GTC-200A Gas Detector Manual
GTC-200A Gas Detector Manual
E-mail : info@[Link]
[Link]
Gas & Flame We sincerely thank you for purchasing the product of Gastron Co. Ltd.
Our Gastron [Link]. is a company specialized in Gas detector and Gas Monitoring System, being
Detection System
recognized by many consumers due to the best quality and use convenience. We always enable you
consumers to find desired products nearby and are ceaselessly studying and striving for development
of Gas detectors satisfying customers. From now on, solve all anguishes concerning Gas detector with
the products of Gastron Co. Ltd, We Gastron Co. will take a responsibility and give you satisfaction.
In the present instruction manual, operation method for Gas detector as well as simple methods for
maintenance and repair, etc. are recorded If you read it in detail and keep it well, for reference when
you have questions, then it will give you much help.
■ For accurate operation of Gas detector, check up and calibrate for more than once in every 6 months.
( * See No. 13 of KOSHA GUIDE : P-135-2013 / 8.3 paragraph on qualification and calibration)
■ For accurate operation of Gas detector, checkup and calibration with calibration gas before measurement
is recommended.
■ When not calibrated, it may cause malfunction of the equipment due to problems resulting from Sensor aging.
■ When the present instrument should be dismantled, those with professional skills for Gas detector should
conduct the operation.
■ For power supply cable, wire specifications should be determined by referring to the item of "Length of
installed cable".
■ For the contents on checkup and calibration of Gas detector, please use our company's engineering
department , e-mail, or web site.
6. Installation·························································································· 16
11. Revision record····················································································· 36
6.1. Power supply and signal configuration for Channel Unit··········································· 16
6.2. Power supply configuration for Wall Mount Type·················································· 17
6.3. Configuration of channel Unit terminal···························································· 18
6.4. How to connect 3 wire type Gas detector· ······················································· 19
6.5. How to connect 2 wire type Gas detector· ······················································· 19
GTC200A Series is ammeter that adopted high-performance A/D Converter and Micro-Process with diversified 3.2. Channel Control Unit
functions embedded. GTC200A Series is configured in centralized style, comprised of a Common alarm unit and a
ITEMS SPECIFICATION
Multi-Channel control unit for several detectors, with the Multi channel control unit being connected to each detector.
Input form Analog 4-20mA
GTC200A Series is protected by the case of DIN Type, and has 2 types of products such as Panel mount type, Wall
Measurement display 4-Digit FND & Bar-graph (32 segment, 3-color LED)
mount type, etc. GTC200A Series has the display function of FND Digital display (PV Value) and the display function of Measuring range 0.000 to 9999 Digital (Arbitrary setting by the user)
3-color LED Bar Graphic display (PV and Alarm set value) embedded, accompanied by 3 Instant alarm functions (1st FND Digital ±1% Full Scale
Measuring accuracy
H/L, 2nd H/L, 3rd H/L) and Trouble alarm. LED Bar ±1% Full Scale
ITEMS SPECIFICATION
Input form RS-485
Input measuring period 100ms 3.3. Power Unit (Option)
Alarm display Audio signal- Audible(Buzzer) and Visual signal- Visual(LED)
ITEMS SPECIFICATION
Alarm clearing Return switch- Manual (Reset switch)
Input power supply DC. 24V
Control input Outside input(Remote reset) - Buzzer stop/ return function
Output power supply DC. 24V (reserve power supply : DC. 27V / 300mA)
Measured output Isolation RS-485 modbus(Option)
Output power supply display FND Digital display
Buzzer - Buzzer SPST Relay dry contact signal output
Main power supply display Green LED display
Breakdown alarm - SPDT Relay Dry contact signal output
reserve power supply display Green LED display
1st alarm - Alarm 1 SPDT Relay dry contact signal output
Alarm output reserve power supply monitoring Red LED display
2nd alarm - Alarm 2 SPDT Relay dry contact signal output
reserve power supply test Test switch for preliminary power switch
3rd alarm - Alarm 3 SPDT Relay dry contact signal output
reserve power supply Ni-Cd Battery 24V / 600mA(less than 6 circuits)
* Relay dry contact capacity : AC125V 10A
Operation power supply DC 24V / 100mA Max
■ No. of Channel units for the maximum access to a common unit is 63ea.
