GTC-200A Gas Detector Manual

The GTC-200A Instruction Manual provides detailed information on the operation, maintenance, and specifications of the Gastron Co. Ltd. gas detection system. It emphasizes the importance of regular calibration and provides contact information for support. The manual includes sections on installation, operation, and features of the gas detector, as well as technical specifications for various components.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
309 views19 pages

GTC-200A Gas Detector Manual

The GTC-200A Instruction Manual provides detailed information on the operation, maintenance, and specifications of the Gastron Co. Ltd. gas detection system. It emphasizes the importance of regular calibration and provides contact information for support. The manual includes sections on installation, operation, and features of the gas detector, as well as technical specifications for various components.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

GTC-200A

Headquarters / Engineering research laboratory :


23 Gunpo Advance d Industry 1-ro(Bugok-dong), Gunpo-si, Gyeonggi-do
Instruction Manual
Tel +82-31-490-0800 Fax +82-31-490-0801

Yeongnam business office / Plant :


55 Gonghangap-gil 85beon-gil, Gangseogu, Busan Metropolitan City
Tel +51-973-8518 Fax +51-973-8519

E-mail : info@[Link]

[Link]

Read in detail for correct use.


GTC-200A
Instruction Manual
Greetings [Link]
02_03

Gas & Flame We sincerely thank you for purchasing the product of Gastron Co. Ltd.
Our Gastron [Link]. is a company specialized in Gas detector and Gas Monitoring System, being

Detection System
recognized by many consumers due to the best quality and use convenience. We always enable you
consumers to find desired products nearby and are ceaselessly studying and striving for development
of Gas detectors satisfying customers. From now on, solve all anguishes concerning Gas detector with
the products of Gastron Co. Ltd, We Gastron Co. will take a responsibility and give you satisfaction.

In the present instruction manual, operation method for Gas detector as well as simple methods for
maintenance and repair, etc. are recorded If you read it in detail and keep it well, for reference when
you have questions, then it will give you much help.

■ For accurate operation of Gas detector, check up and calibrate for more than once in every 6 months.
( * See No. 13 of KOSHA GUIDE : P-135-2013 / 8.3 paragraph on qualification and calibration)
■ For accurate operation of Gas detector, checkup and calibration with calibration gas before measurement
is recommended.
■ When not calibrated, it may cause malfunction of the equipment due to problems resulting from Sensor aging.
■ When the present instrument should be dismantled, those with professional skills for Gas detector should
conduct the operation.
■ For power supply cable, wire specifications should be determined by referring to the item of "Length of
installed cable".
■ For the contents on checkup and calibration of Gas detector, please use our company's engineering
department , e-mail, or web site.

When abnormalities occur after purchasing the product,


The present product and the product manual can be changed without advance notice for performance improvement and
please contact the following address. use convenience of the product.
·Address : 23 Gunpo Advanced Industry 1-ro,
Gunpo-si, Gyeonggi-do
·Tel : 031-490-0800
·Fax : 031-490-0801 * KOSHA GUIDE : P-135-2013
·URL : [Link] Calibration should be executed at periods required by the manufacturer, and should be executed in every quarter
·e-mail : info@[Link] unless there are separate calibration periods.
GTC-200A
Instruction Manual
Contents Contents [Link]
04_05

1. Overview··························································································· 6 9. How to operate Channel Unit······································································· 23


9.1. Power ON····················································································· 23
2. Features···························································································· 6
9.2. Gas Measuring Mode·········································································· 23
9.3. Test Mode···················································································· 24
3. Specifications for channel card····································································· 6
9.4. Checkup mode (Stand-by Mode)······························································· 24
3.1. Common Alarm Unit············································································ 6 9.5. Operation setting· ············································································· 25
3.2. Channel Control Unit··········································································· 7 9.5.1. PROGRAM MODE······································································· 25
3.3. Power Unit (Option)············································································ 7 9.6. ALARM Mode················································································· 27
3.4. Environmental Specifications···································································· 8 9.7. Maintenance Mode············································································ 29

4. Specifications for Wall Mount product······························································· 8


10. Outline drawing and Dimensions···································································· 31

5. Name and description of each part································································· 9 10.1. Power unit···················································································· 31


10.2. Common Unit·················································································· 31
5.1. Configuration and description of Power unit······················································ 9
10.3. Channel Unit·················································································· 32
5.2. Configuration and description of warning unit (Common unit)······································· 10
10.4. Panel mount type·············································································· 33
5.3. Configuration and description of channel unit (Channel unit)· ······································ 12
10.5. Wall mount type(Power Unit applied)····························································· 34
5.4. Configuration and description of Wall mount type················································· 14
10.6. Wall mount type(Power Unit not applied)························································· 35

6. Installation·························································································· 16
11. Revision record····················································································· 36
6.1. Power supply and signal configuration for Channel Unit··········································· 16
6.2. Power supply configuration for Wall Mount Type·················································· 17
6.3. Configuration of channel Unit terminal···························································· 18
6.4. How to connect 3 wire type Gas detector· ······················································· 19
6.5. How to connect 2 wire type Gas detector· ······················································· 19

7. How to operate Power unit·········································································· 20

8. How to operate Common Unit······································································· 21


8.1. Function······················································································ 21
8.2. RS485 MODBUS Interface······································································ 22
8.2.1. Communication setting··································································· 22
8.2.2. RS485 MODBUS communication setting and Register······································· 22
GTC-200A
Instruction Manual
1. Overview 3. Specifications for channel card [Link]
06_07

