AHP - I&O Rev D
AHP - I&O Rev D
2
Installation & Operation Manual
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or
to important information concerning the life of the product.
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious
⚠DANGER
injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious
⚠WARNING
injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate
⚠CAUTION injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not
CAUTION avoided, may result in property damage.
NOTICE indicates special instructions on installation, operation, or maintenance that are important but not
NOTICE related to personal injury or property damage.
3
Installation & Operation Manual
4
Installation & Operation Manual
5
Installation & Operation Manual
Introduction
Thank you for purchasing this heat pump water heater. Properly PREPARING FOR INSTALLATION
installed and maintained, it should give you years of trouble-
free service. 1. Read the entire manual carefully. If you don’t follow
the safety rules, the heat pump water heater may
Abbreviations found in this instruction manual include:
not operate safely. It could cause DEATH, SERIOUS
• HPWH - Heat Pump Water Heater
BODILY INJURY AND/OR PROPERTY DAMAGE.
• ANSI - American National Standards Institute
This manual contains instructions for the installation,
• ASME - American Society of Mechanical Engineers
operation, and maintenance of the heat pump water
• NEC - National Electrical Code
heater (HPWH). It also contains warnings throughout
• NFPA - National Fire Protection Association
the manual that you must read and be aware of. All
• AHRI - Air-conditioning, Heating and Refrigeration
warnings and all instructions are essential to the
Institute
proper operation of the HPWH and your safety.
READ THE ENTIRE MANUAL BEFORE ATTEMPTING
INSTALLER QUALIFICATIONS
TO INSTALL OR OPERATE THIS WATER HEATING
Installation and service of this water heater requires ability APPLIANCE.
equivalent to that of a Qualified Agency (as defined by Detailed installation diagrams are in this manual. These
ANSI below) in the field involved. Installation skills such as diagrams will serve to provide the installer with a reference
plumbing, and electrical supply are required in addition to for the materials and suggested methods of piping. IT IS
electrical testing skills when performing service. NECESSARY THAT ALL WATER PIPING AND THE
This heat pump water heater contains R-513A refrigerant and is ELECTRICAL WIRING BE INSTALLED AND CONNECTED
regulated as a stationary refrigeration appliance under Section AS SHOWN IN THE DIAGRAMS.
608 of the Clean Air Act. Servicing of the refrigeration circuit Particular attention should be given to the installation of the
must only be performed by agencies or individuals possessing system (tank) temperature control.
Type II or Universal certification as defined in Section 608 of
the Clean Air Act.
ANSI Z2223.1 2006 Sec. 3.3.83: “Qualified Agency” - “Any
individual, firm, corporation or company that either in person
or through a representative is engaged in and is responsible
for (a) the installation, testing or replacement of piping or
(b) the connection, installation, testing, repair or servicing of
appliances and equipment; that is experienced in such work;
that is familiar with all precautions required; and that has
complied with all the requirements of the authority having
jurisdiction.
6
Installation & Operation Manual
Introduction (continued)
7
Installation & Operation Manual
8
Installation & Operation Manual
Model 60K 13 31
4
19 30
1 32 22
21
23 20
2 34
35
16
25 17
Front View (with lower panel removed) - Front View (with lower panel & control panel
Model 60K removed) - Model 60k
33
3
24 26
7
6
9 5
8
27
18
29 12
28
28 15 14
Rear View (HEX grill removed) - Model 60K Rear View (lower rear panel removed) - Model 60K
9
Installation & Operation Manual
Model 60K
33
11
10
29
Left Side (inside unit) - Model 60k Front View (HEX grill removed) - Model 60k
Model 140K
35 13 31
19
30
32 4
1
20
22
25
34 17 16
2 17 21 23
Front View (with lower panel removed)- Front View (with lower panel & control panel
Model 140K removed)- Model 140k
10
Installation & Operation Manual
Model 140K
33 3
26
24
9 7
5 8
27 6
18
29 12
15
28 14
Rear View (HEX grill removed) - Model 140K Rear View (lower rear panel removed) - Model 140K
33
11
10
29
Left Side (inside unit) - Model 140k Front View (HEX grill removed) - Model 140k
11
Installation & Operation Manual
Manifold
39
38
36
Display Box
37
KƵƚůĞƚtĂƚĞƌ
ŽŵƉƌĞƐƐŽƌ
ĐĐƵŵƵůĂƚŽƌ ϰtĂLJsĂůǀĞ ŽŶĚĞŶƐĞƌ
KƵƚůĞƚtĂƚĞƌ
/ŶůĞƚtĂƚĞƌ
ĐĐƵŵƵůĂƚŽƌ ϰtĂLJsĂůǀĞ ŽŶĚĞŶƐĞƌ ǀĂƉŽƌĂƚŽƌƐ ZĞĐĞŝǀĞƌdĂŶŬ
/ŶůĞƚtĂƚĞƌ WƵŵƉ
ǀĂƉŽƌĂƚŽƌƐ ZĞĐĞŝǀĞƌdĂŶŬ s͛Ɛ ^ŝŐŚƚ'ůĂƐƐ &ŝůƚĞƌƌŝĞƌ
WƵŵƉ
s͛Ɛ ^ŝŐŚƚ'ůĂƐƐ &ŝůƚĞƌƌŝĞƌ
ĞĨƌŽƐƚKƉĞƌĂƚŝŽŶ
ĞĨƌŽƐƚKƉĞƌĂƚŝŽŶ ŽŵƉƌĞƐƐŽƌ
KƵƚůĞƚtĂƚĞƌ
ŽŵƉƌĞƐƐŽƌ
ĐĐƵŵƵůĂƚŽƌ ϰtĂLJsĂůǀĞ ŽŶĚĞŶƐĞƌ
KƵƚůĞƚtĂƚĞƌ
/ŶůĞƚtĂƚĞƌ
ĐĐƵŵƵůĂƚŽƌ ϰtĂLJsĂůǀĞ ŽŶĚĞŶƐĞƌ ǀĂƉŽƌĂƚŽƌƐ ZĞĐĞŝǀĞƌdĂŶŬ
/ŶůĞƚtĂƚĞƌ WƵŵƉ
ǀĂƉŽƌĂƚŽƌƐ ZĞĐĞŝǀĞƌdĂŶŬ s͛Ɛ ^ŝŐŚƚ'ůĂƐƐ &ŝůƚĞƌƌŝĞƌ
WƵŵƉ
s͛Ɛ ^ŝŐŚƚ'ůĂƐƐ &ŝůƚĞƌƌŝĞƌ
13
Installation & Operation Manual
REFRIGERANT CHARGE
The HPWH is factory-charged with R-513A refrigerant. The
refrigerant charge is weighed in at the factory. It should not
be necessary to add or remove refrigerant during installation,
startup, or service.
STORAGE RECOMMENDATIONS
The HPWH units can be stored indoors or outdoors. Do not
stack units or stack other construction materials on the units
while in storage.
The HPWH units contain electrical/electronic components
and should only be stored in conditions between -20°F to
120°F (-29°C to 49°C) and 5 to 95 percent relative humidity.
Electrical components are not moisture-tolerant.
Note: The limited warranty does not cover damage to the unit
or controls due to negligence during storage.
EQUIPMENT DISPOSAL
This heat pump water heater contains R-513A refrigerant
and is regulated as a stationary refrigeration appliance under
Section 608 of the Clean Air Act. Disposal of this unit must be
performed in accordance with the provisions in Section 608 of
the Clean Air Act and any state or local regulations that may
also apply.
14
Installation & Operation Manual
Performance
NOTES:
1. Models 200 through 350 are composed of combinations of models 60 and 140 which are the certified units.
2. Performance rated at 80.6°F ambient temperature with 63% relative humidity; Inlet water at 70°+ 1°F, Outlet water at 120°F +
5°F.
3. Supply Voltage - 480V/3-phase 60 Hz
4. Variable fan speed across different ambient temperatures.
Maximum allowed working pressure
NOTICE
on a refrigeration circuit:
High side - 347 psi
Low side - 61 psi
Maximum water pressure - 175 psi
The table above lists performance information on 5 unit sizes. These
sizes are based on combinations of the 2 smaller models, AHP060
and AHP140. The table below shows the combination of models
needed to get the desired model performance.
Desired Model
Combination of Models
Performance
AHP200 AHP060 + AHP140
AHP280 AHP140 x 2
AHP350 AHP140 x 2 +AHP060
When servicing this unit, verify the power to the unit is turned off prior to opening the control cabinet door.
15
Installation & Operation Manual
Costs to correct installation errors are not covered under the The HPWH unit can be installed in space where freezing
limited warranty. Before locating the water heater, check: temperature will occur, and is programmed to cycle the pump
to keep water flowing. Heat tape is also installed on the drain
1. Check for nearby connection to: pan, condenser, and water inlet and requires power to the unit.
• Water piping Damage caused by exposure to freezing temperatures is not
• Ducting Options covered under the limited warranty.
• Electrical Power
Coastal regions
2. Locate the appliance so that if water connections should
leak, water damage will not occur. When such locations The exterior materials and components supplied on the
cannot be avoided, it is recommended that a suitable drain HPWH have been tested, and passed the requirements for UL
pan, adequately drained, be installed under the appliance. 60335-2-40.
Under no circumstances is the manufacturer to be held Indoor
responsible for water damage in connection with this When installed indoors it may be necessary to duct HPWH
appliance, or any of its components. outlet air out of the space to prevent over cooling of the room
3. Check area around the water heater. Remove any corrosive which will prevent optimal performance of the water heater.
materials. Ducting air into the water heater may be necessary to maintain
4. If a new water heater will replace an existing water heater, a sufficient air supply to run the unit.
check for and correct system problems, such as system Heat source
leaks causing oxygen corrosion or heat exchanger cracks
from hard water deposits. The HPWH unit should be located where there is an adequate
source of ambient heat and where the cooling benefit can
be utilized when possible. If installation in a space with an
adequate heat source is not possible the HPWH unit can be
ducted to/from another space such as a boiler room or to the
outdoors where sufficient heat is available.
16
Installation & Operation Manual
Clearances: NOTICE
Multiple appliances can be installed side by
side with no clearances between adjacent
1. Recommended clearances for service access, ducting or
appliances because the appliances are
air flow from the top of the unit is 48 inches.
approved for zero clearances; however,
2. To ensure optimal performance a minimum of 36 inches service access will be limited from the sides.
clearances required from the back, and front of the Consult with the local inspection authority
HPWH unit and any wall obstruction. When installed for approval.
on an equipment pad the HPWH must be level.
If you do not provide the recommended
NOTICE
Front / Rear ............................................................................... 36" service clearances shown, it may not be
Top .............................................................................................. 48" possible to service the appliance without
removing it from the space. These
clearances are also needed for adequate air
flow.
TOP
48"
REAR
36"
FRONT
36"
17
Installation & Operation Manual
Fuses supplied with the unit and tested are time delay fuses.
