0% found this document useful (0 votes)
112 views3 pages

6EP19356MF01 Datasheet en

The SITOP Battery Module (6EP1935-6MF01) is a 24V, 12Ah maintenance-free sealed lead-acid battery designed for use with SITOP DC UPS modules. It features various operational specifications including a maximum output current of 30A, a peak current of 30A, and operates within a temperature range of -15 to +50 °C. The module is certified with CE, UL, and has marine classification approvals, ensuring compliance with safety and environmental standards.

Uploaded by

Wolfpackxx86
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
112 views3 pages

6EP19356MF01 Datasheet en

The SITOP Battery Module (6EP1935-6MF01) is a 24V, 12Ah maintenance-free sealed lead-acid battery designed for use with SITOP DC UPS modules. It features various operational specifications including a maximum output current of 30A, a peak current of 30A, and operates within a temperature range of -15 to +50 °C. The module is certified with CE, UL, and has marine classification approvals, ensuring compliance with safety and environmental standards.

Uploaded by

Wolfpackxx86
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Data sheet 6EP1935-6MF01

SITOP Battery module/24V/12AH

SITOP battery module 24 V/12 Ah with maintenance free sealed lead-acid batteries
for SITOP DC UPS module 6 A, 15 A and 40 A

electrical data
end-of-charge voltage at DC
● at -10 °C recommended 29 V
● at 0 °C recommended 28.4 V
● at 10 °C recommended 27.8 V
● at 20 °C recommended 27.3 V
● at 30 °C recommended 26.8 V
● at 40 °C recommended 26.6 V
● at 50 °C recommended 26.3 V
output
battery capacity 12 A·h
output current in buffering mode maximum 30 A
peak current 30 A
charging current maximum 3A
output voltage at DC rated value 24 V
interfaces
communication function No
protection and monitoring
design of short-circuit protection Battery fuse 20 A/32 V (solid-state circuitry blade-type fuse + support)
design of the overload protection Valve control
safety
operating resource protection class Class III
protection class IP IP00
standards, specifications, approvals
certificate of suitability
● CE marking Yes
● UL approval Yes; cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627
● EAC approval Yes
standards, specifications, approvals hazardous environments
certificate of suitability
● ATEX No
● cCSAus, Class 1, Division 2 No
standards, specifications, approvals marine classification
shipbuilding approval Yes
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS) Yes
● Det Norske Veritas (DNV) Yes
standards, specifications, approvals Environmental Product Declaration
Environmental Product Declaration Yes
Global Warming Potential [CO2 eq]

6EP19356MF01 Subject to change without notice


11/9/2024
Page 1/3 © Copyright Siemens
● total 42.3 kg
● during manufacturing 20.2 kg
● during operation 18.4 kg
● after end of life 1.28 kg
ambient conditions
ambient condition For storage, mounting and operation of lead-acid batteries, the relevant
DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN
50272-2) must be observed. You must ensure that the battery site is sufficiently
ventilated. Possible sources of ignition must be at least 50 cm away.
ambient temperature
● during operation -15 ... +50 °C
● during transport -20 ... +50 °C
● during storage -20 ... +50 °C
relative temporary capacity loss at 20 °C in a month typical 3%
service life of energy storage
● typical capacity falls to 80 % of original capacity (according to EUROBAT)
● at 20 °C typical 4a
● at 30 °C typical 2a
● at 40 °C typical 1a
● at 50 °C typical 0.5 a
note Along with the storage and operating temperature, other factors such as the
duration of the storage period and the charge status during storage have a
decisive influence on the possible useful life. Batteries should therefore be
stored as briefly as possible, always fully charged, and within the temperature
range 0 to +20 °C.
connection method
type of electrical connection spring-loaded terminals
● for power supply unit 1 screw terminal each for 0.08 ... 4 mm² for + BAT and - BAT
mechanical data
width × height × depth of the enclosure 253 × 168 × 121 mm
installation width × mounting height 273 × 188 mm
fastening method can be screwed onto flat surface (keyhole mounting for hooking in to M4
screws)
● standard rail mounting No
● S7 rail mounting No
● wall mounting Yes
net weight 9 kg
number of cells 12
accessories
product component included Accessories pack with solid-state circuitry fuse 20 A and 30 A
further information internet links
internet link
● to website: Industry Mall [Link]
● to web page: selection aid TIA Selection Tool [Link]
● to website: Industrial communication [Link]
● to website: CAx-Download-Manager [Link]
● to website: Industry Online Support [Link]
additional information
other information Specifications at rated input voltage and ambient temperature +25 °C (unless
otherwise specified)
security information
security information Siemens provides products and solutions with industrial cybersecurity functions
that support the secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber
threats, it is necessary to implement – and continuously maintain – a holistic,
state-of-the-art industrial cybersecurity concept. Siemens’ products and
solutions constitute one element of such a concept. Customers are responsible
for preventing unauthorized access to their plants, systems, machines and
networks. Such systems, machines and components should only be connected
to an enterprise network or the internet if and to the extent such a connection is
necessary and only when appropriate security measures (e.g. firewalls and/or
network segmentation) are in place. For additional information on industrial
cybersecurity measures that may be implemented, please visit
[Link]/cybersecurity-industry. Siemens’ products and solutions
undergo continuous development to make them more secure. Siemens strongly
recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are
no longer supported, and failure to apply the latest updates may increase

6EP19356MF01 Subject to change without notice


11/9/2024
Page 2/3 © Copyright Siemens
customer’s exposure to cyber threats. To stay informed about product updates,
subscribe to the Siemens Industrial Cybersecurity RSS Feed under
[Link] (V4.7)
Classifications
Version Classification

eClass 14 27-05-04-03
eClass 12 27-05-04-03
eClass 9.1 27-05-04-03
eClass 9 27-05-04-03
eClass 8 27-05-04-03
eClass 7.1 27-05-04-03
eClass 6 27-05-04-90
ETIM 9 EC000357
ETIM 8 EC000357
ETIM 7 EC000357
UNSPSC 15 26-11-17-01

Approvals Certificates
General Product Approval

Manufacturer Declara- Declaration of Con- Miscellaneous


tion formity

Marine / Shipping Dangerous goods Environment

Dangerous goods in-


formation

last modified: 6/25/2024

6EP19356MF01 Subject to change without notice


11/9/2024
Page 3/3 © Copyright Siemens

You might also like