Wind Load Calculation Guide for Sylhet

The document outlines the wind load calculations for a building located in Sylhet, following the BNBC 2006 standards. It includes parameters such as basic wind speed, structural importance coefficients, and sustained wind pressure calculations in both X and Y directions. The calculations detail the wind pressures on various floors and roof levels, providing specific values for different areas of the structure.

Uploaded by

engrsmshajed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
60 views1 page

Wind Load Calculation Guide for Sylhet

The document outlines the wind load calculations for a building located in Sylhet, following the BNBC 2006 standards. It includes parameters such as basic wind speed, structural importance coefficients, and sustained wind pressure calculations in both X and Y directions. The calculations detail the wind pressures on various floors and roof levels, providing specific values for different areas of the structure.

Uploaded by

engrsmshajed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd

Wind Load Calculation , BNBC 2006

Building Location = Sylhet


Exposer Condition= A
Basic Wind Speed Vb= 195 km/h
Velocity to Pressure Co-efficient Cc= 4.72E-05
Structural Importance Category= II
Structural Importance Co-efficient Ci= 1.25 h= 7.62 m

Sustained wind pressure qz=[Link]²= 2.243 Cz


Gust Co-efficient Cg= 1.592

Pressure pz-x= [Link]= 4.822 Cz


Pressure py-x= [Link]= 5.383 Cz

Cz= Combined height and exposure co-efficient


Y
Wind direction X Wind direction Y
X
L= 12.35 m
B= 12.35 m B= 15.58 m
L= 15.58 m L= 12.35 m
h= 7.62 m h= 7.62 m B= 15.58 m

L/B= 1.261538 L/B= 0.792683


h/B= 0.617004 h/B= 0.489089

Cp= 1.350 Cp= 1.507

1st floor height= 4.3434 m


Tpical floor height= 3.2012 m

Wind Pressure Calculation X-Direction Y-Direction


Floor Height Cz Pz-x Pz-x Area Floor Level Pz-y Pz-y Area Floor Level
from GL kN/m² lb/ft² m² Force (Kip) kN/m² lb/ft² m² Force (Kip)
0
1F 3.000 <---ok 0.3680 1.7744 37.06 18.5 7.39 1.9809 41.37 23.4 10.41
2F 3.000 <---ok 0.3680 1.7744 37.06 12.4 4.93 1.9809 41.37 15.6 6.94
3F 5.000 <---ok 0.3680 1.7744 37.06 -18.5 -7.39 1.9809 41.37 -23.4 -10.41
4F 0.000 <---ok 0.3680 1.7744 37.06 -30.9 -12.32 1.9809 41.37 -39.0 -17.35
ROOF 0.000 <---ok 0.3680 1.7744 37.06 13.2 5.26 1.9809 41.37 16.6 7.40
Stair Roof, D4 0.000 <---ok 0.3680 1.7744 37.06 13.0 5.21 1.9809 41.37 10.5 4.67
Stair Roof, D3 0.000 <---ok 0.3680 1.7744 37.06 8.4 3.35 1.9809 41.37 13.3 5.92