Room unit for DXR1 room automation stations

QMX1.M34H

QMX1.M34H offers a range of features and functionalities that work with DXR1
room automation stations to deliver comfort in the required application envi-
ronments.
● Easy-to-read LCD
● Three buttons for interactive operation
● Occupancy status changeover via button
● Adjustable room temperature setpoint
● Incorporated temperature sensor
● Conduit box mounting

A6V11393927_en--_d Smart Infrastructure


2021-08-30
Use
The room unit with RJ45 connector can be connected to the DXR1 room automation stations
via RJ45 cable. The cable transmits measured value and set value of the room temperature,
and occupancy status to the room automation station.

Functions
● Digital display of measured room temperature
● Configurable display: Fahrenheit or Celsius
● Digital setpoint adjustment via buttons
● Occupancy status changeover via button
● Display of occupancy status: occupied and unoccupied
● Communication with Actuating DXR1 via Modbus protocol
● The room unit can be used in combination with DXR1 room automation stations only.

Mechanical design
The room unit consists of the following parts:
1. Front module with LCD display (no backlight) and buttons
2. Mounting frame

Type summary

Product No. Stock No. Description Quantity

QMX1.M34H S55499-D465 Room unit and temperature sensor Single package

Ordering
When ordering, indicate product number, stock number and description.

2
Siemens A6V11393927_en--_d
Smart Infrastructure 2021-08-30
Equipment combinations

Product No. Stock No. Description Datasheet*)

DXR1.M09PDZ-112 S55499-D462 Compact actuating room automation station, BACnet A6V11393929


MS/TP
DXR1.M09PDZ-113 S55499-D463

DXR1.E09PDZ-112 S55499-D456 Compact actuating room automation station, BACnet IP A6V11393931

DXR1.E09PDZ-113 S55499-D457

* The documents can be downloaded from [Link] by specifying the


Datasheet number as shown in the above table.

Product documentation

Topic Title Document ID:

Installation and commissioning QMA1..QMX1.. mounting instructions A6V11393920

CE declaration A6V11791496

Product environmental declaration A6V11805936

Related documents such as environmental declarations, CE declarations, etc., can also be


downloaded at the following Internet address:
[Link]

Notes

Security

CAUTION

National safety regulations


Failure to comply with national safety regulations may result in personal injury and property
damage.
● Observe national provisions and comply with the appropriate safety regulations.

Mounting

● The device is suitable for mounting with conduit box.


● Recommended height: 1.50 m above the floor.

3
Siemens A6V11393927_en--_d
Smart Infrastructure 2021-08-30
● Do not mount the devices in recesses, shelves, behind curtains or doors, or above or
near heat sources.
● Avoid direct sunlight.
● Seal the conduit box or the installation tube if any, as air currents can affect sensor read-
ings.
● Adhere to allowed ambient conditions.
Installation

WARNING

No internal line protection for supply lines to external consumers


Risk of fire and injury due to short-circuits
● Adapt the line diameters as per local regulations to the rated value of the installed fuse.

Engineering

Setting parameters
1. Temperature unit:

– Press button for 10 seconds, the settings icon appears.

– If the symbol ℃ appears, press button or to switch between ℃ and ℉.


2. Absolute (ABS) or relative (REL) setpoint:
– Press button again, the setpoint mode ABS appears. Press button or to
switch between ABS and REL.

3. Temperature offset:
– Press button again, the minimum temperature offset value appears.

4
Siemens A6V11393927_en--_d
Smart Infrastructure 2021-08-30
– Press button or to adjust offset value.

Note: The room unit will always save the current settings and exit parameter setting mode if
there is no interaction for 5 seconds.

Restore factory settings


Press button and simultaneously for 10 seconds, the default home page appears.
Operation

Actual room temperature (Celsius or Fahrenheit)

Settings

Room temperature setpoint:


● Celsius or Fahrenheit
● Absolute or relative

Temperature offset value

Room occupancy indicator


/

Note: User-accessible values and settings will vary based on overall system configuration.
Maintenance
The room unit is maintenance-free. The device can be cleaned with freely available, solvent-
free cleaning agents. Do not use mechanical aids (coarse sponges or similar materials).

5
Siemens A6V11393927_en--_d
Smart Infrastructure 2021-08-30
Disposal

The device is considered an electronic device for disposal in accordance


with European Directive and may not be disposed of as domestic waste.
● Use only designated channels for disposing the devices.
● Comply with all local and currently applicable laws and regulations.

Warranty
Technical data on specific applications are valid only together with Siemens products listed
under "Equipment combinations".

