Mark-Bro 36-En Ulti - r32

The ULTI+ R32 is a modular rooftop heat pump from ETT's Green Line ULTIMA range, designed for optimal performance, energy savings, and environmental compliance. It features customizable capacity, eco-friendly R32 refrigerant, and meets EU ecodesign regulations for energy-related products. The unit is built with recyclable materials and offers various configurations for installation, ensuring flexibility and ease of maintenance.

Uploaded by

diegokalume
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
334 views75 pages

Mark-Bro 36-En Ulti - r32

The ULTI+ R32 is a modular rooftop heat pump from ETT's Green Line ULTIMA range, designed for optimal performance, energy savings, and environmental compliance. It features customizable capacity, eco-friendly R32 refrigerant, and meets EU ecodesign regulations for energy-related products. The unit is built with recyclable materials and offers various configurations for installation, ensuring flexibility and ease of maintenance.

Uploaded by

diegokalume
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

ENVIRONMENTAL

CLIMATE CONTROL
EQUIPMENT & SOLUTIONS

ULTI+ R32

Single flow heat pump

[Link]
ULTI+ R32: A unit from the Green Line ULTIMA range

The ULTIMA Green Line is ETT's new modular rooftop range of the latest generation. It combines quality materials,
performance, energy savings, acoustics, regulation and new generation connected components allowing the units
to operate constantly in an optimal way.
An unrivalled depth of range (flow rates/powers) that perfectly meets the weight and space constraints for existing
units to be replaced.

Its modular design allows you to adapt unit capacity to your needs. You may choose to install the standard ULTI+ R32
heat pump, or to customise the packaged unit with additional modules (condensing boiler(s), extraction module,
extraction module with rotary heat exchanger) to adapt unit performance to the environment and requirements of
your application.

ULTI+ R32

ULTI+ R32 EX ULTI+ R32 DESHU ULTI+ R32 DX


ULTI+ R32 CC+ Extraction and recovery
Extraction module Condensing boilers module module with or without
in-line condenser module

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

2
ULTI+ R32: ErP Ready Rooftop

When they adopted the KYOTO protocol, the Member States of the European Union (EU) voted a set of measures known
as the “energy-climate package”, aiming at:
9 reducing greenhouse gas emissions by 20%;
9 reducing energy consumption by 20%;
9 increasing the proportion of renewable energies to 20% of the final energy consumption.

Directive 2009/125/EC on the ecodesign of ErPs (Energy related Products)


has been adopted to achieve these objectives.
This directive applies to all products using energy or having an impact on energy consumption. It includes a “bunch of
regulations” that sets performance requirements for each type of product. Regulation (EU) 2016/2281 on cooling products,
high temperature process chillers and fan coil units.
• 1 January 2021

From 1st of January 2018


rooftops failing to comply with ErP
Regulation (EU) 2281/2016 may no longer
be marketed in Europe.

st
Regulatory impacts from 1 of January 2018
The European Parliament compels rooftop manufacturers to comply with Regulation (EU) 2281/2016 on ErPs, in order to give
the users the possibility to evaluate their energy consumption.
This regulation defines the Ecodesign minimum requirements and sets a new rating method for rooftop energy efficiency:
the seasonal efficiency.
This new measure gives a more realistic indication of the energy efficiency and environmental impact of any heating or
cooling system.

Seasonal efficiency to be reached according to ErP 2018 and ErP 2021.


SCOP
Seasonal Coefficient of Performance
SCOP corresponds to the ratio between the annual demand
in heating for the reference climate and the annual electricity
138 % 125 % consumption for heating.
SEER: 03.53 SCOP: 03.20
SCOP
ηs,h = - 3%
117 % 115 % 2.5
SEER: 03.00 SCOP: 2.95 SEER
Seasonal efficiency
ηs,c ηs,h SEER corresponds to the ratio between the annual demand in
cooling for the reference climate and the annual electricity
consumption for cooling.
ErP 2018 ErP 2021 ηs,c =
SEER
- 3%
2.5

2.5: Conversion coefficient to the primary energy


A summary sheet stating rated
capacity & seasonal efficiency is 3 %: Control-related factor
available on request.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

3
CONTENTS

ENERGIE ■

Unit description..................................................................................................................................................
Operating principles ......................................................................................................................................
6
9
TRANSFERT ■ Detailed components .................................................................................................................................. 10
THERMIQUE ■ Operational advice ....................................................................................................................................... 15
■ Main options ....................................................................................................................................................... 16

Technical features
■ Ulti+ R32 01 .......................................................................................................................................................... 18
■ Ulti+ R32 11 .......................................................................................................................................................... 25
■ Ulti+ R32 12 .......................................................................................................................................................... 32
■ Ulti+ R32 21 .......................................................................................................................................................... 39
■ Ulti+ R32 22 .......................................................................................................................................................... 46
■ Ulti+ R32 23 .......................................................................................................................................................... 53

Dimensions and connections


■ Ulti+ R32 01 .......................................................................................................................................................... 19
■ Ulti+ R32 11 .......................................................................................................................................................... 26
■ Ulti+ R32 12 .......................................................................................................................................................... 33
■ Ulti+ R32 21 .......................................................................................................................................................... 40
■ Ulti+ R32 22 .......................................................................................................................................................... 47
■ Ulti+ R32 23 .......................................................................................................................................................... 54

Auxiliary: Hot water coils


■ Ulti+ R32 01 .......................................................................................................................................................... 23
■ Ulti+ R32 11 .......................................................................................................................................................... 30
■ Ulti+ R32 12 .......................................................................................................................................................... 37
■ Ulti+ R32 21 .......................................................................................................................................................... 44
■ Ulti+ R32 22 .......................................................................................................................................................... 51
■ Ulti+ R32 23 .......................................................................................................................................................... 58

Auxiliary: Sequential electric heaters


■ Sequential electric heaters ....................................................................................................................... 63

Preheating: Hot water coils


■ Ulti+ R32 01 .......................................................................................................................................................... 24
■ Ulti+ R32 11 .......................................................................................................................................................... 31
■ Ulti+ R32 12 .......................................................................................................................................................... 38
■ Ulti+ R32 21 .......................................................................................................................................................... 45
■ Ulti+ R32 22 .......................................................................................................................................................... 52
■ Ulti+ R32 23 .......................................................................................................................................................... 59

Arrangements
■ Arrangements .................................................................................................................................................... 60

Options weight
■ Options weight .................................................................................................................................................. 64

ULTI+ R32 dehumidification version


■ With heat recovery through in-line condenser ........................................................................... 65

Gravity dampers option


■ Pressure relief gravity dampers ............................................................................................................... 68

Sound level
■ Outside sound power level dB(A) ......................................................................................................... 69

Probes connection scheme


■ Probes connection scheme ..................................................................................................................... 70

Roof curbs & feet


■ Adjustable connection roof curb ......................................................................................................... 72
■ Adjustable ventilated roof curb ............................................................................................................. 73
■ Feet ........................................................................................................................................................................... 75

ULTI+ R32
MARK-BRO_36-EN_A

4
General description

The ETT packaged unit is delivered ready to operate. Its full aluminium structure (frame & casing) ensures an excellent
corrosion protection (20-year anti-corrosion guarantee). The ETT unit can be installed either at ground level or on a
roof.
ECO-DESIGN fosters DISCONSTRUCTION: the recyclability of ETT units is 98% (Reuse and recycling rate based on ULTI+
R32 21).

Environmental impact:
The Ultima Green Line is eco-responsible and uses R32, a refrigerant with a low environmental impact :
9 Zero ozone depletion (ODP)
9 Global Warming Potential (GWP) of 675

Our technical choices have several impacts on the environment

• Legal and regulatory framework: • Consumables: efficient waste management:


- In accordance with Directive 2008/98/EU on - Filtration: ETT units include "ecodesign" air filters (selective
waste, clause 26: "The polluter-pays principle sorting frame - grille - media)
is a guiding principle at European and • Low polluting ETT manufacturing process:
international levels. The waste producer and - Selective sorting, waste recovery, 80% of waste is
the waste holder should manage the waste in a recycled.
way that guarantees a high level of protection - No paint on casings, no use of solvent.
of the environment and human health.", ETT is • ETT Certifications
a member of "Ecologic” for France. - ISO 14001 Certification (Environmental
- In accordance with articles 5.3, 5.4 and 11 of Regulation Management System).
(EC) No 303/2008, ETT holds a certificate of capability to - Iso 9001 Certification our Quality
handle refrigerants (no. 637). organisation is the subject of the AFAQ
• Aluminium: a good choice for the planet! Certificate n° 1994/2016f. Each unit is ISO 9001
- Aluminium is endlessly 100% recyclable. checked and tested at the factory, prior to
- Recycling covers over 30% of aluminium needs. shipment, and a test certificate is issued.

- RCS Evaluation: quality of the CSR


management system - Corporate Social
Responsibility

Op
We placed ease of operation at the heart of our units design:
• The separate technical section facilitates unit control and maintenance and allows measurement and adjustment
during operation.
• The BEST controller is specifically designed for this application. It allows great flexibility, thus optimum performance of
the ETT unit through a user-friendly interface, be it local or remote (with remote display, PC or BMS).

Moreover, each unit is delivered with an EC certificate of conformity and complies with
the standards listed below:

• Machinery Directive 2006/42/EC - Operator's safety of machines


• Low Voltage Directive (LVD) 2014/35/EU • EN 378-2: 2017 – Safety and environmental
• Electromagnetic Compatibility (EMC) Directive requirements
2014/30/EU • Pressure Equipment Directive (PED) 2014/68/EU
• Gas Appliances Directive (GAD) 2009/142/EC (sections 2.10, 2.11, 3.4, 5a and 5d of Annex I)
• EN 60204-1 - Safety of machinery – Electrical equipment • EcoDesign regulations (EU) 2281/2016 on ErPs

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

5
Unit description

Aluminium frame and casing


Optimised tightness and thermal insulation.
Reduced weight, for new and renovation projects.
Numerous available arrangements. Propeller fans
Variable-speed propeller fans, communicating, with
20-Year anti-corrosion guarantee.
bionic blade design, electronically commutated (EC)
motor, optimum performance and low acoustic level.
Ecodesign filtration
Low pressure drop.
Fouling analogue control.
Options ISO Coarse 65% (G4) rechargeable, ISO
ePM10 50% (M5), ISO Coarse 65% (G4)+ISO ePM1 Sealed electrical box
55% (F7), ISO Coarse 65% (G4)+ISO ePM1 80%(F9), Separate electrical board in IP44
ISO ePM1 55% (F7), ISO ePM1 80%(F9). waterproof housing for greater safety.

Connected
components
Optimal machine operation.
Can be connected to the
myETTvision communication
platform

myETTvision

New generation controller with display


Thermal exchangers Control enabling optimum operation in all conditions.
ptimised exchangers for better energy efficiency.
Vinyl option available.

Multi-stage circuit with new generation R32


Internal fans compressors
Variable speed fans Optimum performance whatever the part load.
Electronic expansion valves.
with flow rate measure
Analogue air flow controller (AFC),
communicating, direct transmission,
electronically commutated (EC) motor, Leak detector
optimum performance and low acoustic level. Reduces the frequency of
periodic visits to your equipment.
Low Noise option available.
AFC option available
with flow rate auto-adjustment.

* ErP (Energy related Product) 2021 Ready: the Green Line Ultima range complies with the ecodesign requirements for air
heating products, cooling products (EU Regulation 2016/2281).

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

6
Unit description
tion

Energy QUALITY Accessibility


savings Premium components and and flexibility
processes ■ Technical compartment
The Green Line ULTIMA
MA range is
allowing quick and easy access
an efficient, economical and ■ Sustainable and recyclable
to the air veins.
environmentally friendly solution equipment: Aluminum body and
frame, 100% recyclable, 20-year ■ Free and easy access to the
for buildings heating and air
anti-corrosion guarantee filters by removable panels.
conditioning.
■ Non-polluting process ■ Components easily accessible
The ULTI+ R32 is designed to ■ Eco design approach to for maintenance.
offerr precise control as well as combine economy and optimum
optimum and continuous energy performance (SEER, SCOP) ■ Wide choice of powers to
efficiency during all its operating ■ adapt to the needs of each
Very easy replacement of existing
years. project
units; identical existing roofcurbs
■ Numerous possible
■ Reduced unit dimensions and arrangements to meet the
weight installation requirements of
every project

Connected components R32 refrigerant


New Generation Controller With low GWP
■ Enabling unit communication ■ New ULTIMA Green Line with R32, low GWP
■ Sending technical data from the units to an (675) fluid.
external server to allow optimum remote control ■ Actively participates in compliance with the CO2
with myETTvision equivalent tonnage quota, a legal obligation
imposed on the gas producer/importer.
■ Helps to minimize the impact on the greenhouse
effect.

ETT goes the extra mile...

