Generac Installation Manual
Generac Installation Manual
8 - 22 kW Air-Cooled Generators
This list of Frequently Asked Questions (FAQs) are the frequently asked installation questions
that pertain to ALL Home Standby models.
Some questions may not be applicable to the model(s) covered in this publication.
Please review the Safety Section of your product’s Owners or Installation Manual before operating your Home
Standby Generator.
Q: Do I have to supply the generator with the 100% loaded BTU rated fuel supply and pipe size?
A: Yes, the generator needs the 100% loaded BTU fuel rating to start, run and handle loads. The fuel pipe must
be sized for 100% load, regardless of the load.
Q: Can I use a fuel shut off valve that is not “Full Flow Rated”?
A: No, it must be a Full Flow Rated valve and must also match the required fuel pipe ID dimensions.
Q: Do pipe elbows, tees, drip legs, etc. affect pipe size and flow?
A: Yes, they are restrictions to gas flow. You must add 2.5 ft. (.76 m) per each elbow, tee, etc. to the overall cal-
culated distance from the source to the generator.
Q: Can I leave the unit on the shipping pallet and install it?
A: No, it must be installed per local jurisdiction, code and the instructions as outlined by the manufacturer.
Q: Can I run the Main AC and Control Wires in the same conduit?
A: Yes, this wiring can be run in the same conduit if the appropriate rated wire and insulation is used and it
meets code.
WARNING!
California Proposition 65
Engine exhaust and some of its constituents are known to the state of California to cause cancer,
birth defects, and other reproductive harm.
WARNING!
California Proposition 65
This product contains or emits chemicals known to the state of California to cause cancer,
birth defects, and other reproductive harm.
Section 8 Troubleshooting
8.1 System Diagnosis .................................................................................................................41
Section 10 Accessories
10.1 Descriptions ........................................................................................................................45
Section 11 Diagrams
11.1 Interconnection Diagram ....................................................................................................47
11.2 Installation Diagram ............................................................................................................49
Indicates a hazardous situation or action that, if not avoided, will result in death or serious
injury.
Indicates a hazardous situation or action that, if not avoided, could result in death or seri-
ous injury.
Indicates a hazardous situation or action that, if not avoided, could result in minor or mod-
erate injury.
NOTE: Notes provide additional information important to a procedure or component.
These safety warnings cannot eliminate the hazards they indicate. Observing safety precautions and strict compliance
with the special instructions while performing the action or service are essential to preventing accidents.
Four commonly used safety symbols accompany DANGER, WARNING, and CAUTION boxes and the type of informa-
tion each indicates:
This symbol points out important safety information that, if not followed, could
endanger personnel and/or property.
The operator is responsible for proper and safe use of the equipment. The manufacturer strongly recommends that if
the operator is also the owner, to read their Owner’s Manual and thoroughly understand all instructions before using
this equipment. The manufacturer also strongly recommends instructing other users to properly start and operate the
unit. This prepares them if they need to operate the equipment in an emergency.
Save These Instructions – The manufacturer suggests that these rules for safe oper-
ation be copied and posted near the unit’s installation site. Safety should be
stressed to all operators and potential operators of this equipment.
Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become familiar with
this Installation Manual and with the unit. The generator can operate safely, efficiently and reliably only if it is properly
installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rules or pre-
cautions.
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warnings in this
manual and on tags and decals affixed to the unit are, therefore, not all-inclusive. If using a procedure, work method or
operating technique the manufacturer does not specifically recommend, ensure that it is safe for others. Also, make
sure the procedure, work method or operating technique utilized does not render the generator unsafe.
Despite the safe design of this generator, operating this equipment imprudently, neglecting its mainte-
nance or being careless can cause possible injury or death. Permit only responsible and capable per-
sons to install, operate and maintain this equipment.
+ Potentially lethal voltages are generated by these machines. Ensure all steps are taken to render the
machine safe before attempting to work on the generator.
Parts of the generator are rotating and/or hot during operation. Exercise care near running generators.
Installation must always comply with applicable codes, standards, laws and regulations.
A running generator gives off carbon monoxide, an odorless, colorless poison gas. Breathing in carbon
monoxide can cause headaches, fatigue, dizziness, nausea, vomitting, confusion, fainting, siezures or
death.
• Adequate, unobstructed flow of cooling and ventilating air is critical to correct generator operation. Do not alter
the installation or permit even partial blockage of ventilation provisions, as this can seriously affect safe operation
of the generator. The generator MUST be installed and operated outdoors only.
• Keep hands, feet, clothing, etc., away from drive belts, fans, and other moving or hot parts. Never remove any
drive belt or fan guard while the unit is operating.
