CSC101 Calculation Sheet

The document provides input data and settings for CSC 101/CSC 162 relays used by Easun Reyrolle Limited in India, detailing parameters such as voltage level, CT/PT ratios, and sequence resistances. It includes specific calculations for zone settings related to different fault types and outlines the maximum load resistance observed. The document is created by G. Mahendiran, Senior Engineer, and emphasizes the importance of adhering to the specified resistance values.

Uploaded by

Shivendra Sahu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
29 views10 pages

CSC101 Calculation Sheet

The document provides input data and settings for CSC 101/CSC 162 relays used by Easun Reyrolle Limited in India, detailing parameters such as voltage level, CT/PT ratios, and sequence resistances. It includes specific calculations for zone settings related to different fault types and outlines the maximum load resistance observed. The document is created by G. Mahendiran, Senior Engineer, and emphasizes the importance of adhering to the specified resistance values.

Uploaded by

Shivendra Sahu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd

Easun Reyrolle Limited, India

INPUT DATA for CSC 101 / CSC 162 Relays:

1 Voltage Level (KV)

2 PT Ratio

3 CT Ratio

4 Positive seq. Resistance(R1) / Km

5 Positive seq. Reactance(X1) / Km

6 Zero seq. Resistance(R0) / Km

7 Zero seq. Resistance(X0) / Km

8 Line Length (Km)

9 Maximum Load Current (Primary in A)

10 Operating Power Factor

11 Zone 1 Settings required in %

12 Zone 2 Settings required in %

13 Zone 3 Settings required in %

14 Zone 4 Settings required in %

15 Zero Seq. Mutual Reactance (Xm0)


Fill the following Data

220

2000

800

0.0790

0.4100

0.4000

1.4560

75.7900

800.000

0.9

80

123

231

2.8

0
SETTINGS TO BE ADOPTED

(CT Secondary Rated : 1A, PT Secondary : 110V P-P)

1 KV, CTR, LL ( As It Is)

2 Kr 1.354

3 Kx 0.85

4 Km 0

5 R_Line 2.395

6 X_Line 12.43

7 R1_PE 5

8 X1_PE 9.944

9 R2_PE 7.946

10 X2_PE 15.288

11 R3_PE 10.532

12 X3_PE 28.712

13 R4_PE 0.415

14 X4_PE 0.348

15 R1_PP 5

16 X1_PP 9.944

17 R2_PP 7.946

18 X2_PP 15.288

19 R3_PP 10.532

20 X3_PP 28.712

21 R4_PP 0.415

22 X4_PP 0.348

23 Max Load Resistance Observed on Ohms 36.99


Note : Select the Resitance Value of the Z3 or Z4 such
that it should be less than the Max. Load Resistance
Calculated

Created By:

[Link]
Senior Engineer - Product Management
Easun Reyrolle Limited
Hosur, India - 635 126
Moile : +91 99524 25301.
Email : mahendiran@[Link]

All Rights Reserved to M/s. Eaun Reyrolle Limited., Any


form of Reproduction of this copy is prohibited.
EASUN REYROLLE LIMITED, INDIA

INPUT DATA for CSC 101 / CSC 162 Relays: INPUT

1 Voltage Level (KV) 220

2 PT Ratio 2000

3 CT Ratio 800

4 Positive seq. Resistance(R1) / Km 0.079

5 Positive seq. Reactance(X1) / Km 0.41

6 Zero seq. Resistance(R0) / Km 0.4

7 Zero seq. Resistance(X0) / Km 1.456

8 Line Length (Km) 75.79

9 Maximum Load Current (Primary in A) 800

10 Power Factor 0.9

11 Zone 1 Settings required in % 80

12 Zone 2 Settings required in % 123

13 Zone 3 Settings required in % 231

14 Zone 4 Settings required in % 2.8

15 Zero Seq. Mutual Reactance (Xm0) 0

Zone 2 Ph-E Fault:

R2_pe 2.94580572

X2_pe 15.2883588

max(x2_pe/2,25/LZ+R_line) 12.394964
R2_pe derived (as per Manual) 2.94580572

X2_pe Rect 2.5

Min(8*X2_Rect, R2_pe/4) 0.73645143

R2_pe Rect 5

R2_pe to be Set 7.94580572

Zone 2 Ph-Ph Fault:

R2_pp 2.94580572

X2_pp 15.2883588

max(x2_pp/2,15/LZ+R_line) 8.394964

R2_pp derived (as per Manual) 2.94580572

X2_pp Rect 2.5

Min(8*X2_Rect, R2_pp/4) 0.73645143

R2_pp Rect 5

R2_pp to be Set 7.94580572

Zone 4 Ph-E Fault:

R4_pe 0.067058992

X4_pe 0.34802768

max(x4_pe/2,25/LZ+R_line) 12.394964

R4_pe derived (as per Manual) 0.067058992

X4_pe Rect 0.17401384

Min(8*X4_Rect, R4_pe/4) 0.016764748

R4_pe Rect 0.34802768

R4_pe to be Set 0.415086672

Zone 4 Ph-Ph Fault:

R4_pp 0.067058992
X4_pp 0.34802768

max(x4_pp/2,15/LZ+R_line) 8.394964

R4_pp derived (as per Manual) 0.067058992

X4_pp Rect 0.17401384

Min(8*X4_Rect, R4_pp/4) 0.016764748

R4_pp Rect 0.34802768

R4_pp to beSet 0.415086672


ED, INDIA

COMMON PARAMETERS:

CTR / PTR 0.4

Kr 1.35443037974684

Kx 0.850406504065041

km

R_Line 2.394964

X_line 12.42956

Zone 1 Ph-E Fault:

R1_pe 1.9159712

X1_pe 9.943648

max(x1_pe/2,25/LZ+R_line) 12.394964

R1_pe derived (as per Manual) 1.9159712

X1_pe Rect 2.5

Min(8*X1_Rect, R1_pe/4) 0.4789928

R1_pe Rect 5

R1_pe to be Set 5

Zone 1 Ph-Ph Fault:

R1_pp 1.9159712

X1_pp 9.943648

max(x1_pp/2,15/LZ+R_line) 8.394964

R1_pp derived (as per Manual) 1.9159712

X1_pp Rect 2.5


Min(8*X1_Rect, R1_pp/4) 0.4789928

R1_pp Rect 5

R1_pp to be Set 5

Zone 3 Ph-E Fault:

R3_pe 5.53236684

X3_pe 28.7122836

max(x3_pe/2,25/LZ+R_line) 14.3561418

R3_pe derived (as per Manual) 5.53236684

X3_pe Rect 2.5

Min(8*X3_Rect, R3_pe/4) 1.38309171

R3_pe Rect 5

R3_pe to be Set 10.53236684

Zone 3 Ph-Ph Fault:

R3_pp 5.53236684

X3_pp 28.7122836

max(x3_pp/2,15/LZ+R_line) 14.3561418

R3_pp derived (as per Manual) 5.53236684

X3_pp Rect 2.5

Min(8*X3_Rect, R3_pp/4) 1.38309171

R3_pp Rect 5

R3_pp to be Set 10.53236684

Maximum Load Resistance:

Theta (DEGREES(ACOS(PF))) 25.8419327631671


Factor = (K re * 0.9) / (K rel * K ss* IL max) 0.000685096153846

Factor * KV 150.721153846154

63.4 - Theta 37.5580672368329

Sin(63.4 - Theta) / Sin 63.4 0.681722600583978

Load Resistance Primary 102.750016963018

Load Resistance Secondary 41.1000067852072

90% of Load Resistance 36.9900061066864