PANEL NAME LPF-2
LOCATION PRODUCTION AREA SERVICE 400/230 V, 3 PH, 4 WIRES, 60 HZ
FEED FROM MDB BUS RATING 100 A
MOUNTING WALL Isc 18 KA
CABLE ENTRY DOWN ENTRY MAIN CB RATING 100 AT / 100 AF
WIRE CONDUIT CONDUIT WIRE
LOAD (VA) BREAKER CT. BUS CT. BREAKER LOAD (VA)
DESCRIPTION SIZE CU SIZE SIZE SIZE DESCRIPTION
NO. NO.
mm2 mm2 L1 L2 L3 POLE RATING L1 L2 L3 RATING POLE L1 L2 L3 mm2 mm2
LIGHTING FIXTURES 3*6 25 575 1 16 1 2 16 1 250 25 3*4 SOCKET OUTLET 16A
LIGHTING FIXTURES 3*6 25 500 1 16 3 4 16 1 750 25 3*4 SOCKET OUTLET 16A
LIGHTING FIXTURES 3*6 25 250 1 16 5 6 16 1 750 25 3*4 SOCKET OUTLET 16A
LIGHTING FIXTURES 3*6 25 400 1 16 7 8 16 1 2000 25 3*4 SOCKET OUTLET 16A
LIGHTING FIXTURES 3*6 400 1 32 9 10 16 1 1250 25 3*4 SOCKET OUTLET 16A
AC UNIT 3*6 2500 1 32 11 12 32 1 2500 25 3*4 AC UNIT
AC UNIT 3*6 2500 1 32 13 14 32 1 2500 25 3*4 AC UNIT
AC UNIT 3*6 2500 1 32 15 16 32 1 2500 25 3*6 AC UNIT
SPACE 1 17 18 32 1 2500 25 3*6 AC UNIT
SPACE 1 19 20 32 1 2500 25 3*6 AC UNIT
SPACE 1 21 22 1 25 3*6 SPARE
SPACE 1 23 24 1 25 3*6 SPARE
TOTAL 3475 3400 2750 TOTAL 7250 4500 5750
TOTAL BUS LOAD 10.7 7.9 8.5
TOTAL CONNECTED LOAD 27.1 KVA FEEDER SIZE (4*25)+ 1*16 mm2
FUTURE FACTOR 20%
DEMAND FACTOR 1 FEEDER TYPE CU/XLPE/PVC LPF-2
TOTAL DEMAN LOAD 32.6 KVA
DEMAND CURRENT 47 A