Inside air Acoustic Installation


quality performance Outdoor, on the rooftop or at ground
level.
■ Ecodesign filtration MAIN FEATURES

ETT services
Optimised casing with high ■ New generation variable-
■ 5-year guarantee as standard
performance tightness level speed propellers and fans
■ ■ A team to guide you from
CO2 probe to control fresh air ■ Control system adjusting commissioning to operational support
supply
rotation speed to power stages ■ Manufacturer visits and audits
■ Quick and easy filter
replacement Because environmental noise
■ Installation optimisation and retrofit
■ Service contracts
reduction is essential, our
■ Staff training
standard self-contained units
are designed to meet your ■ Access to the ETT Services hotline
acoustic requirements. myETTvision platform
myETTvision lets you control and
optimise your installation, remotely.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

7
Unit description

A WIDE RANGE
Flow rates (m3/h)

5,000 7,500 10,000 12,500 15,000 17,500 20,000


Unit Capacity
ULTI+ R32 01-040 35
ULTI+ R32 01-045 40
ULTI+ R32 01-050 43

ULTI+ R32 11-040 38


ULTI+ R32 11-045 43
ULTI+ R32 11-050 46
ULTI+ R32 11-055 52
ULTI+ R32 11-065 60
ULTI+ R32 11-075 67

ULTI+ R32 12-050 49


ULTI+ R32 12-055 55
ULTI+ R32 12-065 63
ULTI+ R32 12-075 70
ULTI+ R32 12-080 78
ULTI+ R32 12-090 87
ULTI+ R32 12-100 92

Flow rates (m3/h)

Unit Capacity 12,000 15,000 20,000 25,000 30,000 35,000 40,000 45,000 50,000 54,000
ULTI+ R32 21-090 84
ULTI+ R32 21-095 90
ULTI+ R32 21-110 102
ULTI+ R32 21-115 115
ULTI+ R32 21-130 122
ULTI+ R32 21-140 132

ULTI+ R32 22-115 109


ULTI+ R32 22-130 124
ULTI+ R32 22-140 132
ULTI+ R32 22-150 144
ULTI+ R32 22-160 161
ULTI+ R32 22-180 177
ULTI+ R32 22-200 190

ULTI+ R32 23-180 168


ULTI+ R32 23-200 190
ULTI+ R32 23-220 211
ULTI+ R32 23-245 232
ULTI+ R32 23-270 254
ULTI+ R32 23-285 273

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

8
Operating principles

The unit operates as a reversible The following operating modes In these modes, the unit can operate:
heat pump: are available: > With all recirculated air
> Source: outside air > Heat pump > With all fresh air
> Treated fluid: inside air > Air conditioner > With mixed-air
> Free Cooling: free cooling
through outside air, without
thermodynamics

Heating mode

Heating mode: In winter, comfort temperature


is maintained thanks to the thermodynamic
system and auxiliary heaters (optional).

Cooling mode

Cooling mode: In summer, comfort temperature


is maintained thanks to the thermodynamic
system.

Free Cooling mode

Free Cooling mode: In mid-season, comfort


temperature is maintained using in priority the
difference between outside air and inside air to
cool the building.
Free Cooling allows considerable savings by
delaying the start of the thermodynamic system.

Recycling mode

Recycling mode: Destratification through air


recirculation, when return air temperature is
significantly higher than room temperature, in
winter.

1 Fresh air 2 Return air 3 Supply air

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

9
Detailed components

The ETT packaged unit comprises 4


different sections:

3 1 The external section allows thermal


exchanges with the environment.
4 2
1 The separate technical section houses the
refrigeration components and the control
components.

2
3 The internal section ensures air change and
air treatment.

4 A watertight electrical compartment (IP44).

Aluminium frame and casing:


■ Motorised, aluminium, low pressure drop 2-damper mixing box with class 3 upstream/downstream airtightness and class
B frame airtightness (according to EN1751), the ULTI+ R32 offers:
9 Optimum fresh air supply proportions, thanks to the CO2 probe.
9 Free Cooling mode switch to delay thermodynamic circuit operation and allow significant energy savings.
9 Perfect weather resistance, 20-year anti corrosion guarantee on casing.
■ Watertight floor with drainage outlets around the unit, connected to rubber siphons.
■ Aluminium vertical panels and roof, mounted on aluminium frame.
■ Access through large removable panels. Doors tightness is ensured by a flexible gasket under compression, providing
ideal sealing day after day.
■ Acoustic and thermal insulation using 80 to 100 mm M0 rock wool on frame and 50 mm M0 glass wool on panels and
roof, in accordance with French Public Access Buildings regulations (Article CH36).
■ Optional rain hood on fresh air (to be installed by the installer).

Air assembly:
■ Eco-design filtration, easily removable - ISO Coarse 65% efficiency (G4) in 98 mm pleated media to increase filter life and
reduce pressure drop, clogging controlled by analog pressure switch.
■ Different filtration levels available according to project and requirements : ISO Coarse 65% rechargeable (G4) 98mm,
ISO ePM10 50% (M5) 98mm, ISO Coarse 65% (G4) + ISO ePM1 55% (F7) 48+48mm, ISO ePM1 55% (F7) 98mm, ISO Coarse
65% (G4) + ISO ePM1 80% (F9) 48+48mm, ISO ePM1 80% (F9) 98mm.
■ Replacement filter kit available as an option
■ Propeller fans (High Energy Performance)
Pioneer, ETT has opted for last generation fans:
9 With their new design and electronically commutated “EC”, variable-speed motor, these fans allow an air flow rate
increase of up to 15 %, while keeping the same absorbed power. These "EC" fans ensure a precise temperature for
better comfort and energy savings by adapting their rotation speed to real needs.
9 Innovative blade design resulting in lower compressors consumption thanks to lower HP and higher LP in the different
operating modes.
9 Communicating for real time operation adjustment.
9 Increased diameter for optimum performance and low acoustic level: unprecedented values.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

10
Detailed components

■ Last generation internal fans (High Energy Performance):


9 Direct transmission (gain on maintenance, reliability and consumption).
9 Electronically commutated (EC) variable-speed motor, with analogue air flow controller (AFC) flow rate measurement
(gain on commissioning).
9 With an aluminium wheel design,
9 Communicating for real time operation adjustment.
9 Integrated Soft Starter system for reduced starting current and soft start (textile ducting).

■ Low Noise option available.


■ AFC option with flow rate auto-adjustment, for filter fouling compensation.
■ VDP option (power/flow rate variation) for energy consumption reduction.

Energy and thermodynamic assembly:


■ New generation multi-stage compressors to allow adjustment of compressors capacity to application requirements, for
less consumption and more comfort.
■ Communicating electronic expansion valves combining increased optimisation of the exchangers and fast stabilisation
of the thermodynamic system.
■ Reinforced thermal exchangers made with aluminium fins and copper pipes with double helical grooving for better
thermal exchange. External exchangers designed for delayed frosting and quick and efficient defrosting.
Vinyl coating available on request.
■ Refrigeration circuits compliant with the European directive on pressure equipment (PED 2014/68/EU).
■ R32 refrigerant.
■ Tandem circuits to stage the supplied power and save energy during operation in part load. Operation in part load
considerably reduces the number of defrost cycles and their duration.
■ The refrigeration circuit is fitted with isolation valves at the terminals of the compressor unit. During an intervention on
the compressor group, these isolation valves make it possible to facilitate repair and maintenance of the refrigeration
circuit.
■ Independent refrigeration circuit: each refrigeration circuit has a propeller fan to ventilate the exchanger.
■ Anti-acid filter drier.
■ Cycle reversal valve.
■ Optimised defrosting thanks to the new design of the external section (optimised for ecodesign).
■ Leak detection: The ULTI+ R32 is equipped with a leak detector in standard version. This detector allows to put the unit in
safety stop in case of leakage of R32.
The leak detection also reduces the frequency of periodic visits to your equipment.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

11
Detailed components

Optimised defrosting:

Defrosting principle:
9 The condensation of humidity produces frost on the coil.
9 The concerned propeller fan stops operating (simultaneous defrosting
cycles are banned).
9 The refrigeration system 4-way valve reverses: during defrosting, the coil
operates as a condenser.
9 The coil is dried.
9 The other refrigeration circuit continues to operate normally.

Electrical assembly in a sealed compartment (IP44) :


■ Electrical board compliant with French standards NF EN C 15-100 and NF EN 60204-01, including:
9 An ETT controller with an optional Touch Screen remote display or by native modbus BMS.
9 Power switch with lockable external handle for full load cut-off. Connection using standard universal cable. Optional
copper/aluminium connection boxes.
9 400-230-24 volts transformer for regulation and control circuits.
9 Fault synthesis with pending dry contact on terminal.
9 Numbered terminal blocks with disconnecting terminals for remote controls and transfers.
9 Terminal block for compressors load shedding.
9 Internal wiring with numbered ferrules at both extremities
9 Ik3 breaking capacity of basis 10 kA.
9 All components protected by circuit breakers.
9 PHASE CHECKER
9 The LV distribution rated voltage is regulated by French standards dated 2007/12/24, i.e. rated voltage of 230/400V.
French standards also set minimum and maximum acceptable values at the user supply point (10 lm average values)
within a -10 %/+10 % range from rated values They also define the maximum acceptable value of the voltage drop
gradient to 2 %. The voltage drop gradient represents the additional voltage drop created on a network point if 1 kW
single-phase is added on this point.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

12
Detailed components

Advanced control assembly:


■ Temperature control with 2 setpoints for Cooling/Heating mode according to 2002/91/EC Directive: reactivity, accuracy
and anticipation.
Economy mode or Comfort mode controls available.
■ Filters fouling analogue control (FFAC), fouling measurement and indication on the controller enabling preventive filter
replacement for optimum air quality and reduced consumption.
■ Real time control of propeller fan rotation speed depending on operating mode, outside temperature and thermodynamic
capacity, for optimum acoustic performance and energy savings.
■ VDP function (power/flow rate variation), as an option, to allow inside air flow rate adjustment according to thermodynamic
capacity.
■ Analogue air flow controller (AFC) to measure and display supply air fans flow rate on the controller, with optional flow
rate auto-adjustment for filter fouling compensation.
■ Air quality control with CO2 probe to optimise fresh air quantities and reduce energy consumption.
■ Free Cooling function: cooling with outside air, delaying thermodynamic operation for significant energy savings.
■ Free Cooling banning function, as an option, to reduce latent contribution in Free Cooling phase using inside and
outside specific humidity comparison.
■ Indoor humidity control, optional, with or without energy recovery.
■ Year-round kit function, as an option, for Cooling mode operation at outside temperatures lower than 15°C.
■ Electrical energy metering, with distribution of power consumption according to operating modes.
■ Monitoring, diagnostic and security and fault management (freezestat, smoke detector, fire thermostat, HP switch,
compressor MAP monitoring…), with written fault history.
■ Refrigerant leak detection aid.
■ myETTvision remote communication platform allowing access to parameter setting, operation and energy monitoring,
access to the faults of your machine park.
■ Destratification (comparison between room temperature and outside temperature)

myETTvision:
ETT remote communication platform :

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

13
ULTI+ R32 operational advice

OPERATION: COST, PERFORMANCE AND GUARANTEE


Equipment installation and optimisation have a major impact on units total cost.
They affect 3 levers:
■ Total cost
Energy use
9 Purchase and installation costs (20 to 25%)
9 Operating and maintenance costs (75 to 80%) Assistance costs
Conformity
■ Installation efficiency Operation and
9 Operating cost maintenance
9 Users’ comfort Installation
Maintained
9 Durability and building
performance
9 Availability durability
Users comfort
■ Conformity
9 Regulations
9 Manufacturer’s guarantee

Equipment operation and maintenance must ensure regulatory compliance, starting with commissioning. Operating
instructions aim at optimising unit performance and settings. Also, the validity of the guarantee is conditional upon strict
compliance with these instructions.

Periodic checks must include, at least:


■ Technical features control and setting (safety devices, ventilation, refrigeration circuits, etc.)
■ Control adjustment (setpoints, operating schedule, advanced parameters, etc.)
■ Technical and regulatory checks:
• Leakage checking, once or twice a year
• Commissioning, periodic checks and periodic requalification (pressure
equipment monitoring)
• Filters replacement, 2 to 4 times a year depending on the type of filters and
installation environment
• Sensor element control and replacement for humidity probes, CO2 probes
and smoke detectors
■ Related equipment control and maintenance (diffusion networks, probes
condition, etc.)

ETT services allow trouble-free operation of your equipment and guarantee optimum performance and regulatory
compliance of the installation.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

14
Main options

Frame - Casing ■ Aluminium double skin in internal section


■ Motorised external damper for supply air, except downwards (2006/42/EC Directive)

Acoustics ■ Low Noise EC supply air fans


■ Compressors acoustic jackets

Air handling ■ Operation with all recirculated air (excluding Public Buildings)
■ Operation with all fresh air
■ Actuating smoke detector with battery back-up
■ Epoxy coating for supply air fans
■ Analogue air flow controller (AFC) with supply air fans flow rate auto-adjustment
■ Pressure gauge for supply air filters
■ ISO Coarse 65% (G4) refillable 98mm ISO Coarse 65% (G4) filters with analogue sensor
■ ISO ePM10 50% (M5) 98mm supply air filters with analogue probe
■ Double filters ISO Coarse 65% (G4) + ISO ePM1 55% (F7) or ISO ePM1 80% (F9) (48 + 48mm) on
supply with analog probe
■ ISO ePM1 55% (F7) 98mm supply air filters with analogue probe
■ ISO ePM1 80% (F9) 98mm supply air filters with analogue probe
■ Pressure relief gravity damper
■ Defrost damper
■ Cowl for pressure relief gravity damper
■ Fresh air cowl extension

Thermodynamics ■ Cooling only operating mode (non-reversible unit)


■ Compressor MAP monitoring
■ Vinyl coating on thermodynamic coils
■ Refrigerant leak detection aid
■ HP and LP pressure gauge

Auxiliaries ■ Recovery hot water coil with analogue frost protection thermostat
■ Auxiliary hot water coil with analogue frost protection thermostat
■ Progressive 3-way valve for hot water coil
■ Stop valve on outlet + TA regulating valve on inlet for hot water coil
■ Auxiliary 2-sequential stage electric heaters + Load shedding using dry contact
■ Fresh air preheating through auxiliary 3-stage electric heaters

Electricity ■ Total electrical energy metering according to 2002/91/EC


■ Aluminium/Copper connection terminal blocks (Mandatory for aluminium supply all cable)
■ 230V/16 A single-phase socket in the technical section (separate power supply to be provided
by the installer)
■ IT earthing system compatibility
■ Cable protective cowl for outside power supply (to be mounted by the installer)