GTC200A Series is ammeter that adopted high-performance A/D Converter and Micro-Process with diversified 3.2. Channel Control Unit
functions embedded. GTC200A Series is configured in centralized style, comprised of a Common alarm unit and a
ITEMS SPECIFICATION
Multi-Channel control unit for several detectors, with the Multi channel control unit being connected to each detector.
Input form Analog 4-20mA
GTC200A Series is protected by the case of DIN Type, and has 2 types of products such as Panel mount type, Wall
Measurement display 4-Digit FND & Bar-graph (32 segment, 3-color LED)
mount type, etc. GTC200A Series has the display function of FND Digital display (PV Value) and the display function of Measuring range 0.000 to 9999 Digital (Arbitrary setting by the user)
3-color LED Bar Graphic display (PV and Alarm set value) embedded, accompanied by 3 Instant alarm functions (1st FND Digital ±1% Full Scale
Measuring accuracy
H/L, 2nd H/L, 3rd H/L) and Trouble alarm. LED Bar ±1% Full Scale

2. Features Input measuring period 100 ms


Alarm setting 3-stage alarm (Arbitrary setting by the user)
Alarm setting display 3 Color bar graphic (Green/Red/Yellow LED)
Upon occurrence of Instant alarm and Trouble alarm, GTC200A Series is displayed as Audible(Buzzer) and Alarm display LED bar graphic O
Visual(Alarm LED and Bar graphic LED flashing), and has Max. PV Value holding functions upon occurrence of an Alarm clearing Manual (Common unit)
alarm. GTC200A Series allows remote control for alarm clearing, and can perform interlocked control functions as it Self diagnosis Test switch & Reset switch
Control input, output RS-485
has the output for alarm (SPDT Contact). Common alarm unit of GTC200A Series is supplying communication output
Measured output Analog 4-20mA
(Isolation type RS-485 : Option) to configure Monitoring system such as Gas vision, etc. while each Channel control
Breakdown alarm SPDT Relay dry contact signal output
unit is supplying outputs for measured values (4~20mA. DC). GTC200A Series is configured with the latest parts,
Alarm 1 SPDT Relay dry contact signal output
being equipped with stability and reliability, and is capable of the maximum Expansion (Max. 63 channels) in a given
Alarm output Alarm 2 SPDT Relay dry contact signal output
space. Alarm 3 SPDT Relay dry contact signal output
Relay dry contact capacity : AC250V/3A, 30V/3A
3.1. Common Alarm Unit Operation power supply DC 24V / 100mA Max

ITEMS SPECIFICATION
Input form RS-485
Input measuring period 100ms 3.3. Power Unit (Option)
Alarm display Audio signal- Audible(Buzzer) and Visual signal- Visual(LED)
ITEMS SPECIFICATION
Alarm clearing Return switch- Manual (Reset switch)
Input power supply DC. 24V
Control input Outside input(Remote reset) - Buzzer stop/ return function
Output power supply DC. 24V (reserve power supply : DC. 27V / 300mA)
Measured output Isolation RS-485 modbus(Option)
Output power supply display FND Digital display
Buzzer - Buzzer SPST Relay dry contact signal output
Main power supply display Green LED display
Breakdown alarm - SPDT Relay Dry contact signal output
reserve power supply display Green LED display
1st alarm - Alarm 1 SPDT Relay dry contact signal output
Alarm output reserve power supply monitoring Red LED display
2nd alarm - Alarm 2 SPDT Relay dry contact signal output
reserve power supply test Test switch for preliminary power switch
3rd alarm - Alarm 3 SPDT Relay dry contact signal output
reserve power supply Ni-Cd Battery 24V / 600mA(less than 6 circuits)
* Relay dry contact capacity : AC125V 10A
Operation power supply DC 24V / 100mA Max

■ No. of Channel units for the maximum access to a common unit is 63ea.
GTC-200A
Instruction Manual
3. Specifications for channel card 5. Name and description of each part [Link]
08_09

3.4. Environmental Specifications 5.1. Configuration and description of power supply unit

ITEMS SPECIFICATION
Operation Temperature -20 to 60 ℃
Storage Temperature -20 to 60 ℃
Operation Humidity 5 to 99% RH (Non-condensing)
Pressure Range 90 to 110KPa

4. Specifications for Wall Mount product


ITEMS SPECIFICATION
Input power supply AC 110V/220V 50/60Hz (basic AC220V 50/60Hz)
Upon application of Upon application of
Specification with Channel configuration
0.5A to detector 0.2A to detector
SMPS application per Channel
3(4) Channel 24V / 3.2A(2.4A) 24V / 1.7A(1.4A)
(For SMPS specifications of the installed
product, checking of specifications for SMPS 5(6) Channel 24V / 4.6A(3.9A) 24V / 2.4A(2.1A)
Inside product is required, since specifications 7(8) Channel 24V / 6.0A(5.3A) 24V / 3.2A(2.8A)
on the right side can be changed upon 9(10) Channel 24V / 7.5A(6.8A) 24V / 3.9A(3.5A) [Figure 1. Configuration of power supply unit]
manufacturing)
( ) is basic applied quantity and capacity for the type with Power unit not applied.
Alarm display Audio signal- Audible(Buzzer) and Visual signal- Visual(LED)
Alarm clearing Return switch- Manual (Reset switch) No ITEMS SPECIFICATION
Control input Outside input (Remote reset) - Buzzer stop / return function 1 Front cover case Power Unit front-face Cover
Measured output Isolation RS-485 modbus(Option) 2 Main body case Power Unit main Body
24V DC/600mA 3 Acrylic Acryl for protection of Power Unit front-face cover
Backup power unit(Option)
24V DC/1300mA 4 Front sub cover Power Unit front-face Sub cover
Approval CE, KR, KFI 5 Main body fixed bracket Bracket for fixing of Power Unit
Main power supply voltage and battery voltage are displayed
6 Main/Battery power display
Voltages of power supply supplied to Common unit and channel unit are displayed
LED light for main power supply is turned on when AC power supply is used, while it is
7 Main power LED
turned off when reserve power supply is used
LED for reserve power supply is lighted when reserve power supply is used rather than AC
8 Battery power LED
main power supply is used.
Lighted when voltage of preliminary power voltage is normal above 1.8V after being
9 Battery power good LED
connected.
Lighted when preliminary voltage is below18V, and blinks if the reserve power supply was
10 Battery power trouble LED
not connected.
It is a switch for testing whether reserve power supply operates normally. While the switch
11 Battery power test key is being pushed, voltage of the reserve power supply is applied to operate the gas leakage
alarm. At this time, voltage of the reserve power supply is displayed in FND.
GTC-200A
Instruction Manual
5. Name and description of each part 5. Name and description of each part [Link]
10_11

