Subject: Electrical Panel Board
Dear sir;
In compliance with your kind request, we are pleased to submit our proposal as follows:
Item Qty. Description Price
1 1 Assy “Main Distribution Panel” in Free standing enclosure in NEMA 3R standard for outdoor use Php. 381,000.00
complete with line and grounding bus bars and complete accessories as follows:
1-unit 2000AT/2000AF ACB, 3 Pole, LSIG. Fixed type manually operated
1-unit 1600at/1600af, ACB, 3Pole, LSIG, fixed type, manually operated
2 1 Assy “Main Campus Panel” in Free Standing enclosure in NEMA 3Rstandard for out-door use Php. 306,250.00
complete with line and grounding bus bars and complete accessories.
Main Breaker:
1600AT/2000AF, 80kaic, LSIG, Fixed type manually operated
Branches:
630AT/630AF, MCCB, 3pole,
500AT/630AF, MCCB, 3pole,
400AT/400AF, MCCB, 3pole,
300AT/400AF, MCCB, 3 pole,
200AT/250AF, MCCB, 3 pole,
100AT/100AF, MCCB, 3 pole,
3 1 Assy. “FIRE PUMP PANEL” in Free standing enclosure in NEMA 3R for out-door use complete with Php. 254,500.00
line and grounding bus bfdxar with complete accessories
1 unit 1600AT/2000AF, ACB, 3pole, LSIG. fixed type manually operated,
1 unit 630AT/630AF, MCCB,
4 1 Assy “ATS ” PANEL No. 1 1600AT/2000 AF, 3 pole, LSIG, in NEMA-3R Free standing Php. 277,500.00
Enclosure for outdoor use with line and grounding bus bar and complete accessories.
Type: Air Circuit Breaker;
STANDARD FEATURE:
- Normal Power Phase Failure relay, 3Pole
- Time delay to Transfer Normal to Emergency, adjustable 0-180 secs.
- Time delay to re-transfer Emergency to Normal, adjustable 0- 5 minutes.
- Auto/Manual Operation Mode selector Switch.
- Test to transfer Selector Switch.
- Mechanical Interlocking Device, cable type,
-
5 1 Assy “ATS ” PANEL No. 2 1600AT/2000AF, 3 pole, LSIG in NEMA-3R Free standing Php. 277,500.00
Enclosure for outdoor use with line and grounding bus bar and complete accessories.
Type: Air Circuit Breaker; Brand:
STANDARD FEATURE:
- Normal Power Phase Failure relay, 3Pole
- Time Delay to Transfer Normal to Emergency, adjustable 0-180 secs.
- Time delay to re-transfer Emergency to Normal, adjustable 0- 5 minutes.
- Auto/Manual Operation Mode selector Switch.
- Test to transfer Selector Switch.
Mechanical Interlocking Device, cable type,
6 1 Assy CBPC FIRE PUMP PANEL BOARD, Free standing enclosure in NEMA 3R for outdoor use with Php. 85,000.00
line and grounding bus bar and complete with accessories.
Mian Circuit Breaker: 600AT/630AF, MCCB, 3 pole,
Branches:
1 unit 500AT/630AF, MCCB, 3 pole
1 unit 100AT/100AF, MCCB, 3 pole
7 1 lot Delivery 48,250.00
8 1 lot Mobilization 50,000.00
GRAND TOTAL PRICE (FOB Daet) ------ Php. 1,680,000.00
VAT EXCLUSIVE =========
DELIVERY OF PANEL: Two (2) months after receipt of order and down payment.
TERMS OF PAYMENT: Thirty (50%) Down payment, balance 30 days after delivery.
WARRANTY: Six (6) months after energization or 1 year after delivery whichever comes first under normal use and
operating condition.