Installation ■ Aluminium adjustable connection roof curb


■ Aluminium adaptation connection roof curb
■ Aluminium adjustable ventilated roof curb
■ Aluminium ventilated adaptation roof curb
■ 200, 400 or 600 mm aluminium feet

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

15
Main options

Control ■ Operation in year-round mode (compressor authorisation in Cooling mode with outside
temp. < +15°C)
■ Control function in Comfort mode (setpoint temperatures control by PID)
■ Free Cooling banning based on specific humidity comparison
■ VDP operation (power/flow rate variation)
■ HPE+ operation (High Energy Performance)
■ Dehumidification function level 1 (without heating capacity recovery)
■ Dehumidification function level 2 (with heating capacity recovery & on/off refrigerating 3WV)
■ Average room temperature (4 probes)
■ Minimum fresh air slaving using turret contacts (3 maximum)

Communication ■ myETTvision
■ ETT TouchScreen remote display
■ CCAD remote display
■ Native Modbus RS485
■ Modbus IP
■ BacNet IP
■ LonWorks

Guarantee ■ 6 to 10 years guarantee expansion

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

16
Technical features ULTI+ R32 01

DESCRIPTION Unit 040 045 050


FLOW RATES
Rated air flow rate m3/h 7,500 8,500 8,500
VENTILATION

Minimum air flow rate m3/h 5,500 7,000 8,000


Maximum air flow rate m3/h 8,500 8,500 8,500
ACOUSTICS (Eurovent certified) (1)

Sound power level on supply air dB(A) 76 79 78


Outside sound power level dB(A) 69 77 80
Resultant outdoor sound pressure at 10m ref. 2*10-5 in free field,
dB(A) 41 49 52
direction 2
RATED PERFORMANCES AT +35°C (Eurovent certified) (1)
Net cooling capacity kW 35.1 40.1 43.1
PERFORMANCES

Net EER kW/kW 3.03 3.02 3.01


COOLING

Eurovent class E…A A A A


SEASONAL EFFICIENCY (2)
Design net cooling capacity kW 35.1 40.1 43.1
SEER kW/kW 4.96 4.82 4.58
ηs,C % 195 190 180
RATED PERFORMANCES AT +7°C (Eurovent certified) (1)

Net heating capacity kW 37.1 42.5 46.4


Net COP kW/kW 4.08 3.93 3.81
PERFORMANCES

Eurovent class E…A A A A


RATED PERFORMANCES AT -7°C
HEATING

(3)

Net heating capacity kW 25.7 29.0 32.7


Net COP kW/kW 3.22 3.13 3.08
SEASONAL EFFICIENCY (2)
Design net heating capacity kW 33.1 37.2 40.8
SCOP kW/kW 4.07 3.94 3.90
ηs,H % 160 155 153
ELECTRICAL DATA
Total installed electrical power (5) kW 18.7 22.1 23.5
Total installed electrical intensity (5) A 30.3 35.6 37.9
Starting current A 94.1 123.7 124.8
Maximum absorbed electrical power (5) kW 13.4 15.2 16.3
REFRIGERATION CIRCUIT(S)
Power stages - 2 2 2
OPERATING LIMITS IN COOLING MODE
GENERAL

Maximum outside temperature(6) °C +49 +51 + 50


Minimum outside temperature (6) °C + 15
Minimum internal coil inlet temperature °C +18
OPERATING LIMITS IN HEATING MODE
Minimum outside temperature °C - 15
Minimum internal coil inlet temperature °C + 12
WEIGHT
Unit weight without options (7) kg 521 532 535
Connection roof curb weight kg 73
Standard ventilated roof curb weight kg 102

(1) According to EN 14511. (5) Cooling mode: Inside conditions: +27°C DB/+19°C WB and outside
Cooling mode: Inside conditions: +27°C DB/+19°C WB and outside conditions: +35°C DB/24°C WB. conditions: +35°C DB/24°C WB. Rated air flow rate, 400Pa available
Heating mode: Inside conditions: +20°C DB/+12°C WB and outside conditions: +7°C DB/+6°C WB. pressure on return + supply air & fouled ISO Coarse 65% filters
(2) According to EcoDesign regulations 2016/2281. (6) For indoor conditions: +27°C DB / +19°C WB at rated air flow rate.
(3) According to EN 14511. (7) Weight for an available pressure of 400 Pa.
Heating mode: Inside conditions: +20°C DB and outside conditions: -7°C DB/-8°C WB.
(4) Power to be used for power cables selection.
400V/50 Hz 3-phase power supply + earth without neutral.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

17
Dimensions and connections ULTI+ R32 01

SUPPLY AIR below


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 50

Detail A

1 Fresh air
2 Return air
3 Supply air
Power supply Length Width (1) Height
A Access Casing dimensions 3,304 mm 1,304 mm 1,435 mm
C Technical section

--- Provide 400 mm clearance (minimum)


to allow air passage below the unit. (1) Return air on side: +125 mm

Nota: Fresh air cowls shall be fitted by the installer.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

18
Dimensions and connections ULTI+ R32 01

SUPPLY AIR on top


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 50

Detail A

1 Fresh air
2 Return air
3 Supply air Length Width (1) Height
Power supply Casing dimensions 3,304 mm 1,304 mm 1,435 mm
A Access
C Technical section
--- Provide 400 mm clearance (minimum)
to allow air passage below the unit.
(1) Return air on side: +125 mm

Nota: Fresh air cowls shall be fitted by the installer.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

19
Dimensions and connections ULTI+ R32 01

SUPPLY AIR below, return air on end


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 50
Detail A

1 Fresh air
2 Return air
Length Width (1) Height
3 Supply air
Power supply Casing dimensions 3,304 mm 1,304 mm 1,435 mm
A Access
C Technical section
--- Provide 400 mm clearance (minimum)
to allow air passage below the unit.
(1) Return air on side: +125 mm

Nota: Fresh air cowls shall be fitted by the installer.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

20
Dimensions and connections ULTI+ R32 01

SUPPLY AIR on side


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 50
Detail A

1 Fresh air
2 Return air
3 Supply air Length Width (1) Height
Power supply
Casing dimensions 3,304 mm 1,304 mm 1,435 mm
A Access
C Technical section
--- Provide 400 mm clearance (minimum)
to allow air passage below the unit. (1) Return air on side: +125 mm

Nota: - Fresh air cowls shall be fitted by the installer.


- Lateral box shall be fitted by the installer.
- Supply air damper electrical connection shall be made by the installer.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

21
Auxiliary: Hot water coils ULTI+ R32 01

SCHEMATIC DIAGRAM AND CONNECTION


Top view Principle

Air
flow
way

Option

CAPACITIES
Unit 040 045 050

Heating capacity kW 104.9 113.2 113.2


90/70°C water regime
Water flow rate m /h
3
4.7 5.0 5.0
and
Exchanger pressure drop mWC 1.6 1.8 1.8
Exchanger inlet air temperature Exchanger and 3WV pressure drop (1) mWC 2.4 2.8 2.8
10°C
Exchanger, 3WV, SV and TAV pressure
mWC 3.2 3.8 3.8
drop (2)

Heating capacity kW 88.5 95.4 95.4


80/60°C water regime
Water flow rate m3/h 3.9 4.2 4.2
and
Exchanger pressure drop mWC 1.2 1.4 1.4
Exchanger inlet air temperature Exchanger and 3WV pressure drop (1) mWC 1.8 2.0 2.0
10°C
Exchanger, 3WV, SV and TAV pressure
mWC 2.4 2.7 2.7
drop (2)

Heating capacity kW 89.2 96.2 96.2


90/70°C water regime
Water flow rate m3/h 3.9 4.2 4.2
and
Exchanger pressure drop mWC 1.2 1.4 1.4
Exchanger inlet air temperature Exchanger and 3WV pressure drop (1) mWC 1.8 2.0 2.0
20°C
Exchanger, 3WV, SV and TAV pressure
mWC 2.4 2.7 2.7
drop (2)

Heating capacity kW 72.8 78.4 78.4


80/60°C water regime
Water flow rate m /h
3
3.2 3.5 3.5
and
Exchanger pressure drop mWC 0.8 0.9 0.9
Exchanger inlet air temperature Exchanger and 3WV pressure drop (1) mWC 1.2 1.4 1.4
20°C
Exchanger, 3WV, SV and TAV pressure
mWC 1.6 1.9 1.9
drop (2)
(1) With 3WV option
(2) With 3WV, SV and TAV option
3WV: 3-way valve
SV: Stop valve on outlet
TAV: TA regulating valve on inlet, opened 7/8
Technical data for non-glycol water, at rated air flow rate.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

22
Preheating: Hot water coils ULTI+ R32 01

SCHEMATIC DIAGRAM AND CONNECTION


► Connection opposite the technical section

Top view Side view

► Same connection as the hot water coil


See schematic diagram and connection.

CAPACITIES
Unit 040 045 050
Heating capacity kW 32.9 35.5 35.5
35/30°C water regime
Water flow rate m3/h 5.7 6.2 6.2
and
Exchanger pressure drop mWC 2.6 3.0 3.0
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 3.9 4.5 4.5
temperature 10°C
Exchanger, 3WV, SV and TAV
mWC 5.2 6.0 6.0
pressure drop (2)

Heating capacity kW 17.3 18.6 18.6


35/30°C water regime Water flow rate 3
m /h 3.0 3.2 3.2
and Exchanger pressure drop mWC 0.8 0.9 0.9
Exchanger inlet air Exchanger and 3WV pressure drop (1)
mWC 1.2 1.3 1.3
temperature 20°C
Exchanger, 3WV, SV and TAV
mWC 1.5 1.7 1.7
pressure drop (2)

(1) With 3WV option


(2) With 3WV, SV and TAV option

3WV: 3-way valve


SV: Stop valve on outlet
TAV: TA regulating valve on inlet, opened 7/8
Technical data for non-glycol water, at rated air flow rate.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

23
Technical features ULTI+ R32 11

DESCRIPTION Unit 040 045 050 055 065 075


FLOW RATES
Rated air flow rate m3/h 8,500 9,500 10,500 11,500 13,000 15,000
VENTILATION

Minimum air flow rate m3/h 5,000 6,000 6,500 7,500 9,500 12,500
Maximum air flow rate m3/h 15,000 15,000 15,000 15,000 15,000 15,000
ACOUSTICS (Eurovent certified) (1)

Sound power level on supply air dB(A) 76 75 78 79 82 87


Outside sound power level dB(A) 71 72 72 75 82 88
Resultant outdoor sound pressure at 10m ref. 2*10-5 in free field,
dB(A) 43 44 44 47 54 60
direction 2
RATED PERFORMANCES AT +35°C (Eurovent certified) (1)
Net cooling capacity kW 38.5 43.2 46.5 52.0 59.5 67.0
PERFORMANCES

Net EER kW/kW 3.55 3.40 3.31 3.24 3.17 3.13


COOLING

Eurovent class E…A A A A A A A


SEASONAL EFFICIENCY (2)
Design net cooling capacity kW 38.5 43.2 46.5 52.0 59.5 67.0
SEER kW/kW 5.46 5.31 4.79 4.71 4.60 4.71
ηs,C % 215 210 189 185 181 185
RATED PERFORMANCES AT +7°C (Eurovent certified) (1)

Net heating capacity kW 39.0 43.9 47.5 53.9 61.3 69.3


Net COP kW/kW 4.34 4.25 4.29 4.17 4.06 3.92
PERFORMANCES

Eurovent class E…A A A A A A A


RATED PERFORMANCES AT -7°C
HEATING

(3)

Net heating capacity kW 26.5 30.0 33.0 37.2 42.9 48.2


Net COP kW/kW 3.43 3.39 3.43 3.37 3.25 3.11
SEASONAL EFFICIENCY (2)
Design net heating capacity kW 37.6 40.0 42.7 47.5 54.0 60.9
SCOP kW/kW 4.47 4.33 4.28 4.18 3.99 3.82
ηs,H % 176 170 168 164 157 150
ELECTRICAL DATA
Total installed electrical power (4) kW 22.7 24.9 26.3 29.8 33.0 34.9
Total installed electrical intensity (4) A 36.5 39.9 42.2 48.0 53.3 55.2
Starting current A 100.3 128.0 129.1 159.9 173.6 172.5
Maximum absorbed electrical power (5) kW 13.2 15.3 16.8 19.0 22.0 24.9
REFRIGERATION CIRCUIT(S)
Power stages - 2 2 2 2 2 2
OPERATING LIMITS IN COOLING MODE
GENERAL

Maximum outside temperature(6) °C + 51 +50 + 49 + 51 + 50 + 48


Minimum outside temperature (6) °C + 15
Minimum internal coil inlet temperature °C + 18
OPERATING LIMITS IN HEATING MODE
Minimum outside temperature °C - 15
Minimum internal coil inlet temperature °C + 12
WEIGHT
Unit weight without options (7) kg 698 697 699 745 747 835
Connection roof curb weight kg 80
Standard ventilated roof curb weight kg 112

(1) According to EN 14511. (5) Cooling mode: Inside conditions: +27°C DB/+19°C WB and outside
Cooling mode: Inside conditions: +27°C DB/+19°C WB and outside conditions: +35°C DB/24°C WB. conditions: +35°C DB/24°C WB. Rated air flow rate, 400Pa available
Heating mode: Inside conditions: +20°C DB/+12°C WB and outside conditions: +7°C DB/+6°C WB. pressure on return + supply air & fouled ISO Coarse 65% filters
(2) According to EcoDesign regulations 2016/2281. (6) For indoor conditions: +27°C DB / +19°C WB at rated air flow rate.
(3) According to EN 14511. (7) Weight for an available pressure of 400 Pa.
Heating mode: Inside conditions: +20°C DB and outside conditions: -7°C DB/-8°C WB.
(4) Power to be used for power cables selection.
400V/50 Hz 3-phase power supply + earth without neutral.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

24
Dimensions and connections ULTI+ R32 11

SUPPLY AIR below


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 50

Detail A

1 Fresh air
2 Return air
Length Width (1) Height
3 Supply air
Power supply Casing dimensions 3,304 mm 1,684 mm 1,830 mm
A Access
C Technical section
--- Provide 400 mm clearance (minimum)
to allow air passage below the unit.
(1) Return air on side: +125 mm

Nota: Fresh air cowls shall be fitted by the installer.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

25
Dimensions and connections ULTI+ R32 11

SUPPLY AIR on top


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 50

Detail A

1 Fresh air
2 Return air
Length Width (1) Height
3 Supply air
Power supply Casing dimensions 3,304 mm 1,684 mm 1,830 mm
A Access
C Technical section
--- Provide 400 mm clearance (minimum)
to allow air passage below the unit.
(1) Return air on side: +125 mm

Nota: Fresh air cowls shall be fitted by the installer.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

26
Dimensions and connections ULTI+ R32 11

SUPPLY AIR below, return air on end


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 50

Detail A

1 Fresh air
2 Return air Length Width (1) Height
3 Supply air
Casing dimensions 3,304 mm 1,684 mm 1,830 mm
Power supply
A Access
C Technical section
--- Provide 400 mm clearance (minimum)
to allow air passage below the unit.
(1) Return air on side: +125 mm

Nota: Fresh air cowls shall be fitted by the installer.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

27
Dimensions and connections ULTI+ R32 11

SUPPLY AIR on side


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 50

Detail A

1 Fresh air
2 Return air
3 Supply air Length Width (1) Height
Power supply Casing dimensions 3,304 mm 1,684 mm 1,830 mm
A Access
C Technical section
--- Provide 400 mm clearance (minimum)
to allow air passage below the unit. (1) Return air on side: +125 mm

Nota: - Fresh air cowls shall be fitted by the installer.