No ITEMS SPECIFICATION NO NAME DESCRIPTIONS


on/off switch for preliminary power switch. 1 Front cover case Front-face Cover for Common unit
12 Battery power ON/OFF switch Note1) It is turned off upon shipment of product 2 Main body case Front-face main Body for Common unit
Note2) The preliminary power switch should be turned on after main power supply is turned on.
3 Acrylic Acryl for protection of front-face cover for Common unit front-face
13 Front cover screw Screw for fixing of Power Unit
4 Front SUB cover Front-face Sub cover for Common unit front-face
14 Terminal PCB Power Unit Terminal PCB
5 Main body fixed bracket Bracket for fixing of Common unit
15 Terminal PCB screw Screw for fixing of Power Unit Terminal PCB
Operates as intermittent sound of each upon occurrence of Alarm and trouble in each
16 DC input connector Input connector for power supply of Power Unit 6 Buzzer
channel.
17 Battery connector Input connector for reserve power supply of Power Unit 7 Power LED Power LED is lighted when power is inputted in Common unit
18 DC output connector Voltage output connector for operation of channel card Trouble LED is lighted when trouble occurred in each channel unit.
8 Trouble LED
Ex) Upon occurrence of defective wire connection with detector and of abnormality
[Table 1. Description on configuration of power supply unit] Alarm 3 LED is lighted upon occurrence of the 3rd alarm in each channel unit. Alarm 3 LED
9 Alarm-3 LED is lighted when the 3rd alarm value is reached upon execution of test functions in each
channel
Alarm 2 LED is lighted upon occurrence of the 2nd alarm in each channel unit. Alarm 2 LED
5.2. Configuration and description of alarm unit (Common unit) 10 Alarm-2 LED is lighted when the 2nd alarm value is reached upon execution of test functions in each
channel.
Alarm 1 LED is lighted upon occurrence of the 1st alarm in each channel unit. Alarm 1 LED
11 Alarm-1 LED is lighted when the 1st alarm value is reached upon execution of test functions in each
channel.
Normal communication is realized with entire channel units set in Common unit, COM-
CH LED continues to be lighted, while COM-CH LE blinks when there is a Channel unit
12 Communication LED (Channel)
without realization of communication. (When No. of Channel units is set as less than 1 ea. In
Common unit, it blinks at an interval of 0.5sec.)
When communication DATA transmitted from PC is normally received in Common unit,
COM-PC LED is immediately turned off after being lighted once.
13 Communication LED (PC)
(When Common unit address is set as less than 1ea. In Common unit, it blinks at an interval
of 0.5sec.)
As an alarm occurs in Channel unit, buzzer operates, and buzzer stops when Buzzer stop
switch is pushed. At this time, BZ-STOP LED is lighted, When Buzzer stop switch is pushed
14 Buzzer stop LED
once more in Common unit or Channel unit, BZ-STOP LED is turned Off. (However, it is
lighted only when Alarm type was set as hold in Channel unit
It is the key used for Buzzer stop and Reset when Trouble and Alarm occurred in each
channel unit.
15 Buzzer Stop/Reset key Push once initially.... Buzzer sound is stopped and BZ-STOP LED is lighted.
Push twice consecutively.... As BZ-STOP LED is turned Off, Reset function of all channel
units in Latch state according to Alarm setting is executed.
16 Power ON/OFF switch Power ON/OFF switch for Common unit .
[Figure 2. Configuration and description of alarm unit]
17 Front cover screw Screw for fixing of Common unit
18 Terminal PCB Common Unit Terminal PCB
19 Terminal PCB screw Screw for fixing of Common Unit Terminal PCB
20 Connector Input connector for signals

[Table 2. Description on configuration of alarm unit]


GTC-200A
Instruction Manual
5. Name and description of each part 5. Name and description of each part [Link]
12_13