18
Installation & Operation Manual
Table 1-2 Voltage & Amperage Ratings Table 1-3 Corrosive Contaminants and Sources
Model Volts/Phase/Hz FLA Products to avoid:
AHP060 440-480/3/60 16.9
Spray cans containing chloro/fluorocarbons
AHP140 440-480/3/60 31.9
AHP200 440-480/3/60 48.8 Permanent wave solutions
AHP280 440-480/3/60 63.8 Chlorinated waxes/cleaners
AHP350 440-480/3/60 80.7
Chlorine-based swimming pool chemicals
Note: Amp draws are calculated from base units AHP060
and AHP140 in combinations listed on page 15. Calcium chloride used for thawing
Sodium chloride used for water softening
Refrigerant leaks
Paint or varnish removers
Hydrochloric acid/muriatic acid
Cements and glues
19
Installation & Operation Manual
Back
LAG BOLTS
(QTY. 2)
bars are furnished. The side panels and top of the unit are
not constructed to handle significant force from the sides
Figure 2-4 Remove lower front and rear panels before Assemble water manifold
lifting unit The inlet and outlet manifolds are located in the parts box
along with the mounting bracket and hardware. Figure 2-8
shows the manifold assembled and connected to the base.
)52175($53$1(/7$%6
0,1
6,'(
Figure 2-6 Water heater and forklift fork position Figure 2-9 Multi-Manifold Assembly
21
Installation & Operation Manual
Water Connections
Water piping must be installed in accordance with the
instructions in this manual and all local plumbing codes having
jurisdiction. See Piping Diagrams on pages 28-35 as a reference
for these instructions.
Installation Instructions
1. This HPWH unit is not designed to supply hot water
directly to hot water fixtures. The HPWH unit must be
installed with separate storage tanks as shown in the water
piping diagrams in this manual.
2. Water lines installed between the storage tank and the
HPWH unit MUST NOT be less than the water pipe
connection sizes on the unit. See Figures 4-2 thru 4-9 on
pages 28-35.
3. The HPWH should be plumbed directly to the storage
Electrical Connections tanks.
Correct Voltage and Phase 4. The cold water supply can be connected into the heat
Ensure the power supply voltage and phase at the job site pump inlet manifold or lowest tank connection.
matches the power supply ratings listed on the HPWH rating 5. The outlet (supply) water form the HPWH unit should
label BEFORE INSTALLATION BEGINS. connect to the inlet connection on the storage tank, and
Voltage applied to the HPWH should not vary more than +6% should be located above the inlet connection.
to -6% of the voltage requirement listed on the HPWH rating 6. The inlet (return) water entering the HPWH should
label for satisfactory operation. connect to the inlet connection on the storage tank lower
Energizing the HPWH with the wrong voltage and/or phase than the tank outlet connection.
may cause permanent damage to HPWH components. Damage 7. A T&P valve must be installed in the designated opening on
resulting from applying the wrong power supply voltage or the storage tank per the tank manufacturer’s requirements.
phase to the HPWH is not covered under the limited warranty. See Temperature - Pressure Relief Valve on page 26.
Branch Circuit Disconnect Switch 8. For optimal performance minimize the equivalent length
The power supply wiring and equipment grounding must be of water piping between the HPWH and storage tank.
installed in accordance with local codes or, in the absence of 9. Building hot water recirculation loop should be connected
local codes, the National Electrical Code, ANSI/ NFPA 70 or to the inlet of the backup water heater on two tank
the Canadian Electrical Code, CSA C22.1. preheat configurations or to the storage tank on single
Install an adequately fused disconnect switch as close to the tank configurations. The recirculating pump MUST BE
units as possible. See unit rating label for maximum fuse size controlled by a field supplied thermostat installed in the
(MFS). building recirculation return line near the storage tank
or back up heater. The thermostat should stop pump
Run the power supply lines from the disconnect to the control operation the moment the recirculation line is hot.
box at the top back panel of the unit. Connect the lines to the
terminals on input side of power distribution block L1, L2 & L3
for three phases. Connect ground wire to ground lug. If out of
phase the HPWH will shut down and display error.
23
Installation & Operation Manual
4 System Piping
Read all installation requirements in this manual before *Please note that these illustrations are
NOTICE meant to show system piping concept only,
installation begins.
the installer is responsible for all equipment
The water piping installation must conform to these instructions and detailing required by local codes.
and to all local and national code authority having jurisdiction.
Costs to diagnose, perform service and repair damage caused Cold Water Supply
by installation errors are not covered under the limited Cold water supply lines should be connected directly to the
warranty. HPWH inlet or T fitted into the inlet (return) water piping.
Costs to correct installation errors are not covered under the Water Pressure
limited warranty.
System water pressure should be maintained above 12 PSI.
System water piping methods Local code may require, and the manufacturer recommends,
Observe a minimum of 1/4 inch clearance around all installing a pressure reducing valve (PRV) in the cold water
un-insulated hot water pipes when openings around the pipes supply to the building to maintain consistent water pressure.
are not protected by non-combustible materials. Closed Water Systems
Water connections Water supply systems may, because of code requirements or
The inlet and outlet water connections on the AHP60- AHP140 such conditions as high line pressure, among others, have
are 1-1/4 flange, but the manifolds provided are 1-1/2 NPT. installed devices such as pressure reducing valves, check valves,
and back flow preventers. Devices such as these cause the water
General Piping Information system to be a closed system.
Basic steps are listed below along with illustrations on the Water Chemistry
following pages (FIG. 4-2 thru 4-9), which will guide you
through the installation of the Veritus water heater. Heating of high hardness and/or high total dissolved solids
1. Connect the manifold mounting bracket to the back of water is not recommended for the circulating pump based on
the unit. the water chemistry of the water to be heated. See Table 9-1 in
Start-up Section for recommendations.
2. Connect the inlet manifold to the inlet side of the water
heater with pump connected. Water with a hardness of less than 5 grains per gallon will
usually have a pH which can be aggressive and corrosive
3. Connect the outlet manifold to the outlet side of the water causing non-warrantable damage to the pump, and associated
heater. piping. Corrosion due to water chemistry generally shows up
4. Connect the cold water supply to the inlet side of the water first in the hot water system because heated water increases the
heater. rate of corrosive chemical reactions.
5. Connect the hot water supply to the outlet side of the Condensate Removal
water heater. The HPWH unit produces condensate which must be
6. Install a back flow preventer on the cold feed makeup discharged. If there is no drain easily accessible, a condensate
water line. lift pump must be installed to discharge the condensate to a
remote location. See Condensate Drain Line on page 24 for
7. Install an expansion tank on the system supply. Consult the installation instructions.
tank manufacturer’s instruction for specific information
relating to tank installation. Size the expansion tank for Contaminated Water
the required system volume and capacity.
This HPWH unit must not be used to heat any fluid other than
8. Install a drain valve at the lowest point of the system. water. Corrosive chemicals must not be introduced into the
9. Install field supplied relief valve to the water outlet in waterways in this HPWH unit.
accordance with ASME Boiler and Pressure Vessel Code.
Pipe the discharge of the safety relief valve to a suitable
drain to prevent injury in the event of pressure relief.
Provide piping that is the same size as the safety relief valve
outlet. Never block the outlet of the safety relief valve.
See the piping illustrations included in this section, Figures 4-2
thru 4-9, for suggested guidelines in piping the Veritus water
heater.
25
Installation & Operation Manual
4 System Piping
Check Valves:
Scalding
Field supplied. Check valves are recommended for installation
This water heater can deliver scalding temperature water as shown in Figures 4-2 thru 4-9.
at any faucet in the system. Be careful whenever using hot
Water Heater Isolation Valves:
water to avoid scalding injury. Certain appliances such as
dishwashers and automatic clothes washers may require Field supplied. Full port ball valves are required. Failure to use
increased temperature water. By setting the thermostat on full port ball valves could result in a restricted flow rate through
this water heater to obtain the increased temperature water the water heater.
required by these appliances, you may create the potential for Anti-scald Mixing Valve:
scald injury. To protect against injury, you should install a
mixing valve in the water system. This valve will reduce point Field supplied. An anti-scald mixing valve is recommended
of discharge temperature by mixing cold and hot water in when storing domestic hot water above 115°F.
branch supply lines. Such valves are available from the local Unions:
plumbing supplier. Field supplied. Recommended for unit serviceability.
Figure 4-1 Scald Warning Label Located on the Temperature and Pressure Relief Valve:
Appliance Field Supplied. The temperature and pressure relief valve
is sized to ASME specifications. Storage tanks may require
additional valves depending on local codes.
This heat pump water heater should only be connected
to a storage tank with a properly rated/sized and certified
combination temperature - pressure relief valve. The valve
must be certified by a nationally recognized testing laboratory
that maintains periodic inspection of production of listed
equipment of materials as meeting the requirements for Relief
Valves for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4,
and the code requirements of ASME. The pressure rating of the
The following chart (Table 4-1) details the relationship of water
T&P valve should always be rated equal to or below the working
temperature and time with regard to scald injury and may be
pressure rating of the storage tank or water heater, whichever
used as a guide in determining the safest water temperature for
rating is lower. Contact the manufacturer of the storage tank
your applications.
for assistance in sizing of a temperature and pressure relief
Table 4-1 Approximate Time / Temperature Scald Chart valve. Follow the storage tank manufacturer’s instructions
APPROXIMATE TIME / TEMPERATURE regarding the proper installation of these products.
RELATIONSHIPS IN SCALDS
120°F More than 5 minutes
125°F 1 1/2 to 2 minutes
130°F About 30 seconds
135°F About 10 seconds
140°F Less than 5 seconds
145°F Less than 3 seconds
150°F About 1 1/2 seconds
155°F About 1 second
Piping Components
Water Heater System Piping:
Water heater system piping MUST be sized per the pipe
requirements listed on the tables included with the piping Tank Sensor
diagrams on pages 28-35. The recommended length of
equivalent piping between the tank and water heater should Lochinvar supplies a tank sensor. The tank sensor must be
be kept to a maximum of 500 feet. Reducing the pipe size or installed in the tapping provided in the lower/mid section of
increasing piping distance can restrict the flow rate through the the storage tank to achieve proper operation. As shipped from
water heater, causing high limit shutdowns and poor system the factory, the tank sensor is in the literature package shipped
performance. with the unit. Placing the sensor in the tapping provided on the
storage tank will improve temperature response and prevent
short cycles of operation. While setting the tank setpoint
26
choose the sensor position connected at the system board.
Installation & Operation Manual
4 System
SINGLE Piping
PASS, RETURN TO PRIMARY:
ONE HEAT PUMP, ONE TANK
Figure 4-2 Single Pass - One Heater, One Tank
NOTES:
1. DRAWING ILLUSTRATES SUGGESTED PIPING CONFIGURATION
Min. Required Pipe Size in NPT
LOCAL CODES AND ORDINANCES MAY HAVE ADDITIONAL REQUIREMENTS
Model
2. DO NOT INCLUDE CHECK VALVES BETWEEN HEAT PUMP OUTLET AND TANK UNLESS REQUIRED ( ≤ 5 ft/s @14GPM )
BY CODE. INTERNAL HEAT PUMP VALVE PREVENTS BACKFLOW
3. CHECK VALVE REQUIRED TO PREVENT BACKFLOW TO COLD WATER SUPPLY AHP060 1 - 1/4
4. SYSTEM REQUIRES ONE TANK SENSOR BUT WILL SUPPORT UP TO SIX TANK SENSORS
AHP140 1 - 1/4
RECIRC RETURN SENSOR (OPTIONAL) AHP200 1 - 1/2
AHP280 1 - 1/2
BUILDING
RECIRC AHP350 2
SEE NOTE 3
THERMAL STORAGE
HP WATER HEATER
TANK SENSOR
⚠ CAUTION The piping will not support the weight of the water heater circulator pump. Do not attempt to support
the weight of the water heater circulator pump with the piping or its accessories. Refer to the pump
manufacturer’s installation instructions. Failure to comply could result in severe personal injury, death, or
substantial property damage.