• When working on this equipment, remain alert at all times. Never work on the equipment when physically or men-
tally fatigued.
• Inspect the generator regularly, and contact the nearest Dealer for parts needing repair or replacement.
• Before performing any maintenance on the generator, disconnect its battery cables to prevent accidental start up.
Disconnect the cable from the battery post indicated by a NEGATIVE, NEG or (–) first, then remove the POSI-
TIVE, POS or (+) cable. When reconnecting the cables, connect the POSITIVE cable first, the NEGATIVE cable
last.
• Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may
result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
Improper installation can result in personal injury and damage to the generator. It
may also result in the warranty being suspended or voided. All the instructions
listed below must be followed including location clearances and pipe sizes.
The installation of this product must comply strictly with applicable codes, stan-
dards and regulations. This product can be installed by the homeowner. However, if
you are uncomfortable with the skills or tools required, have a qualified electrician
or contractor perform the installation.
If this generator is used to power electrical load circuits normally powered by a util-
ity power source, it is required by code to install a transfer switch. The transfer
switch must effectively isolate the electrical system from the utility distribution sys-
tem when the generator is operating (NEC 700, 701 & 702). Failure to isolate an elec-
trical system by such means will result in damage to the generator and also may
result in injury or death to utility power workers due to backfeed of electrical energy.
2.3 — Unpacking
1. With the box removed, you can see that this unit came with an automatic transfer switch. The transfer switch is
an option and may not be included.
2. Remove the wood frame and lift the transfer switch, if present, off the top of the generator.
3. Remove bolts and clamps. Exercise caution when removing the generator. Dragging it off the pallet WILL dam-
age the base. The generator must be lifted from the wooden pallet to remove.
Lid
Front
Access Panel
4. The lid will be locked. A set of keys is located behind the breaker door. Open the breaker door and cut the zip tie
to remove the keys. Use the keys to open the lid of the generator.
5. There are two locks securing the lid, one on each side. To properly open the lid, press down, on the lid, above the
side lock and unlock the latch.
6. Repeat for the other side. If pressure is not applied from the top, the lid may appear stuck.
NOTE: Always verify that the side locks are unlocked before attempting to lift the lid.
7. Once the lid is open, remove the front access panel by lifting it up and out. Also remove the black panel, indi-
cated by the arrow, over top of the customer connection area.
8. Perform a visual inspection for any hidden freight damage. If damage is present, contact the freight carrier.
Fuel
Regulator
Battery
Terminal Cap Wire Shielding
MLCB
Terminal Caps
MLCB
Locking Mechanism Wire Nuts
Keys
Existing Wall
18 in (457 mm)
60 in (1524 mm) Minimum Distance 60 in (1524 mm)
These guidelines are based upon fire Clearance from the ends and front of the gener-
testing of the generator enclosure and 36 in ator must be 36 in (914 mm). This would
the manufacturer’s requirement for air (914 mm) include shrubs, bushes or trees. Clearance at
flow for proper operation. Local codes the top should be a minimum of 60 in (1524
may be different and more restrictive mm) from any structure, overhang or projec-
than what is described here. tions from the wall. The generator should not
be placed under a deck or other structure that
is closed in and would limit or constrain air flow.
60 in (1524 mm)
Required
Minimum From Ends
to openings in walls
Generator
18 in (457 mm)
Minimum
Install the generator set, in its protective enclosure, outdoors, where adequate cooling and ventilating air is always
available (Figure 1.9). Consider these factors:
• The installation of the generator must comply strictly with NFPA 37, NFPA 54, NFPA 58 and NFPA 70 standards.
• Install the unit where air inlet and outlet openings will not become obstructed by leaves, grass, snow, etc. If pre-
vailing winds will cause blowing or drifting, consider using a windbreak to protect the unit.
• Install the generator on high ground where water levels will not rise and endanger it. It should not operate in or be
subjected to standing water.
• Allow sufficient room on all sides of the generator for maintenance and servicing. This unit must be installed in
accordance with current applicable NFPA 37 and NFPA 70 standards, as well as any other federal, state and
local codes for minimum distances from other structures. DO NOT install under wooden decks or structures
unless there is at least 5 ft (1.52 m) of clearance above the generator, 3 ft (.91 m) of clearance on sides and front,
and a minimum of 18 in (457 mm) of clearance at the back of the unit.
• Install the unit where rain gutter down spouts, roof run-off, landscape irrigation, water sprinklers or sump pump
discharge does not flood the unit or spray the enclosure, including any air inlet or outlet openings.