- Lateral box shall be fitted by the installer.
- Supply air damper electrical connection shall be made by the installer.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

28
Auxiliary: Hot water coils ULTI+ R32 11

SCHEMATIC DIAGRAM AND CONNECTION


Top view Principle

Air
flow
way

Option

CAPACITIES
Unit 040 045 050 055 065 075
Heating capacity kW 142.2 153.2 163.7 173.6 187.7 205.1
90/70°C water regime Water flow rate m3/h 6.3 6.8 7.3 7.7 8.3 9.1
and Exchanger pressure drop mWC 2.1 2.4 2.7 3.0 3.5 4.1
Exchanger inlet air Exchanger and 3WV pressure drop (1)
mWC 3.6 4.1 4.7 5.2 6.1 7.2
temperature 10°C Exchanger, 3WV, SV and TAV
mWC 5.1 5.9 6.7 7.5 8.8 10.4
pressure drop (2)

Heating capacity kW 120.8 130.1 138.8 147.2 159.1 173.6


80/60°C water regime Water flow rate m /h
3
5.3 5.8 6.1 6.5 7.0 7.7
and Exchanger pressure drop mWC 1.6 1.8 2.0 2.2 2.6 3.0
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 2.6 3.0 3.4 3.8 4.5 5.3
temperature 10°C Exchanger, 3WV, SV and TAV
mWC 3.8 4.3 4.9 5.5 6.4 7.6
pressure drop (2)

Heating capacity kW 121.5 130.8 139.7 148.0 160.0 174.7


90/70°C water regime Water flow rate m3/h 5.4 5.8 6.2 6.6 7.1 7.7
and Exchanger pressure drop mWC 1.5 1.8 2.0 2.2 2.6 3.0
Exchanger inlet air Exchanger and 3WV pressure drop (1)
mWC 2.6 3.0 3.5 3.9 4.5 5.3
temperature 20°C Exchanger, 3WV, SV and TAV
mWC 3.8 4.4 4.9 5.5 6.4 7.6
pressure drop (2)

Heating capacity kW 100.1 107.7 114.8 121.6 131.3 143.1


80/60°C water regime Water flow rate m /h
3
4.4 4.8 5.1 5.4 5.8 6.3
and Exchanger pressure drop mWC 1.1 1.3 1.4 1.6 1.8 2.1
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 1.8 2.1 2.4 2.7 3.1 3.7
temperature 20°C Exchanger, 3WV, SV and TAV
mWC 2.6 3.0 3.4 3.8 4.4 5.2
pressure drop (2)

(1) With 3WV option


(2) With 3WV, SV and TAV option
3WV: 3-way valve
SV: Stop valve on outlet
TAV: TA regulating valve on inlet, opened 7/8
Technical data for non-glycol water, at rated air flow rate.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

29
Preheating: Hot water coils ULTI+ R32 11

SCHEMATIC DIAGRAM AND CONNECTION


► Connection opposite the technical section

Top view Side view

► Same connection as the hot water coil


See schematic diagram and connection.

CAPACITIES
Unit 040 045 050 055 065 075

Heating capacity kW 44.7 48.2 51.5 54.7 59.1 64.6


35/30°C water regime
Water flow rate m3/h 7.7 8.4 8.9 9.5 10.2 11.2
and
Exchanger pressure drop mWC 3.5 4.0 4.5 5.0 5.8 6.8
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 5.8 6.7 7.6 8.5 9.8 11.6
temperature 10°C
Exchanger, 3WV, SV and TAV
mWC 8.2 9.4 10.7 12.0 14.0 16.6
pressure drop (2)

Heating capacity kW 24.1 25.9 27.6 29.3 31.5 34.3


35/30°C water regime
Water flow rate m3/h 4.2 4.5 4.8 5.1 5.5 6.0
and
Exchanger pressure drop mWC 1.1 1.3 1.4 1.6 1.8 2.1
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 1.8 2.1 2.3 2.6 3.0 3.5
temperature 20°C
Exchanger, 3WV, SV and TAV
mWC 2.5 2.9 3.2 3.6 4.2 4.9
pressure drop (2)

(1) With 3WV option


(2) With 3WV, SV and TAV option

3WV: 3-way valve


SV: Stop valve on outlet
TAV: TA regulating valve on inlet, opened 7/8
Technical data for non-glycol water, at rated air flow rate.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

30
Technical features ULTI+ R32 12

DESCRIPTION Unit 050 055 065 075 080 090 100


FLOW RATES
Rated air flow rate m3/h 11,000 12,500 14,000 16,000 18,000 20,000 20,000
VENTILATION

Minimum air flow rate m3/h 6,000 7,000 8,000 11,000 13,000 16,000 19,000
Maximum air flow rate m3/h 20,000 20,000 20,000 20,000 20,000 20,000 20,000
ACOUSTICS (Eurovent certified) (1)

Sound power level on supply air dB(A) 74 76 77 80 83 86 86


Outside sound power level dB(A) 73 75 80 82 80 88 89
Resultant outdoor sound pressure at 10m ref. 2*10-5 in
dB(A) 45 47 52 54 52 60 61
free field, direction 2
RATED PERFORMANCES AT +35°C (Eurovent certified) (1)
kW
PERFORMANCES

Net cooling capacity 48.8 54.9 62.8 69.9 77.6 87.0 92.1
Net EER kW/kW 3.54 3.44 3.35 3.25 3.15 3.01 3.01
COOLING

Eurovent class E…A A A A A A A A


SEASONAL EFFICIENCY (2)
Design net cooling capacity kW 48.8 54.9 62.8 69.9 77.6 87.0 92.1
SEER kW/kW 5.31 5.03 4.91 4.99 4.81 4.96 4.47
ηs,C % 209 198 193 197 189 195 176
RATED PERFORMANCES AT +7°C (Eurovent certified) (1)

Net heating capacity kW 48.1 54.3 63.2 71.3 79.9 91.3 97.4
Net COP kW/kW 4.73 4.65 4.49 4.43 4.26 3.90 3.94
PERFORMANCES

Eurovent class E…A A A A A A A A


HEATING

RATED PERFORMANCES AT -7°C (3)


Net heating capacity kW 33.0 37.3 43.4 48.6 54.9 63.1 66.8
Net COP kW/kW 3.72 3.66 3.53 3.42 3.31 3.05 3.08
SEASONAL EFFICIENCY (2)
Design net heating capacity kW 44.0 48.0 55.5 62.3 69.6 79.0 83.5
SCOP kW/kW 4.68 4.50 4.34 4.34 4.05 3.90 3.73
ηs,H % 184 177 171 171 159 153 146
ELECTRICAL DATA
Total installed electrical power (4) kW 25.2 27.5 32.0 33.8 37.8 46.3 45.1
Total installed electrical intensity (4)
A 40.6 44.5 51.7 53.6 61.6 77.1 72.6
Starting current A 127.5 156.4 172.0 170.9 183.3 242.4 217.1
Maximum absorbed electrical power (5) kW 16.7 19.1 22.2 25.2 28.6 33.8 35.0
REFRIGERATION CIRCUIT(S)
Power stages - 2 2 2 2 2 2 2
OPERATING LIMITS IN COOLING MODE
GENERAL

Maximum outside temperature(6) °C + 50 + 48 +50 + 49 + 50 + 49 + 48


Minimum outside temperature (6) °C +15
Minimum internal coil inlet temperature °C +18
OPERATING LIMITS IN HEATING MODE
Minimum outside temperature °C - 15
Minimum internal coil inlet temperature °C + 12
WEIGHT
Unit weight without options (7) kg 865 886 907 960 988 964 1,001
Connection roof curb weight kg 104
Standard ventilated roof curb weight kg 146

(1) According to EN 14511. (5) Cooling mode: Inside conditions: +27°C DB/+19°C WB and outside
Cooling mode: Inside conditions: +27°C DB/+19°C WB and outside conditions: +35°C DB/24°C WB. conditions: +35°C DB/24°C WB. Rated air flow rate, 400Pa available
Heating mode: Inside conditions: +20°C DB/+12°C WB and outside conditions: +7°C DB/+6°C WB. pressure on return + supply air & fouled ISO Coarse 65% filters
(2) According to EcoDesign regulations 2016/2281. (6) For indoor conditions: +27°C DB / +19°C WB at rated air flow rate.
(3) According to EN 14511. (7) Weight for an available pressure of 400 Pa.
Heating mode: Inside conditions: +20°C DB and outside conditions: -7°C DB/-8°C WB.
(4) Power to be used for power cables selection.
400V/50 Hz 3-phase power supply + earth without neutral.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

31
Dimensions and connections ULTI+ R32 12

SUPPLY AIR below


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 50

Detail A

1 Fresh air
2 Return air
3 Supply air
Power supply Length Width (1) Height
A Access Casing dimensions 3,854 mm 1,954 mm 1,850 mm
C Technical section
--- Provide 400 mm clearance (minimum)
to allow air passage below the unit.
(1) Return air on side: +125 mm

Nota: Fresh air cowls shall be fitted by the installer.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

32
Dimensions and connections ULTI+ R32 12

SUPPLY AIR on top


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 50

Detail A

1 Fresh air
2 Return air
3 Supply air
Power supply
Length Width (1) Height
A Access
C Technical section Casing dimensions 3,854 mm 1,954 mm 1,850 mm

--- Provide 400 mm clearance (minimum)


to allow air passage below the unit.
(1) Return air on side: +125 mm

Nota: Fresh air cowls shall be fitted by the installer.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

33
Dimensions and connections ULTI+ R32 12

SUPPLY AIR below, return air on end


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 50

Detail A

1 Fresh air
2 Return air
3 Supply air Length Width (1) Height
Power supply Casing dimensions 3,854 mm 1,954 mm 1,850 mm
A Access
C Technical section

--- Provide 400 mm clearance (minimum)


to allow air passage below the unit. (1) Return air on side: +125 mm

Nota: Fresh air cowls shall be fitted by the installer.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

34
Dimensions and connections ULTI+ R32 12

SUPPLY AIR on side


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 50

Detail A

1 Fresh air
2 Return air
3 Supply air
Power supply Length Width Height
A Access Casing dimensions 3,854 mm 1,954 mm 1,850 mm
C Technical section
--- Provide 400 mm clearance (minimum)
to allow air passage below the unit.
(1) Return air on side: +125 mm

Nota: - Fresh air cowls shall be fitted by the installer.


- Lateral box shall be fitted by the installer.
- Supply air damper electrical connection shall be made by the installer.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

35
Auxiliary: Hot water coils ULTI+ R32 12

SCHEMATIC DIAGRAM AND CONNECTION


Top view Principle

Air
flow
way

Option

CAPACITIES
Unit 050 055 065 075 080 090 100

Heating capacity kW 179.7 195.7 210.7 229.4 246.8 263.0 263.0


90/70°C water regime Water flow rate m3/h 8.0 8.7 9.4 10.2 11.0 11.7 11.7
and Exchanger pressure drop mWC 0.9 1.1 1.2 1.4 1.6 1.9 1.9
Exchanger inlet air Exchanger and 3WV pressure drop (1)
mWC 1.8 2.1 2.5 2.9 3.3 3.8 3.8
temperature 10°C Exchanger, 3WV, SV and TAV
mWC 2.8 3.3 3.8 4.5 5.2 5.9 5.9
pressure drop (2)

Heating capacity kW 151.6 164.9 177.4 193.0 207.4 220.9 220.9


80/60°C water regime Water flow rate m3/h 6.7 7.3 7.8 8.5 9.2 9.8 9.8
and Exchanger pressure drop mWC 0.7 0.8 0.9 1.0 1.2 1.4 1.4
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 1.3 1.5 1.8 2.1 2.4 2.7 2.7
temperature 10°C Exchanger, 3WV, SV and TAV
mWC 2.0 2.4 2.7 3.2 3.7 4.2 4.2
pressure drop (2)

Heating capacity kW 152.9 166.3 179.0 194.7 209.3 223.0 223.0


90/70°C water regime Water flow rate m3/h 6.7 7.3 7.9 8.6 9.2 9.8 9.8
and Exchanger pressure drop mWC 0.7 0.8 0.9 1.1 1.2 1.4 1.4
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 1.3 1.5 1.8 2.1 2.4 2.7 2.7
temperature 20°C Exchanger, 3WV, SV and TAV
mWC 2.0 2.4 2.8 3.3 3.8 4.3 4.3
pressure drop (2)

Heating capacity kW 124.7 135.5 145.5 158.1 170.0 180.9 180.9


80/60°C water regime Water flow rate m3/h 5.5 6.0 6.4 7.0 7.5 8.0 8.0
and Exchanger pressure drop mWC 0.5 0.5 0.6 0.7 0.8 0.9 0.9
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 0.9 1.0 1.2 1.4 1.6 1.8 1.8
temperature 20°C Exchanger, 3WV, SV and TAV
mWC 1.4 1.6 1.9 2.2 2.5 2.8 2.8
pressure drop (2)

(1) With 3WV option


(2) With 3WV, SV and TAV option
3WV: 3-way valve
SV: Stop valve on outlet
TAV: TA regulating valve on inlet, opened 7/8
Technical data for non-glycol water, at rated air flow rate.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

36
Preheating: Hot water coils ULTI+ R32 12

SCHEMATIC DIAGRAM AND CONNECTION


Connection opposite the technical section

Top view Side view

Same connection as the hot water coil


See schematic diagram and connection.

