJOLTXLGWHPSHUDWXUHEHORZƒ) ƒ& RUDERYHƒ) ƒ& FRQWDFW\RXUQHDUHVW-RKQVRQ&RQWUROV6DOHV2I¿FHIRUDSSOLFD-
tion requirements.

26 JOHNSON CONTROLS
FORM 201.28-EG1 (118)

Physical Data - Microchannel Coil - English (SI) (Cont'd)


The data shown in this table is applicable to selected typical configurations. Other configurations are available
through our configuration/selection software. Please contact your nearest Johnson Controls Sales Office for the
chiller configuration that best matches your specific needs.
UNIT FRAME 39 41 42 42 44 47 48 49 50 52
CONDENSER CODE 8 3 5 8 3 5 3 0 0 3
EVAPORATOR CODE J H H J G J G K J J
GENERAL UNIT DATA
Number of Independent
2
Refrigerant Circuits
Refrigerant Charge, R-134a
475/360 460/345 480/365 475/385 370/370 445/445 385/385 390/390 405/405 445/445
or R-513A, Circuit.-1/ (216/163) (209/156) (218/166) (215/175) (168/168) (202/202) (175/175) (179/179) (184/184) (202/202)
Circuit.-2, lbs (kg)

Oil Charge, Circuit.-1/ 5.6/5.1 5.5/4.3 5.6/4.4 5.6/5.1 5.0/5.0 5.8/5.8 5.1/5.1 5.2/5.2 5.2/5.2 5.4/5.4
Circuit.-2, gal (liters) (21.2/19.3) (20.8/16.3) (21.2/16.7) (21.2/19.3) (18.9/18.9) (22.0/22.0) (19.3/19.3) (19.7/19.7) (19.7/19.7) (20.4/20.4)
Minimum Load % 10%
Chassis Dimensions - 555.3 467.1 555.3 599.3 555.3 599.3 599.3 467.1 467.1 599.3
Length, inches (mm) (14104) (11864) (14104) (15222) (14104) (15222) (15222) (11864) (11865) (15222)
Chassis Dimensions - 88.3 88.3 88.3 88.3 88.3 88.3 88.4 88.3 88.3 88.3
Width, inches (mm) (2243) (2243) (2243) (2243) (2243) (2243) (2244) (2242) (2243) (2243)
Chassis Dimensions - 94.7 94.7 94.7 94.7 94.7 94.7 94.7 94.6 94.7 94.7
Height, inches (mm) (2405) (2405) (2405) (2405) (2405) (2405) (2405) (2403) (2405) (2405)
COMPRESSORS, SEMI-HERMETIC SCREW
Quantity per Chiller 2
CONDENSER FANS
Number Circuit-1/Circuit-2 14/10 12/8 14/10 14/12 12/12 13/13 13/13 10/10 10/10 13/13
Air on Condenser (Min/ 0°F/131°F
Max), °F (°C) (-17.8°C/55°C)
EVAPORATOR, SHELL AND TUBE HYBRID FALLING FILM 2
147 130 130 147 96 147 96 130 147 147
Water Volume, gal (liters)
(556) (492) (492) (556) (363) (556) (363) (492) (556) (556)
Leaving Water Temperature 40/70
(Min/Max), °F (°C) 2 (4.4/21.1)
Maximum Water Side 150
Pressure, psig (barg) (10.3)
Maximum Refrigerant Side 235
Pressure, psig (barg) (16.2)
Evaporator Drain 3/4
Connection, inches (mm) (19)
NOTES:
1. Shipping and operating weights are not show as selected options may add weight to unit. Contact your nearest Johnson Controls Sales
RI¿FHIRUZHLJKWGDWD
2. )RUOHDYLQJOLTXLGWHPSHUDWXUHEHORZƒ) ƒ& RUDERYHƒ) ƒ& FRQWDFW\RXUQHDUHVW-RKQVRQ&RQWUROV6DOHV2I¿FHIRUDSSOLFD-
tion requirements.

