LEGEND : ( Electrical & Fire Alarm System ) LEGEND : ( Electrical System )
S. No. SYMBOL DESCRIPTION POSITION
S. No. SYMBOL DESCRIPTION POSITION
MANUAL CALL POINT 1. LIGHT POINT/ WALL BRACKET 2250
39. 1050
( BREAK GLASS TYPE )
2. LIGHT POINT/ WALL BRACKET (FOR TOILET) 2250
40. TALK BACK UNIT 1200
3. CEILING LIGHT (SURFACE )
41. ELECTRONIC HOOTER / SPEAKER 2250
4. CORRIDOR /STAIR CASE LED LIGHT
42. OPTICAL TYPE SMOKE DETECTOR
5. CEILING LIGHT ( RECESS )
LIFT LIFT 43. RESPONSE INDICATOR 2250
6. MIRROR LIGHT 2000
44. F FOR FIRE ALARM SYSTEM
7. CHANDLIER
45. A/C INDOOR UNIT
8. CEILING FAN
46. A/C OUTDOOR UNIT
LIFT LOBBY 9. EXHAUST FAN / CEILING ROSE 2000
47. F.U. FREEDOM / DISPLAY UNIT
10. WALL MOUNTING REVOLVING FAN 2250
48. EMERGENCY LIGHT POINT INDICATION
11. 6 AMP PLUG POINT 200
49. EXIT SIGNS (SELF ILLUMINATED / AUTO GLOW)
12. 6 AMP PLUG POINT (BED SIDE) 550
INDICATIVE CONDUIT RUN
50. S 2 NOS 6 AMP PLUG POINT FOR SET TOP BOX / DVD
FOR SUBMAIN
1 NO. SWITCH FOR (T.V.) 550
13. T.P.-1 2 NOS AV/TV OUTLET FOR SET TOP BOX / DVD
51. POWER / A.C. CURCUIT
1 NO. 6 AMP SOCKET FOR (T.V.) & 1200
1 NO. TV OUTLET POINT
52. LIGHT / FAN CIRCUIT
14. 6 AMP PLUG POINT 1050
INDICATIVE CONDUIT RUN TELEPHONE / T.V.
53. T 6 AMP SOCKET OUTLET (FOR CHIMNEY)
15. 2250
(SWITCH WILL BE AT MAIN BOARD)
EQ EQ 54. T 6 AMP SOCKET OUTLET (FOR GAS BURNER)
TELEPHONE / T.V. SYSTEM (IN SIDE FLAT) 16.
BELOW COUNTER (SWITCH AT MAIN BOARD) 550
55. WATER PURIFIER
17. 6 AMP PLUG POINT 2250
18. 6 /16 AMP POWER POINT 200
R
Notes : ( Electrical ) 19. 6 /16 AMP POWER POINT 1050
1. R, Y & B indicates phases. 1500 / OR
20. 16 AMP. POWER POINT (FOR TOI. GEYSER)
AS SPECIFIED
2. The number written near the switch board and power points indicates
circuit number. for detail of circuits refer distribution board charts. 16 AMP. POWER SOCKET (FOR KIT.GEYSER)
21. 2250
(CONTROL AT SWITCH BOARD)
3. The size of wires from switch board to different light and fan points shall
be 1.0 sq. m.m. 22. 16 AMP SWITCH CONTROL FOR KIT. GEYSER 1050
4. For secondary power point the circuit wire shall be looped from first 20 AMP SWITCH / SOCKET (POWER POINT) 200 / OR
power point by 2 x 2.5 sq.mm. (Wherever specified) 23.
& 1 NO. CABLE OUTLET SOCKET AS SPECIFIED
5. 6 amp. switch socket shall be connected to the lighting ckt. of that area CABLE OUTLET POINT BEHIND SPLIT AC UNIT 2550 / OR
by 1.0 sq.mm.. 24.
FOR ELECTRICAL CONNECTION AS SPECIFIED
6. The size of submain conduit from electrical shaft to each flat D.B. shall
25. TELEPHONE POINT 200
7. TV / Tel. conduit sizes shall be :
26. TELEPHONE & INTERCOM POINT 200
a) From LV shaft to TV / Tel junction box
(1 No. for T.V. & 1 No. for Telephone / Data / Intercom)
b) From TV / Tel J. B. to further distribution : 25 mm dia. 27. TELEPHONE POINT (BED SIDE) 550
8. The conduits used for wiring shall be as follows :
a) PVC - Heavy duty (2 mm thick) : In RCC slab / 28. INTERCOM POINT 200
RCC Wall
b) PVC - Medium duty (1.6 mm thick) : In brick wall / 29. C CALL BELL PUSH (FOR VDP) 1500
Block Work
c) The minimum conduit size in : 25 mm dia.
