Protocole de Communication - NA0992B
Protocole de Communication - NA0992B
92 B
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
A) Communication medium
● RS485
3-pin connector on terminal 1 of terminal block J11: A or +
terminal 2: B or –
terminal 3: connected to earth for shielding if desired
Two lights provide information on the status of the transmission
- D50 → Receive LED. Usually off; flashes when a message is received by the board.
If this light remains on, the bus is reversed. Swap terminals 1 and 2 on J11.
- D52 → Send LED. Usually off; lights up when the CPU sends a message over the bus.
Main control board for machines with one non-reversible refrigerating circuit
J11 J10 J9
3 2 1 3 2 1 3 2 1 12 11 10 9 8 7 6 5 4 3 2 1 11 10 9 8 7 6 5 4 3 2 1
J7 J5
D50 D52 D46 D48
4321 4321
12 11 10 9 8 7 6 5 4 3 2 1 11 10 9 8 7 6 5 4 3 2 1
J12
W3
J8 J6
J13
7531
8642
J14
+
PL1 SP1
TR1
1 2 3 4 5 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3
J2 J3 J4
B) Transmission mode
● Serial, asynchronous, half duplex, RTU mode.
- 1 start bit,
- 8 data bits,
- The parity is set via parameter P702,
The number of stop bits is set via parameter P703,
- The transmission speed is set via parameter P701,
- The unit number on the bus is set via parameter P705.
● Coding of analogue values
Standard 32-bit IEEE format (2 registers).
Order of values:
- If P704 = No → Low order, high order.
- Si P704 = Yes → High order, low order.
● Function codes used.
1 or 2: read n bits
3 or 4: read multiple registers (16 bits)
5: write one bit …………..
6: write register function………
8: read diagnostics counters
11: read event counter
15: write n bits
16: write multiple registers (16 bits)
Note: the write functions are enabled if parameter P103 is set to "Remote, BMS…"
● Error codes:
1: function code unknown
2: address incorrect
3: data error
1/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
0x20 and 0x21 32 and 33 P285 Heating mode runtime (in hours) Float Read-only
0x22 and 0x23 34 and 35 P286 Cooling mode runtime (in hours) Float Read-only
0x24 and 0x25 36 and 37 P287 Pump 1 runtime (in hours) Float Read-only
0x26 and 0x27 38 and 39 P288 Pump 2 runtime (in hours) Float Read-only
0x28 and 0x29 40 and 41 P310 Number of starts, stage 1, circuit 1 Float Read-only
0x2a and 0x2b 42 and 43 P311 Stage 1, circuit 1 runtime Float Read-only
0x2c and 0x2d 44 and 45 P313 Number of starts, stage 2, circuit 1 Float Read-only
0x2e and 0x2f 46 and 47 P314 Stage 2, circuit 1 runtime Float Read-only
0x30 and 0x31 48 and 49 P340 Number of starts, stage 1, circuit 2 Float Read-only
0x32 and 0x33 50 and 51 P341 Stage 1, circuit 2 runtime Float Read-only
0x34 and 0x35 52 and 53 P343 Number of starts, stage 2, circuit 2 Float Read-only
0x36 and 0x37 54 and 55 P344 Stage 2, circuit 2 runtime Float Read-only
Registers accessible in read mode (Functions 3 or 4) and write mode (Functions 6 or 16)
0x200 512 Year Decimal Read/Write 0 to 99
0x201 513 Month Decimal Read/Write 1 to 12
0x202 514 Day of the month Decimal Read/Write 1 to 31
0x203 515 Day of the week Decimal Read/Write 1 to 7 (1: Monday, 2: Tuesday, etc.)
