0% found this document useful (0 votes)
41 views44 pages

Control Components

The document provides a datasheet for the TeSys Deca contactor (LC1D09M7) and motor circuit breaker (GV2ME06), detailing specifications such as operational voltage, current ratings, motor power capacities, and environmental standards. It includes information on dimensions, connections, and packaging, as well as environmental sustainability initiatives by Schneider Electric. The products are designed for motor control and protection applications, with various compliance certifications and operational parameters.

Uploaded by

MohammedIrfan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
41 views44 pages

Control Components

The document provides a datasheet for the TeSys Deca contactor (LC1D09M7) and motor circuit breaker (GV2ME06), detailing specifications such as operational voltage, current ratings, motor power capacities, and environmental standards. It includes information on dimensions, connections, and packaging, as well as environmental sustainability initiatives by Schneider Electric. The products are designed for motor control and protection applications, with various compliance certifications and operational parameters.

Uploaded by

MohammedIrfan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Product datasheet

Specifications

Contactor, TeSys Deca, 3P(3NO),


AC-3/3e, <=440V, 9A, 220V AC
50/60Hz coil, screw clamp terminals
LC1D09M7

Main
Range of product TeSys Deca

Product or component type Contactor

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Device short name LC1D

Contactor application Motor control


Resistive load

Utilisation category AC-4


AC-3
AC-1
AC-3e

Poles description 3P

[Ue] rated operational voltage Power circuit: <= 690 V AC 25...400 Hz


Power circuit: <= 300 V DC

[Ie] rated operational current 9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
9 A (at <60 °C) at <= 440 V AC AC-3e for power circuit

[Uc] control circuit voltage 220 V AC 50/60 Hz

Complementary
Motor power kW 2.2 kW at 220...230 V AC 50/60 Hz (AC-3)
4 kW at 380...400 V AC 50/60 Hz (AC-3)
4 kW at 415...440 V AC 50/60 Hz (AC-3)
5.5 kW at 500 V AC 50/60 Hz (AC-3)
5.5 kW at 660...690 V AC 50/60 Hz (AC-3)
2.2 kW at 400 V AC 50/60 Hz (AC-4)
2.2 kW at 220...230 V AC 50/60 Hz (AC-3e)
4 kW at 380...400 V AC 50/60 Hz (AC-3e)
4 kW at 415...440 V AC 50/60 Hz (AC-3e)
5.5 kW at 500 V AC 50/60 Hz (AC-3e)
5.5 kW at 660...690 V AC 50/60 Hz (AC-3e)

Motor power hp 1 hp at 230/240 V AC 50/60 Hz for 1 phase motors


2 hp at 200/208 V AC 50/60 Hz for 3 phases motors
2 hp at 230/240 V AC 50/60 Hz for 3 phases motors
5 hp at 460/480 V AC 50/60 Hz for 3 phases motors
7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors
0.33 hp at 115 V AC 50/60 Hz for 1 phase motors

Compatibility code LC1D

Pole contact composition 3 NO

Protective cover With

[Ith] conventional free air thermal 25 A (at 60 °C) for power circuit
current 10 A (at 60 °C) for signalling circuit

Irms rated making capacity 250 A at 440 V for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1

Rated breaking capacity 250 A at 440 V for power circuit conforming to IEC 60947

Feb 3, 2025 AD 1
[Icw] rated short-time withstand 105 A 40 °C - 10 s for power circuit
current 210 A 40 °C - 1 s for power circuit
30 A 40 °C - 10 min for power circuit
61 A 40 °C - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit

Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1


25 A gG at <= 690 V coordination type 1 for power circuit
20 A gG at <= 690 V coordination type 2 for power circuit

Average impedance 2.5 mOhm - Ith 25 A 50 Hz for power circuit

Power dissipation per pole 1.56 W AC-1


0.2 W AC-3
0.2 W AC-3e

[Ui] rated insulation voltage Power circuit: 690 V conforming to IEC 60947-4-1
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified

overvoltage category III

pollution degree 3

[Uimp] rated impulse withstand 6 kV conforming to IEC 60947


voltage
Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO
13849-1

Mechanical durability 15 Mcycles

Electrical durability 0.6 Mcycles 25 A AC-1 at Ue <= 440 V


2 Mcycles 9 A AC-3 at Ue <= 440 V
2 Mcycles 9 A AC-3e at Ue <= 440 V

Control circuit type AC at 50/60 Hz standard

Coil technology Without built-in suppressor module

Control circuit voltage limits 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz


0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
1...1.1 Uc (60…70 °C):operational AC 50/60 Hz

Inrush power in VA 70 VA 60 Hz cos phi 0.75 (at 20 °C)


70 VA 50 Hz cos phi 0.75 (at 20 °C)

Hold-in power consumption in VA 7.5 VA 60 Hz cos phi 0.3 (at 20 °C)


7 VA 50 Hz cos phi 0.3 (at 20 °C)

Heat dissipation 2…3 W at 50/60 Hz

Operating time 12...22 ms closing


4...19 ms opening

Maximum operating rate 3600 cyc/h at 60 °C

2 Feb 3, 2025 AD
Connections - terminals Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without
cable end
Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without
cable end
Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable
end
Power circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with
cable end
Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable
end
Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable
end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without
cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without
cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable
end
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with
cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without
cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without
cable end

Tightening torque Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2

Auxiliary contact composition 1 NO + 1 NC

Auxiliary contacts type type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1


type mirror contact 1 NC conforming to IEC 60947-4-1

Signalling circuit frequency 25...400 Hz

Minimum switching voltage 17 V for signalling circuit

Minimum switching current 5 mA for signalling circuit

Insulation resistance > 10 MOhm for signalling circuit

Non-overlap time 1.5 ms on de-energisation between NC and NO contact


1.5 ms on energisation between NC and NO contact

Mounting support Plate


Rail

Environment
Standards CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 60947-4-1
IEC 60335-1:Clause 30.2
IEC 60335-2-40:Annex JJ
UL 60335-2-40:Annex JJ
CSA C22.2 No 60947-4-1

Product certifications UL
CCC
CSA
Marine
UKCA
EAC
CB Scheme

IP degree of protection IP20 front face conforming to IEC 60529

Protective treatment TH conforming to IEC 60068-2-30

Climatic withstand conforming to IACS E10 exposure to damp heat


conforming to IEC 60947-1 Annex Q category D exposure to damp heat

Feb 3, 2025 AD 3
Permissible ambient air -40…60 °C
temperature around the device 60…70 °C with derating

Operating altitude 0...3000 m

Fire resistance 850 °C conforming to IEC 60695-2-1

Flame retardance V1 conforming to UL 94

Mechanical robustness Vibrations contactor open (2 Gn, 5...300 Hz)


Vibrations contactor closed (4 Gn, 5...300 Hz)
Shocks contactor open (10 Gn for 11 ms)
Shocks contactor closed (15 Gn for 11 ms)

Height 77 mm

Width 45 mm

Depth 86 mm

Product weight 0.32 kg

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 5.000 cm

Package 1 Width 9.200 cm

Package 1 Length 11.500 cm

Package 1 Weight 350.000 g

Unit Type of Package 2 S02

Number of Units in Package 2 20

Package 2 Height 15.000 cm

Package 2 Width 30.000 cm

Package 2 Length 40.000 cm

Package 2 Weight 7.282 kg

Unit Type of Package 3 P06

Number of Units in Package 3 320

Package 3 Height 75.000 cm

Package 3 Width 60.000 cm

Package 3 Length 80.000 cm

Package 3 Weight 123.500 kg

Contractual warranty
Warranty 18 months

4 Feb 3, 2025 AD
Environmental Data

Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity
via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.

Environmental Data explained

How we assess product sustainability

Environmental footprint

Carbon footprint ([Link].CO2 per CR, Total Life cycle) 18

Environmental Disclosure Product Environmental Profile

Use Better

Materials and Substances

Packaging made with recycled cardboard Yes

Packaging without single use plastic Yes

China RoHS Regulation China RoHS declaration

PVC free Yes

Use Again

Repack and remanufacture

Circularity Profile End of Life Information

The product must be disposed on European Union


WEEE markets following specific waste collection and never end
up in rubbish bins

Take-back No

Feb 3, 2025 AD 5
Product datasheet LC1D09M7

Dimensions Drawings

Dimensions

(1) Including LAD 4BB

(2) Minimum electrical clearance

LC1 D09…D18 D093…D123 D099…D129

b without add-on blocks 77 99 80

with LAD 4BB 94 107 95.5

with LA4 D●2 110(1) 123(1) 111.5(1)


b1
with LA4 DF, DT 119(1) 132(1) 120.5(1)

with LA4 DW, DL 126(1) 139(1) 127.5(1)

without cover or add-on blocks 84 84 84


c
with cover, without add-on blocks 86 86 86

c1 with LAD N or C (2 or 4 contacts) 117 117 117

c2 with LA6 DK10, LAD 6K10 129 129 129

with LAD T, R, S 137 137 137


c3
with LAD T, R, S and sealing cover 141 141 141

(1) Including LAD 4BB.