GTC-200A
Instruction Manual
3. Specifications for channel card 5. Name and description of each part [Link]
08_09
3.4. Environmental Specifications 5.1. Configuration and description of power supply unit
ITEMS SPECIFICATION
Operation Temperature -20 to 60 ℃
Storage Temperature -20 to 60 ℃
Operation Humidity 5 to 99% RH (Non-condensing)
Pressure Range 90 to 110KPa
5.3. Configuration and description of concentration display unit (Channel unit) NO NAME DESCRIPTIONS
Alarm 2LED is lighted when the 2nd alarm occurs in channel unit. Alarm 2 LED is lighted
11 Alarm-2 LED
when the 2nd warning value is reached upon execution of test function of the channel unit.
Alarm 1 LED is lighted when the 1st alarm occurs in channel unit. Alarm 1 LED is lighted
12 Alarm-1 LED
when the 1st warning value is reached upon execution of test function of the channel unit.
3 Color bar graphic LED continuously shows, display of measured value and of alarm
setting value as in FND display.
Bar graphic LED is lighted as green when the measured value is less than the 1st alarm,
13 3 color bar graphic LED as orange when it is more than the 1st alarm and less than the 2nd alarm, as red when it is
more than the 2nd alarm.
When the measured value is more than the alarm setting value, Bar graphic is held at the
highest value, and Bar graphic is displayed in blinking state for the alarm.
It performs functions such as Alarm clearing of Channel unit, clearing of Self test, clearing of
14 Reset key
Program setting, etc.
After selection of each mode using [Link], arbitrary values can be selected by using
15 Down key "▲", "▼" Key. When "▲", "▼" Key is pushed for a given time in the mode requiring frequent
changes of setting values, the setting values are changed fast.
When Test switch is pushed, the mode executing self diagnosis function is entered into.
It is the key where the measured value FND blinks, checking of Alarm operation state in
16 Test key Channel unit and Common unit by adjustment of blinking measured values is possible by
using "▲" key or "▼" key.
For clearing of diagnosis, clearing occurs by pushing once the Reset key in each Channel unit.
Function key is the key that inputs data values by conversion and selection of functions such
17 Function key
as setting of warning values. Setting of alarm method, setting of Dead band for alarm, etc.
[Figure 3. Components of channel unit]
After selection of each mode using [Link], arbitrary values can be selected by using
18 Up key "▲", "▼" Key. When"▲", "▼" Key is pushed for a given time in the mode requiring frequent
changes of setting values, the setting values are changed fast.
19 Power ON/OFF switch Power ON/OFF switch for Channel unit.
NO NAME DESCRIPTIONS 20 Front cover screw Screw for fixing of Channel unit
1 Front cover case Front-face Cover for Channel control unit 21 Terminal PCB Channel Unit Terminal PCB
2 Main body case Main Body for Channel control unit 22 Terminal PCB screw Screw for fixing of Channel Unit Terminal PCB
3 Acrylic Acryl for protection of front-face cover for Channel control unit 23 Connector Output connector for signals
4 Front sub cover Front-face Sub cover for Channel control unit
5 Main body fixed bracket Bracket for fixing of Channel control unit [Table 3. Description on components of channel unit]
Measured values of detector connected to each channel are continuously displayed,
6 FND display
and user designated values are displayed in blinking state upon execution of test function.
7 Power LED When Power is Inputted in Channel unit, Power LED is lighted.
8 Check LED STD-BY LED blinks in the case of detector checkup mode.
Trouble LED is lighted when trouble occurs in channel unit and detection unit.
9 Trouble LED
Ex) When defective wire connection with detector and abnormality occur
Alarm 3 LED is lighted when the 3rd alarm occurs in channel unit. Alarm 3 LED is lighted
10 Alarm-3 LED
when the 3rd warning value is reached upon execution of test function of the channel unit.
GTC-200A
Instruction Manual
5. Name and description of each part 5. Name and description of each part [Link]
14_15
NO NAME DESCRIPTIONS
1 Wall mount case front Front-face case of Wall mount Type
2 Wall mount case rear Rear-face case of Wall mount Type
3 Wall mount case cover Terminal cover of Wall mount Type
4 Power unit (option) Unit used upon using reserve power supply (Battery), being provided as an Option.
5 Common unit Common Unit displaying control and alarm signals of channel unit
6 Channel unit Channel Unit displaying the measured values by being connected with detection unit
PCB applied and mounted only upon use of Power unit, protecting the circuit from
7 Mother board filter PCB (option)
electromagnetic waves, noise, surge, etc.
