TEST CERTIFICATE
Megha Power SolutionS Office & Laboratory: Sai Ganesh Building, Ground Floor
( Testing and Diagnostic Solutions ) Opp Morya Complex,Balaji Nagar,Thakurli(E),Thane-421201
Email - mps.m10314@[Link] Registered Office: 201, Hawsa CHS,
Contact No. - 9920234842 / 8828085626 Thakurli(East), Thane ,421201 (MH)
Issued to :- CGM Certificate Date: 24-01-2025
DFCCIL Testing Date: 06-01-2025
TUNDLA
Reference - PO No : 00922200073176 Dated :10/03/2023 Subject : Testing of 3rd Harmonics in Lightening arrestors (LA)
Site of Testing DANWAR/SP Ambient Temperature(°C) : - Relative Humidity : -
Equipment Type LA Code Designation : - Serial No: -
Make - Rating (KVA): - Voltage Ration (volts): -
Oil Qty - [Link] : - Year of Mfy : -
TEST DATA
Certificate No:- MPS/LA/ 2023/ 1739 Ref :- IEC 600999
Code - Location LA-005
Make - Serial No. -
Rating (KV) 42KV
Testing Date Syst Volt Temp °C I total (μA) I THRC (μA) I THRC corrected (μA)
06-01-2025 25KV 19 486 7 24
Remark :- Acceptable
Certificate No:- MPS/LA/ 2023/ 1740
Code - Location LA-006
Make - Serial No. -
Rating (KV) 42KV
Testing Date Syst Volt Temp °C I total (μA) I THRC ( μA) I THRC corrected (μA)
06-01-2025 25KV 18 486 6 21
Remark :- Acceptable
Certificate No:- MPS/LA/ 2023/ 1741
Code - Location LA-003
Make - Serial No. -
Rating (KV) 42KV
Testing Date Syst Volt Temp °C I total (μA) I THRC ( μA) I THRC corrected (μA)
06-01-2025 25KV 19 460 9 32
Remark :- Acceptable
Certificate No:- MPS/LA/ 2023/ 1742
Code - Location LA-004
Make - Serial No. -
Rating (KV) 42KV
Testing Date Syst Volt Temp °C I total (μA) I THRC ( μA) I THRC corrected (μA)
06-01-2025 25KV 19 461 8 28
Remark :- Acceptable
Equipment Detail : LEAKAGE CURRENT MONITORING KIT Make:- SCOPE Model No.:- SA30i+
Ref IEC 60099-5 [Link].:- 3025.00 AJ 0231 Calibrated Due on:- 23-06-2025
Limits :- 1 - 100 Acceptable
101 - 300 Low alarm
301 - 500 Medium alarm Authorised Signatory
501 - 600 High alert For Megha Power Solutions
> 600 Unacceptable