• Install the unit where services will not be affected or obstructed, including concealed, underground or covered
services such as electrical, fuel, phone, air conditioning or irrigation. This could affect Warranty Coverage.
• Where strong prevailing winds blow from one direction, face the generator air inlet openings to the prevailing
winds.
• Install the generator as close as possible to the fuel supply to reduce the length of piping. REMEMBER THAT
LAWS OR CODES MAY REGULATE THE DISTANCE AND LOCATION.
• Install the generator as close as possible to the transfer switch. REMEMBER THAT LAWS OR CODES MAY
REGULATE THE DISTANCE AND LOCATION.
• The generator must be installed on a level surface. The generator must be level within a .5 in (13mm) all around.
• The generator is typically placed on pea gravel, crushed stone or a concrete pad. Check local codes to see what
type is required. If a concrete pad is required, all federal, state and local codes should be followed.
Southwest Research Institute Decal (located inside the generator, next to the generator’s data decal)
http://www.swri.org/4org/d01/fire/listlab/listprod/director.htm
Based on this testing and the requirements of NFPA 37, Sec 4.1.4, the guidelines for installation of the genera-
tors listed above are changed to 18 in (457 mm) from any point of the generator enclosure to a stationary wall,
building or structure. The required distance for maintenance and airflow clearance, the area above the generator
should be at least 5 ft (1.52 m) with a minimum of 3 ft (.91 m) at the front and ends of the enclosure. This would include
trees, shrubs and bushes. Vegetation not in compliance with these clearance parameters could obstruct air flow. In
addition, exhaust fumes from the generator could inhibit plant growth. See Figure 3.1 and the installation drawing within
the owner’s manual for details.
Generator exhaust contains DEADLY carbon monoxide gas. This dangerous gas can cause unconsciousness or
death. Do not place the unit near windows, doors, fresh air intakes (furnaces, etc.) or any openings in the building or
structure, including windows and doors of an attached garage.
If the generator is not set to the OFF mode, it can crank and start as soon as the bat-
tery cables are connected. If the utility power supply is not turned off, sparking can
occur at the battery posts and cause an explosion.
When mounting the generator to concrete, there are four mounting holes available for securing the generator, if codes
require (two holes inside the front of the generator compartment and two holes in the back). See Figure 4.2.
NOTE: The top of the generator carton has a template that can be used to mark the concrete pad to pre-drill
the mounting holes.
FUEL KNOB LOCATIONS SHOWN FROM GENERATOR AIR BOX SIDE VIEW
8 kW GENERATOR
FUEL KNOB
11-22 kW GENERATORS
ORANGE FUEL FUEL KNOB
CONVERSION KNOB
NOTE: All pipe sizing, construction and layout must comply with NFPA 54 for natural gas applications and
NFPA 58 for liquid propane applications. Once the generator is installed, verify that the fuel pressure NEVER
drops below it’s required fuel pressure rating. For further information regarding NFPA requirements refer to
their website at www.nfpa.org.
Prior to installation of the generator, the installer should consult local fuel suppliers or the fire marshal to check codes
and regulations for proper installation. Local codes will mandate correct routing of gaseous fuel line piping around gar-
dens, shrubs and other landscaping to prevent any damage.
Special considerations should be given when installing the unit where local conditions include flooding, tornadoes, hur-
ricanes, earthquakes and unstable ground for the flexibility and strength of piping and their connections.
Use an approved pipe sealant or joint compound on all threaded fittings.
All installed gaseous fuel piping must be purged and leak tested prior to initial start-up in accordance with local codes,
standards and regulations.
* Natural gas is in cubic feet per hour / cubic meters per hour.
** LP is in gallons per hour / liters per hour.
*** Values given are approximate.
Verify that gas meter is capable of providing enough fuel flow to include household appliances and all other loads.
Gaseous fuels such as natural gas and liquid propane (LP) gas are highly explosive.
Even the slightest spark can ignite such fuels and cause an explosion. No leakage of
fuel is permitted. Natural gas, which is lighter than air, tends to collect in high areas.
LP gas is heavier than air and tends to settle in low areas.
NOTE: A minimum of one approved full flow manual shut-off valve must be installed in the gaseous fuel sup-
ply line. The valve must be easily accessible. Local codes determine the proper location.
NOTE: The gas supply and pipe MUST be sized at 100% Load BTU / megajoule rating.
Figure 5-2. Full Flow Shutoff Valve / Accessory Valve with Manometer Port
NOTE: Figure 5-2 illustrates a full flow shutoff valve and a Generac accessory valve with a manometer port for
making fuel pressure checks. This accessory valve permits making pressure checks without going into the
generator enclosure.