8 Mother board common PCB Output terminal for relay contact such as buzzer, breakdown, alarm, etc. is provided
Connection for detection unit as well as output terminal for current of 4~20mA and output
9 Mother board channel PCB
terminal for relay contact such as alarm etc. are provided.
10 Name plate Product name of Wall mount Type is displayed
11 DIN case fixed bracket Bracket for fixing of individual cards
12 Case cover screw Screw for fixing of terminal cover
GTC-200A
Instruction Manual
6. Installation 6. Installation [Link]
16_17
6.1. Power supply and signal configuration for Channel Unit 6.2. Configuration of power supply for Wall Mount Type
■ Configurations of channel Unit, Common Unit and power Unit are as shown in the following figure, where the ■ Unfasten the fixing chain for front case on the left side of Wall mount ,and open the front case to input power
channel unit allows configuration of 63 ea. supply in the circuit breaker for wiring positioned on the bottom left side inside the case.
■ Power supply in use is AC110V or 220V, and is set and released for the voltage in use requested upon product
ordering, and shipped by being set at AC220V unless there is a separate request.
■ Power unit is mounted only when the reserve power supply (Battery) is used. [Figure 5. Configuration of power supply for Wall Mount]
■ When the Power unit is not used, DC24V is directly connected to Connector(CN6) of Common unit in Power
supply for use. (Power unit is provided as an option.)
GTC-200A
Instruction Manual
6. Installation 6. Installation [Link]
18_19
6.3. Configuration of channel Unit terminal 6.4. How to connect 3-wire type Gas detector
NO NAME DESCRIPTIONS ■ When power supply for gas detector and 4-20mA output are configured as 3-wire (V+, mA, V- ), connect to
1 Output 4-20mA + the Channel Unit by the following method.
4-20mA output of measured values for detection unit
2 Output 4-20mA - ■ Connecting cable should be configured with shield cable of CVVS or more than CVVSB.
3 TROUBLE RELAY NO
4 TROUBLE RELAY NC Output Relay for breakdown state
5 TROUBLE RELAY COM
6 Warning3 RELAY NO
7 Warning3 RELAY NC Output Relay for 3rd alarm
8 Warning3 RELAY COM
9 Warning2 RELAY NO
10 Warning2 RELAY NC Output Relay for 2nd alarm
11 Warning2 RELAY COM
12 Warning1 RELAY NO
[Figure 7. Connection method for 3-wire gas detector]
13 Warning1 RELAY NC Output Relay for 1st alarm
14 Warning1 RELAY COM ■ Our company's detector models of the relevant method include TS-1100Ex, TS-2000Ex, TS-2100 Series,
15 Detector Power Supply + TS-4000 Series, TS-4100P Series, TS-5100 Series, GTD-1000 Series, GTD-2000 Series, GTD-3000 Series,
Supply power to detection unit and
16 Detector 4-20mA Input and GIR-3000 Series.
input 4-20mA signals
17 Detector Power Supply -
■ Our company's detector models of the relevant method include TS-1100Tx, TS-2000Tx, TS-3000 Series, and
TS-3100 Series.
GTC-200A
Instruction Manual
7. How to operate Power unit 8. How to operate Common Unit [Link]
20_21
■ Voltage of the main power supply is displayed by figures in FND Digital display. 8.1. Functions
■ When the checkup key for reserve power supply is pushed, the power supply is
NO FUNCTION DESCRIPTION
converted to the reserve power supply, the voltage of which is displayed by figures
When breakdown signals are sent from the Channel unit, alarm sound occurs as a short
in FND Digital display. intermittent sound.
1 Buzzer alarm
■ When the reserve power supply is not connected, the breakdown LED for reserve When alarm signals are sent from the Channel unit, alarm sound occurs as a long
intermittent sound.
power supply blinks at an interval of 0.5 sec. It is an LED lighted when breakdown signals or alarm signals are sent from the Channel unit,
2 Breakdown/alarm LED
■ When the reserve power supply is more than18V, the normal LED for reserve power where the alarm LED blinks during alarm maintenance time.
supply is lighted, while the breakdown LED for reserve power supply is lighted when COM-CH LED shows a state of communication between Common unit and Channel unit,
and is turned off after being lighted for about 0.1 sec upon communication once. Thus,
it is less than 18V. when normal communication occurs as many as the No. of channel units set in the Common
unit, continuously lighted state is maintained (Channel unit access time is 0.1sec).
