PROJECT

LOCATION
CLIENT
CONSULTANT Murzad Ali

Area or Sun Gain or


Item Factor (U) Btu/Hour Watts
Quantity Temp. Diff.
ROOM HEAT Q= U*A*ΔT
ROOM SENSIBLE HEAT
Solar Gain - Glass Area ΔT U
Glass - N SqFt x 20.00 x 1.13 0.00
Glass - NE SqFt x 20.00 x 1.13 0.00
Glass - E SqFt x 20.00 x 1.13 0.00
Glass - SE SqFt x 20.00 x 1.13 0.00
Glass - S 30.13 SqFt x 20.00 x 1.13 680.94
Glass - SW SqFt x 20.00 x 1.13 0.00
Glass - W 30.13 SqFt x 20.00 x 1.13 680.94
Glass - NW SqFt x 20.00 x 1.13 0.00
Skylight SqFt x x 0.00
Solar & Transmission Gain - Walls & Roof
Wall - N SqFt x 20.00 F x 0.45 0.00
Wall - NE SqFt x 20.00 F x 0.45 0.00
Wall - E SqFt x 20.00 F x 0.45 0.00
Wall - SE SqFt x 20.00 F x 0.45 0.00
Wall - S 125.93 SqFt x 20.00 F x 0.45 1,133.37
Wall - SW SqFt x 20.00 F x 0.45 0.00
Wall - W 104.87 SqFt x 20.00 F x 0.45 943.83
Wall - NW SqFt x 20.00 F x 0.45 0.00
Roof 210.00 SqFt x 20.00 F x 0.51 2,142.00
Transmission Gain - Except Walls & Roof
All Glass 60.26 SqFt x 20.00 F x 1.13 1,361.88
Partition 165.00 SqFt x 15.00 F x 0.45 1,113.75
Ceiling 210.00 SqFt x 20.00 F x 0.51 2,142.00
Floor 210.00 SqFt x 15.00 F x 0.28 882.00
INFILTRATION AND BY PASSED AIR
Infiltration 34.50 CFM x 20.00 [Link] x 1.08 745.20
Outside Air 34.44 CFM x 20.00 x BFx1.08 74.39
Internal Heat
People 2.00 Nos. x 245.00 Btu/Hour Per Person 490.00
Lighting 210.00 SqFt x 1.00 W/SqFt x 3.41 716.10
Equipments 150.00 Watts x 3.41 511.50
Power kW/Hp x 0.00
Sub Total 13,617.89
Factor 5-15% 1,702.24
Effective Room Sensible Heat 15,320.13 1.00
ROOM LATENT HEAT
Infiltration 34.50 CFM x 81.00 Gr/Lb x 0.68 1,900.26
Outside Air 34.44 CFM x 81.00 Gr/Lb x BFx0.68 189.70
People 2.00 Nos. x 205.00 Btu/Hour Per Person 410.00
Sub Total 2,499.96
Factor 2.5 - 5% 62.50
Effective Room Latent Heat 2,562.45 2.00
EFFECTIVE ROOM TOTAL HEAT 17,882.58
OUTSIDE AIR HEAT
Sensible 34.44 CFM x 20.00 F(TD) x CF x 1.08 669.51 3.00
Latent 34.44 CFM x 81.00 Gr/Lb x CF x 0.68 1,707.26 4.00
OUTSIDE AIR TOTAL HEAT 2,376.77
GRAND SUB-TOTAL HEAT 20,259.36
Factor 1 - 3% 607.78
GRAND TOTAL HEAT 20,867.14
TONS=GRAND TOTAL HEAT/12000 1.74
FLOOR GROUND
SPACE REFERENCE DIGITAL X RAY
AREA ( SqFt) (WxL) 210.00
False Ceiling Height (Ft) 9.84
Volume (CuFt) 2,066.40
Estimate for Summer
Design Conditions DB (°F) WB (°F) RH (%) SH (Gr/Lb)
Ambient(Out Side) 95.00 82.00 58.00 146.00
Room (InDoor) 75.00 62.00 50.00 65.00
Difference Δ 20.00 20.00 8.00 81.00

By Pass Factor (BF) = 0.10


Contact Factor (CF = 1 - BF) = 0.90
CFM Ventilation
CFM Per Person 5.00 No = 2.00 = 10.00
CFM Per SqFt 0.06 Sqft x 210.00 = 12.60
Air Change Per Hour (CFM) = 1.00
CFM [Link] 2,066.40 x 1.00 x1/60 = 34.44
CFM Infiltration
Swinging x cfm/door = 0.00
Revolving Doors (People) x cfm/door = 0.00
Open Doors 1.00 x 34.44 cfm/door = 34.44
Crack (feet) x cfm/ft = 0.06
34.50
Supply CFM from Machine
Effective Room Sensible Heat Factor =
Effective Room Sensible Heat/Eff Room Total Heat = 0.86
Apparatus Dew Point (ADP)
Indicated ADP (°F) =
Selected ADP (°F) = 52.00
Dehumidified Rise
(Room DB - ADP) x CF = 20.70
DEHUMIDIFIED AIR QUANTITY
Effective Room Sensible Heat = 685.28 CFM
Dehumidified Rise x 1.08
= 322.08 L/s
TOTAL HEAT CAPACITY
Grand Total Heat = 1.74 TR

SENSIBLE HEAT CAPACITY


Grand Sensible Heat = 1.74 TR
12,000.00

Notes:
General U values
Exposed Glass(Window) 1.13
Roof 0.51
Floor 0.28
Partition/Wall 0.45

ADP Condition ESHF ADP


DB-75 1 55.2
RH-50 0.92 54
0.84 52
0.78 50
0.74 48
0.71 46
0.69 44
0.66 40
0.64 34