Sediment
Trap
3. When connecting the gas line to the generator, use the provided section of UL Listed or AGA-approved flexible
fuel line in accordance with local regulations. The purpose of the flexible fuel line is to ensure that vibration from
the generator does not cause a gas leak at one of the connection points, so it’s important that the line be installed
with as few bends as possible. Configure the sediment trap (if applicable or required by code) as illustrated.
4. Never bend the flexible fuel line to avoid using an elbow. Bending the flexible line decreases its ability to absorb
vibrations and defeats its purpose, as well as constricts the actual fuel flow. See Figure 5-4.
5. Check for leaks by spraying all connection points with a soap solution made of dishwashing soap and water. You
should not see the solution be “blown away” or form “bubbles”. Next, check the gas pressure at the regulator in
the generator by following these steps.
– Close gas supply valve.
– Remove the top gas pressure test port from the regulator, and install the gas pressure tester (manometer). See
Figure 5-5.
– Open the gas supply valve and ensure that the pressure is within the specified values.
6. Close gas valve when completed.
Fuel Regulator
MANUAL SHUT
OFF VALVE
11 kW and Below = 0000001
5"-7" WC REGULATOR
16 kW and Above =
TRAP 3.5"-7" WC REGULATOR
GAS MAIN
2-5 PSI
NG BTU = CUBIC FEET/HOUR X 1000
PRIMARY REGULATOR
BEST PRACTICE SPECIFIED BY THE REGULATOR
MANUFACTURER (SUPPLIED BY INSTALLING
CONTRACTOR)
MANUAL SHUT
FUEL PRESSURE OFF VALVES
10-12” WC
TRAP
NOTE: When sizing a secondary regulator for LP or high pressure natural gas applications be sure to note the
maximum individual load capabilities which will be lower than total capacity. This could impact generator start-
ing performance if sized too small.
NOTE: It is not recommended to reduce the fuel pipe size exiting the secondary regulator unless necessary to
accommodate the ½” or ¾” flexible fuel line that is shipped with the generator. This may potentially cause
starting or performance issues.
A YELLOW #1 & #2 N1 & N2 - 240 VAC - Sensing for Utility Dropout and Pickup
NOTE: Wires 23, 194 and 0 must be run through the provided wire shielding provided in the manual bag to sep-
arate the low voltage from the high voltage wires unless the requirement of 300.3(c)(1) of the NEC are met (see
the Parts Shipped Loose section).
NOTE: Must be connected to keep battery charged whether unit is running or not.
NOTE: Main AC (E1, E2 and Neutral) wiring must be in accordance with local jurisdiction and codes.
1. Strip the insulation off the wire ends. Do not remove excessive insulation.
2. Remove the two cap plugs located behind the breaker door and to the right of the Main Breaker.
3. Loosen the lugs of the Main Breaker through the access holes.
4. Insert a power wire (E1 or E2) through the opening in the back cover and into the bottom lug. Torque to the
proper specification.
NOTE: There are three (3) screws inside the top of the breaker panel (behind the breaker door). Removing
these screws will allow the entire breaker box to be carefully pulled out. When reinstalling, be certain that the
tabs on the bottom lock into place.
5. Connect the Neutral wire to the Neutral Lug and torque to the required specification. See Figure 6-1.
6. Connect the Ground wire to the Ground Lug and torque to the required specification. See Figure 6-1.
NOTE: Neutral Bonding - For installations that require the neutral to be bonded to the ground, this is to be
done on the customer connections terminals inside the generator. Connect a suitably sized wire from the neu-
tral bar to the ground bar. This is normally required when the generator is the source in a separately derived
system. It is not required when the generator is a backup source in a utility supplied electrical system with a 2-
pole transfer switch. See Figure 6-1.
NOTE: Torque all wiring lugs, bus bars and connection points to the proper torque specifications. Torque
specifications for the Main Line Circuit Breaker (MLCB) can be found on a decal located on the inside of the
Main Line Circuit Breaker Door.
Battery cables were factory connected at the generator. See Figure 6-3. Connect cables to battery posts as follows:
4. Connect the red battery cable (from starter contactor) to the battery post indicated by a positive, POS or (+).
5. Connect the black battery cable (from frame ground) to the battery post indicated by a negative, NEG or (—).
6. Install the red battery post cover (included).
NOTE: Dielectric grease should be used on battery posts to aid in the prevention of corrosion.
NOTE: Damage will result if battery connections are made in reverse.