3 Communication LED
When communication DATA transmitted from PC is normally received in the Common unit,
Note1) It is turned off upon shipment of product.
COM-PC LED is immediately turned off after being lighted once.
Note2) Turn on the switch for reserve power supply after turning on the main power supply. When SW1and SW2 are set in the Common unit as less than 1 ea. 1it blinks at an interval of
0.5 sec(COM-CH/ COM-PC LED).
As an alarm occurs in the Channel unit, buzzer operates. When Buzzer stop switch is
pushed. The buzzer is stopped, at which time BZ-STOP LED is lighted (However, it is
4 Buzzer-Stop LED lighted only when Alarm type was set as hold in the Channel unit).
When the Buzzer stop switch is pushed once more in Common unit or channel unit, BZ-
STOP LED is turned Off.
It is a key used for Buzzer Stop and Reset when Trouble and Alarm occurs in each Channel
unit.
Buzzer stop and
5 Push once initially.... Buzzer sound is stopped and BZ-STOP LED is lighted.
Reset key
Push twice consecutively.... As BZ-STOP LED is turned Off Reset function of all channel
units in Latch state according to Alarm setting is executed.
GTC-200A
Instruction Manual
8. How to operate Common Unit 9. How to operate Channel Unit [Link]
22_23
[Table 6. Register of concentration values for channel Unit RS485] - Gas concentration value received from the detector is displayed as figures in FND Digital display.
- 3 Color Bar graphic LED displays gas concentration, in green when the concentration is less than
the 1st Alarm, in orange when it is more than the 1st Alarm and less than the 2nd Alarm, and in red
■ Bit data for Channel unit state (Data for reading of data input contact) when it is more than the 2nd Alarm.
- The setting value for the stage 3 Alarm is constantly displayed by 3 Color bar graphic LED, in green
NO FUNCTION NAME ADDRESS OTHER for the 1st Alarm value, in orange for the 2nd Alarm value, and in red for the 3rd Alarm value.
State data for Alarm1 10001 - When the detector is not connected or has abnormality, the characters of "Undr" are displayed by
State data for Alarm2 10002 blinking at an interval of about 0.5 sec.
State data for Alarm3 10003 - Trouble LED lamp is lighted.
8Bit each assigned per - Circular LED at the most bottom among 3 Color bar graphic LED is lighted in red.
Channel-1 unit State data for
10004 1 Channel unit
breakdown - When the current value inputted from the detector is higher than the set High Scale by 10%, the text
State data for checkup 10005 of "Ouer" is displayed by blinking at an interval of 0.5 sec.
- Circular LED on the topmost among 3 Color bar graphic LED's is lighter in red.
Preliminary data 10006~10008
- When the gas concentration value is recognized to be more than the Alarm setting value, the relevant
State data for Alarm1 10009 Alarm function counts the alarm maintenance time so that Alarm function is operated if it is more than
State data for Alarm2 10010 the Alarm maintenance time.
State data for Alarm3 10011 - While the Alarm maintenance time is being counted Alarm LED Lamp blinks at an interval of 0.5sec,
8Bit each assigned per and is lighted when it becomes more than the Alarm maintenance time.
Channel-2 unit State data for
10012 1 Channel unit - Alarm relay is turned ON after more than the Alarm maintenance time is elapsed.
breakdown
- If the Alarm latch type is in "on" mode, Alarm state and gas concentration value are maintained at the
State data for checkup 10013 maximum value when Alarm function is operated, and is not cleared even though the gas
Preliminary data 10014~10016 concentration falls below the Alarm value, and must always be cleared by using "Reset" key.
Channel-n unit State data 10001+((n-1)*8) ~ 10001+(((n-1)*8)+8) - When the Alarm latch type is in "off" mode, the Alarm function is automatically cleared according to
gas concentrations.
[Table 7. Register of state for channel Unit RS485]
GTC-200A
Instruction Manual
9. How to operate Channel Unit 9. How to operate Channel Unit [Link]
24_25
- It is a function allowing test in the Channel unit without injection of detector sensor gas while the figure - The setting message for position of decimal point as the 1st function of setting functions for program
of gas concentration is displayed by blinking upon entering into the Test mode. When the user pushes data is displayed as "dP-S".
- When "Func" key is pushed, the setting function for decimal point is entered into.