5.3. Configuration and description of concentration display unit (Channel unit) NO NAME DESCRIPTIONS
Alarm 2LED is lighted when the 2nd alarm occurs in channel unit. Alarm 2 LED is lighted
11 Alarm-2 LED
when the 2nd warning value is reached upon execution of test function of the channel unit.
Alarm 1 LED is lighted when the 1st alarm occurs in channel unit. Alarm 1 LED is lighted
12 Alarm-1 LED
when the 1st warning value is reached upon execution of test function of the channel unit.
3 Color bar graphic LED continuously shows, display of measured value and of alarm
setting value as in FND display.
Bar graphic LED is lighted as green when the measured value is less than the 1st alarm,
13 3 color bar graphic LED as orange when it is more than the 1st alarm and less than the 2nd alarm, as red when it is
more than the 2nd alarm.
When the measured value is more than the alarm setting value, Bar graphic is held at the
highest value, and Bar graphic is displayed in blinking state for the alarm.
It performs functions such as Alarm clearing of Channel unit, clearing of Self test, clearing of
14 Reset key
Program setting, etc.
After selection of each mode using [Link], arbitrary values can be selected by using
15 Down key "▲", "▼" Key. When "▲", "▼" Key is pushed for a given time in the mode requiring frequent
changes of setting values, the setting values are changed fast.
When Test switch is pushed, the mode executing self diagnosis function is entered into.
It is the key where the measured value FND blinks, checking of Alarm operation state in
16 Test key Channel unit and Common unit by adjustment of blinking measured values is possible by
using "▲" key or "▼" key.
For clearing of diagnosis, clearing occurs by pushing once the Reset key in each Channel unit.
Function key is the key that inputs data values by conversion and selection of functions such
17 Function key
as setting of warning values. Setting of alarm method, setting of Dead band for alarm, etc.
[Figure 3. Components of channel unit]
After selection of each mode using [Link], arbitrary values can be selected by using
18 Up key "▲", "▼" Key. When"▲", "▼" Key is pushed for a given time in the mode requiring frequent
changes of setting values, the setting values are changed fast.
19 Power ON/OFF switch Power ON/OFF switch for Channel unit.
NO NAME DESCRIPTIONS 20 Front cover screw Screw for fixing of Channel unit
1 Front cover case Front-face Cover for Channel control unit 21 Terminal PCB Channel Unit Terminal PCB
2 Main body case Main Body for Channel control unit 22 Terminal PCB screw Screw for fixing of Channel Unit Terminal PCB
3 Acrylic Acryl for protection of front-face cover for Channel control unit 23 Connector Output connector for signals
4 Front sub cover Front-face Sub cover for Channel control unit
5 Main body fixed bracket Bracket for fixing of Channel control unit [Table 3. Description on components of channel unit]
Measured values of detector connected to each channel are continuously displayed,
6 FND display
and user designated values are displayed in blinking state upon execution of test function.
7 Power LED When Power is Inputted in Channel unit, Power LED is lighted.
8 Check LED STD-BY LED blinks in the case of detector checkup mode.
Trouble LED is lighted when trouble occurs in channel unit and detection unit.
9 Trouble LED
Ex) When defective wire connection with detector and abnormality occur
Alarm 3 LED is lighted when the 3rd alarm occurs in channel unit. Alarm 3 LED is lighted
10 Alarm-3 LED
when the 3rd warning value is reached upon execution of test function of the channel unit.
GTC-200A
Instruction Manual
5. Name and description of each part 5. Name and description of each part [Link]
14_15

5.4. Configuration and description of Wall mount type NO NAME DESCRIPTIONS


13 Front case fixed hook Hook for fixing of front-face case cover
14 Wall mount fixed hole Hole for fixing of Wall mount Type
15 Main power switch Power supply switch of Wall mount Type
16 Power supply Power supply device
17 Battery (option) Battery for reserve power supply
18 Battery cover (option) Battery Cover for reserve power supply

[Table 5. Description on components of wall mount]

[Table 4. Components of wall mount]

NO NAME DESCRIPTIONS
1 Wall mount case front Front-face case of Wall mount Type
2 Wall mount case rear Rear-face case of Wall mount Type
3 Wall mount case cover Terminal cover of Wall mount Type
4 Power unit (option) Unit used upon using reserve power supply (Battery), being provided as an Option.
5 Common unit Common Unit displaying control and alarm signals of channel unit
6 Channel unit Channel Unit displaying the measured values by being connected with detection unit
PCB applied and mounted only upon use of Power unit, protecting the circuit from
7 Mother board filter PCB (option)
electromagnetic waves, noise, surge, etc.
8 Mother board common PCB Output terminal for relay contact such as buzzer, breakdown, alarm, etc. is provided
Connection for detection unit as well as output terminal for current of 4~20mA and output
9 Mother board channel PCB
terminal for relay contact such as alarm etc. are provided.
10 Name plate Product name of Wall mount Type is displayed
11 DIN case fixed bracket Bracket for fixing of individual cards
12 Case cover screw Screw for fixing of terminal cover
GTC-200A
Instruction Manual
6. Installation 6. Installation [Link]
16_17

6.1. Power supply and signal configuration for Channel Unit 6.2. Configuration of power supply for Wall Mount Type
■ Configurations of channel Unit, Common Unit and power Unit are as shown in the following figure, where the ■ Unfasten the fixing chain for front case on the left side of Wall mount ,and open the front case to input power
channel unit allows configuration of 63 ea. supply in the circuit breaker for wiring positioned on the bottom left side inside the case.
■ Power supply in use is AC110V or 220V, and is set and released for the voltage in use requested upon product
ordering, and shipped by being set at AC220V unless there is a separate request.

[Figure 4. Power supply and signal configuration for channel card]

■ Power unit is mounted only when the reserve power supply (Battery) is used. [Figure 5. Configuration of power supply for Wall Mount]

■ When the Power unit is not used, DC24V is directly connected to Connector(CN6) of Common unit in Power
supply for use. (Power unit is provided as an option.)
GTC-200A
Instruction Manual
6. Installation 6. Installation [Link]
18_19

6.3. Configuration of channel Unit terminal 6.4. How to connect 3-wire type Gas detector

NO NAME DESCRIPTIONS ■ When power supply for gas detector and 4-20mA output are configured as 3-wire (V+, mA, V- ), connect to
1 Output 4-20mA + the Channel Unit by the following method.
4-20mA output of measured values for detection unit
2 Output 4-20mA - ■ Connecting cable should be configured with shield cable of CVVS or more than CVVSB.
3 TROUBLE RELAY NO
4 TROUBLE RELAY NC Output Relay for breakdown state
5 TROUBLE RELAY COM
6 Warning3 RELAY NO
7 Warning3 RELAY NC Output Relay for 3rd alarm
8 Warning3 RELAY COM
9 Warning2 RELAY NO
10 Warning2 RELAY NC Output Relay for 2nd alarm
11 Warning2 RELAY COM
12 Warning1 RELAY NO
[Figure 7. Connection method for 3-wire gas detector]
13 Warning1 RELAY NC Output Relay for 1st alarm
14 Warning1 RELAY COM ■ Our company's detector models of the relevant method include TS-1100Ex, TS-2000Ex, TS-2100 Series,
15 Detector Power Supply + TS-4000 Series, TS-4100P Series, TS-5100 Series, GTD-1000 Series, GTD-2000 Series, GTD-3000 Series,
Supply power to detection unit and
16 Detector 4-20mA Input and GIR-3000 Series.
input 4-20mA signals
17 Detector Power Supply -