6 Feb 3, 2025 AD
Product datasheet LC1D09M7

Connections and Schema

Wiring

Feb 3, 2025 AD 7
Product datasheet
Specifications

Motor circuit breaker, TeSys GV2,


3P, 1-1.6 A, thermal magnetic,
screw clamp terminals
GV2ME06

Main
Range TeSys Deca

product name TeSys GV2

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product or component type Motor circuit breaker

Device short name GV2ME

Device application Motor protection

Trip unit technology Thermal-magnetic

Complementary
Poles description 3P

network type AC

Utilisation category Category A conforming to IEC 60947-2


AC-3 conforming to IEC 60947-4-1
AC-3e conforming to IEC 60947-4-1

Network frequency 50/60 Hz conforming to IEC 60947-4-1

Motor power kW 0.37 kW at 400/415 V AC 50/60 Hz


0.55 kW at 400/415 V AC 50/60 Hz
0.37 kW at 500 V AC 50/60 Hz
0.55 kW at 500 V AC 50/60 Hz
0.75 kW at 500 V AC 50/60 Hz
0.75 kW at 690 V AC 50/60 Hz
1.1 kW at 690 V AC 50/60 Hz

Breaking capacity 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2


100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2

[Ics] rated service short-circuit 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2

Control type Push-button

[In] rated current 1.6 A

Thermal protection adjustment 1…1.6 A conforming to IEC 60947-4-1


range
Magnetic tripping current 26.2 A

[Ith] conventional free air thermal 1.6 A conforming to IEC 60947-4-1


current
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2

[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand 6 kV conforming to IEC 60947-2


voltage

03-Feb-2025 1
Phase failure sensitivity Yes conforming to IEC 60947-4-1

Suitability for isolation Yes conforming to IEC 60947-1

Power dissipation per pole 2.5 W

Mechanical durability 100000 cycles

Electrical durability 100000 cycles for AC-3 at 415 V In


100000 cycles for AC-3e at 415 V In

Rated duty Continuous conforming to IEC 60947-4-1

Tightening torque 1.7 N.m - on screw clamp terminal

Fixing mode 35 mm symmetrical DIN rail: clipped


Panel: screwed (with adaptor plate)

Mounting position Horizontal


Vertical

Width 45 mm

Height 89 mm

Depth 78.5 mm

Product weight 0.26 kg

Colour Dark grey

Environment
Standards EN/IEC 60947-2
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
IEC/EN 60335-2-40:Annex JJ
IEC/EN 60335-1:Clause 30.2

Product certifications CCC


UL
CSA
EAC
ATEX
LROS (Lloyds register of shipping)
BV
RINA
DNV-GL
UKCA

IK degree of protection IK04

IP degree of protection IP20 conforming to IEC 60529

Climatic withstand conforming to IACS E10

Ambient air temperature for -40…80 °C


storage
Fire resistance 960 °C conforming to IEC 60695-2-11

Ambient air temperature for -20…60 °C


operation
Mechanical robustness Shocks: 30 Gn for 11 ms
Vibrations: 5 Gn, 5...150 Hz

Operating altitude 2000 m

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 4.500 cm

Package 1 Width 8.500 cm

2 03-Feb-2025
Package 1 Length 9.000 cm

Package 1 Weight 253.000 g

Unit Type of Package 2 S02

Number of Units in Package 2 24

Package 2 Height 15.000 cm

Package 2 Width 30.000 cm

Package 2 Length 40.000 cm

Package 2 Weight 6.228 kg

Unit Type of Package 3 P06

Number of Units in Package 3 384

Package 3 Height 75.000 cm

Package 3 Width 60.000 cm

Package 3 Length 80.000 cm

Package 3 Weight 110.504 kg

Contractual warranty
Warranty 18 months

03-Feb-2025 3
Environmental Data

Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity
via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.