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
NOTICE
for all equipment. The installer must follow all manufacturer’s instructions for each system component. The
28 installer is responsible for compliance with local codes.
Installation & Operation Manual
4
SINGLE PASS, RETURN TO PRIMARY:
System Piping (continued)
ONE HEAT PUMP, ONE TANK, PARALLEL BACKUP
Figure 4-3 Single Pass - One Heater, One Tank with Parallel Backup
NOTES:
1. DRAWING ILLUSTRATES SUGGESTED PIPING CONFIGURATION
LOCAL CODES AND ORDINANCES MAY HAVE ADDITIONAL REQUIREMENTS
Min. Required Pipe Size in NPT
2. DO NOT INCLUDE CHECK VALVES BETWEEN HEAT PUMP OUTLET AND TANK UNLESS REQUIRED Model
BY CODE. INTERNAL HEAT PUMP VALVE PREVENTS BACKFLOW ( ≤ 5 ft/s @14GPM )
3. CHECK VALVE REQUIRED TO PREVENT BACKFLOW TO COLD WATER SUPPLY
4. SYSTEM REQUIRES ONE TANK SENSOR BUT WILL SUPPORT UP TO SIX TANK SENSORS
AHP060 1 - 1/4
AHP140 1 - 1/4
RECIRC RETURN SENSOR (OPTIONAL) AHP200 1 - 1/2
AHP280 1 - 1/2
BUILDING
RECIRC AHP350 2
INSTANTANEOUS
OR
THERMAL STORAGE ELECTRIC TANK
HP WATER HEATER
TANK SENSOR
SEE NOTE 4
SYSTEM RETURN
SENSOR (OPTIONAL)
⚠ CAUTION The piping will not support the weight of the water heater circulator pump. Do not attempt to support
the weight of the water heater circulator pump with the piping or its accessories. Refer to the pump
manufacturer’s installation instructions. Failure to comply could result in severe personal injury, death, or
substantial property damage.
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
NOTICE
for all equipment. The installer must follow all manufacturer’s instructions for each system component. The
installer is responsible for compliance with local codes. 29
Installation & Operation Manual
4 System
SINGLE Piping
PASS RETURN TO PRIMARY:
ONE HEAT PUMP, TWO TANKS
Figure 4-4 Single Pass - One Heater, Two Tanks
NOTES:
1. DRAWING ILLUSTRATES SUGGESTED PIPING CONFIGURATION
LOCAL CODES AND ORDINANCES MAY HAVE ADDITIONAL REQUIREMENTS Min. Required Pipe Size in NPT
Model
2. DO NOT INCLUDE CHECK VALVES BETWEEN HEAT PUMP OUTLET AND TANK UNLESS REQUIRED ( ≤ 5 ft/s @14GPM )
BY CODE. INTERNAL HEAT PUMP VALVE PREVENTS BACKFLOW
3. CHECK VALVE REQUIRED TO PREVENT BACKFLOW TO COLD WATER SUPPLY AHP060 1 - 1/4
4. SYSTEM REQUIRES ONE TANK SENSOR BUT WILL SUPPORT UP TO SIX TANK SENSORS
AHP140 1 - 1/4
AHP200 1 - 1/2
RECIRC RETURN SENSOR (OPTIONAL) AHP280 1 - 1/2
AHP350 2
BUILDING
RECIRC
SEE NOTE 3
TANK
SENSOR SYSTEM RETURN
SENSOR (OPTIONAL)
⚠ CAUTION The piping will not support the weight of the water heater circulator pump. Do not attempt to support
the weight of the water heater circulator pump with the piping or its accessories. Refer to the pump
manufacturer’s installation instructions. Failure to comply could result in severe personal injury, death, or
substantial property damage.
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
NOTICE
for all equipment. The installer must follow all manufacturer’s instructions for each system component. The
30 installer is responsible for compliance with local codes.
Installation & Operation Manual
4SINGLE
System Piping
PASS RETURN TO SWING TANK: (continued)
TWO HEAT PUMPS, ONE TANK, SWING TANK
Figure 4-5 Single Pass - Two Heaters, One Tank with Swing Tank and Gas Backup Heat
NOTES:
1. DRAWING ILLUSTRATES SUGGESTED PIPING CONFIGURATION
LOCAL CODES AND ORDINANCES MAY HAVE ADDITIONAL REQUIREMENTS
2. DO NOT INCLUDE CHECK VALVES BETWEEN HEAT PUMP OUTLET AND TANK UNLESS REQUIRED Min. Required Pipe Size in NPT
Model
BY CODE. INTERNAL HEAT PUMP VALVE PREVENTS BACKFLOW ( ≤ 5 ft/s @14GPM )
3. CHECK VALVE REQUIRED TO PREVENT BACKFLOW TO COLD WATER SUPPLY
4. SYSTEM REQUIRES ONE TANK SENSOR BUT WILL SUPPORT UP TO SIX TANK SENSORS AHP060 1 - 1/4
AHP140 1 - 1/4
AHP200 1 - 1/2
RECIRC RETURN SENSOR (OPTIONAL)
AHP280 1 - 1/2
BUILDING AHP350 2
RECIRC
SEE NOTE 3
SWING TANK
TANK
SYSTEM RETURN
SENSOR
SENSOR (OPTIONAL)
⚠ CAUTION The piping will not support the weight of the water heater circulator pump. Do not attempt to support
the weight of the water heater circulator pump with the piping or its accessories. Refer to the pump
manufacturer’s installation instructions. Failure to comply could result in severe personal injury, death, or
substantial property damage.
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
NOTICE
for all equipment. The installer must follow all manufacturer’s instructions for each system component. The
installer is responsible for compliance with local codes. 31
Installation & Operation Manual
4 System
SINGLE Piping
PASS RETURN TO SWING TANK:
TWO HEAT PUMPS, ONE TANK, SWING TANK
Figure 4-6 Single Pass - Two Heaters, One Tank with Swing Tank
NOTES:
1. DRAWING ILLUSTRATES SUGGESTED PIPING CONFIGURATION
LOCAL CODES AND ORDINANCES MAY HAVE ADDITIONAL REQUIREMENTS
2. DO NOT INCLUDE CHECK VALVES BETWEEN HEAT PUMP OUTLET AND TANK UNLESS REQUIRED Min. Required Pipe Size in NPT
Model
BY CODE. INTERNAL HEAT PUMP VALVE PREVENTS BACKFLOW ( ≤ 5 ft/s @14GPM )
3. CHECK VALVE REQUIRED TO PREVENT BACKFLOW TO COLD WATER SUPPLY
4. SYSTEM REQUIRES ONE TANK SENSOR BUT WILL SUPPORT UP TO SIX TANK SENSORS AHP060 1 - 1/4
AHP140 1 - 1/4
RECIRC RETURN SENSOR (OPTIONAL)
AHP200 1 - 1/2
BUILDING
AHP280 1 - 1/2
RECIRC
AHP350 2
SWING TANK
TANK
SENSOR
SYSTEM RETURN
SENSOR (OPTIONAL)
⚠ CAUTION The piping will not support the weight of the water heater circulator pump. Do not attempt to support
the weight of the water heater circulator pump with the piping or its accessories. Refer to the pump
manufacturer’s installation instructions. Failure to comply could result in severe personal injury, death, or
substantial property damage.
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
NOTICE
for all equipment. The installer must follow all manufacturer’s instructions for each system component. The
32 installer is responsible for compliance with local codes.
Installation & Operation Manual
4SINGLE
TWO
PASS RETURN TO PRIMARY:
System Piping
HEAT PUMPS, TWO TANKS (continued)
SEE NOTE 3
⚠ CAUTION The piping will not support the weight of the water heater circulator pump. Do not attempt to support
the weight of the water heater circulator pump with the piping or its accessories. Refer to the pump
manufacturer’s installation instructions. Failure to comply could result in severe personal injury, death, or
substantial property damage.
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
NOTICE
for all equipment. The installer must follow all manufacturer’s instructions for each system component. The
installer is responsible for compliance with local codes. 33
Installation & Operation Manual
4 System Piping
SINGLE PASS RETURN TO PRIMARY:
Figure
TWO HEAT4-8PUMPS,
Single Pass
TWO - Two Heaters,
TANKS, Two Tanks
ELECTRIC with Electric Backup
BACKUP
SYSTEM SUPPLY
SENSOR (OPTIONAL)
SEE NOTE 3
SYSTEM RETURN
SENSOR (OPTIONAL)
TANK
SENSOR
BACKUP PUMP
⚠ CAUTION The piping will not support the weight of the water heater circulator pump. Do not attempt to support
the weight of the water heater circulator pump with the piping or its accessories. Refer to the pump
manufacturer’s installation instructions. Failure to comply could result in severe personal injury, death, or
substantial property damage.
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
NOTICE
for all equipment. The installer must follow all manufacturer’s instructions for each system component. The
installer is responsible for compliance with local codes.
34
Installation & Operation Manual
4 System
MULTI Piping
PASS, RETURN TO PRIMARY: (continued)
ONE HEAT PUMP, ONE TANK
Figure 4-9 Multi Pass - One Heater, One Tank
NOTES:
1. DRAWING ILLUSTRATES SUGGESTED PIPING CONFIGURATION
LOCAL CODES AND ORDINANCES MAY HAVE ADDITIONAL REQUIREMENTS Min. Required Pipe Size in NPT
Model
2. DO NOT INCLUDE CHECK VALVES BETWEEN HEAT PUMP OUTLET AND TANK UNLESS REQUIRED
BY CODE. INTERNAL HEAT PUMP VALVE PREVENTS BACKFLOW
( ≤ 5 ft/s @14GPM )
3. CHECK VALVE REQUIRED TO PREVENT BACKFLOW TO COLD WATER SUPPLY AHP060 1 - 1/4
4. SYSTEM REQUIRES ONE TANK SENSOR BUT WILL SUPPORT UP TO SIX TANK SENSORS
AHP140 1 - 1/4
RECIRC RETURN SENSOR (OPTIONAL)
AHP200 1 - 1/2
AHP280 1 - 1/2
BUILDING
RECIRC
AHP350 2
SEE NOTE 3
SYSTEM SUPPLY
SENSOR (OPTIONAL)
THERMAL STORAGE
HP WATER HEATER
TANK SENSOR
SEE NOTE 4
SYSTEM RETURN
SENSOR (OPTIONAL)
⚠ CAUTION The piping will not support the weight of the water heater circulator pump. Do not attempt to support
the weight of the water heater circulator pump with the piping or its accessories. Refer to the pump
manufacturer’s installation instructions. Failure to comply could result in severe personal injury, death, or
substantial property damage.
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
NOTICE
for all equipment. The installer must follow all manufacturer’s instructions for each system component. The
installer is responsible for compliance with local codes. 35
Installation & Operation Manual
Negative Pressure
Ducting supply air only to an alternate location, such as the
outdoors, may cause excessive negative air pressure inside
The supply (outlet) air from a HPWH installed in a garage or a the building envelope. Excessive negative pressure inside the
unit drawing return (inlet) air from a garage or any area where building structure may result in cold or hot air from outdoors
solvents or other chemicals that emit potentially harmful fumes being drawn inside the building and place additional load on
are stored or automobiles are located must never be ducted space heating and cooling equipment. Negative air pressure
to any other space inside the building structure. This would in buildings can also cause reverse flow in chimneys and gas
include all occupied and unoccupied spaces such as attics or vents.
basements. Potentially harmful fumes and vapors could be
introduced into occupied spaces. See Unit Placement on page Positive Pressure
16. Ducting return air only from an alternate location, such as the
outdoors, may cause excessive positive air pressure inside the
Duct Sizing building envelope.
