LPF-2 Electrical Load Calculation

The document details the specifications and load calculations for the LPF-2 panel located in the production area, including service voltage, bus rating, and total connected load. It lists various lighting fixtures and AC units with their respective load ratings and breaker sizes. The total demand load is calculated to be 32.6 KVA with a demand current of 47 A.

Uploaded by

sulaiman.str
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
111 views1 page

LPF-2 Electrical Load Calculation

The document details the specifications and load calculations for the LPF-2 panel located in the production area, including service voltage, bus rating, and total connected load. It lists various lighting fixtures and AC units with their respective load ratings and breaker sizes. The total demand load is calculated to be 32.6 KVA with a demand current of 47 A.

Uploaded by

sulaiman.str
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

PANEL NAME LPF-2

LOCATION PRODUCTION AREA SERVICE 400/230 V, 3 PH, 4 WIRES, 60 HZ


FEED FROM MDB BUS RATING 100 A
MOUNTING WALL Isc 18 KA
CABLE ENTRY DOWN ENTRY MAIN CB RATING 100 AT / 100 AF

WIRE CONDUIT CONDUIT WIRE


LOAD (VA) BREAKER CT. BUS CT. BREAKER LOAD (VA)
DESCRIPTION SIZE CU SIZE SIZE SIZE DESCRIPTION
NO. NO.
mm2 mm2 L1 L2 L3 POLE RATING L1 L2 L3 RATING POLE L1 L2 L3 mm2 mm2
LIGHTING FIXTURES 3*6 25 575 1 16 1 2 16 1 250 25 3*4 SOCKET OUTLET 16A
LIGHTING FIXTURES 3*6 25 500 1 16 3 4 16 1 750 25 3*4 SOCKET OUTLET 16A
LIGHTING FIXTURES 3*6 25 250 1 16 5 6 16 1 750 25 3*4 SOCKET OUTLET 16A
LIGHTING FIXTURES 3*6 25 400 1 16 7 8 16 1 2000 25 3*4 SOCKET OUTLET 16A
LIGHTING FIXTURES 3*6 400 1 32 9 10 16 1 1250 25 3*4 SOCKET OUTLET 16A
AC UNIT 3*6 2500 1 32 11 12 32 1 2500 25 3*4 AC UNIT
AC UNIT 3*6 2500 1 32 13 14 32 1 2500 25 3*4 AC UNIT
AC UNIT 3*6 2500 1 32 15 16 32 1 2500 25 3*6 AC UNIT
SPACE 1 17 18 32 1 2500 25 3*6 AC UNIT
SPACE 1 19 20 32 1 2500 25 3*6 AC UNIT
SPACE 1 21 22 1 25 3*6 SPARE
SPACE 1 23 24 1 25 3*6 SPARE
TOTAL 3475 3400 2750 TOTAL 7250 4500 5750
TOTAL BUS LOAD 10.7 7.9 8.5

TOTAL CONNECTED LOAD 27.1 KVA FEEDER SIZE (4*25)+ 1*16 mm2
FUTURE FACTOR 20%
DEMAND FACTOR 1 FEEDER TYPE CU/XLPE/PVC LPF-2
TOTAL DEMAN LOAD 32.6 KVA
DEMAND CURRENT 47 A