Environmental Data explained

How we assess product sustainability

Environmental footprint

Carbon footprint ([Link].CO2 per CR, Total Life cycle) 43

Environmental Disclosure Product Environmental Profile

Use Better

Materials and Substances

Packaging made with recycled cardboard No

Packaging without single use plastic No

SCIP Number 04104e70-ba29-493c-b2cc-b5837d1f879b

China RoHS Regulation China RoHS declaration

Use Again

Repack and remanufacture

Circularity Profile End of Life Information

The product must be disposed on European Union


WEEE markets following specific waste collection and never end
up in rubbish bins

Take-back No

4 03-Feb-2025
Product datasheet GV2ME06

Performance Curves

Thermal-Magnetic Tripping Curves for GV2ME and GV2P


Average Operating Times at 20 °C Related to Multiples of the Setting Current

1 3 poles from cold state

2 2 poles from cold state

3 3 poles from hot state

Current Limitation on Short-Circuit for GV2ME and GV2P (3-Phase 400/415 V))
Dynamic Stress
I peak = f (prospective Isc) at 1.05 Ue = 435 V

03-Feb-2025 5
Product datasheet GV2ME06

1 Maximum peak current

2 24-32 A

3 20-25 A

4 17-23 A

5 13-18 A

6 9-14 A

7 6-10 A

8 4-6.3 A

9 2.5-4 A

10 1.6-2.5 A

11 1-1.6 A

12 Limit of rated ultimate breaking capacity on short-circuit of GV2ME (14, 18, 23, and 25 A ratings).

Thermal Limit on Short-Circuit for GV2ME


Thermal Limit in kA2s in the Magnetic Operating Zone
Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V

6 03-Feb-2025
Product datasheet GV2ME06

1 24-32 A

2 20-25 A

3 17-23 A

4 13-18 A

5 9-14 A

6 6-10 A

7 4-6.3 A

8 2.5-4 A

9 1.6-2.5 A

10 1-1.6 A

03-Feb-2025 7
Product datasheet GV2ME06

Dimensions Drawings

Dimension
GV2ME

(1) Maximum

X1 Electrical clearance = 40 mm for Ue ≤ 690 V

GV2ME●● 89

GV2ME●●3 101

Mounting
GV2ME
On 35 mm rail

c = 78.5 on AM1 DP200 (35 x 7.5)


c = 86 on AM1 DE200, ED200 (35 x 15)
On panel with adapter plate GV2AF02

On pre-slotted plate AM1 PA

On rails DZ5 MB201

8 03-Feb-2025
Product datasheet GV2ME06

GV2AF01
Combination GV2ME + TeSys k contactor

GV2AF3
Combination GV2ME + TeSys d contactor

GV2ME + LC1D09…D18 LC1D25 and D32

b 176.4 186.8

c1 94.1 100.4

c 99.6 105.9

GV2AF4 + LAD311
Combination GV2ME + TeSys d contactor

03-Feb-2025 9
Product datasheet GV2ME06

GV2ME + LC1D09…D18 LC1D25 and D32

b 176.4 186.8

c1 103.1 136.4

c 135.6 141.9

d1 107 107

d 112.5 112.5

GV2ME + GV1L3 (Current Limiter)

X1 = 10 mm for Ue = 230 V or 30 mm for 230 V < Ue ≤ 690 V

10 03-Feb-2025
Product datasheet GV2ME06

Connections and Schema

GV2ME•• and GV2RT

Connection of Undervoltage Trip for Dangerous Machines (Conforming to INRS) on GV2ME Only

03-Feb-2025 11
Product datasheet
Specifications

Motor circuit breaker, TeSys GV2,


3P, 0.4-0.63 A, thermal magnetic,
screw clamp terminals
GV2ME04

Main
Range TeSys Deca

product name TeSys GV2

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product or component type Motor circuit breaker

Device short name GV2ME

Device application Motor protection

Trip unit technology Thermal-magnetic

Complementary
Poles description 3P

network type AC

Utilisation category Category A conforming to IEC 60947-2


AC-3 conforming to IEC 60947-4-1
AC-3e conforming to IEC 60947-4-1

Network frequency 50/60 Hz conforming to IEC 60947-4-1

Motor power kW 0.12 kW at 400/415 V AC 50/60 Hz


0.18 kW at 400/415 V AC 50/60 Hz
0.37 kW at 690 V AC 50/60 Hz

Breaking capacity 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2


100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2

[Ics] rated service short-circuit 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2