Supply and return air ducting must be sized properly to Excessive positive pressure inside the building structure may
ensure requirements for the total equivalent supply and return place additional load on space heating and cooling equipment
duct lengths allowed. Exceeding those maximum lengths will by interfering with the delivery of conditioned air.
adversely affect the operation of the heat pump. Consult the
factory for sizing. When to Install Ducting
Duct Insulation HPWH units are often installed in unoccupied spaces or
equipment rooms where there is an ample source of ambient
The cooled air from the HPWH may be below room dew point. heat and no need to redirect the supply air to another location.
Insulate the supply duct to prevent dripping from moisture Ductwork is not necessary in these circumstances. See Heat
condensing on the duct. It is not necessary to insulate return Source on page 16.
ducts unless the air in the return duct is colder than the room
air. Also consider insulating all ductwork to reduce blower Typical applications when ducting is installed.
noise from the unit. • Duct supply (outlet) air to alternate location for spot
cooling or discard supply air not wanted in the installed
Make Duct Connections space.
Install all ductwork to and from unit in accordance with all • Duct return (inlet) air from an alternate location (outdoors,
applicable codes. Duct construction must allow unit to operate warm equipment room) to optimize efficiency.
within the limits of the unit external static pressure as in the
HPWH unit’s performance and specification sheets. See Table
1-1 on page 18 also. Use flexible connections to minimize duct-
to-duct alignment problems and noise transmission. Install
ductwork, accessory grilles, and plenums so that they do not
restrict access to the optional filter (consult factory for merv
rating), and so they prevent dirt, dust, and debris from settling
in the unit.
36
Installation & Operation Manual
Supply Air Ducting • The air temperature drops approximately 12°F to 20°F (7°C
to 11°C) as it flows through the HPWH unit. If the return air
Observe and follow these guidelines and instructions when
to the HPWH unit is derived from a location that is above
installing supply (outlet) air duct:
80°F (27°C) the supply air from the HPWH unit will not be
• When duct work is not field connected to the supply air suitable for offsetting the building cooling load. This will
outlet on the HPWH unit a field supplied safety guard often be the case when the return air is ducted from a warm
must be installed over the supply air connection. Failure equipment room or from the outdoor atmosphere. In these
to comply could result in severe injury. circumstances do not duct supply air to another location for
• All duct work and plenums shall be field supplied or spot cooling.
fabricated. • Ducting supply air only to an alternate location, such as the
• Cooling output (supply air) from the HPWH is outdoors, may cause excessive negative air pressure inside
supplemental only and must not be factored into sizing the building envelope.
calculations for space cooling equipment. Cooling output • Provision must be made to prevent a negative pressure in
is only produced when the HPWH is operating to satisfy a the installed space or building envelope. Return air must be
water heating demand. Once the storage tank temperature supplied to the HPWH from the alternate location through
is satisfied, the HPWH will stop until the next water ducting or louvers that communicate with the alternate
heating demand is initiated regardless of space cooling location where the supply ducting terminates. See the Return
needs. Air Ducting section that follows.
• All duct work and plenums shall be field supplied or • When installing the duct, install a flex connector between
depending on the temperature of the air entering the the duct and unit for serviceability.
HPWH unit the supply air may not be suitable for
supplemental space cooling purposes. A field supplied/
fabricated flex connector should be added between the
unit and duct for service work when required.
37
Installation & Operation Manual
38
Installation & Operation Manual
6 Outdoor Installations
Outdoor Air Inlet and Outlet
Keep HPWH air intake areas free of obstructions. Keep area
clean and free of corrosive materials. Maintain a minimum
of 36 inches (915 mm) clearance to the air inlet. To avoid a
blocked air inlet or outlet condition, keep the air inlet, air
outlet, and drain clear of leaves, debris, etc.
Do not install outdoor models directly on the ground. You
must install the outdoor unit on a concrete, brick, block, or
other noncombustible pad.
Do not locate unit so that high winds can deflect off of adjacent
walls, buildings, or shrubbery causing recirculation.
Locate unit at least 10 feet (3.05 m) away from any forced air
inlet. See Figure 6-1.
Locate unit at least 3 feet (0.91 m) outside any overhang.
Clearances around outdoor installations can change with time.
Do not allow the growth of trees, shrubs, or other plants to
obstruct the proper operation of the outdoor vent system.
Do not install in locations where rain from building runoff
drains will spill onto the unit.
)25&('$,5,1/(7
)((7
39
Installation & Operation Manual
7 Field Wiring
⚠ WARNING
ELECTRICAL SHOCK HAZARD – For Installation must comply with:
your safety, turn off electrical power supply
1. National Electrical Code and any other national, state,
before making any electrical connections
provincial, or local codes, or regulations.
to avoid possible electric shock hazard.
Failure to do so can cause severe personal 2. In Canada, CSA C22.1 Canadian Electrical Code Part 1,
injury or death. and any local codes.
Line voltage connections
Wiring must be N.E.C. Class 1.
NOTICE 1. Connect 480 VAC 3PH power wiring to the line voltage
If original wiring as supplied with the fuse block in the junction box, as shown in FIG. 7-1.
water heater must be replaced, use only
type 105°C wire or equivalent. 2. Provide and install a fused disconnect (or service switch
sized per the HPWH amp draw (shown on the HPWH
The water heater must be electrically rating plate) as required by the code.
grounded as required by National
Electrical Code ANSI/NFPA 70 – latest 3. For alternate voltages, consult factory.
edition. 4. Route pump wires through the knockouts in the lower
back panel of the unit, as shown in Figure 7-2.
Label all wires prior to disconnection 5. The display panel with require 120 VAC to power the
⚠ CAUTION
when servicing controls. Wiring errors can system board. Route all wires (power wire 18 gauge)
cause improper and dangerous operation. through the conduit using knockouts in the bottom side
of the display panel, as shown in Figure 7-3.
If an optional field-installed E-Stop
⚠ CAUTION
is required, it MUST BE wired in series
with all nongrounded current-carrying
conductors per local and national codes to
ensure proper power disconnect per each
water heater. There is no other electrical
connection to the water heater that serves
as an emergency disconnect.
40
Installation & Operation Manual
+($7&$%/( 1(875$/ :
*5281' *
/,1( %.
1(875$/ :
%2267(5 *5281' *
)$1
/,1( %.
1(875$/ :
':+3803 *5281' *
%.
/,1(
%.
3:06,*1$/287
3803 %/
&20081,&$7,21 3:05()(5(1&(
%5
3:06,*1$/,1
/,1(92/7$*(
:,5,1*.12&.2876
&20081,&$7,21
:,5,1*.12&.2876
41
Installation & Operation Manual
7 Field Wiring
Low Voltage Connections ModBus / BACnet
1. Route all low voltage wires through the knockouts in the When the optional ModBus / BACnet interface module is
bottom of the display panel, and reference connections in installed, the RS-485 ModBus / BACnet cable is connected
Figure 7-5. to these terminals. Use shielded, 2-wire twisted pair cable. If
2. Connect low voltage wiring to the system control board as desired, the shield can be connected to ground by installing a
shown in Figure 7-1 of this manual and the HPWH wiring jumper wire between terminals 1 and 3 on connector X5 on the
diagram. optional ModBus / BACnet interface module.
42
Installation & Operation Manual
43
J14 PUMP RELAYS 1 J4 PUMP RELAYS 2
7
44
24VAC-N RECIRC PUMP 24VAC-N PUMP3
24VAC-L RECIRC PUMP 24VAC-L PUMP3 J1 ECOPORT J7 PC
24VAC-N PUMP2 24VAC-N PUMP4 GND PC_GND
24VAC-L PUMP2 24VAC-L PUMP4 RS485_B PC_B
24VAC RS485_A PC_A
PC_+5V
J13 RELAY OUTPUT J5 RELAY OUTPUT
24VAC-N BACKUP HEAT1 24VAC-N LOUVER
Field Wiring
DISPLAY
J2 DIGITAL IN
GND J22 DIGITAL IN
ENABLE LOUVER PROVING
-- GND
-- --
GND --
NFC KEY
BMS ENABLE
J3 TEMP SENSORS J20 TEMP SENSORS J10 ANALOG OUT J18 ANALOG IN J11 CASCADE
GND GND DGND BMS 0-10V (+) RS485_GND
TANK 1 SYSTEM SUPPLY -- BMS 0-10V (-) RS485_B
GND GND DGND -- RS485_A
TANK 2 SYSTEM RETURN BACKUP 1 OUT -- RS485_GND
GND GND DGND -- RS485_B
TANK 3 RECIRCULATION BACKUP 2 OUT -- RS485_A
GND GND -- -- RS485_GND
TANK 4 OUTDOOR -- -- RS485_B
GND GND RS485_A
TANK 5 AUX1
GND GND
TANK 6 AUX2
Installation & Operation Manual
Installation & Operation Manual
8 Installation Checklist
The list below represents some of the most critical installation 12. Tee into the inlet of the HPWH, but in some cases
requirements that, when overlooked, often result in operational piping directly to the tank is possible. See the Service and
problems, down time and needless parts replacement. This is Installation Notes for Inlet & Outlet Water Temperature
not a complete list. Before performing any troubleshooting on page 24.
procedures use the list below to check for installation errors. 13. Connect building recirculation loop piping to the
Costs to correct installation errors are not covered under the backup water heater inlet on two tank preheat piping
limited warranty. Ensure all installation requirements and configurations.
instructions in this manual have been followed.
14. Ensure the building recirculation loop pump is controlled
Location by a field supplied line thermostat and that it stops
1. Ensure the HPWH is located where there is a adequate the pump when the recirculation line temp exceeds the
supply of ambient heat for optimal performance or that manufacturer’ specifications.
the HPWH is ducted to such a location. 15. The manufacturer recommends installing a strainer at the
2. Ensure required clearances are maintained and there is inlet water line on the HPWH to help prevent scale build
access for servicing. See Clearances on page 17. up in the heat exchanger. Service costs to clear blockages
from the HPWH unit’s heat exchanger due to debris are
3. Ensure the HPWH is properly supported. not covered under the limited warranty.
Air Flow & Ducting
Condensate Drain
4. Ensure all supply and return ductwork connected to the 16. Ensure there is a water trap installed in the condensate
HPWH is properly sized, does not exceed maximum
line at the HPWH. Condensate will not drain without a
equivalent length requirements. Consult the factory for
water trap.
sizing.
17. Ensure the condensate drain is properly connected to
5. Ensure all supply duct work is insulated to prevent the HPWH and draining freely to a suitable floor drain
condensation from forming on the ductwork.
or condensate lift pump that discharges condensate to a
6. Ensure all return air duct is insulated if the return air remote location. See Condensate Drain Line on page 24.
temperatures are expected to fall below the surrounding
room air temperature during normal operation. Electrical
Water Piping 18. BEFORE ENERGIZING THE UNIT ensure the power
supply voltage and phase matches the requirements on the
7. Ensure the outlet (supply) and inlet (return) water piping HPWH rating label. Damage resulting from applying the
connected to the HPWH are not less than the connection
wrong voltage or phase is not covered under the limited
size on the unit.
warranty.