"▲" key or "▼" key , an arbitrary gas concentration value can be set, and the Alarm function is
- When "Reset" key is pushed, the concentration display mode is returned to.
normally operated with the concentration value designated by the user.
- When "Func" key is pushed for more than 2sec, FND/LED/Bar LED test function is entered into.
- When "Reset" key is pushed, the concentration display mode is returned to.
- It is the Test mode for FND/LED/Bar LED, where FND figure is displayed as 4-digit figure and overall
display (8888)are displayed at an interval of 0.5 sec, and 4-digit figure displays setting values for PC
Add(SW1) and CH CNT(SW2) of the Common unit.
- Decimal point is sued when there is a need for change according to the measuring range.
- 3 Color bar graphic LED alternatingly displays green, orange and red at an interval of 0.5sec, and
When position of the decimal point is set, position of the decimal point is changed to 3 types as
each function LED blinks at an interval of 0.5sec.
shown on the left side whenever"▲" key or "▼" key is pushed.
- When "Func" key is pushed, the mode where normal operation of communication of Channel unit with
- If "FUNC" is pushed when the desired position of decimal point is displayed, the position of the decimal
Common unit is checked is entered into.
point is set and the next item is entered into.
- When "Reset" key is pushed, the concentration display mode is returned to. - When "Reset" key is pushed, the concentration display mode is returned to.
- It is the mode for checking of Channel unit where communication with Common unit is normally
operated, and the No. of Channel unit where normal communication is realized is sequentially displayed
at an interval of 0.5sec.
- If there is a channel unit No. where all of the No. of Channel units set in Common unit is not displayed
and omitted, it becomes a Channel unit with no communication.
- When "Func" key is pushed, the gas concentration Test function is returned to. - The message for setting of High scale as a function for setting the maximum value of gas
- When "Reset" key is pushed, the concentration display mode is returned to. concentration display is displayed as "H-SL".
- When "Func" key is pushed, the setting function for High scale is entered into.
- When "Reset" key is pushed,, the concentration display mode is returned to.
- High scale value is set for the range specified by domestic regulations upon product shipment.
9.4. Checkup mode (Stand-by Mode)
- The setting value for High scale value can be changed according to the measuring range, and the
- When "▼(Standby)" key of Channel unit is pushed for more than 2sec in the display state of gas Scale value is increased or decreased whenever "▲" key or "▼" key is pushed.
concentration, the checkup mode is entered into. - If "FUNC" is pushed when the desired High scale value is displayed, the High scale value is set and
- In checkup mode ,The checkup mode is cleared and the display state of gas concentration is the next item is entered into. When "Reset" key is pushed, the concentration display mode is returned to.
returned to only when "▼(Standby)" key is pushed in Channel unit. ▼▲ - The present setting mode shall be set for the same measuring range as detection unit upon factory
- In the locking mode, It is a mode where all remaining functions operate as STD-BY LED blinks while shipment.
output of Trouble/Alarm relay contact for Common unit and Channel unit does not operate . Ex) When Range was set for 100
Upon inputting of 4 [Link]................... 0 Display
- When "▼(Standby)" key is pushed, the concentration display mode is returned to.
Upon inputting of 20 [Link]................... 100 Display
GTC-200A
Instruction Manual
9. How to operate Channel Unit 9. How to operate Channel Unit [Link]
26_27
- It is a mode for setting the direction for operation of Alarm1, where"1H "or "1L " is displayed whenever
"▲" key or "▼" key is pushed.
- "1H " mode is the mode operating when it is larger than or the same as the setting value for Alarm1,
while "1L " mode is the mode operating when it is smaller than or the same as the setting value for
Alarm1.
- If "FUNC" key is pushed when the desired mode is displayed the mode is set and the next item is
entered into.
- When "Reset" key is pushed, the concentration display mode is returned to.
- Alarm type has flammability set upon factory shipment as 1H and 2H and 3H / oxygen: 3H and 2L
and 1L / toxicity: 1H and 2H and 3H Type.
GTC-200A
Instruction Manual
9. How to operate Channel Unit 9. How to operate Channel Unit [Link]
28_29
- It is a mode for setting Dead band value for operation of Alarm1, and the value is increased or - The message for setting function of Alarm1 blink output as a function for setting of ON/OFF function
decreased whenever "▲"key or "▼" key is pushed. for Alarm1 contact output at an interval of 1 sec while the buzzer is operating is displayed as "A1bL".