Control type Push-button

[In] rated current 0.63 A

Thermal protection adjustment 0.4…63 A conforming to IEC 60947-4-1


range
Magnetic tripping current 9.3 A

[Ith] conventional free air thermal 0.63 A conforming to IEC 60947-4-1


current
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2

[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand 6 kV conforming to IEC 60947-2


voltage
Phase failure sensitivity Yes conforming to IEC 60947-4-1

Suitability for isolation Yes conforming to IEC 60947-1

03-Feb-2025 1
Power dissipation per pole 2.5 W

Mechanical durability 100000 cycles

Electrical durability 100000 cycles for AC-3 at 415 V In


100000 cycles for AC-3e at 415 V In

Rated duty Continuous conforming to IEC 60947-4-1

Tightening torque 1.7 N.m - on screw clamp terminal

Fixing mode 35 mm symmetrical DIN rail: clipped


Panel: screwed (with adaptor plate)

Mounting position Horizontal


Vertical

Width 45 mm

Height 89 mm

Depth 78.5 mm

Product weight 0.26 kg

Colour Dark grey

Environment
Standards EN/IEC 60947-2
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
IEC/EN 60335-2-40:Annex JJ
IEC/EN 60335-1:Clause 30.2

Product certifications CCC


UL
CSA
EAC
ATEX
LROS (Lloyds register of shipping)
BV
RINA
DNV-GL
UKCA
UKCA

IK degree of protection IK04

IP degree of protection IP20 conforming to IEC 60529

Climatic withstand conforming to IACS E10

Ambient air temperature for -40…80 °C


storage
Fire resistance 960 °C conforming to IEC 60695-2-11

Ambient air temperature for -20…60 °C


operation
Mechanical robustness Shocks: 30 Gn for 11 ms
Vibrations: 5 Gn, 5...150 Hz

Operating altitude 2000 m

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 4.500 cm

Package 1 Width 8.500 cm

Package 1 Length 9.500 cm

2 03-Feb-2025
Package 1 Weight 216.000 g

Unit Type of Package 2 S02

Number of Units in Package 2 24

Package 2 Height 15.000 cm

Package 2 Width 30.000 cm

Package 2 Length 40.000 cm

Package 2 Weight 5.718 kg

Unit Type of Package 3 P06

Number of Units in Package 3 384

Package 3 Height 75.000 cm

Package 3 Width 60.000 cm

Package 3 Length 80.000 cm

Package 3 Weight 98.088 kg

Contractual warranty
Warranty 18 months

03-Feb-2025 3
Environmental Data

Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity
via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.

Environmental Data explained

How we assess product sustainability

Environmental footprint

Carbon footprint ([Link].CO2 per CR, Total Life cycle) 43

Environmental Disclosure Product Environmental Profile

Use Better

Materials and Substances

Packaging made with recycled cardboard No

Packaging without single use plastic No

SCIP Number 04104e70-ba29-493c-b2cc-b5837d1f879b

China RoHS Regulation China RoHS declaration

Use Again

Repack and remanufacture

Circularity Profile End of Life Information

The product must be disposed on European Union


WEEE markets following specific waste collection and never end
up in rubbish bins

Take-back No

4 03-Feb-2025
Product datasheet GV2ME04

Performance Curves

Thermal-Magnetic Tripping Curves for GV2ME and GV2P


Average Operating Times at 20 °C Related to Multiples of the Setting Current

1 3 poles from cold state

2 2 poles from cold state

3 3 poles from hot state

Current Limitation on Short-Circuit for GV2ME and GV2P (3-Phase 400/415 V))
Dynamic Stress
I peak = f (prospective Isc) at 1.05 Ue = 435 V

03-Feb-2025 5
Product datasheet GV2ME04

1 Maximum peak current

2 24-32 A

3 20-25 A

4 17-23 A

5 13-18 A

6 9-14 A

7 6-10 A

8 4-6.3 A

9 2.5-4 A

10 1.6-2.5 A

11 1-1.6 A

12 Limit of rated ultimate breaking capacity on short-circuit of GV2ME (14, 18, 23, and 25 A ratings).

Thermal Limit on Short-Circuit for GV2ME


Thermal Limit in kA2s in the Magnetic Operating Zone
Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V

