Public Addressable System

The document outlines the specifications and features of the Jay Public Addressable Fire Alarm Panel Je190, which supports 2 to 60 zones and complies with IS 2189 standards. It includes details on the internal power supply, relay contact ratings, panel indications, and external controls for operation. Additionally, it provides contact information for Synopsys Tech Pvt. Ltd.

Uploaded by

weldie.dimtsu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
60 views3 pages

Public Addressable System

The document outlines the specifications and features of the Jay Public Addressable Fire Alarm Panel Je190, which supports 2 to 60 zones and complies with IS 2189 standards. It includes details on the internal power supply, relay contact ratings, panel indications, and external controls for operation. Additionally, it provides contact information for Synopsys Tech Pvt. Ltd.

Uploaded by

weldie.dimtsu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

To smoke Detectors

MCP + Hooter nth Floor

To smoke Detectors

MCP + Hooter Second Floor

To smoke Detectors

MCP + Hooter First Floor

WIRING DIAGRAM OF PUBLIC ADDRESSABLE PANEL Je190


Fire Alarm Panel
JAY Public Addressable System_Je190
Salient Features:-
 The panel consists of 2 to 60 Zones.
 The panel complies with IS 2189 specification.
 The panel has separate fire and fault indications.
 The panel also has separate fire and common fault relay.
 The panel comprises of a 4Amp power supply unit.
 Battery backup is provided along with the AC
supply.(Optional)
 The panel is equipped with a 24VdC piezoelectric buzzer
for fault and fire.

Synopsys Tech Pvt. Ltd.


A-001, Fressia CHS LTD, Baburao Ranade Marg, Off. L.M. Road, Behind Bank of India, Dahisar West,
Mumbai-400068. Tel. 022-28904500/6800/6500 Email :- info@[Link]
Technical Specifications:-
INTERNAL POWER SUPPLY UNIT
 Constant potential battery charger 27.5V DC Adjustable
 Output Current limited to 2 A
 Low battery voltage monitored at 18 V DC Adjustable
 Battery charger monitoring for failure
 Mains supply monitoring for failure
 Mains supply input voltage range 230V AC + or – 10 %, 50 Hz
 Total panel quiescent current 50mA nominal
 Approx. Standby time 4.5 AH 36 hrs.
 Battery recharge time from discharge 1 Hr. approx.

INTERNAL RELAY CONTACT RATING


 Fire Relay 5 Amps S.P. 240 V DC
 Common fault relay 5 Amps S.P. 240 V DC
 Aux. Fire relay 5 Amps S.P. 240 V AC

Panel Indications:-
 System ON Green LED - System normal
 Common Fault Amber LED – Internal buzzer will sound intermittently
 Common Fire Red LED - Detector activated
 Zone fault Amber LED – Indicates zone wiring and detector faults
 Zone fire Red LED – indicates zone where fire has been detected
 AC fail Amber LED – Indicates loss of mains
 DC fail Amber LED – Indicates battery fault
 Batt. Low Amber LED – Indicates battery supply below 18V DC

EXTERNAL CONTROLS:-
 Sound - To sound external as well as internal sounders.
 Silence -To silence external as well as internal sounders.
 Reset -Lamp test & resets the panels.
 Isolate -the zone to add/clean detectors.
 Test -International standard walk test.
 Auto/manual -Amplifier in auto/manual mode.
 Volume -Increase/ decrease amplifier volume.
 Call All -Announcement to all zones simultaneously.