6.5. How to connect 2-wire type Gas detector


■ When the output for gas detector is configured with 2-wires (V+, V- ), connect to the Channel Unit by the
following method.
■ Connecting cable should be configured with shield cable of CVVS or more than CVVSB 1.5sq.
[Figure 6. Configuration of
Channel Unit terminal]

[Figure 8. Connection method for 2-wire 3 gas detector]

■ Our company's detector models of the relevant method include TS-1100Tx, TS-2000Tx, TS-3000 Series, and
TS-3100 Series.
GTC-200A
Instruction Manual
7. How to operate Power unit 8. How to operate Common Unit [Link]
20_21

■ Voltage of the main power supply is displayed by figures in FND Digital display. 8.1. Functions
■ When the checkup key for reserve power supply is pushed, the power supply is
NO FUNCTION DESCRIPTION
converted to the reserve power supply, the voltage of which is displayed by figures
When breakdown signals are sent from the Channel unit, alarm sound occurs as a short
in FND Digital display. intermittent sound.
1 Buzzer alarm
■ When the reserve power supply is not connected, the breakdown LED for reserve When alarm signals are sent from the Channel unit, alarm sound occurs as a long
intermittent sound.
power supply blinks at an interval of 0.5 sec. It is an LED lighted when breakdown signals or alarm signals are sent from the Channel unit,
2 Breakdown/alarm LED
■ When the reserve power supply is more than18V, the normal LED for reserve power where the alarm LED blinks during alarm maintenance time.
supply is lighted, while the breakdown LED for reserve power supply is lighted when COM-CH LED shows a state of communication between Common unit and Channel unit,
and is turned off after being lighted for about 0.1 sec upon communication once. Thus,
it is less than 18V. when normal communication occurs as many as the No. of channel units set in the Common
unit, continuously lighted state is maintained (Channel unit access time is 0.1sec).
3 Communication LED
When communication DATA transmitted from PC is normally received in the Common unit,
Note1) It is turned off upon shipment of product.
COM-PC LED is immediately turned off after being lighted once.
Note2) Turn on the switch for reserve power supply after turning on the main power supply. When SW1and SW2 are set in the Common unit as less than 1 ea. 1it blinks at an interval of
0.5 sec(COM-CH/ COM-PC LED).
As an alarm occurs in the Channel unit, buzzer operates. When Buzzer stop switch is
pushed. The buzzer is stopped, at which time BZ-STOP LED is lighted (However, it is
4 Buzzer-Stop LED lighted only when Alarm type was set as hold in the Channel unit).
When the Buzzer stop switch is pushed once more in Common unit or channel unit, BZ-
STOP LED is turned Off.
It is a key used for Buzzer Stop and Reset when Trouble and Alarm occurs in each Channel
unit.
Buzzer stop and
5 Push once initially.... Buzzer sound is stopped and BZ-STOP LED is lighted.
Reset key
Push twice consecutively.... As BZ-STOP LED is turned Off Reset function of all channel
units in Latch state according to Alarm setting is executed.
GTC-200A
Instruction Manual
8. How to operate Common Unit 9. How to operate Channel Unit [Link]
22_23

8.2. RS485 MODBUS Interface 9.1. Power ON


8.2.1. Setting for communication ■ Check wire connections of operation power supply, with detection unit, between alarm unit and channel unit.
■ Turn ON the power supply switch after checking input power supply.
■ Baud rate : 9600BPS
■ Check that "SELF" is displayed in FND.
■ Stop bit : 1 Stop
■ Parity : Even parity
When the power supply is turned ON for Channel unit, "SELF" blinks in FND of the channel unit for
15sec, and breakdown alarm occurs when abnormality occurs in detection unit.

8.2.2. Setting for RS485 MODBUS communication and Register


■ Concentration value for Channel unit (Analog input)

NO FUNCTION NAME ADDRESS OTHER


9.2. Gas Measuring Mode
1 Concentration value for Channel-1 unit 30001
Address increased by 1 at
2 Concentration value for Channel-2 unit 30002 ■ When there is no abnormality in SELF TEST after Power ON, the following gas measuring state is automatically
each time per Channel unit.
n Concentration value for Channel-n unit 30xxx entered into.

[Table 6. Register of concentration values for channel Unit RS485] - Gas concentration value received from the detector is displayed as figures in FND Digital display.
- 3 Color Bar graphic LED displays gas concentration, in green when the concentration is less than
the 1st Alarm, in orange when it is more than the 1st Alarm and less than the 2nd Alarm, and in red
■ Bit data for Channel unit state (Data for reading of data input contact) when it is more than the 2nd Alarm.
- The setting value for the stage 3 Alarm is constantly displayed by 3 Color bar graphic LED, in green
NO FUNCTION NAME ADDRESS OTHER for the 1st Alarm value, in orange for the 2nd Alarm value, and in red for the 3rd Alarm value.
State data for Alarm1 10001 - When the detector is not connected or has abnormality, the characters of "Undr" are displayed by
State data for Alarm2 10002 blinking at an interval of about 0.5 sec.
State data for Alarm3 10003 - Trouble LED lamp is lighted.
8Bit each assigned per - Circular LED at the most bottom among 3 Color bar graphic LED is lighted in red.
Channel-1 unit State data for
10004 1 Channel unit
breakdown - When the current value inputted from the detector is higher than the set High Scale by 10%, the text
State data for checkup 10005 of "Ouer" is displayed by blinking at an interval of 0.5 sec.
- Circular LED on the topmost among 3 Color bar graphic LED's is lighter in red.
Preliminary data 10006~10008
- When the gas concentration value is recognized to be more than the Alarm setting value, the relevant
State data for Alarm1 10009 Alarm function counts the alarm maintenance time so that Alarm function is operated if it is more than
State data for Alarm2 10010 the Alarm maintenance time.
State data for Alarm3 10011 - While the Alarm maintenance time is being counted Alarm LED Lamp blinks at an interval of 0.5sec,
8Bit each assigned per and is lighted when it becomes more than the Alarm maintenance time.
Channel-2 unit State data for
10012 1 Channel unit - Alarm relay is turned ON after more than the Alarm maintenance time is elapsed.
breakdown
- If the Alarm latch type is in "on" mode, Alarm state and gas concentration value are maintained at the
State data for checkup 10013 maximum value when Alarm function is operated, and is not cleared even though the gas
Preliminary data 10014~10016 concentration falls below the Alarm value, and must always be cleared by using "Reset" key.
Channel-n unit State data 10001+((n-1)*8) ~ 10001+(((n-1)*8)+8) - When the Alarm latch type is in "off" mode, the Alarm function is automatically cleared according to
gas concentrations.
[Table 7. Register of state for channel Unit RS485]
GTC-200A
Instruction Manual
9. How to operate Channel Unit 9. How to operate Channel Unit [Link]
24_25