30. B BUZZER (JUNCTION BOX ONLY) 2250
RCC Slab / RCC Wall shall be
d) M.S.(16 SWG) : All surface conduit inside shaft
31. VDP VIDEO DOOR PHONE 1200
9. RG -6 T.V. coaxial wire shall be laid from L.V. shaft / T.V. & Tel.junction
box to each T.V outlet separately. 32. SWITCH BOARD 1050
10. Cat - 6 cable for Tel. / Data / EPABX shall be laid from L.V shaft / T.V. &
Tel.junction box to Tel. point in Loop. 33. SWITCH BOARD (BED SIDE) 550
11. Parking / Corridor / Staircase lights shall be directly controlled from MCB
- DB through 2 x 1.5 sq.mm wires as shown in drawings. 34. TV T.V. & TEL.JUNCTION BOX (IN APARTMENT) 2250
12. No two dissimilar phase circuit / wire shall run together through same
conduit. 35. T T.V. & TEL.JUNCTION BOX (IN DUCT) 1200
13. Light and power circuit shall be drawn through separate conduit.
36. DISTRIBUTION BOARD (TOP LEVEL) 2100
14. Wiring shall be carried out as per colour code i.e. R, Y, B phases and
black - neutral and green - earth. INDICATES CONTROLLING OF LIGHT/ FAN
37.
FROM SWITCH BOARD
15. The sequence of phase distribution in different apartments will be INDICATES CONTROLLING OF EMERGENCY
different for overall phase balancing. 38.
LIGHT POINT
16. The position mentioned in legend is bottom of switch board / outlets.
R2 19.07.2017 Revised as per arch. plan & telephone revised.
17. The openings inside Electrical, LV & Fire shaft should be sealed at each
floor. R1 15.06.2016 Issued as G.F.C.
18. Conduit drop should be precisely co-ordinated with brick work. It is
adviced to mark brick work layout on slab before casting for exact
rev. no. date revision
position of conduit drop.
19. In case of two way fans, the switch will be provided on main board, project
while regulator will be provided on bed side board.
20. In case of any discrepancy in the drawing, the same may be brought to
ORANGE CASTLE AT LUCKNOW
the notice of electrical consultant for approval before execution.
21. The Earth Continuity wire has to be laid for all electrical outlets / sockets title
/ light / fan points. Size of earth wire shall be as follows : -
ELECTRICAL WIRING DRAWING
Phase Wire
( sq.mm. ) 2x1.5 2x2.5 2x4 2x6 2x10 2x16 4x6 4x10 4x16 (TOWER-K)
Earth Wire
1x1.0 1x1.5 1x2.5 1x4 1x6 1x6 2x4 2x6 2x6
( sq.mm. ) subtitle
TYPICAL FLOOR PLAN (B+S+13)
(LEVEL- 3rd,5th & 7th FLOOR)
drawing released for
APPROVAL SUBMISSION
ADVANCE COPY CONSTRUCTION
Drg. No :
CES / OC / T- K / EL-03 (sheet # 1 of 2)
Scale : Drawn By :
1: 65 @ A1 Desraj
Date : Design By :
June 2016 M. Sadiq
Ckd By :
Anand Havelia
500
CONDUIT
FU
Architects : C-28C, Sector-8,
100 500 Noida - 201301 (UP)
T 91 120 46 40 300
A R C H HM F 91 120 42 46 788
2100
ARCHITECTURE URBANISM
ENGINEERING INTERIORS [email protected]
www.archohm.com
services consultant
Consummate Engineering Services (P) Ltd.
Noida Office : B - 67, Sector - 67, Noida - 201 301
Tel : (0120) 6943500 ( 24 Lines )
Lko. Office : R 006, Rohtas Plumeria, Gomti Nagar, Lucknow
Typical Elevation of D.B & e mail : [email protected], website : www.cespl.in
Freedom / Display Unit