8. The unit pumps will perform best if check valves are not 19. Ensure the power supply breaker or the fuses disconnect
installed between the heat pump outlet and tank unless
switch are within the requirements for the unit as shown
required by code on the system diagrams. The ball valve
on the HPWH rating label.
internal to the unit can prevent hot water short circuiting.
20. Ensure the power supply wiring meets the MCA (Minimum
9. When the HPWH is connected to a storage tank ensure Circuit Ampacity) requirements shown in this manual and
the storage tank is equipped with a properly rated and
on the HPWH data label.
sized Temperature and Pressure (T&P) relief valve.
Refer to the storage tank manufacturer’s instructions 21. Ensure the HPWH is properly grounded according to the
for T&P valve sizing and installation requirements. instructions in this manual and local code requirements.
22. Ensure the power supply connections to the HPWH are
Note: This is a critical installation requirement that must connected properly and securely tightened.
not be overlooked. Call the toll free technical support
phone number 1-800-722-2101 for further assistance.
23. Ensure all electrical connections in the HPWH control
panel are securely tightened.
10. DO NOT install a T&P valve in the outlet (supply) water
line of the HPWH unless required by local code.
24. When the factory supplied temperature sensor is used:
• Insure the sensor is installed properly.
11. Ensure isolation valves are installed on the HPWH supply
• Ensure the temperature sensor has been installed in a
and return water line at the storage tank for servicing and
designated temperature control opening in the mid/
purging the air from the HPWH during start-up.
lower portion of the storage tank.
• Ensure the supplied temperature sensor is coated with a
suitable heat transfer compound (paste).
45
Installation & Operation Manual
9 Start-up
3 Phase Start-Up Procedures Check/control Water Chemistry
1. Make sure the disconnect is off and confirm there is no Conduct water quality testing prior to
NOTICE
power on the distribution block on the electrical panel. installing the appliance. Various solutions
are available to adjust water quality.
2. Pull the unit fuses from the fuse block in the back panel
of the unit. See the following table for properly operating the water heater
3. With disconnect back on, check and make sure the with the appropriate water chemistry. Good water quality will
power at the distribution block is the same as the power help extend the life of the appliance by reducing the effects of
requirements on the data sticker that is on the electrical scale buildup and corrosion.
panel. Table 9-1 Water Chemistry
4. Turn power off and reinstall fuses. WATER CHEMISTRY
Specification Range Requirement
Final checks before starting the water
Follow
heater recommendations
< 5 gpg
detailed below (See
q Read the Veritus Water Heater Service Manual to familiarize Hardness Notice 3)
yourself with SMART TOUCH control module operation.
Read the preceding Start-up sections in this manual, for Water softening system
> 15 gpg
required (See Notice 4)
proper steps to start the appliance.
Dissolved Hardness level must
q Verify all the pre-check procedures have been completed. < 350 ppm
Solids be met
q Verify the appliance and system are full of water and all pH Level 6.5 to 8.5 Acceptable range
system components are correctly set for operation.
Chloride < 150 ppm Acceptable range
q Verify electrical connections are correct and securely
attached. 1. Do not use the water heater to directly
NOTICE
q Inspect vent piping and air piping for signs of deterioration heat swimming pool or spa water.
from corrosion, physical damage, or sagging. Verify air 2. At initial fill and during water heater
piping and vent piping are intact and correctly installed per start-up and testing, check system
this manual. thoroughly for any leaks. Repair all
leaks before proceeding further.
Check system and water heater
3. When water hardness levels are less
q Check water piping than 5 gpg or 85.5 mg/l, the following
is recommended:
1. Check system piping for leaks. If found, shut down the a. Flush and clean existing water heating
water heater and repair immediately. (See WARNINGS system prior to installation.
on pages 59 and 60 (start-up) regarding failure to repair
b. Inspect and, if necessary, replace the
leaks.)
anodes in any existing tanks.
2. Check Delta T. Reference Section 4 - System Piping of this
manual for more information regarding Delta T. c. Install a Y-strainer on the inlet of each
3. Vent any remaining air from the system using manual water heater as detailed in Section 7.
vents. Air in the system will interfere with circulation and d. Limit the run time of the hot water
cause heat distribution problems and noise. recirculation loop.
q Check vent ducting and air piping. e. Filter the hot water recirculation loop
to a level of 10 microns. CAUTION:
1. Check seal at every connection, seam of air piping, and Check recirculation pump size to
vent piping. verify it is sized for filter addition.
4. When water softener is required, a
Template Assisted Crystallization
system is recommended.
46
Installation & Operation Manual
9 Start-up (continued)
8. Pump Test – You should be able to hear the water flowing 4. Display control panel houses the system control board that
through the system. If not, there is a good chance the has connections for up to 6 tank sensors. Install the tank
system is air bound and the air needs to be removed before temperature sensors in a designated temperature control
starting the compressor. opening in the mid/lower portion of the storage tank.
5. Use a suitable heat transfer compound on the probe to
OIL DILUTION! Bearing malfunction! It is ensure an accurate temperature reading.
⚠CAUTION
important to ensure that new compressors
6. Check the voltage into the terminal block and make sure
are not subjected to liquid abuse. Turn
that it is 120V before applying power to the display panel.
the crankcase heater on 4 - 6 hours before
starting the compressor. Commissioning Mode
High discharge pressure operation! Upon the initial startup, each heat pump will be forced to
⚠CAUTION
Compressor damage! Do not use compressor step through a three-step commissioning sequence to help
to test opening set point of high-pressure ensure proper installation and operation. Each step must be
cutout. Bearings are susceptible to damage acknowledged by the user by holding the button on the unit
before they have had several hours of control box for 5 seconds. The three-character LED on the heat
normal running. Liquid and high pressure pump control board will display SR1, SR2, or SR3 depending
loads could be detrimental to new bearings. on which step of commissioning mode is currently active.
It is therefore important to ensure that new
compressors are not subjected to liquid 1. SR1 - System Prime – The water valve will be set to fully
abuse and high-pressure run tests. open without the pump running. This is to help charge
water to the system and remove any air.
2. SR2 - Manual Flow – The pump will run at the highest
flow set point. The flow rate cannot be changed during
commissioning. Check for any system water leaks.
3. SR3 - Manual Run – Water heating will be requested,
and the unit will run at 160°F (71°C). Verify proper
temperatures and pressures.
After advancing past step three, the unit will be set to normal
operation.
47
Installation & Operation Manual
9 Start-up
Rotation Direction Start-up
Scroll compressors, like several other types of compressors, This start-up refers to several tools and test instruments
will only compress in one rotational direction. Three-phase needed to complete the procedure. See Required Tools and
compressors will rotate in either direction depending upon Materials on page 22.
phasing of the power to L1, L2 and L3. Since there is a 50/50 1. Ensure the Installation Checklist has been completed.
chance of connecting power in such a way as to cause rotation
in the reverse direction, it is important to include notices and 2. Ensure the HPWH, storage tank and water system has
instructions in appropriate locations on the equipment to been purged of air and all valves are in the position for
ensure proper rotation direction is achieved when the system is normal operation.
installed and operated. Observing that suction pressure drops 3. Turn on power at the circuit breaker or disconnect switch
and discharge pressure rises when the compressor is energized serving the HPWH.
allows verification of proper rotation direction. There is no
negative impact on durability caused by operating three-phase 4. Turn the power switch on inside the display panel to monitor
Copeland Scroll™ compressors in the reversed direction for a the refrigerant pressures, the inlet water temperature, and the
short period of time, (under one hour), but oil may be lost. outlet temperatures to ensure water temperature is rising.
After a few seconds of operation in reverse, the compressor
Core Sense system will lockout due to reversed phase. However, NOTE: It may be helpful to record the operating data
if allowed to repeatedly restart and run in reverse without initially every 10 to 30 minutes just to see how the heat
correcting the situation, the compressor will be permanently pump is performing.
damaged. All three-phase Scroll compressors are identically 5. The factory temperature setting is 120°F. Refer to page 50
wired internally. for adjusting setpoint. (This can be adjusted later as well,
If the CoreSense locks out with a compressor reversed phase NEVER SET HIGHER THAN 160°F).
fault, switch two legs of incoming 480VAC power at the main
6. The unit is equipped with inlet and outlet water
connections into the HPWH at the rear of the unit.
sensors. There values will be displayed on the display
Starting Sound screen. Ensure the water outlet (supply) and inlet
(return) valves are fully open. Start the HPWH and
During the very brief start-up, a clicking sound is audible, allow it to operate for 5 minutes. with the HPWH
resulting from initial contacting of the spirals and is normal. No operating record the inlet and outlet temperatures.
start assist devices are required for three-phase compressors,
even if a system uses non-bleed expansion valves. Due to During normal operation, the outlet line should be 8°F to
the design of the Copeland Scroll, the internal compression 120°F (4°C to 67°C) hotter than the inlet line. This is the
components always start unloaded even if system pressures temperature rise through the heat exchanger inside the
are not balanced. In addition, since internal compressor HPWH unit. Note: Temperature rise and water flow rate
pressures are always balanced at start-up, low voltage starting through the heat exchanger inside the HPWH are uniformly
characteristics are excellent for Copeland Scroll™ compressors. linked. As water flow is decreased the temperature rise will
Moreover, if low voltage conditions exist at start up, protector increase and as water flow is increased the temperature
trips could result. rise will decrease. Because of this relationship between
temperature rise and flow rate this test can be useful to
determine if the flow rate through the heat exchanger is
adequate. Other factors may also affect water flow rate
and temperature rise such as debris or lime scale build
up inside heat exchanger or water pump operation.
48
Installation & Operation Manual
9 Start-up (continued)
49
Installation & Operation Manual
9 Start-up
Adjust set point temperature(s) Set clock and date
During normal operation, set point temperatures can be The SMART TOUCH control has a built-in clock that it uses
adjusted from the Home Screen by pressing the SETPOINT for logging events. This clock must be set when the appliance
button in the middle of the screen (see FIG. 10-1). is installed and anytime the appliance has been powered off for
1. To change a set point, use the pull down list to adjust the more than four (4) hours. Use the following procedure to set
set points as shown in FIG. 9-1. the clock:
2. Once the set point has been adjusted to the desired setting, 1. Press the SETTINGS button (gear icon) at the top center
press the SAVE SETPOINTS dialog box (right). of the screen (see Figure 9-1).
2. Press the SET APPLIANCE TIME button, then press SET
NOTE: The SAVE SETPOINTS dialog box must be pressed
MANUAL TIME.
to complete programming of the controls. Failure to press the
SAVE SETPOINTS dialog box will result in an unprogrammed 3. Deselect automatic date and time at the top section of the
control. The Door Menu button will become highlighted when menu.
there are changes that can be applied. 4. Proceed to set the date and time.
3. Follow the same steps to set the tank temperature 5. Press the triangle navigation button on the bottom of the
(Figure 9-2). screen to exit this menu.
50
Installation & Operation Manual
9 Start-up (continued)
51
Installation & Operation Manual
10 Operating Information
General Vacation Mode
How the water heater operates This mode is used to reduce temperature setpoint by the
vacation offset while the building is not occupied. If enabled
The Veritus water heater uses a scroll compressor to compress the tank setpoint temperature will be reduced by the amount
low pressure vapor refrigerant to a high pressure vapor state. specified by the Vacation Offset Temperature.