6
Siemens A6V11393927_en--_d
Smart Infrastructure 2021-08-30
Technical data
Power data

Power supply (supplied by DXR1)

Operating voltage DC 12…26.4 V, 5 mA

Operational data

Temperature range

Operating temperature 0…50 ℃

Temperature measurement accuracy ±0.5 ℃ at 25 ℃


±1 ℃ max.

Sensing element type

NTC 10k

Interfaces

Interface

Customized interface RJ45 (shield CAT 5-E)


Wiring length: 30 m

Pin Description

1 Ground

2 Not connected

3 Modbus A+

4, 5 +12…26.4 V

6 Modbus B-

7, 8 Not connected

Modbus registers (note for connection to other devices)


QMX1.M34H acts as a Modbus slave device using fixed communication parameters as be-
low:

Communication parameters

Device address 1

Baud rate 9600

Data bits 8

Parity Even

Stop bits 1

7
Siemens A6V11393927_en--_d
Smart Infrastructure 2021-08-30
Register name Description I/O Modbus func- Modbus Start Register Data type
type tion code register address number
type

TR Room temperature from AI 04: Read input Input 0 2 Float, F32-L-S


QMX1.M34H integrated register register
sensor

SpShftIn Setpoint shift input value AI 04: Read input Input 2 2 Float, F32-L-S
from QMX1.M34H button register register

PscBtnIn Presence button input BI 04: Read input Input 4 1 U16-B


value from QMX1.M34H register register 0x0001: occupied
0x0000: unoccupied

TRRu Room Temperature for AO 16: Write Holding 0 2 Float, F32-L-S


QMX1.M34H visualization multiple register register

PrSpShftRu Setpoint shift for AO 16: Write Holding 2 2 Float, F32-L-S


QMX1.M34H visualization multiple register register

PrSpRu Present setpoint for AO 16: Write Holding 4 2 Float, F32-L-S


QMX1.M34H visualization multiple register register

PscBtnRu Presence button for BO 16: Write Holding 6 1 U16-B


QMX1.M34H visualization multiple register register 0x0001: occupied
0x0000: unoccupied

SplyVtg Power supply voltage for ACnf 16: Write Holding 7 1 U16-B
QMX1.M34H Val1) multiple register register 0x000F: 15 V power
supply (default value)
0x0018: 24 V power
supply

SpTRShftLm Setpoint shift ACnf 16: Write Holding 8 2 Float, F32-L-S


limitation(symmetric) Val1) multiple register register Min setpoint shift = -
SpTRShftLm
Max setpoint shift =
SpTRShftLm
Max range is 10.0K
(Default value)

SysUn2) System of unit BCnf 16: Write Holding 10 1 U16-B


Val1) multiple register register 0x0000: ℃
0x0001: ℉

Note:
1) ACnfVal (Analog configuration value) and BCnfVal (Binary configuration value) should only

be updated when initialize the room unit or the value is changed


2) This data point has the same effect as local Temperature unit setting.

8
Siemens A6V11393927_en--_d
Smart Infrastructure 2021-08-30
Conformity

Ambient conditions and protection classification

Degree of protection of housing to IEC EN 60529 IP30

Overvoltage category to IEC EN 60730-1 Class III

Climatic ambient conditions


● Transport (packaged for transport) as per ● Class 2K3
EN 60721-3-2 Temperature -25...70 °C (-13... 158 °F)
Air humidity 5...95%.
● Operation as per EN 60721-3-3. ● Class 3K5
Temperature -5...50 °C (23... 122 °F)
Air humidity 5...95%.

Mechanical ambient conditions


Transport as per EN 60721-3-2 Class 2M2
Operation as per EN 60721-3-3 Class 3M2

Standards, directives and approvals

EU conformity (CE) A6V11791496*)

RCM conformity A6V11791501*)

Environmental compatibility The product environmental declaration (A6V11805936*) contains


data on environmentally compatible product design and assessments
(RoHS compliance, materials composition, packaging, environmental
benefit, disposal).

*) The documents can be downloaded from [Link]

General data

General

Dimensions 86 mm × 86 mm × 16 mm

Color Signal white (RAL9003)

Weight Net weight: 87.9 g


Gross weight: 145.3 g

9
Siemens A6V11393927_en--_d
Smart Infrastructure 2021-08-30
Dimensions

10
Siemens A6V11393927_en--_d
Smart Infrastructure 2021-08-30
Issued by
© Siemens Switzerland Ltd, 2021
Siemens Switzerland Ltd
Technical specifications and availability subject to change without notice.
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
[Link]/buildingtechnologies

Document ID A6V11393927_en--_d
Edition 2021-08-30