0x204 516 Hours Decimal Read/Write 0 to 23
0x205 517 Minutes Decimal Read/Write 0 to 59
2/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
3/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
4/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
5/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
CONFIGURATION PARAMETERS
Hexadecimal Decimal
Description Format Type Setting
bit number bit numbe
Registers accessible in read mode (functions 3 or 4) and write mode (functions 6 for 'Char' or 16)
Configuration parameters
0x1000 4096 P99 Lock Char Read/Write 0 or 1
0: R407c
0x1001 4097 P01 Refrigerant type Char Read/Write 1: 134a
2: 404a
1: Water-to-water unit
0x1002 4098 P02 Unit type Char Read/Write 2: Air-to-water unit
3: Reversible air-to-water unit
0x1003 4099 P03 Number of circuits Char Read/Write 1 or 2
0x1004 4100 P04 Number of stages on circuit 1 Char Read/Write 1 or 2
0x1005 4101 P05 Number of stages on circuit 2 Char Read/Write 1 or 2
0x1006 4102 P06 Number of evaporators Char Read/Write 1 or 2
0: Maneurop
0x1007 4103 P07 Compressor supplier Char Read/Write 1: Copeland
2: inverter
0: Propeller
0x1008 4104 P10 Fan type Char Read/Write 1: Centrifugal
2: Pressure
0: Intertwined
0x1009 4105 P11 Coil type Char Read/Write 1: Split
2: Mixed
0x100A 4106 P12 Pressure balancing valve Char Read/Write 0 or 1
0x100B 4107 P13 Balanced tandem compressors Char Read/Write 0 or 1
0x100C 4108 P14 Number of coil sensors per circuit Char Read/Write 1 to 4
0x100D 4109 P20 All-season function Char Read/Write 0 or 1
0: No control
0x100E 4110 P21 Speed control Char Read/Write 1: Acoustic optimisation
2: Energy optimisation
0x100F 4111 P22 Presence of electric auxiliary heaters Char Read/Write 0 or 1
0x1010 4112 P25 Number of pumps supplied by CIAT Char Read/Write 0 to 2
0x1011 4113 P26 0-10 V programmable output Char Read/Write 0: Two-way valve
1: Three-way valve
0x1012 4114 P27 Pump controlled by boiler Char Read/Write 0 or 1
0x1013 4115 P28 Master/Slave (2 machines) Char Read/Write 0 or 1
0x1014 4116 P29 Total recovery Char Read/Write 0 or 1
0x1015 4117 P29. 1 Recovery exchanger frost protection Char Read/Write 0 or 1
0x1016 & 0x1017 4118 & 4119 P30 HP1 sensor high value float Read/Write
0x1018 & 0x1019 4120 & 4121 P31 HP1 sensor low value float Read/Write
0x101a & 0x101b 4122 & 4123 P32 HP2 sensor high value float Read/Write
0x101c & 0x101d 4124 & 4125 P33 HP2 sensor low value float Read/Write
0x101e & 0x101f 4126 & 4127 P36 LP1 sensor high value float Read/Write
0x1020 & 0x1021 4128 & 4129 P37 LP1 sensor low value float Read/Write
0x1022 & 0x1023 4130 & 4131 P38 LP2 sensor high value float Read/Write
0x1024 & 0x1025 4132 & 4133 P39 LP2 sensor low value float Read/Write
0: None
0x1026 4134 P42 Electronic expansion valve driver Char Read/Write 1: Alco driver
2: CIAT driver
6/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
Hexadecimal Decimal
Description Format Type Setting
bit number bit numbe
0x1042 4162 P605 Valve opening at AC mode start, circuit 1 Char Read/Write
0x104b 4171 P615 Valve opening at AC mode start, circuit 1 Char Read/Write
7/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
ADJUSTMENT PARAMETERS
Hexadecimal Decimal
Description Format Type Setting
bit number bit numbe
Registers accessible in read mode (functions 3 or 4) and write mode (functions 6 for 'Char' or 16)
0: French
1: English
2: German
0x1200 4608 P100 Local console language Char Read-only 3: Spanish
4: Dutch
5: Italian
6: Russian
0: As a function of On/Off
0x1201 4609 P108 Pump 2 control Char Read/Write