CAPACITIES
Unit 050 055 065 075 080 090 100
Heating capacity kW 56.1 61.1 65.8 71.7 77.1 82.2 82.2
35/30°C water regime Water flow rate m3/h 9.7 10.6 11.4 12.4 13.4 14.2 14.2
and Exchanger pressure drop mWC 1.5 1.7 2.0 2.3 2.7 3.0 3.0
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 2.8 3.3 3.9 4.5 5.2 5.9 5.9
temperature 10°C
Exchanger, 3WV, SV and TAV
mWC 4.4 5.2 6.0 7.0 8.1 9.2 9.2
pressure drop (2)

Heating capacity kW 29.5 32.0 34.4 37.3 40.0 42.5 42.5


35/30°C water regime Water flow rate m /h
3
5.1 5.5 6.0 6.5 6.9 7.4 7.4
and Exchanger pressure drop mWC 0.4 0.5 0.6 0.7 0.8 0.9 0.9
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 0.8 0.9 1.1 1.3 1.5 1.6 1.6
temperature 20°C
Exchanger, 3WV, SV and TAV
mWC 1.2 1.4 1.7 2.0 2.2 2.5 2.5
pressure drop (2)

(1) With 3WV option


(2) With 3WV, SV and TAV option

3WV: 3-way valve


SV: Stop valve on outlet
TAV: TA regulating valve on inlet, opened 7/8
Technical data for non-glycol water, at rated air flow rate.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

37
Technical features ULTI+ R32 21

DESCRIPTION Unit 090 095 110 115 130 140 (8)


FLOW RATES
Rated air flow rate m3/h 19,000 21,000 23,000 25,000 27,000 27,000
m /h
3
VENTILATION

Minimum air flow rate 12,000 13,000 19,000 19,000 25,000 25,000
Maximum air flow rate m3/h 27,000 27,000 27,000 27,000 27,000 27,000
ACOUSTICS (Eurovent certified) (1)
Sound power level on supply air dB(A) 77 79 80 81 83 83
Outside sound power level dB(A) 78 78 84 85 88 91
Resultant outdoor sound pressure at 10m ref. 2*10-5 in free field,
dB(A) 50 50 56 57 60 63
direction 2
RATED PERFORMANCES AT +35°C (Eurovent certified) (1)
Net cooling capacity kW 84.2 90.0 101.8 114.6 121.8 131.5
PERFORMANCES

Net EER kW/kW 3.51 3.38 3.26 3.17 3.15 3.06


COOLING

Eurovent class E…A A A A A A -


SEASONAL EFFICIENCY (2)
Design net cooling capacity kW 84.2 90.0 101.8 114.6 121.8 131.5
SEER kW/kW 5.40 5.07 4.91 4.77 4.94 4.60
ηs,C % 213 200 193 188 194 181
RATED PERFORMANCES AT +7°C (Eurovent certified) (1)
Net heating capacity kW 84.5 90.9 105.9 120.1 127.3 139.5
Net COP kW/kW 4.26 4.27 4.04 3.99 3.98 3.84
Eurovent class E…A A A A A A -
PERFORMANCES

RATED PERFORMANCES AT -7°C (3)


HEATING

Net heating capacity kW 57.4 62.5 72.3 81.9 86.4 95.1


Net COP kW/kW 3.39 3.40 3.20 3.16 3.11 3.02
SEASONAL EFFICIENCY (2)
Design net heating capacity kW 76.8 80.3 92.5 101.5 111.1 117.3
SCOP kW/kW 4.06 3.99 3.79 3.74 3.69 3.43
ηs,H % 159 157 149 146 144 134
ELECTRICAL DATA
Total installed electrical power (4) kW 45.5 48.6 56.6 61.7 63.5 68.9
Total installed electrical intensity (4)
A 74.2 78.8 91.8 100.1 101.9 111.0
Starting current A 188.7 209.0 222.0 304.8 306.7 353.4
Maximum absorbed electrical power (5) kW 29.5 32.6 37.6 42.8 45.7 50.1
REFRIGERATION CIRCUIT(S)
Power stages - 4 4 4 4 4 4
OPERATING LIMITS IN COOLING MODE
GENERAL

Maximum outside temperature(6) °C + 50 + 49 + 49 + 49 + 48 + 48


Minimum outside temperature (6) °C + 15
Minimum internal coil inlet temperature °C + 18
OPERATING LIMITS IN HEATING MODE
Minimum outside temperature °C - 15
Minimum internal coil inlet temperature °C + 12
WEIGHT
Unit weight without options (7) kg 1,218 1,225 1,302 1,329 1,386 1,380
Connection roof curb weight kg 121
Standard ventilated roof curb weight kg 169

(1) According to EN 14511. (5) Cooling mode: Inside conditions: +27°C DB/+19°C WB and outside
Cooling mode: Inside conditions: +27°C DB/+19°C WB and outside conditions: +35°C DB/24°C WB. conditions: +35°C DB/24°C WB. Rated air flow rate, 400Pa available
Heating mode: Inside conditions: +20°C DB/+12°C WB and outside conditions: +7°C DB/+6°C WB. pressure on return + supply air & fouled ISO Coarse 65% filters
(2) According to EcoDesign regulations 2016/2281. (6) For indoor conditions: +27°C DB / +19°C WB at rated air flow rate.
(3) According to EN 14511. (7) Weight for an available pressure of 400 Pa.
Heating mode: Inside conditions: +20°C DB and outside conditions: -7°C DB/-8°C WB. (8) Unit not Eurovent certified
(4) Power to be used for power cables selection.
400V/50 Hz 3-phase power supply + earth without neutral.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

38
Dimensions and connections ULTI+ R32 21

SUPPLY AIR below


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 63

Detail A

1 Fresh air
2 Return air
3 Supply air Length Width (1) Height
Power supply Casing dimensions 4,777 mm 2,204 mm 1,980 mm
A Access
C Technical section
--- Provide 400 mm clearance (minimum)
to allow air passage below the unit. (1) Return air on side: +125 mm

Nota: Fresh air cowls shall be fitted by the installer.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

39
Dimensions and connections ULTI+ R32 21

SUPPLY AIR on top


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 63

Detail A

1 Fresh air
2 Return air
3 Supply air Length Width (1) Height
Power supply Casing dimensions 4,777 mm 2,204 mm 1,980 mm
A Access
C Technical section
--- Provide 400 mm clearance (minimum)
to allow air passage below the unit. (1) Return air on side: +125 mm

Nota: Fresh air cowls shall be fitted by the installer.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

40
Dimensions and connections ULTI+ R32 21

SUPPLY AIR below, return air on end


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 63

Detail A

1 Fresh air
2 Return air
3 Supply air Length Width (1) Height
Power supply Casing dimensions 4,777 mm 2,204 mm 1,980 mm
A Access
C Technical section
--- Provide 400 mm clearance (minimum)
to allow air passage below the unit.
(1) Return air on side: +125 mm

Nota: Fresh air cowls shall be fitted by the installer.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

41
Dimensions and connections ULTI+ R32 21

SUPPLY AIR on side


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 63

Detail A Installer
support

1 Fresh air
2 Return air
3 Supply air
Power supply Length Width (1) Height
A Access
C Technical section Casing dimensions 4,777 mm 2,204 mm 1,980 mm

--- Provide 400 mm clearance (minimum)


to allow air passage below the unit.
(1) Return air on side: +125 mm

Nota: - Fresh air cowls shall be fitted by the installer.


- Lateral box shall be fitted by the installer.
- Supply air damper electrical connection shall be made by the installer.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

42
Auxiliary: Hot water coils ULTI+ R32 21

SCHEMATIC DIAGRAM AND CONNECTION


Top view Principle

Air
flow
way

Option

CAPACITIES
Unit 090 095 110 115 130 140

Heating capacity kW 287.6 306.6 324.5 341.6 357.9 357.9


90/70°C water regime Water flow rate m3/h 12.8 13.6 14.4 15.2 15.9 15.9
and Exchanger pressure drop mWC 2.0 2.3 2.6 2.8 3.1 3.1
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 4.3 4.9 5.5 6.1 6.7 6.7
temperature 10°C Exchanger, 3WV, SV and TAV
mWC 6.9 7.9 8.8 9.7 10.7 10.7
pressure drop (2)

Heating capacity kW 242.7 258.6 273.5 287.8 301.3 301.3


80/60°C water regime Water flow rate m3/h 10.7 11.4 12.1 12.7 13.3 13.3
and Exchanger pressure drop mWC 1.5 1.7 1.9 2.1 2.3 2.3
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 3.1 3.5 4.0 4.4 4.8 4.8
temperature 10°C Exchanger, 3WV, SV and TAV
pressure drop (2)
mWC 5.0 5.6 6.3 6.9 7.6 7.6

Heating capacity kW 244.6 260.6 275.7 290.1 303.8 303.8


90/70°C water regime Water flow rate m3/h 10.8 11.5 12.2 12.8 13.4 13.4
and Exchanger pressure drop mWC 1.5 1.7 1.9 2.1 2.3 2.3
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 3.2 3.6 4.0 4.4 4.8 4.8
temperature 20°C Exchanger, 3WV, SV and TAV
mWC 5.0 5.7 6.4 7.0 7.7 7.7
pressure drop (2)

Heating capacity kW 199.7 212.6 224.8 236.3 247.3 247.3


80/60°C water regime Water flow rate m3/h 8.8 9.4 9.9 10.5 10.9 10.9
and Exchanger pressure drop mWC 1.0 1.2 1.3 1.4 1.6 1.6
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 2.1 2.4 2.7 3.0 3.2 3.2
temperature 20°C Exchanger, 3WV, SV and TAV
mWC 3.4 3.8 4.3 4.7 5.1 5.1
pressure drop (2)

(1) With 3WV option


(2) With 3WV, SV and TAV option
3WV: 3-way valve
SV: Stop valve on outlet
TAV: TA regulating valve on inlet, opened 7/8
Technical data for non-glycol water, at rated air flow rate.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

43
Preheating: Hot water coils ULTI+ R32 21

SCHEMATIC DIAGRAM AND CONNECTION


► Connection opposite the technical section

Top view Side view

► Same connection as the hot water coil


See schematic diagram and connection.

Capacities
Unit 090 095 110 115 130 140

Heating capacity kW 90.1 96.0 101.7 107.0 112.1 112.1


35/30°C water regime Water flow rate 3
m /h 15.6 16.6 17.6 18.5 19.4 19.4
and Exchanger pressure drop mWC 3.3 3.7 4.2 4.6 5.0 5.0
Exchanger inlet air Exchanger and 3WV pressure drop (1)
mWC 6.8 7.7 8.7 9.6 10.5 10.5
temperature 10°C
Exchanger, 3WV, SV and TAV
pressure drop (2)
mWC 10.8 12.2 13.7 15.2 16.6 16.6

Heating capacity kW 47.4 50.4 53.3 56.0 58.5 58.5


35/30°C water regime Water flow rate m3/h 8.2 8.7 9.2 9.7 10.1 10.1
and Exchanger pressure drop mWC 1.0 1.1 1.2 1.4 1.5 1.5
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 2.0 2.2 2.5 2.7 2.9 2.9
temperature 20°C
Exchanger, 3WV, SV and TAV
mWC 3.1 3.5 3.8 4.2 4.6 4.6
pressure drop (2)

(1) With 3WV option


(2) With 3WV, SV and TAV option

3WV: 3-way valve


SV: Stop valve on outlet
TAV: TA regulating valve on inlet, opened 7/8
Technical data for non-glycol water, at rated air flow rate.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

44
Technical features ULTI+ R32 22

DESCRIPTION Unit 115 130 140 (8) 150 (8) 160 (8) 180 (8) 200 (8)
FLOW RATES
Rated air flow rate m3/h 25,000 27,000 30,000 33,000 35,000 38,000 38,000
m /h
3
VENTILATION

Minimum air flow rate 17,000 18,000 21,000 21,000 30,000 34,000 37,000
Maximum air flow rate m3/h 38,000 38,000 38,000 38,000 38,000 38,000 38,000
ACOUSTICS (Eurovent certified) (1)
Sound power level on supply air dB(A) 77 78 80 82 84 85 85
Outside sound power level dB(A) 84 86 88 90 86 88 91
Resultant outdoor sound pressure at 10m ref. 2*10-5 in
dB(A) 56 58 60 62 58 60 63
free field, direction 2
RATED PERFORMANCES AT +35°C (1)
Net cooling capacity kW 109.2 123.8 131.7 143.7 161.0 177.4 189.8
PERFORMANCES