6 03-Feb-2025
Product datasheet GV2ME04

1 24-32 A

2 20-25 A

3 17-23 A

4 13-18 A

5 9-14 A

6 6-10 A

7 4-6.3 A

8 2.5-4 A

9 1.6-2.5 A

10 1-1.6 A

03-Feb-2025 7
Product datasheet GV2ME04

Dimensions Drawings

Dimension
GV2ME

(1) Maximum

X1 Electrical clearance = 40 mm for Ue ≤ 690 V

GV2ME●● 89

GV2ME●●3 101

Mounting
GV2ME
On 35 mm rail

c = 78.5 on AM1 DP200 (35 x 7.5)


c = 86 on AM1 DE200, ED200 (35 x 15)
On panel with adapter plate GV2AF02

On pre-slotted plate AM1 PA

On rails DZ5 MB201

8 03-Feb-2025
Product datasheet GV2ME04

GV2AF01
Combination GV2ME + TeSys k contactor

GV2AF3
Combination GV2ME + TeSys d contactor

GV2ME + LC1D09…D18 LC1D25 and D32

b 176.4 186.8

c1 94.1 100.4

c 99.6 105.9

GV2AF4 + LAD311
Combination GV2ME + TeSys d contactor

03-Feb-2025 9
Product datasheet GV2ME04

GV2ME + LC1D09…D18 LC1D25 and D32

b 176.4 186.8

c1 103.1 136.4

c 135.6 141.9

d1 107 107

d 112.5 112.5

GV2ME + GV1L3 (Current Limiter)

X1 = 10 mm for Ue = 230 V or 30 mm for 230 V < Ue ≤ 690 V

10 03-Feb-2025
Product datasheet GV2ME04

Connections and Schema

GV2ME•• and GV2RT

Connection of Undervoltage Trip for Dangerous Machines (Conforming to INRS) on GV2ME Only

03-Feb-2025 11
Product datasheet
Specifications

Motor circuit breaker, TeSys GV2,


3P, 0.25-0.4 A, thermal magnetic,
screw clamp terminals
GV2ME03

Main
Range TeSys Deca

product name TeSys GV2

Product or component type Motor circuit breaker

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Device short name GV2ME

Device application Motor protection

Trip unit technology Thermal-magnetic

Complementary
Poles description 3P

network type AC

Utilisation category Category A conforming to IEC 60947-2


AC-3 conforming to IEC 60947-4-1
AC-3e conforming to IEC 60947-4-1

Network frequency 50/60 Hz conforming to IEC 60947-4-1

Motor power kW 0.12 kW at 400/415 V AC 50/60 Hz


0.18 kW at 400/415 V AC 50/60 Hz
0.37 kW at 690 V AC 50/60 Hz

Breaking capacity 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2


100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2

[Ics] rated service short-circuit 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2

Control type Push-button

[In] rated current 0.4 A

Thermal protection adjustment 0.25…0.4 A conforming to IEC 60947-4-1


range
Magnetic tripping current 5.8 A

[Ith] conventional free air thermal 0.4 A conforming to IEC 60947-4-1


current
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2

[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand 6 kV conforming to IEC 60947-2


voltage
Phase failure sensitivity Yes conforming to IEC 60947-4-1

Suitability for isolation Yes conforming to IEC 60947-1

Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.

Feb 3, 2025 1
Power dissipation per pole 2.5 W

Mechanical durability 100000 cycles

Electrical durability 100000 cycles for AC-3 at 415 V In


100000 cycles for AC-3e at 415 V In

Rated duty Continuous conforming to IEC 60947-4-1

Tightening torque 1.7 N.m - on screw clamp terminal

Fixing mode 35 mm symmetrical DIN rail: clipped


Panel: screwed (with adaptor plate)

Mounting position Horizontal


Vertical

Width 45 mm

Height 89 mm

Depth 78.5 mm

Product weight 0.26 kg

Colour Dark grey

Environment
Standards EN/IEC 60947-2
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
IEC/EN 60335-2-40:Annex JJ
IEC/EN 60335-1:Clause 30.2