JOHNSON CONTROLS 27
FORM 201.28-EG1 (118)

Physical Data - Round Tube Coil


The data shown in this table is applicable to selected typical configurations. Other configurations are available
through our configuration/selection software. Please contact your nearest Johnson Controls Sales Office for the
chiller configuration that best matches your specific needs.
UNIT FRAME 15 18 21 23 26 27 27 30
CONDENSER CODE 3 3 3 3 3 0 3 3
EVAPORATOR CODE B A A B B D D C
GENERAL UNIT DATA
Number of Independent
2
Refrigerant Circuits
Refrigerant Charge, R-134a or
211/211 229/191 229/229 273/235 273/273 304/304 328/328 371/308
R-513A, Circuit.-1/Circuit.-2, lbs
(96/96) (104/87) (104/104) (124/107) (124/124) (138/138) (149/149) (168/140)
(kg)
Oil Charge, Circuit.-1/Circuit.-2, 2.1/2.0 2.4/2.0 2.5/2.5 2.7/2.6 2.7/2.7 3.0/3.0 3.0/3.0 4.1/3.0
gal (liters) (8.0/7.7) (9.2/7.7) (9.3/9.3) (10.1/9.7) (10.1/10.1) (11.4/11.4) (11.4/11.4) (15.5/11.4)
Minimum Load % 10%
Chassis Dimensions - Length, 203.3 247 291.2 291.2 335.2 291.2 335.2 379.2
inches (mm) (5163) (6274) (7397) (7397) (8514) (7397) (8514) (9631)
Chassis Dimensions - Width, 88.3 88.3 88.3 88.3 88.3 88.3 88.3 88.3
inches (mm) (2242) (2242) (2242) (2242) (2242) (2242) (2242) (2242)
Chassis Dimensions - Height, 94.6 94.6 94.6 94.6 94.6 94.6 94.6 94.6
inches (mm) (2403) (2403) (2403) (2403) (2403) (2403) (2403) (2403)
COMPRESSORS, SEMI-HERMETIC SCREW
Quantity per Chiller 2
CONDENSER FANS
Number Circuit-1/Circuit-2 4/4 6/4 6/6 7/5 7/7 6/6 7/7 9/7
Air on Condenser (Min/Max), 0°F/131°F
°F (°C) (-17.8°C/55°C)
EVAPORATOR, SHELL AND TUBE HYBRID FALLING FILM 2
58 48 48 58 58 82 71
Water Volume, gal (liters) 82 (310)
(220) (182) (182) (220) (220) (310) (269)
Leaving Water Temperature 40/70
(Min/Max), °F (°C) 2 (4.4/21.1)
Maximum Water Side Pressure, 150
psig (barg) (10.3)
Maximum Refrigerant Side 235
Pressure, psig (barg) (16.2)
Evaporator Drain Connection,
3/4
inches (mm)
NOTES:
1. Shipping and operating weights are not show as selected options may add weight to unit. Contact your nearest Johnson Controls Sales
RI¿FHIRUZHLJKWGDWD
2. )RUOHDYLQJOLTXLGWHPSHUDWXUHEHORZƒ) ƒ& RUDERYHƒ) ƒ& FRQWDFW\RXUQHDUHVW-RKQVRQ&RQWUROV6DOHV2I¿FHIRUDSSOLFD-
tion requirements.

28 JOHNSON CONTROLS
FORM 201.28-EG1 (118)

Physical Data - Round Tube Coil (Cont'd)