The high pressure vapor is passed through a brazed plate heat
exchanger along with cold water that passes through the heat If Vacation mode is active an icon on the home screen
exchanger in channels flowing in the opposite direction. The will appear under the tank setpoint location with the word
heat from the refrigerant is used to heat up the water and VACATION.
refrigerant returns to a liquid state. The amount of the liquid
refrigerant flow is metered by electronic expansion valves Night setback
(EEVs) as it enters 2 evaporators where air forced through the Night Setback allows tank temperatures to be offset (lowered)
evaporators heats the refrigerant enough to change it back into during periods where the building is either unoccupied or
a vapor. The vapor refrigerant returns to the compressor where seasonal use allows lower temperatures. Twelve schedules will
the cycle starts over. allow the user to customize systems to maintain comfort while
Defrost conserving energy during low-demand periods. From this
screen you can enable/disable by pressing the enable check box
In low ambient temperatures, the unit has the ability to reverse for the listed schedule. If a schedule is active, an icon on the
refrigerant flow using the 4-way valve. There are sensors home screen will appear under the tank setpoint location with
located on the evaporators that allow the unit to know when the words NSB#, where # is the active schedule. Night Setback
defrost is needed. When this occurs, the 4-way valve directs the Schedules can be added or edited by pressing the Edit Schedule
hot refrigerant from the compressor straight to the evaporators Icon or Add Schedule button. Toggle through the month, days,
reversing the flow. When the evaporators have reached the days of the week, and time to set the schedule.
desired temperature that indicates all frost has melted, the fan
runs for a short amount of time to allow things to dry. Once Protection features
this time has elapsed the 4-way valve switches positions and
the unit goes back to normal operation.
Outlet temperature, ambient temperature,
and refrigerant pressures
Control inputs and outputs The outlet temperature is monitored by the water heater outlet
Enable / tank sensor temperature sensor. When the outlet temperature exceeds
167°F, the control will shut the unit down until the temperature
Both Enable and Tank Sensor inputs are used to call for heating
drops 5°F.
from the water heater.
The control module monitors the air temperature by a sensor
0 - 10VDC input (set point)
located inside the unit. As the air temperature rises the control
The Veritus water heater can be controlled by a Building module reduces the fan speed. When the air temperature
Management System (BMS) using a 0 - 10 VDC signal. The exceeds 120°F the control will shut the unit down. The unit will
control can be configured by the installer to use this signal to restart automatically once the air temperature drops 10°F (6°C)
either control set point. This signal can be sent to the heater and the minimum off time has expired.
through ModBus as well.
The refrigerant pressures are monitored at the suction and
discharge pipes of the compressor. The discharge pressure
Temperature control
switch opens at 400 psig shutting the compressor off, and when
Water Flow the pressure drops to 280 psig or lower, the switch closes to
The Veritus water heater water flow is controlled to produce allow the compressor to run. Low pressure is limited on the
water to a given set point. The flow will vary as water inlet or suction side of the compressor. If the pressure drops to
temperature, ambient air temperature and set point change. 5 psig, the switch opens and the compressor shuts off. When
pressure reaches 20 psig on the line, the switch opens and the
compressor is once again allowed to run. The compressor will
also lockout at a high temperature on the discharge of 250°F.
For operation to be allowed to resume the temperature must
cool down for 20 minutes. If the refrigerant manages to reach
the hard lock out temperature of 275°F, the oil will break down
and must be replaced. The 140K unit Core Sense Module has a
hard lockout at 260°F to prevent oil damage, but this feature is
not available on the 60K unit.
52
Installation & Operation Manual
53
Installation & Operation Manual
10 Operating Information
Low water cutoff protection Sequence of the cascade
1. The SMART TOUCH control module uses temperature To equalize the runtime of all water heaters on the Cascade,
sensing of both supply and return areas of the heat the operating sequence will automatically be changed at set
exchanger. If the flow rate is too low or the outlet intervals.
temperature too high, the control module shuts the water For the first 24 hours after initializing the Cascade, the
heater down. This ensures water heater shutdown in the sequence will be changed every hour. After that the sequence
event of low water or low flow conditions. will be changed once every 24 hours. For example, switching
2. Some codes and jurisdiction may accept these integral on/off sequence will be as follows for 8 HPWHs in the cascade:
features of the control in lieu of requiring an additional If a water heater locks out, a different unit will be turned on
limit control or low water cutoff. Consult local jurisdiction instead.
to determine.
Night Setback operation with cascade
Cascade Night Setback operation of the water heaters within the
When multiple water heaters are installed, they can be wired Cascade is available. Programming of the Night Setback will be
together in a cascade sequence. Multiple water heaters can be done through the display. Refer to the Veritus Water Heater
controlled from a single control. The system control board Service manual for information regarding Night Setback.
located in the display panel box will control all heat pumps
to run in an optimized order to give all heat pumps an equal
amount of run time. Access modes
Once the heat pump water heater receives a call for heat User
from a tank sensor or BMS, the control will determine what The USER can set the tank set point, turn the unit OFF and
the set point will be. A fixed temperature set point can be ON, and set up Wi-Fi.
programmed into the control. See page 49 of this manual to
program the set point. Installer
If the water temperature at the tank is less than the set point - Most parameters are available only to the installer, accessible
differential, then the control will initiate a call for heat on the by entering the installer password, see the Veritus Water
Cascade (see the Veritus Water Heater Service Manual for an Heater Service Manual.
explanation of the differential). The system control board will NOTE: The password will timeout after an hour from entry.
energize a heat pump(s) in the Cascade.
54
Installation & Operation Manual
Sequence of operation
1. Upon a call for heat, the control turns on the DHW pump.
The control confirms that the refrigerant high and low pressure switches, blocked drain switch, limits, louver
3. proving switch (optional), and contacts close.
Once the fan is at desired speed, cycle is complete, the control lowers the fan speeds, initiates compressor,
5. and opens the water valve.
Once the DHW call for heat is satisfied, the control will turn off the compressor. Any pumps that are running will
6. begin their respective Pump Delay cycles.
7. At the end of the pump cycle, the louver relay contacts will de-energize.
8. At the end of the Pump Delay cycle(s), the pump(s) will be turned off.
55
Installation & Operation Manual
10 Operating Information
The Home Screen displays basic information on how the unit is running. It is divided into the following sections: System Status,
System Sensors, Heat Pump Status, and Navigation.
• The System Status Section is located on the top left of the • The Navigation Section is located in the top portion of
screen and displays tank setpoints, BMS active or inactive, the screen. There are five (5) sections located below the
and the setpoint button for adjusting setpoint. Lochinvar icon: Home, View, Setup, Information (About),
and Settings. The Home Section is the screen shown
• The System Sensor Section is located on the top right of the above. The View Section provides more detailed
screen and displays the outdoor air temperature, system information including subsections for: System Sensors,
supply temperature, building recirc line temperature, Runtime, Faults, and System Details. The Setup Section
system return temperature, and 6 tank temperatures has several screens to aid in setting up the appliance. The
(system may not required all 6 tank sensors). Setup Section includes screens for adjusting: Set Points,
BMS settings, Backup Heat Settings, Boost Settings,
• The Heat Pump Unit Status Section is located on the BAS Settings, Service Mode, Service Notification, and
bottom of the screen and displays operating information System Configuration. The Setting Section enables
on the heat pumps connected to the system. This can be up several interface setup features including: Temperature
to 64 heat pumps. Each heat pump block displays if the unit Units, Time Setup, WiFi Setup, Screen Settings, System
is currently running (i.e. run, stand-by, blocking, lockout), Updates, and Terminal Reboot.
outlet temperature, inlet temperature, and flow rate in
GPM.
56
Installation & Operation Manual
11 Maintenance
Maintenance and annual startup
Table 11-1 Service and Maintenance Schedules
General:
57
Installation & Operation Manual
11 Maintenance
Follow the service and maintenance procedures given throughout this manual and in component literature
⚠ WARNING
shipped with the water heater. Failure to perform the service and maintenance could result in damage to the
water heater or system. Failure to follow the directions in this manual and component literature could result in
severe personal injury, death, or substantial property damage.
The water heater should be inspected annually only by a qualified service technician. In addition, the
⚠ WARNING
maintenance and care of the water heater designated in Table 11-1 and explained on the following pages must be
performed to assure maximum water heater efficiency and reliability. Failure to service and maintain the water
heater and system could result in equipment failure.
⚠ WARNING Electrical shock hazard – Turn off power to the water heater before any service operation on the water heater
except as noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical
shock, causing severe personal injury or death.
Should the unit have to be serviced with live electricity, only trained and qualified technicians should carry out
⚠ WARNING
the service. Failure to follow all of the safety warnings may result in serious injury or death.
1. Remove the front access cover and inspect the interior of 3. Watch the system pressure as the water heater heats up
the water heater. (during testing) to ensure pressure does not rise too high.
2. Inspect for oil on the components and base which could Excessive pressure rise indicates expansion tank sizing or
indicate a refrigerant leak. performance problem.
3. Vacuum any sediment from inside the water heater and 4. Inspect automatic air vents and air separators. Remove air
components. Remove any obstructions. vent caps and briefly push valve to flush vent. Replace caps.
Make sure vents do not leak. Replace any leaking vents.
Check all piping for leaks
Eliminate all system or water heater leaks.
⚠ WARNING
Leaking water may cause severe property
damage.
1. Inspect the condensate drain line, condensate PVC fittings,
and condensate trap.
2. Look for signs of leaking lines and correct any problems
found.
58
Installation & Operation Manual
11 Maintenance (continued)
59
Installation & Operation Manual
11 Maintenance
Evaporator Cleaning and Inspection 3. Remove as much dirt and organic material from the
insulation using a vacuum device with a HEPA filter
Read all of the warnings provided for the (99.97%) efficient at 0.3 micron particles). Be careful not to
⚠ WARNING
cleaning products used for refrigeration coil tear the insulation during the cleaning procedure.
cleaning. Follow all instructions for personal 4. Apply the microbial cleaning agent as prescribed by the
protection and safe application of the application and usage instructions.
products. Before cleaning the evaporator, 5. Allow the unit to dry thoroughly.
disconnect all power to the unit and follow 6. If necessary, apply an anti-microbial agent on the insulation
the prescribed lock-out/tag-out procedure. per the instructions provided on the product label. Discard
Inspect the evaporator coil for dirt buildup or fin crush on at collected microbial contaminants as required by local or
least once per year. If there are signs of fin fold over, use a fin state codes.
comb to straighten the fins. Should the coils need cleaning,
follow the steps listed below: Drain Pain
Warning: Read all of the warnings on the bottle of the cleaning Warning: Read all of the warnings on the bottle of the cleaning
products used for evaporator cleaning. Follow all instructions products used for drain pan cleaning. Follow all instructions
for personal protection and safe application of the products. for personal protection and safe application of the products.