9.3. Test Mode 9.5. Setting for operation


■ When there is no abnormality in SELF TEST after Power On, the following state of gas measurement is automatically 9.5.1. PROGRAM MODE
entered into.
- When "▲", "▼" keys are simultaneously pushed for more than 2sec in the display state of gas
- When "Test" key is pushed for more than 2sec in the display state of gas concentration, Test mode concentration.
is entered into. - When 10sec passes after the last key operation in program setting function, the display state of gas
- When 30 min is elapsed in the Test mod after the last key operation, the display state for gas concentration is returned to.
concentration is automatically returned to.

- It is a function allowing test in the Channel unit without injection of detector sensor gas while the figure - The setting message for position of decimal point as the 1st function of setting functions for program
of gas concentration is displayed by blinking upon entering into the Test mode. When the user pushes data is displayed as "dP-S".
- When "Func" key is pushed, the setting function for decimal point is entered into.
"▲" key or "▼" key , an arbitrary gas concentration value can be set, and the Alarm function is
- When "Reset" key is pushed, the concentration display mode is returned to.
normally operated with the concentration value designated by the user.
- When "Func" key is pushed for more than 2sec, FND/LED/Bar LED test function is entered into.
- When "Reset" key is pushed, the concentration display mode is returned to.
- It is the Test mode for FND/LED/Bar LED, where FND figure is displayed as 4-digit figure and overall
display (8888)are displayed at an interval of 0.5 sec, and 4-digit figure displays setting values for PC
Add(SW1) and CH CNT(SW2) of the Common unit.
- Decimal point is sued when there is a need for change according to the measuring range.
- 3 Color bar graphic LED alternatingly displays green, orange and red at an interval of 0.5sec, and
When position of the decimal point is set, position of the decimal point is changed to 3 types as
each function LED blinks at an interval of 0.5sec.
shown on the left side whenever"▲" key or "▼" key is pushed.
- When "Func" key is pushed, the mode where normal operation of communication of Channel unit with
- If "FUNC" is pushed when the desired position of decimal point is displayed, the position of the decimal
Common unit is checked is entered into.
point is set and the next item is entered into.
- When "Reset" key is pushed, the concentration display mode is returned to. - When "Reset" key is pushed, the concentration display mode is returned to.
- It is the mode for checking of Channel unit where communication with Common unit is normally
operated, and the No. of Channel unit where normal communication is realized is sequentially displayed
at an interval of 0.5sec.
- If there is a channel unit No. where all of the No. of Channel units set in Common unit is not displayed
and omitted, it becomes a Channel unit with no communication.
- When "Func" key is pushed, the gas concentration Test function is returned to. - The message for setting of High scale as a function for setting the maximum value of gas
- When "Reset" key is pushed, the concentration display mode is returned to. concentration display is displayed as "H-SL".
- When "Func" key is pushed, the setting function for High scale is entered into.
- When "Reset" key is pushed,, the concentration display mode is returned to.
- High scale value is set for the range specified by domestic regulations upon product shipment.
9.4. Checkup mode (Stand-by Mode)
- The setting value for High scale value can be changed according to the measuring range, and the
- When "▼(Standby)" key of Channel unit is pushed for more than 2sec in the display state of gas Scale value is increased or decreased whenever "▲" key or "▼" key is pushed.
concentration, the checkup mode is entered into. - If "FUNC" is pushed when the desired High scale value is displayed, the High scale value is set and
- In checkup mode ,The checkup mode is cleared and the display state of gas concentration is the next item is entered into. When "Reset" key is pushed, the concentration display mode is returned to.
returned to only when "▼(Standby)" key is pushed in Channel unit. ▼▲ - The present setting mode shall be set for the same measuring range as detection unit upon factory
- In the locking mode, It is a mode where all remaining functions operate as STD-BY LED blinks while shipment.
output of Trouble/Alarm relay contact for Common unit and Channel unit does not operate . Ex) When Range was set for 100
Upon inputting of 4 [Link]................... 0 Display
- When "▼(Standby)" key is pushed, the concentration display mode is returned to.
Upon inputting of 20 [Link]................... 100 Display
GTC-200A
Instruction Manual
9. How to operate Channel Unit 9. How to operate Channel Unit [Link]
26_27