Product certifications CCC


UL
CSA
EAC
ATEX
LROS (Lloyds register of shipping)
BV
RINA
DNV-GL
UKCA

IK degree of protection IK04

IP degree of protection IP20 conforming to IEC 60529

Climatic withstand conforming to IACS E10

Ambient air temperature for -40…80 °C


storage
Fire resistance 960 °C conforming to IEC 60695-2-11

Ambient air temperature for -20…60 °C


operation
Mechanical robustness Shocks: 30 Gn for 11 ms
Vibrations: 5 Gn, 5...150 Hz

Operating altitude 2000 m

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 9.3 cm

Package 1 Width 4.8 cm

Package 1 Length 8.5 cm

Package 1 Weight 226 g

2 Feb 3, 2025
Unit Type of Package 2 S02

Number of Units in Package 2 24

Package 2 Height 15 cm

Package 2 Width 30 cm

Package 2 Length 40 cm

Package 2 Weight 5.746 kg

Unit Type of Package 3 P06

Number of Units in Package 3 384

Package 3 Height 75 cm

Package 3 Width 60 cm

Package 3 Length 80 cm

Package 3 Weight 104.1 kg

Contractual warranty
Warranty 18 months

Feb 3, 2025 3
Environmental Data

Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity
via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.

Environmental Data explained

How we assess product sustainability

Environmental footprint

Carbon footprint ([Link].CO2 per CR, Total Life cycle) 43

Environmental Disclosure Product Environmental Profile

Use Better

Materials and Substances

Packaging made with recycled cardboard No

Packaging without single use plastic No

SCIP Number 04104e70-ba29-493c-b2cc-b5837d1f879b

China RoHS Regulation China RoHS declaration

Use Again

Repack and remanufacture

Circularity Profile End of Life Information

The product must be disposed on European Union


WEEE markets following specific waste collection and never end
up in rubbish bins

Take-back No

4 Feb 3, 2025
Product datasheet GV2ME03

Performance Curves

Thermal-Magnetic Tripping Curves for GV2ME and GV2P


Average Operating Times at 20 °C Related to Multiples of the Setting Current

1 3 poles from cold state

2 2 poles from cold state

3 3 poles from hot state

Current Limitation on Short-Circuit for GV2ME and GV2P (3-Phase 400/415 V))
Dynamic Stress
I peak = f (prospective Isc) at 1.05 Ue = 435 V

Feb 3, 2025 5
Product datasheet GV2ME03

1 Maximum peak current

2 24-32 A

3 20-25 A

4 17-23 A

5 13-18 A

6 9-14 A

7 6-10 A

8 4-6.3 A

9 2.5-4 A

10 1.6-2.5 A

11 1-1.6 A

12 Limit of rated ultimate breaking capacity on short-circuit of GV2ME (14, 18, 23, and 25 A ratings).

Thermal Limit on Short-Circuit for GV2ME


Thermal Limit in kA2s in the Magnetic Operating Zone
Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V

6 Feb 3, 2025
Product datasheet GV2ME03

1 24-32 A

2 20-25 A

3 17-23 A

4 13-18 A

5 9-14 A

6 6-10 A

7 4-6.3 A

8 2.5-4 A

9 1.6-2.5 A

10 1-1.6 A

Feb 3, 2025 7
Product datasheet GV2ME03

Dimensions Drawings

Dimension
GV2ME

(1) Maximum

X1 Electrical clearance = 40 mm for Ue ≤ 690 V

GV2ME●● 89

GV2ME●●3 101

Mounting
GV2ME
On 35 mm rail

c = 78.5 on AM1 DP200 (35 x 7.5)


c = 86 on AM1 DE200, ED200 (35 x 15)
On panel with adapter plate GV2AF02

On pre-slotted plate AM1 PA

On rails DZ5 MB201

8 Feb 3, 2025
Product datasheet GV2ME03

GV2AF01
Combination GV2ME + TeSys k contactor

GV2AF3
Combination GV2ME + TeSys d contactor

GV2ME + LC1D09…D18 LC1D25 and D32

b 176.4 186.8

c1 94.1 100.4

c 99.6 105.9

GV2AF4 + LAD311
Combination GV2ME + TeSys d contactor

Feb 3, 2025 9
Product datasheet GV2ME03

GV2ME + LC1D09…D18 LC1D25 and D32

b 176.4 186.8

c1 103.1 136.4

c 135.6 141.9

d1 107 107

d 112.5 112.5

GV2ME + GV1L3 (Current Limiter)