Red Lead
From Starter
Contactor
Black Lead
To Frame
Red (+)
Black (-)
12VDC System
12VDC
NOTE: In areas where temperatures regularly fall below 32 °F (0 °C), a pad type battery heater and engine oil
warmer are required to be installed to aid in cold climate starting. This is available as a cold weather kit
through an independent authorized service dealer and is also available on Generac.com.
With AUTO mode active, the engine may crank and start at any time without warning.
Such automatic starting occurs when utility power source voltage droops below a
preset level or during the normal exercise cycle. To prevent possible injury that
might be caused by such sudden starts, always push the OFF button, remove the
fuses, and disconnect the battery before working on or around the generator or
transfer switch. Then, place a “DO NOT OPERATE” tag on the generator panel and
on the transfer switch.
LCD Screen
Up Arrow Button
Enter Button
Auto Button
Manual Button
OFF Button
Down Arrow Button
Escape
Auto Selecting this button activates fully automatic system operation. Automatic operation allows the unit to automatically start
and exercise the generator according to the exercise timer settings (see Setting the Exercise Timer section).
Off This button shuts down the generator and also prevents automatic operation and exercise of the unit.
Manual This button will crank and start the generator. Transfer to standby power will not occur unless there is a utility
failure.
Generator Size 8 kW 11 kW 16 kW / 20 kW 22 kW
Exercise Speed n/a* n/a* 2400 rpm 1950 rpm
Exercise Frequency Weekly/Bi-Weekly/Monthly Weekly/Bi-Weekly/Monthly Weekly/Bi-Weekly/Monthly Weekly/Bi-Weekly/Monthly
Options
Exercise Time Length 12 minutes 12 minutes 5 minutes 5 minutes
* exercise at 3600 rpm
Table 7-1. Generator Exercise Characteristics
3600
3400
3000
2800
2600
2400
2200
2000
1800
0 sec 5s 10 s 15 s 20 s 25 s 30 s 35 s 40 s 45 s 1 min 5 min
Exercise Time
3200
Low Speed Exercise PrŽĮůĞ - 16 to 20 kW Generators
3000
Exerccise Speed (RPM)
2800
2600
2400
2200
2000
0 sec 5s 10 s 1 min 5 min
Exercise Time
ACTIVATION CHART
Display Reads: Generator Active is displayed on the If the wrong language is selected, it may be changed
Up Arrow = (+) LCD screen when the unit is first later using the Edit menu.
powered up. After displaying firmware
and hardware version codes, as well as
Language
- English + other system information, the Installation
Wizard is launched, and the Language
screen is displayed.
Press ENTER.
Down Arrow = (-)
Display Reads: Press ENTER. Press the ESCAPE key to abort the activation
sequence. NOT ACTIVATED is displayed and the
generator will run in manual mode only. Disconnect and
Activate me (ENT) or reconnect the negative battery cable to restart the
ESC to run in manual activation routine. If power is removed after a
successful activation, no data is lost, but the time and
date must be updated.
Display Reads: Use ARROW keys to increment or Press the ESCAPE to return to preceding digits if a
decrement the digit to correspond to the correction becomes necessary.
first number of the pass code.
SN 1234567890 If attempts to enter the activation code are
PASS CODE XXXXX Press ENTER. unsuccessful, check the number against the code
given on activategen.com. If it is correct, contact 1-888-
Repeat step to enter remaining digits. 9ACTIVATE (922-8482, US & CA only).
Never operate the engine with the oil level below the “Add” mark on the dipstick.
Doing this could damage the engine.
NOTE: This unit comes filled with 30 weight organic oil from the factory. Check the oil level and add the appro-
priate viscosity and amount if necessary.
This will only come up the Įrst Ɵme the generator is powered. If ESC is pressed to skip the
acƟvaƟon process, the baƩĞry must be disconnected to allow acƟvaƟon again and this process
"Generator"
will reiniƟĂůŝze. If power is removed aŌĞr a successful acƟvaƟon, the data is remembered and the
"AcƟve"
acƟvaƟon steps are skipped.
ENTER
"Install Wizard" IF NOT YET ACTIVATED ENTER
"......."
"AcƟvate me (ENT) or" ESCAPE
ENTER "NOT ACTIVATED !"