9.6. ALARM Mode


- The message for setting function of SAD value as a function to compensate errors for measured
values occurring in detection unit is displayed as "SAd ". ■ When "Func" key is pushed for more than 2sec in the display state of gas concentration, the setting function for
- When "Func" key is pushed, the setting function for SAD value is entered into.
alarm value data is entered into.
- When "Reset" key is pushed, the concentration display mode is returned to.
■ When 10sec passes after the last key operation in the setting function for alarm value, the display state for gas
- It is a function for setting of SAD value, and the SAD value is increased or decreased whenever
concentration is automatically returned to.
"▲" key or "▼"key is pushed . In the case of negative (minus) value, "-" symbol is displayed by being
added onto the first figure.
- If "FUNC" key is pushed when the desired SAD value is displayed, the SAD value is set, and the next - The message for setting function of Alarm latch type as a function for setting of Alarm latch type is
item is entered into. displayed as "LACH".
- When "Reset" key is set, the concentration display mode is returned to. - When "Func" key is pushed, the setting function for Alarm latch type is entered into.
Ex) When SAD was set as 2: When the output error in detector is -2, Display displays the SAD - When "Reset" key is set, the concentration display mode is returned to.
setting value as 0 after calibration of 2, although actual display should indicate -2.
- It is a mode for changing Alarm reset type, where "" on" and " oFF" modes are changed whenever
- The message for setting of Channel number as a function for setting of recognition No. of Channel "▲" key or "▼" key is pushed.
unit is displayed as "CHno ". - If "FUNC" key is pushed when the desired Alarm latch type is displayed, the Alarm latch type is set
- When "Func" key is pushed, the setting function for Channel number is entered into. and the next item is entered into.
- When "Reset" key is pushed, the concentration display mode is returned to. - When "Reset" key is pushed, the concentration display mode is returned to.
- Alarm latch type has 2 modes of " on" and " oFF" ,where the Alarm is automatically Reset in OFF mode
- Channel No is a mode where Channel unit address is inputted so that operation situation of each while Alarm is reset only when the user makes sure to push Reset key for clearing.
Channel unit can be checked, and Address [Link] is increased or decreased whenever"▲" key
or "▼" key is pushed. - The message for setting function of Alarm1 value as a function for setting of Alarm 1 value is
- If "FUNC" is pushed when the desired Address NO is displayed, the Address NO value is set and displayed as"AL-1".
Alarm reset type function as the next item is entered into. - When "Func" key is pushed. The setting function for Alarm1 value is entered into.
- When "Reset" key is pushed, the concentration display mode is returned to. - When "RESET" key is pushed, the concentration display mode is returned to.
Note1) Unless Channel [Link] inputted, communication between Channel unit and common unit does - Alarm level is set for the concentration specified by domestic regulations upon product shipment.
not occur
Note2) For Channel No, mutually different numbers should always be inputted. - It is a function for changing the setting value for Alarm1, where the maximum values is possible up to
the High scale value, and the Alarm value is increased or decreased whenever "▲" key or "▼" key is
pushed.
- If "FUNC" is pushed when the desired Alarm 1 value is displayed, the Alarm1 value is set and the next
▼▲ item is entered into.
Full Range - When "RESET" key is pushed, the concentration display mode is returned to.

- It is a mode for setting the direction for operation of Alarm1, where"1H "or "1L " is displayed whenever
"▲" key or "▼" key is pushed.
- "1H " mode is the mode operating when it is larger than or the same as the setting value for Alarm1,
while "1L " mode is the mode operating when it is smaller than or the same as the setting value for
Alarm1.
- If "FUNC" key is pushed when the desired mode is displayed the mode is set and the next item is
entered into.
- When "Reset" key is pushed, the concentration display mode is returned to.
- Alarm type has flammability set upon factory shipment as 1H and 2H and 3H / oxygen: 3H and 2L
and 1L / toxicity: 1H and 2H and 3H Type.
GTC-200A
Instruction Manual
9. How to operate Channel Unit 9. How to operate Channel Unit [Link]
28_29

- It is a mode for setting Dead band value for operation of Alarm1, and the value is increased or - The message for setting function of Alarm1 blink output as a function for setting of ON/OFF function
decreased whenever "▲"key or "▼" key is pushed. for Alarm1 contact output at an interval of 1 sec while the buzzer is operating is displayed as "A1bL".
- When Alarm1 is in "1H " mode, Alarm 1 operates below the Alarm 1 value minus Dead band value, - When "Func" key is pushed, the setting function for Alarm1 blink output is entered into.
while Alarm1 is cleared above the Alarm 1 value plus Dead band value when it is in “1L” mode . - When "RESET" key is pushed, the concentration display mode is returned to.
▼▲ - If "FUNC" key is pushed when the desired value of Alarm1 Dead band is displayed, the value of - It is a mode to change the Alarm1 blink output, where " on"과 " oFF" modes are changed whenever
Alarm1 Dead band is set and the next item is entered into. "▲" key or "▼" key is pushed.
- When "Reset" key is pushed, the concentration display mode is returned to. - If "FUNC" key is pushed when the desired mode of Alarm1 blink output is displayed, the mode of
- As the concentration value is reached near the setting value for Alarm, Alarm continues On/Off. Alarm1 blink output is set and the next item is entered into.
This function is a function for giving hysteresis value to remove such phenomenon, and it is set for - When "Reset" key is pushed, the concentration display mode is returned to.
0 upon factory shipment. - Alarm1 blink output has 2 modes of " on" and " oFF" , where Alarm1 blink output is not operated in oFF
- Ex) When the alarm setting value is 20%LEL / Dead band: 2%LEL, the alarm occurs at 22% LEL mode while Alarm1 blink output is operated in on mode.(However, it is operated when the mode of
based on 20%LEL, and is cleared at 18%LEL. Alarm1 contact output is on.)
- Both the 2nd alarm(Alarm2) and the 3rd alarm (Alarm3) have the same menu structure.
- The message for setting of Alarm 1 delay time as the function for setting of Alarm 1 delay time is
displayed as "AL1t".
- The message informing completion of setting function is displayed as "End" for 2sec, and the display
- If "Func" key is pushed, the setting function for Alarm1 delay time is entered into.
state of gas concentration is returned to.
- When "RESET" key is pushed, the concentration display mode is returned to.