1: As a function of the control mode
0x1202 4610 P109 Pump 2 time delay Char Read/Write
0: Max. power
0x1203 4611 P111 Programmable output Char Read/Write 1: Boiler output
2: Cooling/heating output
0x1204 4612 P112 Number of electric stages Char Read/Write
0: Disabled
1: Load shedding of electric
0x1205 4613 P113 Programmable input Char Read/Write
auxiliary heaters
2: Electric auxiliary heaters forced on
0x1206 4614 P116 Link with Aeroconnect Char Read/Write 0 or 1
0: Cooling only
1: Heating only
2: Cooling/heating via console
0x1207 4615 P119 Operating mode Char Read/Write
or BMS
3: Cooling/heating via on/off input
4: Automatic cooling/heating
1: 1 setpoint
2: 2 setpoints via console or
0x1208 4616 P120 Number of setpoints Char Read/Write BMS
3: 2 setpoints via On/Off input
4: setpoint via 4-20 mA input
0x1208 to 0x1218 reserved
P127 Cooling controlled as a function of the
0x1219 4633 Char Read/Write 0 or 1
outdoor temperature
0x121a & 0x121b 4634 & 4635 P128 Drift start in cooling mode Float Read/Write
0x121c & 0x121d 4636 & 4637 P129 Drift end in cooling mode Float Read/Write
0x121e & 0x121f 4638 & 4639 P130 Cooling setpoint at end of drift Float Read/Write
P131 Heating controlled as a function of the
0x1220 4640 Char Read/Write 0 or 1
outdoor temperature
0x1221 & 0x1222 4641 & 4642 P132 Drift start in heating mode Float Read/Write
0x1223 & 0x1224 4643 & 4644 P133 Drift end in heating mode Float Read/Write
0x1225 & 0x1226 4645 & 4646 P134 Heating setpoint at end of drift Float Read/Write
0x1227 & 0x1228 4647 & 4648 P135 Minimum boiler setpoint Float Read/Write
0x1129 & 0x122a 4949 & 4650 P136 Max. outdoor temp. in auto heating mode Float Read/Write
0x122b & 0x122c 4651 & 4652 P137 Min. outdoor temp. in auto cooling mode Float Read/Write
8/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
Hexadecimal Decimal
Description Format Type Setting
bit number bit numbe
9/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
Hexadecimal Decimal
Description Format Type Setting
bit number bit number
10/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
OPERATION PARAMETER
Hexadecimal Decimal
Description Format Type Setting
bit number bit number
11/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
Hexadecimal Decimal
Description Format Type Setting
bit number bit number
12/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
Hexadecimal Decimal
Description Type Setting
bit number bit number
13/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
Hexadecimal Decimal
Description Type Setting
bit number bit number
FAULT MEMORY
Hexadecimal Decimal
Description Format Type Setting
bit number bit number
14/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
Hexadecimal Decimal
Description Format Type Setting
bit number bit number
0x2068 & 0x2069 8296 & 8297 Fault memory condensing temperature Float Read-only
0x206a & 0x206b 8298 & 8299 Fault memory LP Float Read-only
0x206c & 0x206d 8300 & 8301 Fault memory evaporating temperature Float Read-only
0x206e & 0x206f 8302 & 8303 Fault memory suction temperature Float Read-only
0x2070 & 0x2071 8304 & 8305 Fault memory superheat Float Read-only
0x2072 8306 Stage 1 circuit x discharge Char Read-only
0x2073 8307 Stage 2 circuit x discharge Char Read-only
0x2074 & 0x2075 8308 & 8309 Outdoor temperature Float Read-only
0x2076 & 0x2077 8310 & 8311 Control setpoint Float Read-only
0x2078 & 0x2079 8312 & 8313 Water inlet temperature Float Read-only
0x207a & 0x207b 8314 & 8315 Circuit x water outlet temperature Float Read-only