"ESC to run in manual"
"Language" ENTER
"<- XXXXX ->" Note1: Can run in MANUAL only
"To acƟvate go to" if NOT ACTIVATED
Note1: Language only shows up "www.acƟvategen.com"
Įƌst Ɵme it is powered unless
"- English +" enter is pressed to skip through 3 sec delay Note2: Must disconnect baƩĞry
"- Espanol +" to allow acƟvaƟon again
the install wizard
"- Francois +"
"Install Wizard"
"Set Exercise"
ENTER
"- NO +" Note: Low speed
"Quiet Test Mode"
"YES +" exercise selecƟŽn
ENTER
"- WEEKLY +"
"Select Frequency" - BIWEEKLY +" Note: Set Exercise Time
MONTHLY +"
"Select Hour (0-23)"
"Select Minute (0-59)"
If Freq=Weekly or Biweekly
"Select Day"
"Sunday" If Freq=Monthly
"Monday" Select "1- 28"
"Tuesday"
"Wednesday"
"Thursday"
"Friday"
"Saturday"
ENTER
"XXXXX"
"XXXXX"
Note: Finishes at status screen
Do not attempt manual transfer switch operation until all power voltage supplies to
the transfer switch have been positively turned off. Failure to turn off all power volt-
age supplies will result in extremely hazardous and possibly fatal electrical shock.
The transfer switch is now electrically “hot.” Contact with “hot” parts will result in
extremely hazardous and possibly fatal electrical shock. Proceed with caution.
5. Use an accurate AC voltmeter to check utility power source voltage across transfer switch terminals N1 and N2.
Nominal line-to-line voltage should be 240 volts AC. If it’s not, verify AC output and wiring from utility source to
N1 and N2 lugs at transfer switch.
6. Check utility power source voltage across terminals N1 and the transfer switch neutral lug; then across terminal
N2 and neutral. Nominal line-to-neutral voltage should be 120 volts AC. If it’s not, verify AC output and wiring
from utility source to N1 and N2 lugs at transfer switch.
7. When certain that utility supply voltage is compatible with transfer switch and load circuit ratings, turn OFF the
utility power supply to the transfer switch to simulate a power outage.
NOTE: Do not remove the N1 and N2 fuses in order to simulate an outage.
8. On the generator panel, push the MANUAL button. The engine should crank and start.
9. Let the engine warm up for about five minutes to allow internal temperatures to stabilize. Then, set the genera-
tor’s main circuit breaker to its ON (or closed) position.
Proceed with caution! Generator power voltage is now supplied to the transfer
switch. Contact with live transfer switch parts will result in dangerous and possibly
fatal electrical shock.
10. Connect an accurate AC voltmeter and a frequency meter across transfer switch terminal lugs E1 and E2. Volt-
age should be 238-242 at a frequency of 59.5-60.5 Hertz. If it’s not, verify that the MLCB is closed and verify AC
output and frequency (Hertz or Hz) at the MLCB. Also verify wiring from generator to E1 and E2 lugs at transfer
switch.
11. Connect the AC voltmeter test leads across terminal lugs E1 and neutral; then across E2 and neutral. In both
cases, voltage reading should be 119-121 volts AC. If it’s not, verify that the MLCB is closed and verify AC output
between the E1 and E2 of the MLCB and Neutral at the generator. Also, verify wiring from generator to E1, E2
ans Neutral lugs at transfer switch.
12. Set the generator’s main circuit breaker to its OFF (or OPEN) position.
13. Push the generator’s OFF button. The engine should shut down.
NOTE: It is important not to proceed until certain that generator AC voltage and frequency are correct and
within the stated limits.
Do not attempt manual transfer switch operation until all power voltage supplies to
the transfer switch have been positively turned off. Failure to turn off all power volt-
age supplies will result in extremely hazardous and possibly fatal electrical shock.
4. Manually set the transfer switch to the STANDBY position, i.e., load terminals connected to the generator’s E1/
E2 terminals. The transfer switch operating lever should be down.
5. Push the generator’s MANUAL button. The engine should crank and start immediately.
6. Let the engine stabilize and warm up for a few minutes.
7. Set the generator’s main circuit breaker to its ON (or CLOSED) position. Loads are now powered by the standby
generator.
8. Turn ON the circuit breaker/electrical loads that are powered by the generator one by one.
9. Connect a calibrated AC voltmeter and a frequency meter across terminal lugs E1 and E2. Voltage should be
approximately 240 volts and frequency should be 60 Hz. If the voltage and frequency are rapidly dropping as the
loads are applied, the generator may be overloading or there may be a fuel issue. Check amperage value of
loads and/or fuel pressure.
10. Let the generator run at full rated load for 20-30 minutes. Listen for unusual noises, vibration or other indications
of abnormal operation. Check for oil leaks, evidence of overheating, etc.