Net EER kW/kW 3.56 3.48 3.44 3.31 3.21 3.07 2.97
COOLING

Eurovent class E…A A A - - - - -


SEASONAL EFFICIENCY (2)
Design net cooling capacity kW 109.2 123.8 131.7 143.7 161.0 177.4 189.8
SEER kW/kW 5.32 5.33 5.26 5.09 4.85 4.61 4.57
ηs,C % 210 210 208 200 191 181 180
RATED PERFORMANCES AT +7°C (1)

Net heating capacity kW 107.5 123.0 130.9 144.3 163.4 183.4 199.5
Net COP kW/kW 4.64 4.57 4.57 4.47 4.23 4.05 3.93
Eurovent class E…A A A - - - - -
PERFORMANCES

RATED PERFORMANCES AT -7°C (3)


HEATING

Net heating capacity kW 72.8 82.7 89.3 98.8 112.3 127.7 139.2
Net COP kW/kW 3.51 3.48 3.48 3.38 3.18 3.03 2.91
SEASONAL EFFICIENCY (2)
Design net heating capacity kW 93.0 106.5 116.7 119.8 139.0 156.9 170.0
SCOP kW/kW 4.25 4.13 4.18 4.01 3.70 3.37 3.45
ηs,H % 167 162 164 157 145 132 135
ELECTRICAL DATA
Total installed electrical power (4) kW 58.7 63.9 65.7 71.1 82.1 90.6 95.3
Total installed electrical intensity (4) A 95.0 103.3 105.1 114.2 132.3 144.1 152.4
Starting current A 225.2 308.0 309.9 356.6 374.7 397.2 417.4
Maximum absorbed electrical power (5) kW 36.7 42.1 45.5 51.2 58.3 66.6 66.4
REFRIGERATION CIRCUIT(S)
Power stages - 4 4 4 4 4 4 4
OPERATING LIMITS IN COOLING MODE
GENERAL

Maximum outside temperature(6) °C + 50 + 50 + 49 + 48 + 49 + 48 + 48


Minimum outside temperature (6) °C + 15
Minimum internal coil inlet temperature °C + 18
OPERATING LIMITS IN HEATING MODE
Minimum outside temperature °C - 15
Minimum internal coil inlet temperature °C + 12
WEIGHT
Unit weight without options (7) kg 1,774 1,819 1,856 1,895 1,924 2,036 2,017
Connection roof curb weight kg 163
Standard ventilated roof curb weight kg 228

(1) According to EN 14511. (5) Cooling mode: Inside conditions: +27°C DB/+19°C WB and outside
Cooling mode: Inside conditions: +27°C DB/+19°C WB and outside conditions: +35°C DB/24°C WB. conditions: +35°C DB/24°C WB. Rated air flow rate, 400Pa available
Heating mode: Inside conditions: +20°C DB/+12°C WB and outside conditions: +7°C DB/+6°C WB. pressure on return + supply air & fouled ISO Coarse 65% filters
(2) According to EcoDesign regulations 2016/2281. (6) For indoor conditions: +27°C DB / +19°C WB at rated air flow rate.
(3) According to EN 14511. (7) Weight for an available pressure of 400 Pa.
Heating mode: Inside conditions: +20°C DB and outside conditions: -7°C DB/-8°C WB. (8) Unit not Eurovent certified
(4) Power to be used for power cables selection.
400V/50 Hz 3-phase power supply + earth without neutral.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

45
Dimensions and connections ULTI+ R32 22

SUPPLY AIR below


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 63

Detail A

1 Fresh air
2 Return air
3 Supply air Length Width (1) Height
Power supply Casing dimensions 5,702 mm 2,354 mm 2,475 mm
A Access
C Technical section

--- Provide 400 mm clearance (minimum)


to allow air passage below the unit.
(1) Return air on side: +125 mm

Nota: Fresh air cowls shall be fitted by the installer.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

46
Dimensions and connections ULTI+ R32 22

SUPPLY AIR on top


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 63

Detail A

1 Fresh air
2 Return air
3 Supply air Length Width (1) Height
Power supply
Casing dimensions 5,702 mm 2,354 mm 2,475 mm
A Access
C Technical section
--- Provide 400 mm clearance (minimum)
to allow air passage below the unit. (1) Return air on side: +125 mm

Nota: Fresh air cowls shall be fitted by the installer.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

47
Dimensions and connections ULTI+ R32 22

SUPPLY AIR below, return air on end


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 63

Detail A

1 Fresh air
2 Return air
3 Supply air Length Width (1) Height
Power supply Casing dimensions 5,702 mm 2,354 mm 2,475 mm
A Access
C Technical section
--- Provide 400 mm clearance (minimum)
to allow air passage below the unit. (1) Return air on side: +125 mm

Nota: Fresh air cowls shall be fitted by the installer.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

48
Dimensions and connections ULTI+ R32 22

SUPPLY AIR on side


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 63

Detail A Installer
support

1 Fresh air
2 Return air
3 Supply air
Power supply Length Width (1) Height
A Access Casing dimensions 5,702 mm 2,354 mm 2,475 mm
C Technical section

--- Provide 400 mm clearance (minimum)


to allow air passage below the unit.
(1) Return air on side: +125 mm

Nota: - Fresh air cowls shall be fitted by the installer.


- Lateral box shall be fitted by the installer.
- Supply air damper electrical connection shall be made by the installer.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

49
Auxiliary: Hot water coils ULTI+ R32 22

SCHEMATIC DIAGRAM AND CONNECTION


Top view Principle

Air
flow
way

Option

CAPACITIES
Unit 115 130 140 150 160 180 200

Heating capacity kW 299.0 314.3 336.2 356.8 370.0 388.9 388.9


90/70°C water regime Water flow rate m3/h 13.3 14.0 14.9 15.9 16.4 17.3 17.3
and Exchanger pressure drop mWC 2.2 2.4 2.7 3.0 3.3 3.6 3.6
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 4.7 5.1 5.9 6.6 7.1 7.8 7.8
temperature 10°C Exchanger, 3WV, SV and TAV
mWC 7.4 8.2 9.4 10.6 11.3 12.5 12.5
pressure drop (2)

Heating capacity kW 252.7 265.5 283.7 301.0 311.9 327.7 327.7


80/60°C water regime Water flow rate m3/h 11.2 11.7 12.5 13.3 13.8 14.5 14.5
and Exchanger pressure drop mWC 1.6 1.8 2.0 2.2 2.4 2.6 2.6
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 3.4 3.7 4.2 4.7 5.1 5.6 5.6
temperature 10°C Exchanger, 3WV, SV and TAV
mWC 5.3 5.9 6.7 7.5 8.1 8.9 8.9
pressure drop (2)

Heating capacity kW 254.6 267.5 285.9 303.3 314.4 330.3 330.3


90/70°C water regime Water flow rate m3/h 11.2 11.8 12.6 13.4 13.9 14.6 14.6
and Exchanger pressure drop mWC 1.6 1.8 2.0 2.2 2.4 2.6 2.6
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 3.4 3.7 4.3 4.8 5.1 5.7 5.7
temperature 20°C Exchanger, 3WV, SV and TAV
mWC 5.4 6.0 6.8 7.7 8.2 9.1 9.1
pressure drop (2)

Heating capacity kW 208.2 218.6 233.5 247.5 256.4 269.2 269.2


80/60°C water regime Water flow rate m3/h 9.2 9.7 10.3 10.9 11.3 11.9 11.9
and Exchanger pressure drop mWC 1.1 1.2 1.4 1.5 1.6 1.8 1.8
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 2.3 2.5 2.9 3.2 3.5 3.8 3.8
temperature 20°C Exchanger, 3WV, SV and TAV
mWC 3.6 4.0 4.6 5.1 5.5 6.1 6.1
pressure drop (2)

(1) With 3WV option


(2) With 3WV, SV and TAV option
3WV: 3-way valve
SV: Stop valve on outlet
TAV: TA regulating valve on inlet, opened 7/8
Technical data for non-glycol water, at rated air flow rate.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

50
Preheating: Hot water coils ULTI+ R32 22

SCHEMATIC DIAGRAM AND CONNECTION


► Connection opposite the technical section

Top view Side view

► Same connection as the hot water coil


See schematic diagram and connection.

CAPACITIES
Unit 115 130 140 150 160 180 200

Heating capacity kW 93.7 98.5 105.4 111.9 116.0 121.9 121.9


35/30°C water regime Water flow rate m3/h 16.2 17.1 18.3 19.4 20.1 21.1 21.1
and Exchanger pressure drop mWC 3.5 3.9 4.4 4.9 5.3 5.8 5.8
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 7.3 8.1 9.2 10.4 11.1 12.3 12.3
temperature 10 °C
Exchanger, 3WV, SV and TAV
mWC 11.6 12.8 14.6 16.5 17.7 19.5 19.5
pressure drop (2)

Heating capacity kW 49.6 52.0 55.5 58.8 60.8 63.8 63.8


35/30°C water regime Water flow rate 3
m /h 8.6 9.0 9.6 10.2 10.5 11.1 11.1
and Exchanger pressure drop mWC 1.1 1.2 1.3 1.5 1.6 1.7 1.7
Exchanger inlet air Exchanger and 3WV pressure drop (1)
mWC 2.1 2.3 2.6 3.0 3.2 3.5 3.5
temperature 20°C
Exchanger, 3WV, SV and TAV
mWC 3.3 3.6 4.1 4.6 5.0 5.5 5.5
pressure drop (2)

(1) With 3WV option


(2) With 3WV, SV and TAV option

3WV: 3-way valve


SV: Stop valve on outlet
TAV: TA regulating valve on inlet, opened 7/8
Technical data for non-glycol water, at rated air flow rate.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

51
Technical features ULTI+ R32 23

DESCRIPTION Unit 180 200 220 245 270 285


FLOW RATES
Rated air flow rate m3/h 38,000 42,000 46,000 50,000 54,000 54,000
m /h
3
VENTILATION

Minimum air flow rate 24,000 26,000 30,000 36,000 46,000 52,000
Maximum air flow rate m3/h 54,000 54,000 54,000 54,000 54,000 54,000
ACOUSTICS (1)
Sound power level on supply air dB(A) 80 81 83 85 85 86
Outside sound power level dB(A) 86 88 90 85 88 91
Resultant outdoor sound pressure at 10m ref. 2*10-5 in
dB(A) 58 60 62 57 60 63
free field, direction 2
RATED PERFORMANCES AT +35°C (1)
PERFORMANCES

Net cooling capacity kW 168.2 190.4 211.1 231.6 254.0 273.5


COOLING

Net EER kW/kW 3.55 3.42 3.32 3.24 3.10 2.99


SEASONAL EFFICIENCY (2)
Design net cooling capacity kW 168.2 190.4 211.1 231.6 254.0 273.5
SEER kW/kW 6.47 5.74 5.67 5.06 5.16 4.90
ηs,C % 256 227 224 200 203 193
RATED PERFORMANCES AT +7°C (1)

Net heating capacity kW 164.8 186.4 210.3 234.2 259.7 285.2


Net COP kW/kW 4.48 4.27 4.27 4.16 4.00 3.79
PERFORMANCES

RATED PERFORMANCES AT -7°C (3)


HEATING

Net heating capacity kW 114.5 129.6 145.7 162.8 181.4 200.3


Net COP kW/kW 3.60 3.48 3.45 3.36 3.25 3.12
SEASONAL EFFICIENCY (2)
Design net heating capacity kW 152.7 173.9 181.0 202.4 224.9 247.9
SCOP kW/kW 4.72 4.46 4.46 4.23 4.21 3.89
ηs,H % 186 175 176 166 165 152
ELECTRICAL DATA
Total installed electrical power (4) kW 92.1 99.8 108.4 125.4 136.2 147.0
Total installed electrical intensity (4)
A 151.0 170.0 180.6 204.4 222.4 240.4
Starting current A 281.2 313.2 385.3 409.1 464.8 482.8
Maximum absorbed electrical power (5) kW 56.8 65.9 74.7 82.7 94.6 102.9
REFRIGERATION CIRCUIT(S)
Power stages - 4 4 4 4 4 4
OPERATING LIMITS IN COOLING MODE
GENERAL

Maximum outside temperature(6) °C + 52 + 51 + 50 + 51 + 50 + 49


Minimum outside temperature (6) °C - 15
Minimum internal coil inlet temperature °C + 18
OPERATING LIMITS IN HEATING MODE
Minimum outside temperature °C - 15
Minimum internal coil inlet temperature °C + 12
WEIGHT
Unit weight without options (7) kg 2,595 2,588 2,682 2,751 2,755 2,755
Connection roof curb weight kg 210
Standard ventilated roof curb weight kg 294

(1) According to EN 14511. (5) Cooling mode: Inside conditions: +27°C DB/+19°C WB and outside
Cooling mode: Inside conditions: +27°C DB/+19°C WB and outside conditions: +35°C DB/24°C WB. conditions: +35°C DB/24°C WB. Rated air flow rate, 400Pa available
Heating mode: Inside conditions: +20°C DB/+12°C WB and outside conditions: +7°C DB/+6°C WB. pressure on return + supply air & fouled ISO Coarse 65% filters
(2) According to EcoDesign regulations 2016/2281. (6) For indoor conditions: +27°C DB / +19°C WB at rated air flow rate.
(3) According to EN 14511. (7) Weight for an available pressure of 400 Pa.
Heating mode: Inside conditions: +20°C DB and outside conditions: -7°C DB/-8°C WB.
(4) Power to be used for power cables selection.
400V/50 Hz 3-phase power supply + earth without neutral.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

52
Dimensions and connections ULTI+ R32 23

SUPPLY AIR below


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 63

Detail A

1 Fresh air
2 Return air
Length Width (1) Height
3 Supply air
Power supply Casing dimensions 7,161 mm 2,354 mm 3,225 mm
A Access
C Technical section
--- Provide 400 mm clearance (minimum)
to allow air passage below the unit.
(1) Return air on side: +125 mm

Nota: Fresh air cowls shall be fitted by the installer.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

53
Dimensions and connections ULTI+ R32 23

SUPPLY AIR on top


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 63

Detail A

1 Fresh air
2 Return air
3 Supply air Length Width (1) Height
Power supply Casing dimensions 7,161 mm 2,354 mm 3,225 mm
A Access
C Technical section

--- Provide 400 mm clearance (minimum)


to allow air passage below the unit.
(1) Return air on side: +125 mm

Nota: Fresh air cowls shall be fitted by the installer.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

54
Dimensions and connections ULTI+ R32 23

SUPPLY AIR below, return air on end


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 63

Detail A

1 Fresh air
2 Return air Length Width (1) Height
3 Supply air Casing dimensions 7,161 mm 2,354 mm 3,225 mm
Power supply
A Access
C Technical section
(1) Return air on side: +125 mm
--- Provide 400 mm clearance (minimum)
to allow air passage below the unit.
Nota: Fresh air cowls shall be fitted by the installer.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

55
Dimensions and connections ULTI+ R32 23

SUPPLY AIR on side


Front view:

Top view:

Return air side view: Supply air side view:

Detail A

Installation area = 63

Detail A
Installer
support

1 Fresh air
2 Return air
3 Supply air
Power supply Length Width (1) Height
A Access
Casing dimensions 7,161 mm 2,354 mm 3,225 mm
C Technical section

--- Provide 400 mm clearance (minimum)


to allow air passage below the unit.
(1) Return air on side: +125 mm

Nota: - Fresh air cowls shall be fitted by the installer.