- It is a function to prevent occurrence of instantaneous malfunction in detector due to external impact


and effects of noise rather than normal operation, and Alarm 1 delay time is increased or decreased
by the unit of second whenever "▲" key or "▼" key is pushed. ■ Both the 2nd alarm and the 3rd alarm have the same menu structure.
- "FUNC" key is pushed when the desired Alarm 1delay time is displayed, the Alarm1 delay time is set
and the next item is entered into.
- When "Reset" key is pushed, the concentration display mode is returned to.
- Ex) The alarm based on 20%LE occurs when the measured value of more than the alarm setting 9.7. Maintenance Mode
value exists for more than 5 sec in the case of Alarm setting value: 20% LEL / Delay time: 5 sec,
while the alarm does not occur when the value is lowered below the alarm setting value within 5 Sec.
- When "TEST" and "RESET" keys are simultaneously pushed as "SELF" is blinking after power supply
- The message for setting of Alarm1 contact output as a function for setting Alarm 1 contact output is ON, the setting function for Maintenance is entered into.
displayed as "A1rl". - When "Reset" key is surely pushed in Maintenance mode, the display state for gas concentration is
- When "Func" key is pushed, the setting function for Alarm1 contact output is entered into.. returned to.
- When "Reset" key is pushed, the concentration display mode is returned to.
- It is a mode for selecting the function to set current input value and output value as the reference for
- It is a mode to change Alarm1 contact output, where " on "and "oFF" modes are changed whenever Alarm
"▲ key or "▼" key is pushed. - Channel unit, and ""-In-"or "-oUt" is displayed whenever "▲" key or "▼" key is pushed.
- If "FUNC" key is pushed when the desired mode for Alarm 1 contact output is displayed, the mode for - If "FUNC" is pushed when the desired mode is displayed, the relevant mode is entered into.
Alarm1 contact output is set and the next item is entered into. - When "-In-" was selected, we have the mode for setting current input value, while it is mode for
- When "Reset" key is pushed, the concentration display mode is returned to. setting current output value when "-oUt" was selected.
- Alarm1 contact output has 2 modes of " on" and "oFF" where Alarm1contact output does not operated - When "Reset" key is pushed, the concentration display mode is returned to.
in oFF mode and is operated in on mode.
- It is the case where "-In-"was selected, as a mode for setting by inputting 20mA current, and the
message is displayed as "IA20".
- When "Func" key is pushed, the function for displaying current input value as figures is entered into.
- When "Reset" key is pushed, the concentration display mode is returned to.
GTC-200A
Instruction Manual
9. How to operate Channel Unit 10. Outline drawing and Dimensions [Link]
30_31

- It is a mode where the value transformed in the process is displayed by figures after inputting 20mA 10.1. Power unit
current in (mA) terminal.
- "Func" key is pushed when the displayed figures re stable, the input value for current is set, and the
next item is entered into.
- When "Reset" key is pushed, the concentration display mode is returned to.
- It is the case of selecting "-Out" and the next mode after input current. It is the mode for setting of 4mA
output current, 7 the message is displayed as "A-04".
- If "Func" key is pushed when the ammeter accurately displays 4mA by pushing "▲" key or "▼" key
while watching the ammeter after connecting the ammeter to output terminal of 4~20mA, the output
current value is set and the next item is entered into.
- When "RESET" key is pushed, the concentration display mode is returned to.
- It is a mode for setting 20mA output current, and the message is displayed as "A-20".
- If "Func" key is pushed when the ammeter accurately displays 4mA by pushing "▲" key or "▼" key
while watching the ammeter after connecting the ammeter to output terminal of 4~20mA, the output
current value is set and the next item is entered into.
- When "RESET" key is pushed, the concentration display mode is returned to.

- The message informing completion of the setting function is displayed as "End" for 2sec,
7 the concentration display mode is returned to.
[Figure 9. Outline drawing of Power Unit]

10.2. Common Unit

[Figure 10. Outline drawing of Common Unit]


GTC-200A
Instruction Manual
10. Outline drawing and Dimensions 10. Outline drawing and Dimensions [Link]
32_33

10.3. Channel Unit 10.4. Panel mount type

Upon mounting of
Panel 2 stage,
Cut-out spacing shall be
more than 30mm at least.

[Figure 11. Outline drawing of Channel Unit]

[Figure 12. Outline drawing of Panel mount]

CHANNEL A(MM) B(MM) CHANNEL A(MM) B(MM)


1 Channel 108 107 6 Channel 288 287
2 Channel 144 143 7 Channel 324 323
3 Channel 180 179 8 Channel 360 359
4 Channel 216 215 9 Channel 396 395
5 Channel 252 251 10 Channel 432 431
Power Unit is optional, and the width of 36mm for Power unit should be subtracted from the above dimension
when only Common unit and Channel unit are sued.
Ex) When Power unit is not used in the case of 5 Channel, A is 216mm(252mm-36mm), and
B becomes 215mm(251mm-36mm)

[Table 8. Dimension according to setting for Panel Mount channel]


GTC-200A
Instruction Manual
10. Outline drawing and Dimensions 10. Outline drawing and Dimensions [Link]
34_35

10.5. Wall mount type(Power Unit applied) 10.6. Wall mount type(Power Unit not applied)

[Figure 13. Outline drawing of Panel Mount (Power Unit not applied)] [Figure 14. Outline drawing of Panel Mount(Power Unit applied)]

Channel A(mm) B(mm) Channel A(mm) B(mm) Channel A(mm) B(mm) Channel A(mm) B(mm)
3 Channel 218 147 7 Channel 361 291 4 Channel 218 147 8 Channel 361 291
5 Channel 289 219 9 Channel 433 363 6 Channel 289 219 10 Channel 433 363
Note1) Basic types include 4 types above, and Wall mount of other different sizes is for separate order specifications. Note1) Basic types include 4 types above, and Wall mount of other different sizes is for separate order specifications.

[Table 9. Dimension per channel of Wall Mount Type(Power Unit not applied)] [Table 10. Dimension per channel of Wall Mount Type(Power Unit applied)]
GTC-200A
Instruction Manual
11. Revision record [Link]
36_37

Version Contents Date


0.0 Manual revised initially 2011. 06. 27
1.0 Font changed, typo corrected 2016. 10. 27