11. Verify gas pressure while under full load.
12. When testing under load is complete, turn OFF electrical loads.
13. Set the generator’s main circuit breaker to the OFF (or open) position.
14. Let the engine run at no-load for 2-5 minutes.
15. Push the generator’s OFF button. The engine should shut down.
Engine cranks but will not 1. Out of fuel. 1. Replenish fuel / Turn on fuel valve.
start. 2. Defective fuel solenoid (FS). 2. *
3. Defective spark plug(s). 3. Clean, re-gap or replace plug(s).
4. Valve lash out of adjustment. 4. Reset valve lash.
Engine starts hard and runs 1. Air cleaner plugged or damaged. 1. Check / replace air cleaner.
rough. 2. Defective spark plug(s). 2. Clean, re-gap or replace plug(s).
3. Fuel regulator not set. 3. Set fuel regulator.
4. Fuel pressure incorrect. 4. Confirm fuel pressure to regulator is 10-
12” water column (19-22mm mercury)
for LP, and 3.5 - 7” water column (9-
13mm mercury) for natural gas.
5. Fuel selector in wrong position. 5. Move selector to correct position.
6. Choke remains closed. 6. Verify choke plate moves freely.
Generator is set to OFF, but 1. Controller wired incorrectly 1. Repair wiring or replace controller*
the engine continues to run. 2. Defective control board. 2. Replace controller
No AC output from genera- 1. Main line circuit breaker is in the OFF 1. Reset circuit breaker to ON (or
tor. (or OPEN) position. CLOSED).
2. Generator internal failure. 2. *
Unit consumes large 1. Engine over filled with oil. 1. Adjust oil to proper level.
amounts of oil. 2. Engine breather defective. 2. *
3. Improper type or viscosity of oil. 3. See “Engine Oil Recommendations”.
4. Damaged gasket, seal or hose. 4. Check for oil leaks.
Unit shuts down during RED Check the LED’s / HIGH Check ventilation around the generator,
operation. Screen for alarms. TEMPERATURE intake, exhaust and rear of generator. If no
obstruction contact serving dealer.
Unit shuts down during RED Check the LED’s / OVERLOAD Clear alarm and remove household loads
operation. Screen for alarms. REMOVE LOAD from the generator. Put back in AUTO and
restart.
Unit was running and RED check the LED’s / RPM SENSE LOSS Clear alarm and remove household loads
shuts down, attempts to Screen for alarms. from the generator. Put back in AUTO and
restart. restart. It may be a fuel issue so contact
the servicing dealer.
Unit will not start in NONE See if screen says unit NOT ACTIVATED Refer to activation section in owners man-
AUTO with utility loss. not activated. ual.
Unit will not start in GREEN Check screen for start None If the start up delay is greater than
AUTO with utility loss. delay countdown. expected, contact servicing dealer to
adjust from 2 to 1500 seconds.
Unit will not start in RED Check the LED’s / LOW OIL Check Oil Level / Add Oil Per Owners
AUTO with utility loss. Screen for alarms. PRESSURE Manual. If oil level is correct contact servic-
ing dealer.
Unit will not start in RED Check the LED’s / RPM SENSE LOSS Clear alarm. Check the battery using the
AUTO with utility loss. Screen for alarms. control panel under the MAIN menu using
the BATTERY MENU option. If it states
battery is GOOD contact servicing dealer.
If it states CHECK BATTERY replace the
battery.
Unit will not start in RED Check the LED’s / OVERCRANK Check fuel line shutoff valve is in the ON
AUTO with utility loss. Screen for alarms. position. Clear alarm. Attempt to start the
unit in MANUAL. If it does not start or starts
and runs rough, contact servicing dealer.
Unit will not start in RED Check the LED’s / LOW VOLTS Clear alarm and remove household loads
AUTO with utility loss. Screen for alarms. REMOVE LOAD from the generator. Put back in AUTO and
restart.
Unit will not start in RED Check the LED’s / FUSE PROBLEM Check the 7.5amp fuse. If it is bad replace
AUTO with utility loss. Screen for alarms. it with an ATO 7.5Amp fuse, if not contact
servicing dealer.
Unit will not start in RED Check the LED’s / OVERSPEED Contact servicing dealer.
AUTO with utility loss. Screen for alarms.
Unit will not start in RED Check the LED’s / UNDERVOLTAGE Contact servicing dealer.
AUTO with utility loss. Screen for alarms.
Unit will not start in RED Check the LED’s / STEPPER Contact servicing dealer.
AUTO with utility loss. Screen for alarms. OVERCURRENT
Unit will not start in RED Check the LED’s / MISWIRE Contact servicing dealer.
AUTO with utility loss. Screen for alarms.
Unit will not start in RED Check the LED’s / OVERVOLTAGE Contact servicing dealer.
AUTO with utility loss. Screen for alarms.