0x207c & 0x207d 8316 & 8317 Hot water temperature Float Read-only
0x207e & 0x207f 8318 & 8319 Refrigerant temperature Float Read-only
Fault memory area 3
Unsigned
0x20c0 8384 Fault number in fault memory Read-only
int
0x20c1 8385 Fault memory year Char Read-only
0x20c2 8386 Fault memory month Char Read-only
0x20c3 8387 Fault memory day of month Char Read-only
0x20c4 8388 Fault memory hour Char Read-only
0x20c5 8389 Fault memory minutes Char Read-only
0x20c6 & 0x20c7 8390 & 8391 Fault memory HP Float Read-only
0x20c8 & 0x20c9 8392 & 8393 Fault memory condensing temperature Float Read-only
0x20ca & 0x20cb 8394 & 8395 Fault memory LP Float Read-only
0x20cc & 0x20cd 8396 & 8397 Fault memory evaporating temperature Float Read-only
0x20ce & 0x20cf 8398 & 8399 Fault memory suction temperature Float Read-only
0x20d0 & 0x20d1 8400 & 8401 Fault memory superheat Float Read-only
0x20d2 8402 Stage 1 circuit x discharge Char Read-only
0x20d3 8403 Stage 2 circuit x discharge Char Read-only
0x20d4 & 0x20d5 8404 & 8405 Outdoor temperature Float Read-only
0x20d6 & 0x20d7 8406 & 8407 Control setpoint Float Read-only
0x20d8 & 0x20d9 8408 & 8409 Water inlet temperature Float Read-only
0x20da & 0x20db 8410 & 8411 Circuit x water outlet temperature Float Read-only
0x20dc & 0x20dd 8412 & 8413 Hot water temperature Float Read-only
0x20de & 0x20df 8414 & 8415 Refrigerant temperature Float Read-only
Fault memory area 4
Unsigned
0x2120 8480 Fault number in fault memory Read-only
int
0x2121 8481 Fault memory year Char Read-only
0x2122 8482 Fault memory month Char Read-only
0x2123 8483 Fault memory day of month Char Read-only
0x2124 8484 Fault memory hour Char Read-only
0x2125 8485 Fault memory minutes Char Read-only
0x2126 & 0x2127 8486 & 8487 Fault memory HP Float Read-only
0x2128 & 0x2129 8488 & 8489 Fault memory condensing temperature Float Read-only
0x212a & 0x212b 8490 & 8491 Fault memory LP Float Read-only
0x212c & 0x212d 8492 & 8493 Fault memory evaporating temperature Float Read-only
0x212e & 0x212f 8494 & 8495 Fault memory suction temperature Float Read-only
0x2130 & 0x2131 8496 & 8497 Fault memory superheat Float Read-only
15/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
Hexadecimal Decimal
Description Format Type Setting
bit number bit number
16/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
Hexadecimal Decimal
Description Format Type Setting
bit number bit number
0x21fa & 0x21fb 8698 & 8699 Circuit x water outlet temperature Float Read-only
0x21fc & 0x21fd 8700 & 8701 Hot water temperature Float Read-only
0x21fe & 0x21ff 8702 & 8703 Refrigerant temperature Float Read-only
Fault memory area 7
Unsigned
0x2240 8768 Fault number in fault memory Read-only
int
0x2241 8769 Fault memory year Char Read-only
0x2242 8770 Fault memory month Char Read-only
0x2243 8771 Fault memory day of month Char Read-only
0x2244 8772 Fault memory hour Char Read-only
0x2245 8773 Fault memory minutes Char Read-only
0x2246 & 0x2247 8774 & 8775 Fault memory HP Float Read-only
0x2248 & 0x2249 8776 & 8777 Fault memory condensing temperature Float Read-only
0x224a & 0x224b 8778 & 8779 Fault memory LP Float Read-only
0x224c & 0x224d 8780 & 8781 Fault memory evaporating temperature Float Read-only
0x224e & 0x224f 8782 & 8783 Fault memory suction temperature Float Read-only
0x2250 & 0x2251 8784 & 8785 Fault memory superheat Float Read-only
0x2252 8786 Stage 1 circuit x discharge Char Read-only
0x2253 8787 Stage 2 circuit x discharge Char Read-only
0x2254 & 0x2255 8788 & 8789 Outdoor temperature Float Read-only