The data shown in this table is applicable to selected typical configurations. Other configurations are available
through our configuration/selection software. Please contact your nearest Johnson Controls Sales Office for the
chiller configuration that best matches your specific needs.
UNIT FRAME 32 33 34 37 41 44 48 49 52
CONDENSER CODE 3 3 3 3 3 3 3 0 3
EVAPORATOR CODE E C E F H G G K J
GENERAL UNIT DATA
Number of Independent
2
Refrigerant Circuits
Refrigerant Charge, R-134a or
367/367 371/371 391/391 537/308 568/417 478/478 502/502 480/480 562/562
R-513A, Circuit.-1/Circuit.-2, lbs
(166/166) (168/168) (177/177) (244/140) (258/189) (217/217) (228/228) (218/218) (255/255)
(kg)
Oil Charge, Circuit.-1/Circuit.-2, 4.1/4.1 4.1/4.1 4.2/4.2 5.3/2.9 5.5/4.3 5.0/5.0 5.1/5.1 5.2/5.2 5.8/5.8
gal (liters) (15.5/15.5) (15.5/15.5) (15.9/15.9) (20.1/11.0) (20.8/16.3) (18.9/18.9) (19.3/19.3) (19.7/19.7) (22.0/22.0)
Minimum Load % 10%
Chassis Dimensions - Length, 379.2 423.1 423.1 467.1 467.1 555.3 599.3 467.1 599.3
inches (mm) (9631) (10748) (10748) (11864) (11864) (14104) (15222) (11864) (15222)
Chassis Dimensions - Width, 88.3 88.3 88.3 88.3 88.3 88.3 88.4 88.3 88.3
inches (mm) (2242) (2242) (2242) (2243) (2243) (2243) (2244) (2242) (2243)
Chassis Dimensions - Height, 94.6 94.6 94.6 94.7 94.7 94.7 94.7 94.6 94.7
inches (mm) (2403) (2403) (2403) (2405) (2405) (2405) (2405) (2403) (2405)
COMPRESSORS, SEMI-HERMETIC SCREW
Quantity per Chiller 2
CONDENSER FANS
Number Circuit-1/Circuit-2 8/8 9/9 9/9 13/7 12/8 12/12 13/13 10/10 13/13
Air on Condenser (Min/Max), 0°F/131°F
°F (°C) (-17.8°C/55°C)
EVAPORATOR, SHELL AND TUBE HYBRID FALLING FILM 2
113 71 113 96 130 96 96 130 147
Water Volume, gal (liters)
(428) (269) (428) (363) (492) (363) (363) (492) (556)
Leaving Water Temperature 40/70
(Min/Max), °F (°C) 2 (4.4/21.1)
Maximum Water Side Pressure, 150
psig (barg) (10.3)
Maximum Refrigerant Side 235
Pressure, psig (barg) (16.2)
Evaporator Drain Connection,
3/4
inches (mm)
NOTES:
1. Shipping and operating weights are not show as selected options may add weight to unit. Contact your nearest Johnson Controls Sales
RI¿FHIRUZHLJKWGDWD
2. )RUOHDYLQJOLTXLGWHPSHUDWXUHEHORZƒ) ƒ& RUDERYHƒ) ƒ& FRQWDFW\RXUQHDUHVW-RKQVRQ&RQWUROV6DOHV2I¿FHIRUDSSOLFD-
tion requirements.

JOHNSON CONTROLS 29
FORM 201.28-EG1 (118)

Evaporator Options
OPTIONAL ONE-PASS EVAPORATOR

ALL DIMENSIONS - INCHES (MM)

YVAA
MINIMUM MAXIMUM
WATER
E CHILLED CHILLED
VOLUME.
FRAME

COND.

A,B C D NOZZLE WATER FLOW WATER FLOW


GALLONS
SIZE RATE RATE
(LITERS)
GPM (L/S) GPM (L/S)

20.8 6.8 34.5 58 500 1970


15 3 8
(528) (173) (876) (220) (32) (124)
20.8 29.2 56.1 58 500 1970
16 5 8
(528) (742) (1425) (220) (32) (124)
20.8 34.9 70 71 590 2190
17 8 8
(528) (886) (1778) (269) (37) (138)
19.8 17.7 56.8 48 400 1230
18 3 6
(503) (450) (1443) (182) (25) (77)
19.8 61.5 56.7 48 400 1230
19 5 6
(503) (1562) (1440) (182) (25) (77)
21 117.3 56.1 58 500 1970
19 8 8
(533) (2979) (1425) (220) (32) (124)
20.8 1.7 38.1 71 590 2190
20 0 8
(528) (43) (968) (269) (37) (138)
19.8 61.7 56.8 48 400 1230
21 3 6
(503) (1567) (1443) (182) (25) (77)
20.8 34.9 70 71 590 2190
21 5 8
(528) (886) (1778) (269) (37) (138)
21 78.9 70 71 590 2190
21 8 8
(533) (2004) (1778) (269) (37) (138)
Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are permitted. Glycol
OLPLWVDUHKLJKHU3OHDVHFRQWDFW\RXU-RKQVRQ&RQWUROV6DOHV2I¿FHIRUUDWLQJVDQGIXUWKHULQIRUPDWLRQ