- When Alarm1 is in "1H " mode, Alarm 1 operates below the Alarm 1 value minus Dead band value, - When "Func" key is pushed, the setting function for Alarm1 blink output is entered into.
while Alarm1 is cleared above the Alarm 1 value plus Dead band value when it is in “1L” mode . - When "RESET" key is pushed, the concentration display mode is returned to.
▼▲ - If "FUNC" key is pushed when the desired value of Alarm1 Dead band is displayed, the value of - It is a mode to change the Alarm1 blink output, where " on"과 " oFF" modes are changed whenever
Alarm1 Dead band is set and the next item is entered into. "▲" key or "▼" key is pushed.
- When "Reset" key is pushed, the concentration display mode is returned to. - If "FUNC" key is pushed when the desired mode of Alarm1 blink output is displayed, the mode of
- As the concentration value is reached near the setting value for Alarm, Alarm continues On/Off. Alarm1 blink output is set and the next item is entered into.
This function is a function for giving hysteresis value to remove such phenomenon, and it is set for - When "Reset" key is pushed, the concentration display mode is returned to.
0 upon factory shipment. - Alarm1 blink output has 2 modes of " on" and " oFF" , where Alarm1 blink output is not operated in oFF
- Ex) When the alarm setting value is 20%LEL / Dead band: 2%LEL, the alarm occurs at 22% LEL mode while Alarm1 blink output is operated in on mode.(However, it is operated when the mode of
based on 20%LEL, and is cleared at 18%LEL. Alarm1 contact output is on.)
- Both the 2nd alarm(Alarm2) and the 3rd alarm (Alarm3) have the same menu structure.
- The message for setting of Alarm 1 delay time as the function for setting of Alarm 1 delay time is
displayed as "AL1t".
- The message informing completion of setting function is displayed as "End" for 2sec, and the display
- If "Func" key is pushed, the setting function for Alarm1 delay time is entered into.
state of gas concentration is returned to.
- When "RESET" key is pushed, the concentration display mode is returned to.
- It is a mode where the value transformed in the process is displayed by figures after inputting 20mA 10.1. Power unit
current in (mA) terminal.
- "Func" key is pushed when the displayed figures re stable, the input value for current is set, and the
next item is entered into.
- When "Reset" key is pushed, the concentration display mode is returned to.
- It is the case of selecting "-Out" and the next mode after input current. It is the mode for setting of 4mA
output current, 7 the message is displayed as "A-04".
- If "Func" key is pushed when the ammeter accurately displays 4mA by pushing "▲" key or "▼" key
while watching the ammeter after connecting the ammeter to output terminal of 4~20mA, the output
current value is set and the next item is entered into.
- When "RESET" key is pushed, the concentration display mode is returned to.
- It is a mode for setting 20mA output current, and the message is displayed as "A-20".
- If "Func" key is pushed when the ammeter accurately displays 4mA by pushing "▲" key or "▼" key
while watching the ammeter after connecting the ammeter to output terminal of 4~20mA, the output
current value is set and the next item is entered into.
- When "RESET" key is pushed, the concentration display mode is returned to.
- The message informing completion of the setting function is displayed as "End" for 2sec,
7 the concentration display mode is returned to.
[Figure 9. Outline drawing of Power Unit]
Upon mounting of
Panel 2 stage,
Cut-out spacing shall be
more than 30mm at least.
10.5. Wall mount type(Power Unit applied) 10.6. Wall mount type(Power Unit not applied)
[Figure 13. Outline drawing of Panel Mount (Power Unit not applied)] [Figure 14. Outline drawing of Panel Mount(Power Unit applied)]
Channel A(mm) B(mm) Channel A(mm) B(mm) Channel A(mm) B(mm) Channel A(mm) B(mm)
3 Channel 218 147 7 Channel 361 291 4 Channel 218 147 8 Channel 361 291
5 Channel 289 219 9 Channel 433 363 6 Channel 289 219 10 Channel 433 363
Note1) Basic types include 4 types above, and Wall mount of other different sizes is for separate order specifications. Note1) Basic types include 4 types above, and Wall mount of other different sizes is for separate order specifications.
[Table 9. Dimension per channel of Wall Mount Type(Power Unit not applied)] [Table 10. Dimension per channel of Wall Mount Type(Power Unit applied)]
GTC-200A
Instruction Manual
11. Revision record [Link]
36_37