Yellow LED illuminated in YELLOW Check the screen for LOW BATTERY Clear alarm. Check the battery using the
any state. additional information. control panel under the MAIN menu using
the BATTERY MENU option. If it states
battery is GOOD contact servicing dealer.
If it states CHECK BATTERY replace the
battery.
Yellow LED illuminated in YELLOW Check the screen for BATTERY Contact servicing dealer.
any state. additional information. PROBLEM
Yellow LED illuminated in YELLOW Check the screen for CHARGER Contact servicing dealer
any state. additional information. WARNING
Yellow LED illuminated in YELLOW Check the screen for SERVICE A Perform SERVICE A maintenance, hit
any state. additional information. ENTER to clear.
Yellow LED illuminated in YELLOW Check the screen for SERVICE B Perform SERVICE B maintenance, hit
any state. additional information. ENTER to clear.
Yellow LED illuminated in YELLOW Check the screen for Inspect Battery Inspect Battery, hit ENTER to clear.
any state. additional information.
Accessory Description
Cold Weather Kit Required in areas where temperatures regularly fall below 32 ºF (0 ºC).
Scheduled Maintenance Kit Includes all pieces necessary to perform maintenance on the generator along
with oil recommendations.
Auxiliary Transfer Switch Lockout Enables any of the transfer switches to completely lock out one large electrical
load by tying into its control system.
Fascia Skirt Wrap Standard on 22 kW units. It is available for all other current production 8 -20
kW units. It snaps together, around the base and mounting pad of the genera-
tor, to provide a smoothing, contoured look as well as rodent / insect protec-
tion. Requires use of the mounting pad shipped with the generator.
Mobile Link™ Provides a personalized web portal that displays the generator’s status, main-
tenance schedule, event history and much more. This portal is accessible via
computer, tablet or smart phone. Sends emails and/or text notifications the
moment there is any change in the generator’s status. Notification settings
can be customized to what type of alert is sent and how often. For more infor-
mation visit www.standbystatus.com.
Wireless Local Monitor Completely wireless and battery powered, the Wireless Monitor provides you
with instant status without ever leaving the house. Status lights (red, yellow
and green) alert owners when the generator needs attention. Magnetic back-
ing permits refrigerator mounting and gives a 600 foot line of sight communi-
cation.
Touch-Up Paint Kit Very important to maintain the look and integrity of the generator enclosure.
This kit includes touch-up paint and instructions.
Extended Warranty Coverage Extend your generator’s warranty coverage by purchasing the 5 year
extended warranty coverage. Covers 5 years of both parts and labor.
Extended coverage can be purchased within 12 months of the end-users
purchase date. This extended coverage is applicable to registered units and
end-user proof of purchase must be available upon request.
Available for Generac®, Guardian® and Centurion® products.
Not available for Corepower™ and EcoGen products or all international
purchases.
15B +12V
23 TRANSFER T1
NEUTRAL
AIR 1
CONTACTOR
1 N1 N2
AIR 2
CONTACTOR
2
PRIORITY 1 CONTACTOR
3
PRIORITY 2
PRIORITY 3
UTILITY
CONTACTOR
0
23
194
N1 N2 T1
GROUND
E1
E1
E2 E2
WHITE CUSTOMER LOAD
GREEN
(DISTRIBUTION PANEL)
TO GROUNDING
N1 N2 0
T1 194 23 ELECTRODE
EVOLUTION
PANEL
11.1 COMPLETED WIRING INTERCONNECTION DRAWINGS
GENERATOR OUTPUT
CIRCUIT BREAKER
2 POLE
SIDE VIEW
TOP
VIEW
47
The complete wiring is shown, depending on the configuration of the transfer switch location (Drawing 0K2516-B)
48
Diagrams
A BONDING JUMPER IS N1 N2
PROVIDED BETWEEN
THE NEUTRAL LUG
AND ENCLOSURE
AT THIS LOCATION
(FACTORY INSTALLED)
N1 N2 0
T1 194 23 LOAD SHED N1
N2
DEVICE T1
UTILITY
(C1 & VR1)
NEUTRAL BAR
0D9618-TO
IN PANELBOARD
0
GROUNDING ELECTRODE E1 T1 T2 E2
23
194
CONNECTION
(LOCATED ON THE
REAR OF UNIT)
UTILITY
METER
E1 GFCI SOCKET
E2
WHITE BREAKER
GREEN
TO GROUNDING
E1
N1 N2 0 E2 ELECTRODE
T1 194 23
EVOLUTION
PANEL
GENERATOR OUTPUT
CIRCUIT BREAKER
2 POLE
SIDE VIEW
TOP
VIEW