0x2256 & 0x2257 8790 & 8791 Control setpoint Float Read-only
0x2258 & 0x2259 8792 & 8793 Water inlet temperature Float Read-only
0x225a & 0x225b 8794 & 8795 Circuit x water outlet temperature Float Read-only
0x225c & 0x225d 8796 & 8797 Hot water temperature Float Read-only
0x225e & 0x225f 8798 & 8799 Refrigerant temperature Float Read-only
Fault memory area 8
Unsigned
0x22a0 8864 Fault number in fault memory Read-only
int
0x22a1 8865 Fault memory year Char Read-only
0x22a2 8866 Fault memory month Char Read-only
0x22a3 8867 Fault memory day of month Char Read-only
0x22a4 8868 Fault memory hour Char Read-only
0x22a5 8869 Fault memory minutes Char Read-only
0x22a6 & 0x22a7 8870 & 8871 Fault memory HP Float Read-only
0x22a8 & 0x22a9 8872 & 8873 Fault memory condensing temperature Float Read-only
0x22aa & 0x22ab 8874 & 8875 Fault memory LP Float Read-only
0x22ac & 0x22ad 8876 & 8877 Fault memory evaporating temperature Float Read-only
0x22ae & 0x22af 8878 & 8879 Fault memory suction temperature Float Read-only
0x22b0 & 0x22b1 8880 & 8881 Fault memory superheat Float Read-only
0x22b2 8882 Stage 1 circuit x discharge Char Read-only
0x22b3 8883 Stage 2 circuit x discharge Char Read-only
0x22b4 & 0x22b5 8884 & 8885 Outdoor temperature Float Read-only
0x22b6 & 0x22b7 8886 & 8887 Control setpoint Float Read-only
0x22b8 & 0x22b9 8888 & 8889 Water inlet temperature Float Read-only
0x22ba & 0x22bb 8890 & 8891 Circuit x water outlet temperature Float Read-only
0x22bc & 0x22bd 8892 & 8893 Hot water temperature Float Read-only
0x22be & 0x22bf 8894 & 8895 Refrigerant temperature Float Read-only
17/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
Hexadecimal Decimal
Description Format Type Setting
bit number bit number
18/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
Hexadecimal Decimal
Description Format Type Setting
bit number bit number
19/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
Hexadecimal Decimal
Description Format Type Setting
bit number bit number
20/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
Hexadecimal Decimal
Description Format Type Setting
bit number bit number
21/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
Hexadecimal Decimal
Description Format Type Setting
bit number bit number
22/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
Hexadecimal Decimal
Description Format Type Setting
bit number bit number
23/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
Decimal
Hexadecimal
fault Description
fault number
number
0x002 2 Power cut
0x003 3 Water flow fault
0x004 4 Outdoor temperature too low
0x005 5 Fan fault
0x006 6 Auxiliary heater board input 1 fault
0x007 7 Auxiliary heater board input 2 fault
0x008 8 EEPROM fault
0x00c 12 Automated self-regulating control
0x00d 13 Multiconnect link fault
0x012 18 Aeroconnect fault
0x013 19 Aeroconnect link fault
0x014 20 Outdoor temperature too high in cooling mode
24/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
Decimal
Hexadecimal
fault Description
fault number
number
0x185 389 Circuit 1 HP sensor fault
0x186 390 Circuit 1 LP sensor fault
0x187 391 Coil B circuit 1 freon sensor fault
0x188 392 Circuit 1 suction sensor fault
0x189 393 Circuit 1 expansion valve board link fault
0x18a 394 Circuit 1 expansion valve motor fault
0x18b 395 Circuit 1 superheat fault
0x18c 396 Circuit 1 VCM module fault
0x18d 397 Circuit 1 inverter discharge fault
0x18e 398 Auxiliary heater board link fault
0x18f 399 Circuit 1 reversible board link fault
0x190 400 Circuit 2 reversible board link fault