X1 = 10 mm for Ue = 230 V or 30 mm for 230 V < Ue ≤ 690 V

10 Feb 3, 2025
Product datasheet GV2ME03

Connections and Schema

GV2ME•• and GV2RT

Connection of Undervoltage Trip for Dangerous Machines (Conforming to INRS) on GV2ME Only

Feb 3, 2025 11
Product datasheet
Specifications

TeSys GV2 & GV3 - auxiliary


contact - 1 NO + 1 NO (fault)
GVAD1010

Main
Range TeSys
TeSys Deca

Device short name GVAD

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product or component type Auxiliary contact block

Product compatibility GV2L


GV2P
GV2RT
GV3L
GV2LE
GV3P
GV2ME

Mounting location Left side

Auxiliary contacts operation Fault signal 1 NO

Pole contact composition 2 NO

Complementary
[Ui] rated insulation voltage 690 V conforming to IEC 60947-1
300 V conforming to UL 508
300 V conforming to CSA C22.2 No 14

[Ue] rated operational voltage 48...690 V AC


24...240 V DC

[Ith] conventional free air thermal 6A


current 2.5 A for fault signalling

Mechanical durability 100000 cycles

Minimum switching current 5 mA

Minimum switching voltage 17 V

Protection type GB2CB... circuit breaker


GG fuse 10 A

Rated operational power in VA 300 VA at 48 V AC-15 - electrical durability: 100000 cycles


414 VA at 690 V AC-15 - electrical durability: 100000 cycles
500 VA at 110…127 V AC-15 - electrical durability: 100000 cycles
500 VA at 500 V AC-15 - electrical durability: 100000 cycles
650 VA at 440 V AC-15 - electrical durability: 100000 cycles
720 VA at 230…240 V AC-15 - electrical durability: 100000 cycles
850 VA at 380…415 V AC-15 - electrical durability: 100000 cycles
36 VA at 24 V AC-14 - electrical durability: 1000 cycles
48 VA at 48 V AC-14 - electrical durability: 1000 cycles
72 VA at 110…127 V AC-14 - electrical durability: 1000 cycles

Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.

Feb 3, 2025 1
Rated operational power in W 120 W at 240 V DC-13 - electrical durability: 100000 cycles
140 W at 110 V DC-13 - electrical durability: 100000 cycles
140 W at 24 V DC-13 - electrical durability: 100000 cycles
180 W at 60 V DC-13 - electrical durability: 100000 cycles
240 W at 48 V DC-13 - electrical durability: 100000 cycles
15 W at 48 V DC-13 - electrical durability: 1000 cycles
24 W at 24 V DC-13 - electrical durability: 1000 cycles
9 W at 60 V DC-13 - electrical durability: 1000 cycles

Tightening torque 1.4 N.m - on screw clamp terminals

Height 89 mm

Width 9.3 mm

Depth 66 mm

Product weight 0.055 kg

Colour Dark grey

Environment
Environmental characteristic Normal environment

Product certifications UKCA

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 1.500 cm

Package 1 Width 6.500 cm

Package 1 Length 8.700 cm

Package 1 Weight 42.000 g

Unit Type of Package 2 BB1

Number of Units in Package 2 10

Package 2 Height 9.500 cm

Package 2 Width 10.000 cm

Package 2 Length 15.000 cm

Package 2 Weight 470.000 g

Unit Type of Package 3 S02

Number of Units in Package 3 60

Package 3 Height 15.000 cm

Package 3 Width 30.000 cm

Package 3 Length 40.000 cm

Package 3 Weight 3.104 kg

Contractual warranty
Warranty 18 months

2 Feb 3, 2025
Environmental Data

Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity
via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.

Environmental Data explained

How we assess product sustainability

Environmental footprint

Carbon footprint ([Link].CO2 per CR, Total Life cycle) 1

Environmental Disclosure Product Environmental Profile

Use Better

Materials and Substances

Packaging made with recycled cardboard Yes

Packaging without single use plastic No

China RoHS Regulation China RoHS declaration

Use Again

Repack and remanufacture

Circularity Profile End of Life Information

The product must be disposed on European Union


WEEE markets following specific waste collection and never end
up in rubbish bins

Take-back No