- Lateral box shall be fitted by the installer.
- Supply air damper electrical connection shall be made by the installer.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

56
Auxiliary: Hot water coils ULTI+ R32 23

SCHEMATIC DIAGRAM AND CONNECTION


Top view Principle

Air
flow
way

Option

CAPACITIES
Unit 180 200 220 245 270 285

Heating capacity kW 313.9 334.7 354.3 372.9 390.7 390.7


90/70°C water regime
Water flow rate m3/h 14.0 14.9 15.7 16.6 17.4 17.4
and
Exchanger pressure drop mWC 2.4 2.7 3.0 3.3 3.6 3.6
Exchanger inlet air Exchanger and 3WV pressure drop (1)
mWC 5.1 5.8 6.5 7.2 7.9 7.9
temperature 10°C
Exchanger, 3WV, SV and TAV
mWC 8.2 9.3 10.4 11.5 12.6 12.6
pressure drop (2)

Heating capacity kW 265.2 282.5 298.8 314.4 329.2 329.2


80/60°C water regime
Water flow rate m /h
3
11.7 12.5 13.2 13.9 14.6 14.6
and
Exchanger pressure drop mWC 1.8 2.0 2.2 2.4 2.6 2.6
Exchanger inlet air Exchanger and 3WV pressure drop (1)
mWC 3.7 4.2 4.7 5.1 5.6 5.6
temperature 10°C
Exchanger, 3WV, SV and TAV
mWC 5.9 6.7 7.4 8.2 9.0 9.0
pressure drop (2)

Heating capacity kW 267.1 284.6 301.1 316.8 331.8 331.8


90/70°C water regime
Water flow rate m3/h 11.8 12.6 13.3 14.0 14.7 14.7
and
Exchanger pressure drop mWC 1.8 2.0 2.2 2.4 2.7 2.7
Exchanger inlet air Exchanger and 3WV pressure drop (1)
mWC 3.7 4.2 4.7 5.2 5.7 5.7
temperature 20°C
Exchanger, 3WV, SV and TAV
mWC 6.0 6.8 7.6 8.3 9.1 9.1
pressure drop (2)

Heating capacity kW 218.4 232.4 245.7 258.4 270.4 270.4


80/60°C water regime
Water flow rate m /h
3
9.7 10.3 10.9 11.4 12.0 12.0
and
Exchanger pressure drop mWC 1.2 1.4 1.5 1.7 1.8 1.8
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 2.5 2.9 3.2 3.5 3.8 3.8
temperature 20°C
Exchanger, 3WV, SV and TAV
mWC 4.0 4.5 5.1 5.6 6.1 6.1
pressure drop (2)

(1) With 3WV option


(2) With 3WV, SV and TAV option
3WV: 3-way valve
SV: Stop valve on outlet
TAV: TA regulating valve on inlet, opened 7/8
Technical data for non-glycol water, at rated air flow rate.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

57
Preheating: Hot water coils ULTI+ R32 23

SCHEMATIC DIAGRAM AND CONNECTION


► Connection opposite the technical section

Top view Side view

► Same connection as the hot water coil


See schematic diagram and connection.

CAPACITIES
Unit 180 200 220 245 270 285

Heating capacity kW 98.4 104.9 111.1 116.9 122.5 122.5


35/30°C water regime
Water flow rate m3/h 17.1 18.2 19.2 20.3 21.2 21.2
and
Exchanger pressure drop mWC 3.9 4.4 4.9 5.4 5.9 5.9
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 8.1 9.1 10.2 11.3 12.4 12.4
temperature 10 °C
Exchanger, 3WV, SV and TAV pressure drop (2) mWC 12.8 14.5 16.2 18.0 19.7 19.7

Heating capacity kW 52.0 55.2 58.4 61.3 64.1 64.1


35/30°C water regime
Water flow rate m3/h 9.0 9.6 10.1 10.6 11.1 11.1
and
Exchanger pressure drop mWC 1.2 1.3 1.4 1.6 1.7 1.7
Exchanger inlet air Exchanger and 3WV pressure drop (1) mWC 2.3 2.6 2.9 3.2 3.5 3.5
temperature 20°C
Exchanger, 3WV, SV and TAV pressure drop (2)
mWC 3.6 4.1 4.6 5.0 5.5 5.5

(1) With 3WV option


(2) With 3WV, SV and TAV option

3WV: 3-way valve


SV: Stop valve on outlet
TAV: TA regulating valve on inlet, opened 7/8
Technical data for non-glycol water, at rated air flow rate.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

58
Arrangements

SUPPLY AIR downwards


Installation on roof curb or customer frame on roof

Arrangement 1.1 Arrangement 1.2


2

2 3 1 3

Arrangement 1.3 Arrangement 1.4: with whistle shaped cowl (optional)


2 1

1
3
3
Arrangement 1.5: with whistle shaped cowl (optional) Arrangement 1.6
1

2 3 1 3
Arrangement 1.7 Arrangement 1.8

1
2
2
1

3 3

Arrangement 1.9: with whistle shaped cowl (optional) Arrangement 1.10


1

2 2

3 1 3

1 Fresh air 2 Return air 3 Supply air

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

59
Arrangements

SUPPLY AIR upwards


Installation on feet (400 mm minimum) or customer frame
Feet are optional. A supply air damper is necessary for units bigger than 10,000 m3/h in Public Access Buildings.

Arrangement 2.1 Arrangement 2.2


3 2 3

2 1

Arrangement 2.3 Arrangement 2.4: with whistle shaped cowl (optional)


2 3 1 3

2
1

Arrangement 2.5: with whistle shaped cowl (optional) Arrangement 2.6


1 3 3

2 1

Arrangement 2.7 Arrangement 2.8


3 3

2
2
1

Arrangement 2.9: with whistle shaped cowl (optional) Arrangement 2.10


1 3 3

2 2

1 Fresh air 2 Return air 3 Supply air

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

60
Arrangements

SUPPLY AIR on side


Opposite the technical section (with 400 mm feet minimum)

Arrangement 3.1 Arrangement 3.2


2

3 3

2 1

Arrangement 3.3 Arrangement 3.4: with whistle shaped cowl (optional)

2 1

2
3 3

Arrangement 3.5: with whistle shaped cowl (optional) Arrangement 3.6

1
2

3 3

2 1

Arrangement 3.7 Arrangement 3.8

1
3 2 3
2
1

Arrangement 3.9: with whistle shaped cowl (optional) Arrangement 3.10


1

2 3 2 3

1 Fresh air 2 Return air 3 Supply air

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

61
Auxiliary: Sequential electric heaters

SCHEMATIC DIAGRAM

Electric heaters

AVAILABLE CAPACITIES (in kW)


Total capacity (kW) Current ULTI+ R32 ULTI+ R32 ULTI+ R32 ULTI+ R32 ULTI+ R32 ULTI+ R32 Weight
1st stage 2nd stage
(A) 01 11 12 21 22 23 (kg)

7.5 10.8 3 4.5 • 2.4


9 13.0 3 6 • 2.9
12 17.3 4.5 7.5 • 3.4
12 17.3 3 9 • 3.4
15 21.7 6 9 • • 4.2
18 26.0 9 9 • 4.7
18 26.0 6 12 • • 5.0
21 30.3 6 15 • • • 5.9
21 30.3 9 12 • • 5.5
24 34.6 9 15 • • • • • 6.4
27 39.0 12 15 • • • • 7.2
30 43.3 12 18 • • • • 7.8
33 47.6 9 24 • • 8.6
33 47.6 12 21 • 6.4
36 52.0 12 24 • • 9.4
36 52.0 15 21 • 10.6
39 56.3 15 24 • • 10.3
39 56.3 18 21 • 12.4
42 60.6 12 30 • 11.3
42 60.6 18 24 • • • 12.1
45 65.0 15 30 • • 12.2
45 65.0 21 24 • • 12.7
48 69.3 18 30 • • 14.0
54 77.9 18 36 • • • 17.6
60 86.6 24 36 • 18.0
60 86.6 18 42 • • 18.8
66 95.3 24 42 • • 19.2
72 103.9 30 42 • • 21.1
81 116.9 39 42 • • 25.3
90 129.9 33 57 • 26.6
99 142.9 39 60 • 31.2
108 155.9 39 63 • 31.8
117 168.9 54 63 • 35.9

Nota: For higher performances, please contact us.

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

62
Options weight (kg)

ULTI+ R32 ULTI+ R32 ULTI+ R32 ULTI+ R32 ULTI+ R32 ULTI+ R32
Options
01 11 12 21 22 23
Frame - Casing

Unit with Vertical (V) or Lateral (L) supply air 31 55 73 84 119 169

Removal of FA + RA dampers -10 -16 -22 -33 -34 -48

50 mm double skin 28 40 54 70 97 152

Fresh air cowl 7 9 10 19 20 20

Air handling

Pressure relief gravity dampers (return air below) 17 22 26 32 39 39

Thermal exchangers
Hot water coil as auxiliary or for preheating, with
21 35 47 60 76 76
water

Hot water coil as auxiliary or for preheating, with


23 37 49 63 79 79
water, with 3WV option

Hot water coil as auxiliary or for preheating, with


26 39 53 66 83 83
water, with 3WV, SV and TAV option

Dehumidification level 2 18 33 43 38 40 82

Installation

Ventilated aluminium connection roof curb 73 80 104 121 163 210

Aluminium ventilated roof curb 102 112 146 169 228 294

3WV: 3-way valve


SV: Stop valve on outlet
TAV: TA regulating valve on inlet, opened 7/8

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

63
Dehumidification option with heat recovery through in-
line condenser

The dehumidification option enables room humidity control. This feature is particularly suited for large and medium-sized
stores, where the installation of numerous closed refrigerated showcases requires a treatment of latent contributions
through air handling.
Various configurations are available to adapt to each specific project.
Return air flows through the evaporator(s), causing humidity contained in the air to condense.
Recovered calories can be transferred thanks to the in-line condenser (optional). The heating capacity of the thermodynamic
cycle is thus returned to treated air.
Calories can also be rejected on the external condenser (in summer).
Depending on outdoor and indoor conditions, control enables dehumidification through fresh air introduction, thus
delaying the start of the thermodynamic system.

Winter
COND. 1

.1
ap
Ev
AUXILIARIES
CONDENSER
EVAP. 2
IN-LINE

Summer
Evap. 1

. 1
ND
CO

.2
ND
CO
Evap. 2

Mid-season
Evap. 1

. 1
ND
CO
CONDENSER
Evap. 2
IN-LINE

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

64
Dehumidification option with heat recovery through in-
line condenser
OPTION LEVELS PER CIRCUIT

Level 1: Level 2:
Dehumidification without energy recovery. Dehumidification with energy recovery through in-line
The refrigeration circuit features a year-round kit in condenser, on/off refrigeration 3-way valve (for one
order to enable dehumidification operation in winter. circuit) and year-round kit (for all the circuits). The heat
Heat is evacuated through the external condenser. recovered is transferred either to the air stream or to the
external condenser depending on the season or on the
supply air temperature setpoint.