Before cleaning the drain pan or evaporators, disconnect all Before cleaning the drain pan, disconnect all power to the unit
power to the unit and follow the prescribed lock-out/tag-out and follow the prescribed lock-out/tag-out procedure.
procedure. The condensate pan and drain line must be checked for
Direct stream of water should be avoided, cleanliness, growth, and blockage at least every six months. To
⚠ CAUTION clean the drain pan, start by disconnecting the power to the
to prevent damage to evaporators. instead
using a fanned-out method. unit. Find a cleaner that is safe to use on ABS plastics. Wear
the appropriate personal protective equipment prescribed by
1. Disconnect all power to the unit and follow the prescribed the cleaning product instructions. Apply the cleaning solution,
lock-out/tag-out procedure. allow it to sit for prescribed amount of time, then rinse. Remove
2. Wear the prescribed personal protective equipment any particles that could potentially block the drain line.
prescribed from the cleaning product instructions.
3. Install a block-off sheet to prevent splash over into the dry
Braze Plate Cleaning Instructions
sections of the HPWH.
4. Prepare the cleaning solution as prescribed from the In some applications the heat exchanger may be subjected to
cleaning product instructions and fill the mixture into a severe fluid conditions, including high temperature hard water
high-pressure sprayer. conditions, causing accelerated scaling and corrosion rates,
5. Start spraying both sides of the coil keeping the nozzle and will diminish performance.
perpendicular to the coil at least 6 inches from the coil face. It is important to establish regular cleaning schedules. A 5%
If the water pressure is questionable, observe the impact solution of Phosphoric Acid or Oxalic Acid may be considered.
of cleaning on a small section of coil before implementing Other types of solutions can be obtained from your local
universally. wholesaler. Make sure cleaning solution is applicable for
6. Thoroughly rinse the cleaned coil with cool, clean water. stainless steel and copper and all directions are followed.
7. Straighten out any fins displaced during the cleaning using
Do not heat solution. Be sure to flush heat exchanger with
a fin comb.
fresh water after cleaning using flush valves provided with
8. Confirm the drain pan line is not clogged.
manifolds. See Figure 11-1.
9. Replace all panels on the unit and wipe down any standing
cleaning solution or water on or around the unit. Figure 11-1 Braze plate
Cleaning Internal Pipe Insulation
Inspect the internal pipe insulation on a yearly basis for any
microbial growth. The insulation never has to be cleaned unless
microbial growth is detected. If microbial growth is detected,
follow the removal steps below:
1. Disconnect all power to the unit and follow the prescribed
lock-out/tag-out procedure.
2. Wear the prescribed personal protective equipment
prescribed from the cleaning product instructions.
60
Installation & Operation Manual
11 Maintenance (continued)
11 Maintenance
Table 11-4 Saturated Temperature Chart
R513A SATURATED TEMPERATURE CHART
Saturated Temperature °F Saturated Temperature °C Saturated Pressure PSI
0 -18 9.1
5 -15 11.9
10 -12 15.0
15 -9 18.3
20 -7 21.9
25 -4 25.9
30 -1 30.1
35 2 34.6
40 4 39.6
45 7 44.8
50 10 50.5
55 13 56.5
60 16 63.0
65 18 69.9
70 21 77.3
75 24 85.1
80 27 93.4
85 29 102.0
90 32 112.0
95 35 121.0
100 38 132.0
105 41 143.0
110 43 155.0
115 46 167.0
120 49 180.0
125 52 193.0
130 54 207.0
135 57 222.0
140 60 238.0
145 63 254.0
150 66 271.8
155 68 289.9
160 71 308.9
62
Installation & Operation Manual
11 Maintenance (continued)
Troubleshooting
63
Installation & Operation Manual
11 Maintenance
Troubleshooting continued
64
Compressor Fan
SINGLE HOUSIN
DUAL SENSOR
OPTIONAL ITEM
Contactor
BOX DEPICTS
24VJ5-1
J29-1 120V-L J2-6120V-N J28-4 120V-L J29-5 Heat Trace Pump Relay
480 VAC
120 VAC
Switch
Booster
Compressor Coresense
24V J15-3
J2-10 120V-L Blower RelayDrain Pan
120V-N J15-2
Installation & Operation Manual
Safety Fan
Contactor Contactor Demand
24V J2-3 120V-N J28-2 120V-L J15-1 Heat Trace
L2
Fan Booster
Blocked Drain Compressor
65
Panel Ground Contactor 120V-L J28-1
DISCONNECT POWER
Low Voltage
Switch Coresense
BEFORE SERVICING
480 VAC
120 VAC
OPTIONAL ITEMS
DUAL SENSOR
BOX DEPICTS
Demand
24V J2-13120V-L J28-3
Contactor 24V-N J19-3 24V J2-6 24V 120V Booster
Pump Relay
J20-1 120V-N Xfmr Low Pressure Blower Relay
480V - 3Φ
Switch
120V-N J28-2
On/Off Safety Fan
120V-N J25-2
24V J2-10
J20-3 120V-L 120V-L J28-1
!
480V Heater
BOX DEPICTS
120V Coresense
BEFORE SERVICING
WARNING
24V
100370016 REV C
Contactor 24V-N J19-3 Switch
120V
3. Actual connector block locations may vary from those shown on diagrams. Refer to actual components for proper connector block locations when using diagrams to troubleshoot unit.
J20-1 120V-N
24V J2-10Xfmr
Exceptions: Replacement shielded cables must be purchased from the factory. Use of a non-approved wire or cable can lead to operational problems which could result in non-repairable
Safety Fan
2. If any original equipment wire as supplied with the appliance must be replaced, it must be replaced with wire having the same wire gauge (AWG) and rated for a minimum of 105°C.
GND Contactor Contactor
HPC 24V J2-3 L2
On/Off (Heat Pump Controller) 120V-N J25-2
Blocked Drain Compressor
PanelJ20-3
Ground120V-L
!
Switch Coresense
BEFORE SERVICING
J16-4 120V-L
WARNING
L1
L3 Safety High Water High
24V-L J19-1
Demand
Temperature Pressure 480V GND
L2 Contactor 120V 24V-N J19-3 24V
Contactor
Switch Switch Xfmr 120V
J20-1 120V-N Xfmr
L1
M2 M1 120V-N J16-3 Water Inlet Unit Pump
1. All wiring must be installed in accordance with: local, state, provincial and national code requirements per either N.E.C. in USA or C.S.A. in Canada.
Demand On/Off 120V-N J25-2
Contactor Compressor J120V-L J16-2 Heat Trace J20-3 120V-L
!
Switch
Coresense 120V-L J25-1
J5-8
L3 J5-7
480V
L2 J5-2 120V-N J29-6 120V
Condenser
J5-1 Xfmr
120V-L J29-5 Heat Trace
L1 Booster Aux Heat
J16-5 120V-N
Blower Cable
Compressor Coresense J15-3 120V-L 120V-N J15-2 Drain Pan
Demand
120V-L J15-1 Heat Trace
Fan
Contactor
Low Voltage
J29-1 120V-L
120V-N J28-4
480 VAC
120 VAC
J29-2 120V-N
120V-L J28-3
Booster
Blower Relay
120V-N J28-2
Booster Blower
Panel Ground 120V-L J28-1
Crankcase Pump Relay
Compressor Fan
SINGLE HOUSING
OPTIONAL ITEMS
DUAL SENSOR
BOX DEPICTS
Heater
BOX DEPICTS
24V J2-13
24V J2-6 Pump Relay
Low Pressure
480V - 3Φ
Switch
Switch Coresense
BEFORE SERVICING
WARNING
L1
24V-L J19-1
Demand
Ladder
Figure 12-1 DISCONNECT
NOTES:
L2 Xfmr
12 L1
J8D ---- System Supply J20-11 Ou
HMI)
C
y
x
w Sensor
K
J26E DGND
oblique)
Trace
Trace
enser
Bare
e Pressure
vertical)
EV Front
Trace
ctor N.O. Feedback
ump
elay
ducer
ducer
EV Rear
Pressure
Button
BK
Inlet
W
Pan
Sys Supply Ret J20-12 O
Bare
Safety Contactor N.O. Feedback
Bare
R
BK
R
RCAD (HMI)
Discharge Pressure
J8A RCAD-A Recirc
BR
Suction Pressure
J8B RCAD-B Sys
Reset Button
Transducer
Transducer
BR
R
BL
Installation & Operation Manual
5
4
3
2
1
5
4 Low Pressure Switch
3
2 EEV Front
1
J8C DGND Sys
Flow Sensor
Blocked Drain Switch
BK
J8D ---- Syst
(oblique)
(vertical)
EEV Rear
J27-4
J27-3
J27-2
J27-1
BK
BL BK
Sys
downstream
Bare
Display
Heat Pump
HMI
Cascade
RS485-B
RS485-A
----
DGND
12
(HPC)
Diagrams
J27-4
J27-3
J27-2
J27-1
IN
downstream
Display Display
Heat PumpR GND
HMI
Cascade 120V-N 5
Figure 12-2 Wiring Diagram
RS485-B
RS485-A
----
DGND RS485(+) 7
(HPC)
Enclosure
Panel
L1
CTA-2045
R
RS485(-) 1
120V-L 12
480V – 3ø
IN
L1
BOX DEPICTS NOTES:
DGND 8
NING
Fan Contactor
480 VAC
DUAL SENSOR 1. All wiring must be installed in accordance with: local, state, provincial and national code requirements per either N.E.C. in USA or C.S.A. in Canada.
L2
BL
L2
BL
GY
GY
BKL3 G
BR
Fan
GY
W
120 VAC
BR
PR
ORS485 A
BL
SINGLE HOUSING
W
R
Y
RS485 B
T POWER 2. If any original equipment wire as supplied with the appliance must be replaced, it must be replaced with wire having the same wire gauge (AWG) and rated for a minimum of 105°C.
10BK
GND
Low Voltage Exceptions: Replacement shielded cables must be purchased from the factory. Use of a non-approved wire or cable can lead to operational problems which could result in non-repairable
L3
BK
BOX DEPICTS
RVICING
BK
W
OPTIONAL ITEMS damage to the integrated controller or other components.
Switch
On/Off
BK
R
W
3. Actual connector block locations may vary from those shown on diagrams. Refer to actual components for proper connector block locations when using diagrams to troubleshoot unit. 100370015 REV C
BK
R
120V
GN
Xfmr
R
BK
BOX DEPICTS Bare NOTES:
R
WARNING
R
480 VAC
Demand Contactor
! 120VAC-N J20-1
GND
J28-1
J28-2
J28-3
J28-4
J28-5
J28-6
J15-1
J15-2
J15-3
J15-4
J29-1
J29-2
J29-3
J29-4
J29-5
J29-6
J29-7
J16-1 ----
J16-2
J16-3
J16-4
J16-5
DUAL SENSOR
L1 L2 L3 G
1. All wiring must be installed in accordance with: local, state, provincial and national code requirements per either N.E.C. in USA or C.S.A. in Canada.
Compressor
GN
GN
BK
BK
W
SINGLE HOUSING 120 VAC ---- J20-2
2. If any original equipment wire as supplied with the appliance must be replaced, it must be replaced with wire having the same wire gauge (AWG) and rated for a minimum of 105°C.
BL
BL
DISCONNECT POWER
R
RS485 +
Low120VAC-L
Voltage J20-3
RS485 -
GND
BK
BOX DEPICTS Exceptions: Replacement shielded cables must be purchased from the factory. Use of a non-approved wire or cable can lead to operational problems which could result in non-repairable
120V-L Pump Relay
120V-N Pump Relay
120V-L Booster Blower Relay
120V-N Booster Blower Relay
----
----
BK
BK
Chassis Ground
Panel Ground
damage to the integrated controller or other components.
