DISTRIBUTION PANEL ENCLOSURE MAIN C.B.
RATING VOLTAGE Mains
WAYS 18Way Mounting FLUSHED MOUNTED Trip Rating (AMPS) 25 Voltage 380/220v Fed from MDB
Panel- TYPE NPP-2-DB IP 44 Frame - Frequency 50HZ Cable Type PVC/PVC/CU
LOCATION Main Entry TOP TYPE MCB S.C Rating - Cable Size (4x6)+6E
Circuit Phase Load (A) Trip Rating (AMPS) Phase Load (A) cable/wire Size Circuit
Note LOAD LOCATION cable/wire Size mm2 LOAD LOCATION Note
No. R Y B R Y B R Y B mm2 No.
COFFEE CORNER & COLLABORATIVE
1 a OASIS & COFFEE CORNER SOCKETS 3x4 8 20 ᴖ 20 6 3X4 a 2
AREA & OASIS SOCKETS
SUPERVISOR & COLLABORATIVE AREA
3 a HR DIRECTOR & FILING ROOM SOCKETS 3x4 6 20 ᴖ 20 8 3X4 a 4
SOCKETS
5 a HR OFFICES SOCKETS 3x4 10 20 ᴖ 16 1 3X3 PA OFFICESS & SUPERVISOR LIGHTING a 6
HR DIRECTOR & FILING ROOM
7 a PA OFFICES & SUPERVISOR SOCKETS 3x4 10 20 ᴖ 16 0.7 3X3 a 8
LIGHTING
MEETING ROOM & TRACK LIGHT
HR OFFICES & SUPERVISOR &
9 a CORRIDOR & COLLABORATIVE AREA 3x3 2 16 ᴖ 16 1.65 3X3 a 10
COLLABORATIVE AREA LIGHTING
LIGHTING
11 a MEETING ROOM SOCKETS 3x4 8 20 ᴖ 20 6 3X4 DRIVERS ROOM SOCKET a 12
13 a SPARE - - 16 20 - - SPARE a 14
15 a DRIVERS ROOM SOCKET 3x4 6 20 20 - - SPARE a 16
17 a SPARE - - 16 20 - - SPARE a 18
18 14 18 6.7 9.65 7
TOTAL (A) 24.7 23.65 25 PHASE BALANCE 5.4 %
SOCKETS MOTORS
Lighting (KVA) MISC (KVA) TOTAL
(KVA) (KVA) NOTES
CONNECTED. LOAD 1.2 15.0 0.0 16.1 b Residual Current Circuit breaker
DIVERSITY FACTOR 0.9 0.7 0.7 0.7 g CONTROLLED VIA TIMER
MAX. DEMAND 1.1 10.5 0.0 11.5 a Earth Leakage Relay, 30 mA