For each level, an additional auxiliary heater may be installed for winter operation, depending on project characteristics.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

65
Dehumidification option with heat recovery through in-
line condenser

TECHNICAL FEATURES

ULTI+ R32 01 040 045 050


Return air conditions Dehumidification capacity kg/h 13.8 15.2 16.6
Cooling mode Recovery capacity through in-
26°C DB / 50% RH (1) kW 44.4 49.9 52.5
line condenser (optional)

Return air conditions Dehumidification capacity kg/h 10.6 11.7 12.7


Heating mode Recovery capacity through in-
20°C DB / 50% RH (2) kW 40.3 45.0 47.5
line condenser (optional)

ULTI+ R32 11 040 045 050 055 065 075


Return air conditions Dehumidification capacity kg/h 15.3 17.3 18.0 21.0 23.4 26.7
Cooling mode Recovery capacity through in-
26°C DB / 50% RH (1) kW 48.5 54.7 58.9 66.9 75.7 87.0
line condenser (optional)

Return air conditions Dehumidification capacity kg/h 11.8 13.3 13.8 16.0 17.8 20.6
Heating mode Recovery capacity through in-
20°C DB / 50% RH (2) kW 44.3 49.7 53.6 60.7 68.6 79.3
line condenser (optional)

ULTI+ R32 12 050 055 065 075 080 090 100


Return air conditions Dehumidification capacity kg/h 19.4 22.3 25.3 29.6 30.9 33.0 37.8
Cooling mode Recovery capacity through in-
26°C DB / 50% RH (1) kW 61.7 70.9 80.5 92.8 101.7 112.3 121.1
line condenser (optional)

Return air conditions Dehumidification capacity kg/h 15.0 17.1 19.4 23.0 23.6 25.2 29.2
Heating mode Recovery capacity through in-
20°C DB / 50% RH (2) kW 56.4 64.6 73.2 84.9 92.7 101.7 109.9
line condenser (optional)

ULTI+ R32 21 090 095 110 115 130 140


Return air conditions Dehumidification capacity kg/h 30.7 32.4 37.7 41.2 43.8 50.3
Cooling mode Recovery capacity through in-
26°C DB / 50% RH (1) kW 54.3 60.2 61.2 73.6 74.8 85.0
line condenser (optional)

Return air conditions Dehumidification capacity kg/h 28.5 30.7 35.0 38.1 41.3 46.6
Heating mode Recovery capacity through in-
20°C DB / 50% RH (2) kW 49.2 54.5 55.5 66.5 67.7 77.1
line condenser (optional)

ULTI+ R32 22 115 130 140 150 160 180 200


Return air conditions Dehumidification capacity kg/h 39.3 44.1 45.8 50.7 56.4 62.9 71.3
Cooling mode Recovery capacity through in-
26°C DB / 50% RH (1) kW 63.7 77.9 79.5 95.5 96.0 117.3 121.7
line condenser (optional)

Return air conditions Dehumidification capacity kg/h 37.2 41.3 44.0 48.5 53.4 59.1 65.8
Heating mode Recovery capacity through in-
20°C DB / 50% RH (2) kW 58.0 70.8 72.5 86.8 87.9 106.5 110.3
line condenser (optional)

ULTI+ R32 23 180 200 220 245 270 285


Return air conditions Dehumidification capacity kg/h 61.8 67.5 74.5 82.5 94.7 105.1
Cooling mode Recovery capacity through in-
26°C DB / 50% RH (1) kW 108.5 120.1 134.4 147.9 164.9 173.5
line condenser (optional)

Return air conditions Dehumidification capacity kg/h 57.3 62.3 69.0 75.7 87.5 95.8
Heating mode Recovery capacity through in-
20°C DB / 50% RH (2) kW 98.5 108.9 121.8 133.8 149.2 156.8
line condenser (optional)

(1) At 80% of rated air flow rate, for an outside temperature of +35°C, with 95% saturation
(2) At 80% of rated air flow rate, for an outside temperature of +7°C, with 95% saturation

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

66
Option: Pressure relief gravity dampers

DESCRIPTION:
The pressure relief gravity damper option is recommended for buildings with a high tightness level.
It offers passive exhaust to avoid overpressure in the building due to significant air intake, especially in Free Cooling
mode.
When the unit is stopped or operates with all recirculated air, the gravity dampers remain closed (backdraft function).
Pressure relief gravity dampers are available for arrangements: 1.1 - 1.2 - 1.3 - 1.5 / 2.1 - 2.2 - 2.3 - 2.5 / 3.1 - 3.2 - 3.3 - 3.5.

OPERATING PRINCIPLE:
Heating mode

Cooling mode

Free Cooling mode

Recycling mode

1 Fresh air 2 Return air 3 Supply air 4 Exhaust air

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

67
Sound level

OUTSIDE SOUND POWER LEVEL DB(A)


FREQUENCY BANDS (Hz)
Fan
Overall level
Lw (dB(A))(1)
62.5 125 250 500 1,000 2,000 4,000 8,000

01-040 45 59 61 64 62 58 56 49 69
01-045 46 62 69 71 71 68 63 57 77
01-050 48 65 72 75 74 72 66 60 80

11-040 47 60 63 66 65 60 58 51 71
11-045 48 61 64 67 66 62 59 53 72
11-050 48 61 64 67 66 62 59 53 72
11-055 44 60 67 70 70 67 61 55 75
11-065 48 67 73 77 76 74 68 61 82
11-075 59 70 79 84 83 79 74 65 88

12-050 52 64 65 68 67 63 60 54 73
12-055 55 66 69 69 68 64 62 56 75
12-065 48 65 72 75 75 72 66 58 80
12-075 49 68 74 78 77 74 69 60 82
12-080 56 64 72 75 74 73 69 60 80
12-090 57 68 78 84 81 79 76 64 88
12-100 56 69 81 85 82 80 77 69 89

21-090 58 69 72 72 71 67 65 59 78
21-095 58 69 72 72 71 67 65 59 78
21-110 51 68 75 78 78 75 69 61 84
21-115 52 70 77 80 79 77 71 63 85
21-130 57 72 80 84 83 80 75 65 88
21-140 61 74 82 87 85 82 77 67 91

22-115 54 70 77 79 79 76 70 61 84
22-130 55 72 79 81 81 78 72 63 86
22-140 59 75 81 84 83 80 74 65 88
22-150 62 77 83 86 84 81 76 66 90
22-160 59 70 78 81 80 78 74 65 86
22-180 61 72 80 83 82 80 76 67 88
22-200 61 74 83 87 85 82 80 70 91

23-180 54 72 78 81 81 79 73 65 86
23-200 54 73 80 83 83 80 74 67 88
23-220 55 75 81 85 84 81 76 68 90
23-245 60 68 77 79 79 77 73 65 85
23-270 67 73 81 83 82 81 78 68 88
23-285 64 74 82 86 84 83 80 71 91

(1) Eurovent certified

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

68
Probes connection principle

1
3
2

1 Room probe:1 twisted shielded pair wire, 2 x 0.75 mm2 LiY-CY (max. length 100 lm)
2 CO2 probe: 2 twisted shielded pairs wire, 4 x 0.75 mm2 LIY-CY (max. length 100 lm)
Humidity probe: 2 twisted shielded pairs wire, 4 x 0.75 mm2 LIY-CY (max. length 100 lm)
3 (Optional)

Nota: - Please note that the value indicated can vary depending on probe location. For more representative
results, do not install them:
> Close to heat sources (spotlights, cooking appliances, glass walls, smoke ducts)
> In draft zones (close to entrance, stockrooms, openings)
> In dead zones (behind shelvings, in a corner)
> Close to crowded areas (checkouts, fitting rooms)
- For accurate measurements:
> Do not install the probes in the axis of the duct used for their wiring.
> Do not install control cables and power cables in the same duct (risk of electromagnetic
interference).

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

69
Installation accessories: Roof curbs

DESCRIPTION
The roof curb provides interfacing between the roof and the rooftop unit. It has been designed to facilitate assembly on
the roof and unit installation.

Adapter interface Packaged roof curb


on existing roof curb: Adjustable ventilated roof curb
■ Compliant with French ■ Compliant with French welded on the sheet metal for
standard NF P 84-206-1 (Grooved standard NF P 84-206-1 (Grooved a better fastening than gluing
sheet metal roofing with sheet metal roofing with methods. Insulation limits thermal
waterproofing coating) and fire- waterproofing coating) and fire- losses and avoids under-surface
safety regulations for PAB. safety regulations for PAB. condensation.
■ Aluminium packaged roof curb, ■ Aluminium packaged roof curb, ■ Cap flashing allows continuous
lighter than other galvanised steel lighter than other galvanised steel insulation and waterproofing
constructions. constructions. membrane (up to 100 mm thick) on
■ Adjustable angles to compensate ■ Adjustable angles to compensate roof curb external side as stipulated
roof slope. Other slope percentages roof slope. Other slope percentages by 2002/91/EC Directive.
are available on request (optional). are available on request (optional). ■ Roof curbs are intended for steel
Please confirm the roof slope Please confirm the roof slope decks up to 145 mm high and
percentage and direction upon percentage and direction upon insulation up to 200 mm high (i.e.
order confirmation. order confirmation. max. H = 345 mm).
■ Cap flashing allows continuous ■ 200 mm ventilated air space in ■ Lifting lugs to facilitate cranage.
insulation and waterproofing accordance with French fire-
membrane (up to 100 mm thick) on safety regulations for PAB. 4 (or 6)
roof curb external side as stipulated feet fixed by bolting and tightness
by 2002/91/EC Directive. guaranteed with foam gasket
■ Roof curbs are intended for steel on supply air and return air ducts
decks up to 145 mm high and frames.
insulation up to 200 mm high (i.e. ■ The air space also provides acoustic
max. H = 345 mm). insulation since it considerably
reduces airborne noise from below
the unit.
■ 200 mm length double skin
insulated supply and return air
ducts connections, with external Packaged roof curb
aluminium mechanical protection. Adjustable connection roof curb
■ Cable pipes below the unit for ■ Bespoke roof curb to be adapted
power supply cable and hot water
on any type of existing roof
coils pipework. curb or header according to
■ The insulation below the roof curb dimensions sent by the installer
is made of 25 mm glass wool with (see our particular clauses for this
a protection veil. The insulation equipment).
is secured with aluminium clips

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

70
Installation accessories: Roof curbs

ADJUSTABLE CONNECTION ROOF CURB

A
B

WARNING: For this roof curb installation, the installer has the decennial responsibility for cover guarantee. Please indicate
the roof slope and direction when placing the order. Roof curbs are intended for steel decks up to 145 mm high and
insulation up to 200 mm high (i.e. max. H = 345 mm). Roof curbs have to be back-drilled after mounting. Mastic application
below unit frame.

Maxi slope Maxi slope


Overall Overall Overall
Dimensions (mm) A B H lengthwise widthwise Weight
width length height
(%) (%)

ULTI+ R32 01 1,320 1,970 550 1,534 2,178 568 5.0 7.5 73

ULTI+ R32 11 1,700 1,970 550 1,914 2,178 563 5.0 5.8 80

Ulti+ R32 12 1,970 2,450 600 2,184 2,658 618 5.0 6.2 104

Ulti+ R32 21 2,220 2,770 600 2,434 2,978 618 5.0 6.2 121

ULTI+ R32 22 2,370 3,160 600 2,584 3,368 618 5.0 6.7 163

Ulti+ R32 23 2,370 4,020 650 2,586 4,428 668 5.0 8.5 210

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

71
Installation accessories: Roof curbs

ADJUSTABLE VENTILATED ROOF CURB

200

A
B

WARNING: For this roof curb installation, the installer has the decennial responsibility for cover guarantee. Please indicate
the roof slope and direction when placing the order. Roof curbs are intended for steel decks up to 145 mm high and
insulation up to 200 mm high (i.e. max. H = 345 mm). Roof curbs have to be back-drilled after mounting. The unit must be
bolted to the roof curb. Mastic application below unit frame.

Maxi slope Maxi slope


Dimensions Overall Overall Overall
A B H lengthwise widthwise Weight
(mm) width length height
(%) (%)

ULTI+ R32 01 1,320 1,970 550 1,524 2,168 768 5.0 7.5 102

ULTI+ R32 11 1,700 1,970 550 1,904 2,168 763 5.0 5.8 112

Ulti+ R32 12 1,970 2,450 600 2,174 2,648 818 5.0 6.2 146

Ulti+ R32 21 2,220 2,770 600 2,424 2,968 818 5.0 6.2 169

ULTI+ R32 22 2,370 3,160 600 2,574 3,358 818 5.0 6.7 228

Ulti+ R32 23 2,370 4,020 650 2,576 4,418 868 5.0 8.5 294

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

72
Installation accessories: Roof curbs

ROOF CURBS INSTALLATION PRINCIPLE

Sealant gasket between the frame


and the roof curb on the periphery

Outer insulation shall be included in the


waterproofing package
(not supplied by ETT)
Unit frame

600 (or 650 according to the unit)


150 min.
Waterproofing
Connection roof curb membrane

Insulation

H
Optional: side insulation

Steel deck

Binding joist

Roof curbs are intended for steel decks Nota: One (for connection roof curb) or two (for ventilated
up to 145 mm high and insulation up to roof curb) optional cover sheets can be added to
200 mm high (i.e. max. H=345 mm). protect the building from the weather during the time
between roof curb installation and unit installation.

ULTI+ R32 ETT may change equipment technical data without prior notice.
MARK-BRO_36-EN_A Specifications given in this document are for information only and are not contractual.

73
Installation accessories: Feet

Aluminium fixed foot


Unit weight: 1kg 200, 400 or 600 mm

157 mm
157 m
m

The feet shall be mounted at the corners of the frame. Concerning the ULTI+ R32 - 23 boxes, two dditionnal feet shall
be placed at the center of the frame.

ULTI+ R32 01 ULTI+ R32 11 ULTI+ R32 12 ULTI+ R32 21 ULTI+ R3 22 ULTI+ R32 23
No. of feet 4 4 4 4 4 6 (*)

(*) The central feet have a 200 x 200 base (instead of 157 x 157 mm).

ETT may change equipment technical data without prior notice. ULTI+ R32
Specifications given in this document are for information only and are not contractual. MARK-BRO_36-EN_A

74
Design: ETT - Document printed by an environmentally friendly printer labelled by Green Print using vegetable-based ink on PEFC paper created from sustainably-managed forests.

Reference: MARK-BRO_36-EN_A
ETT - Route de Brest - BP26
29830 Ploudalmézeau - France
Tel: +33(0)2 98 48 14 22
Fax: +33(0)2 98 48 09 12
Export Contact: +33(0)2 98 48 00 70
ETT Services: +33(0)2 98 48 02 22 [Link]