M2
M1
D
L2
L1
480V
Xfmr
Crankcase
3. Actual connector block locations may vary from those shown on diagrams. Refer to actual components for proper connector block locations when using diagrams to troubleshoot un
Heater
BK W
120VAC-L J25-1
W
Y
N
Bare
24Vac
120Vac
120VAC-N J25-2
120V
R
Xfmr
BK
PK
BR
BK
W
Y
W
PK
120V
BL
W
Y
BK
BK
W
BK
BL
L
BK
24VAC-L J19-1
BL
W
---- J19-2 120V-N
W
Auxillary Heat Cable
24VAC-N J19-3 J19-1 24VAC-L 120V-L
BK
BK
W
J19-3 24VAC-N ---- J10-2
Booster Blower
BL
120V-L
BL
24VAC-L J14-1 Backup 1 J10-3
Ball Valve
W
24VAC-L J14-2
BK
DGND J10-4
EcoPort
J1-1 EcoPort-A
BL
PR
DGND J14-3 Backup 2 J10-5
J1-2 EcoPort-B
R
W
24VAC-L 4Way J14-4 DGND J10-6
Booster
Blower
Relay
J1-3 DGND
Temperature
High Water
L
N
G
PR
---- J14-7 J14-1 14VAC-N
PWM Out
PWM Ref
W
PWM In
---- J14-8 J14-2 SW1 24VAC-L
Pump
4 Way Valve
Pump Relays
PR
BMS 0-10V- J18-1
(Heat Pump Controller)
Condenser
Water Inlet
Analog In
Heat Trace
Heat Trace
Heat Trace
Drain Pan
PR
J14-3 24VAC-N
PR
Relay
Pump
J14-4 SW2 24VAC-L
BK
W
---- J18-3
Pressure
Switch
High
BR
-------
W BL
BR
BL
24VAC-L Light J1-2 J4-2 24VAC-N ---- J18-8
BK
BL BK
J4-3 SW3 24VAC-L
HPC
J4-4 24VAC-N
PWM Out J10-1
0-10V WOutput
Status
Light
Digital IN
J2-2 T-stat/Enable IN
BR
Enclosure
Panel
Display
CTA-2045
RS485(+) 7
---- J10-5
120V-N 5
RS485(-) 1
Backup 2 SW J13-4
120V-L 12
J2-4 ----
GND 10
DGND 8
RelaysGNOut
---- J10-6 Alarm J13-5
GY
GY
BR
BK
GY
W
BR
PR
O
BL
W
R
Y
PR
Alarm SW J13-6
R
BK
W
W
Runtime J13-7
120V
Xfmr
---- J17-1 120VAC-N J20-1
Runtime SW J13-8
J28-1
J28-2
J28-3
J28-4
J28-5
J28-6
J15-1
J15-2
J15-3
J15-4
J29-1
J29-2
J29-3
J29-4
J29-5
J29-6
J29-7
J16-1 ----
J16-2
J16-3
J16-4
J16-5
J5-1
J5-2
J5-3
J5-4
J5-5
J5-6
J5-7
J5-8
GN
BK
BK
W
Digital IN
NFC
R
High Water
High Water Temp Switch_0
----
----
----
----
High Pressure Switch_1
High Pressure Switch_0
120VAC-L J20-3
GND
BK
120V-L Pump Relay
120V-N Pump Relay
120V-L Booster Blower Relay
120V-N Booster Blower Relay
----
----
Key
J8-1 ----
RS485-B J17-4 J22-3 Louver Prove GND
Compressor
BK W
120VAC-L J25-1
Mix V Open J5-2
W
Y
N
J8-2 ----
R
24Vac
120Vac
120VAC-N J25-2
120V
Xfmr
DGND J17-5 J22-4 Louver Proving
Bare
J8-3 RS485-A
BL
Y
J8-4 RS485-B Mix V Close SW J5-3
BK
BK
BL
L
J8-5 DGND
Mix V Close J5-4
Bare
24VAC-L J19-1
BL
---- J19-2
J7-1 +5V Louver Relay SW J5-5
Bare R BK
24VAC-L J14-1
J7-3 PC-B Backup 1 J10-3
W
J9-3 RS485-B
RS485-A J27-3
Ball Valve
J9-4 DGND
Bare
EcoPort
J1-1 EcoPort-A
RS485-B J27-4 DGND J14-3 J7-4 DGND Tank 1 Ret J3-1 Backup 2 J10-5
Disch
J1-2 EcoPort-B
Blocked Drain SW
Pump Relays
Safety FB
Cascade RS485
J11-2 B
Analog In
J3-2 Inlet Water
PR
J14-3 24VAC-N
GN +12V
RS485-A
DGND
DGND
DGND
DGND
DGND
DGND
J11-3 A
Reset
+12V J23-1
DGND J6-4
DGND J6-2
DGND
-------
W BL
J11-4 GND
---- J6-9
---- J6-8
---- J6-7
----
J2-13
J2-12
J2-11
J2-10
HPC
J2-6
J2-5
J2-4
J2-3
J2-9
J2-2
J2-8
J2-1
BK R BR
J4-4 24VAC-N
J3-13 Ambient PWM Out J10-1 J11-6 A
0-10V Output
Status
J2-2 T-stat/Enable
BR
---- J10-4
J3-7 Evap 1A J11-8 B J2-3 ---- Backup Heat 2 J13-3
J2-4Tank 6 Ret J3-11
Y
J3-8 Outlet Water B ---- J10-6 J11-9 A J2-5 BMS Enable GND Alarm J13-5
Tank 6 Temp J3-12
BL
GN
GY
GN
GN
BR
BR
PK
PR
PRGY
BK
---- J17-1
BK
PR
BL
W
O
Y
Y
R
Runtime SW J13-8
R
Sensors
Temp
Digital IN
NFC Key
J22-1 ----
J4-1 Evap 1B ---- J17-2 ---- J20-1
Temperature Input
V Close J5-4
BK
J4-6 Evap 2A
Key
Bare R BK
---- J27-2
PC
Blocked Drain SW
Compressor FB
R
EEV Two EEV One 0-10V Input OUT Tank 2 Ret J3-3
Pulse Count
RCAD (HMI)
RecircJ11-1 GND
PWM Input
Discharge Pressure
J11-2 B
Cascade RS485
RS485-A
EEV_4
EEV_3
EEV_2
EEV_1
EEV_1
EEV_2
EEV_3
EEV_4
DGND
DGND
DGND
DGND
DGND
DGND
DGND
+12V
+12V
Reset
DGND J6-4
DGND J6-2
DGND
Reset Button
Transducer
----
----
----
----
---- J6-10
J11-4 GND
---- J6-9
---- J6-8
---- J6-7
----
SCB
B
J26-6
J26-5
J26-4
J26-3
J26-2
J26-1
J13-5
J13-4
J13-3
J13-2
J13-1
J23-4
J23-3
J23-2
J23-1
J2-14
J2-13
J2-12
J2-11
J2-10
4 Temp J3-8
J2-7
J2-6
J2-5
J2-4
J2-3
J2-9
J2-2
J2-8
J2-1
J7-4
J7-3
J7-2
J7-1
BK
J11-6 A
J8D ---- System Supply
J11-7 GND J20-11 Tank 5 Ret J3-9
Tank 5 Temp J3-10
Sys J11-8
SupplyB Ret J20-12 Tank 6 Ret J3-11
Bare
J11-9 A
Tank 6 Temp J3-12
GN
GN
GY
GY
GY
GN
GN
BK
BK
BR
PK
BR
PR
PR
BK
BK
BL
PR
W
O
O
Y
R
R
Y
Y
R
R
Sensors
Temp
---- J20-4
NFC
Key
J26D Cascade-B
BK
Blocked Drain Switch
Low Pressure Switch
Safety
Bare
Display
RCAD (HMI)
Discharge Pressure
Suction Pressure
Reset Button
Transducer
Transducer
R
5
4
3
2
1
5
4
3
2 EEV Front
1
RS485-B
RS485-A
----
DGND
BK
J27-4
J27-3
J27-2
J27-1
downstream
Display
Heat Pump
HMI
Cascade
RS485-B
RS485-A
----
DGND
(HPC)
IN
12 Diagrams
Figure 12-3 Display Panel Wiring Diagram
! WARNING
DISCONNECT POWER
BEFORE SERVICING
GND
GN
J23-1
W
J25-2
120Vac
W
N
BOX DEPICTS
Voltage
480 VAC
Board
DUAL SENSOR J23-2
SINGLE HOUSING 120 VAC J25-1 J23-3
BK
BK
BK
L
BOX DEPICTS Low Voltage
OPTIONAL ITEMS
W
Y
24Vac
120V
Xfmr
10 GND
5 120V-N
12 120V-L
CTA-2045
RS485(+) 7
RS485(-) 1
BK
BL
DGND 8
J19-1 24VAC-L
Backup 1 J10-3
DGND J10-4
EcoPort
J1-1 EcoPort-A
J1-2 EcoPort-B Backup 2 J10-5
J1-3 DGND DGND J10-6
Rate Output J10-7
DGND J10-8
J14-1 14VAC-N
J14-2 SW1 24VAC-L
Pump Relays
BMS 0-10V- J18-1
Analog In
J14-3 24VAC-N
J14-4 SW2 24VAC-L BMS 0-10V+ J18-2
---- J18-3
J4-1 SW4 24VAC-L -------
J4-2 24VAC-N ---- J18-8
J4-3 SW3 24VAC-L
J4-4 24VAC-N
J22-1 ----
J22-2 ----
Mix V Open SW J5-1
J22-3 Louver Prove GND
Mix V Open J5-2
J22-4 Louver Proving
Mix V Close SW J5-3
Mix V Close J5-4
J7-1 +5V Louver Relay SW J5-5
J7-2 PC-A Louver Relay J5-6
PC
J7-3 PC-B
J7-4 DGND Tank 1 Ret J3-1
Tank 1 Temp J3-2
(System Control)
J11-1 GND
Tank 2 Temp J3-4
Cascade RS485
J11-2 B
BK
J11-3 A
R
Sensors
Temp
---- J20-1
downstream
J26A +5V
Heat Pump
NFC Key
---- J20-2
Cascade
J26B ----
RS485-B
RS485-A
----
DGND
(HPC)
---- J20-4
NFC
Key
J26D Cascade-B
BK
J12-1 RS485-A
J12-2 RS485-B
J12-3 DGND
CONTROL
DISPLAY
HMI
NOTES:
1. All wiring must be installed in accordance with: local, state, provincial and national code requirements per either N.E.C. in USA or C.S.A. in Canada.
2. If any original equipment wire as supplied with the appliance must be replaced, it must be replaced with wire having the same wire gauge (AWG) and rated for a minimum of 105°C.
Exceptions: Replacement shielded cables must be purchased from the factory. Use of a non-approved wire or cable can lead to operational problems which could result in non-repairable
damage to the integrated controller or other components.
3. Actual connector block locations may vary from those shown on diagrams. Refer to actual components for proper connector block locations when using diagrams to troubleshoot unit.
67
Revision Notes: Revision A (PCP #3000056598/ CN #500042943)
initial release.
Revision B (PCP #3000057735/ CN #500043946) reflects updates
throughout.
Revision C (PCP #3000058985 / CN #500045045) relfects updates
throughout prior to release.
Revision D (PCP #3000059127 / CN #500045231) reflects update
throughout as well as updated ladder diagrams.
100371005_2000627791_Rev D
01/24