0x191 401 Coil C circuit 1 freon sensor fault
0x192 402 Coil D circuit 1 freon sensor fault
0x193 403 Circuit 1 liquid sensor fault
0x194 404 Stage 1, circuit 1 discharge sensor fault
0x195 405 Stage 2, circuit 1 discharge sensor fault
25/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
Decimal
Hexadecimal
fault Description
fault number
number
0x28c 652 Circuit 2 VCM module fault
0x28d 653 Coil C circuit 2 freon sensor fault
0x28e 654 Coil D circuit 2 freon sensor fault
0x28f 655 Circuit 2 liquid sensor fault
0x290 656 Discharge 4 sensor fault
0x291 657 Stage 1, circuit 1 discharge sensor fault
0x292 658 Stage 2, circuit 1 discharge sensor fault
TIME SCHEDULES
Registers accessible in read mode (functions 3 or 4) and write mode (functions 6 for 'Char' or 16)
Time schedule 1
0x3000 12288 Start time Char Read/Write
0x3001 12289 Start minutes Char Read/Write
0x3002 12290 End time Char Read/Write
0x3003 12291 End minutes Char Read/Write
0x3004 12292 Selected day Char Read/Write
Time schedule 2
0x3010 12304 Start time Char Read/Write
0x3011 12305 Start minutes Char Read/Write
0x3012 12306 End time Char Read/Write
0x3013 12307 End minutes Char Read/Write
0x3014 12308 Selected day Char Read/Write
Time schedule 3
0x3020 12320 Start time Char Read/Write
0x3021 12321 Start minutes Char Read/Write
0x3022 12322 End time Char Read/Write
0x3023 12323 End minutes Char Read/Write
0x3024 12324 Selected day Char Read/Write
0x3025 12325 Program type Char Read/Write
Time schedule 4
0x3030 12336 Start time Char Read/Write
0x3031 12337 Start minutes Char Read/Write
0x3032 12338 End time Char Read/Write
0x3033 12339 End minutes Char Read/Write
0x3034 12340 Selected day Char Read/Write
Time schedule 5
0x3040 12352 Start time Char Read/Write
0x3041 12353 Start minutes Char Read/Write
0x3042 12354 End time Char Read/Write
0x3043 12355 End minutes Char Read/Write
0x3044 12356 Selected day Char Read/Write
26/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01
Time schedule 6
0x3050 12368 Start time Char Read/Write
0x3051 12369 Start minutes Char Read/Write
0x3052 12370 End time Char Read/Write
0x3053 12371 End minutes Char Read/Write
0x3054 12372 Selected day Char Read/Write
Holiday zone 1
0x3100 12544 Start day Char Read/Write
0x3101 12545 Start month Char Read/Write
0x3102 12546 End day Char Read/Write
0x3103 12547 End month Char Read/Write
0x3104 12548 Zone type Char Read/Write
Holiday zone 2
0x3110 12560 Start day Char Read/Write
0x3111 12561 Start month Char Read/Write
0x3112 12562 End day Char Read/Write
0x3113 12563 End month Char Read/Write
0x3114 12564 Zone type Char Read/Write
Holiday zone 3
0x3120 12576 Start day Char Read/Write
0x3121 12577 Start month Char Read/Write
0x3122 12578 End day Char Read/Write
0x3123 12579 End month Char Read/Write
0x3124 12580 Zone type Char Read/Write
Holiday zone 4
0x3130 12592 Start day Char Read/Write
0x3131 12593 Start month Char Read/Write
0x3132 12594 End day Char Read/Write
0x3133 12595 End month Char Read/Write
0x3134 12596 Zone type Char Read/Write
Holiday zone 5
0x3140 12608 Start day Char Read/Write
0x3141 12609 Start month Char Read/Write
0x3142 12610 End day Char Read/Write
0x3143 12611 End month Char Read/Write
0x3144 12612 Zone type Char Read/Write
Holiday zone 6
0x3150 12624 Start day Char Read/Write
0x3151 12625 Start month Char Read/Write
0x3152 12626 End day Char Read/Write
0x3153 12627 End month Char Read/Write
0x3154 12628 Zone type Char Read/Write
27/28
NA 09. 92 B
CONNECT 2
09 - 2010
COMMUNICATION PROTOCOL 3991051.01