Control Interface Slave

Function Code 79

C IS I/O Use the control interface slave function code to interface a


(7 9 )
Harmony controller to a control I/O module. Control I/O mod-
N
N+1 ules have four analog inputs, two analog outputs, three digital
N+2 inputs, and four digital outputs. This function code defines the
N+3
characteristics of that I/O module and how the system
N+4
S10 responds to an I/O module failure.
N+5
S11
The control system must be carefully
N+6
evaluated to establish default values that will
N+7 WARNING
N+8 prevent personal injury and/or property
S15
damage in case of module failure.
S16
S17
S18 Outputs
N+9
Blk Type Description
N R Analog input 1
N+1 R Analog input 2
N+2 R Analog input 3
N+3 R Analog input 4
N+4 R Analog output 1 feedback
N+5 R Analog output 2 feedback
N+6 B Digital input 1
N+7 B Digital input 2
N+8 B Digital input 3
N+9 B I/O module status flag: 0 = good, 1 = bad

Specifications

Spec Tune Default Type Range Description


S1 N 0 I 0 - 63 Control interface I/O module address
S2 N 0.000 R Full Analog input 1 zero in engineering units
S3 N 0.000 R Full Analog input 1 span in engineering units
S4 N 0.000 R Full Analog input 2 zero in engineering units
S5 N 0.000 R Full Analog input 2 span in engineering units
S6 N 0.000 R Full Analog input 3 zero in engineering units

WBPEEUI210504C0 79 - 1
Specifications (continued)

Spec Tune Default Type Range Description


S7 N 0.000 R Full Analog input 3 span in engineering units
S8 N 0.000 R Full Analog input 4 zero in engineering units
S9 N 0.000 R Full Analog input 4 span in engineering units
S10 N 2 I 0 - 2046 Block address of analog output 1
S11 N 2 I 0 - 2046 Block address of analog output 2
S12 N 2 I 0 or 1 Digital input 1 logic sense
S13 N 2 I 0 or 1 Digital input 2 logic sense
S14 N 2 I 0 or 1 Digital input 3 logic sense
S15 N 2 I 0 - 2046 Block address of digital output 1
S16 N 2 I 0 - 2046 Block address of digital output 2
S17 N 2 I 0 - 2046 Block address of digital output 3
S18 N 2 I 0 - 2046 Block address of digital output 4
S19 N 0 I 0 or 1 Failure action (lack of I/O module response or bad
analog input reference voltage):
XX0 = trip module
XX1 = continue to operate
I/O module status flag (bad status indication):
0XX = set I/O module status flag output N+9 to
bad when the CIS module fails or is in
error mode
1XX = set I/O module status flag output N+9 to
bad when the I/O module fails or there is
a bad quality on one of the module's I/O
points

Explanation
Outputs
This block provides analog and digital I/O on the same board.
The final output is an I/O module status flag, which shows the
status of the control I/O module.

0 = good
1 = bad

Analog output feedbacks (N+4 and N+5) provide feedback to


M/A stations (function code 80) that have hardware stations
with bypass capabilities. This feedback signal provides an
alignment reference for the software logic, before establishing

79 - 2 WBPEEUI210504C0
control of the process when exiting from bypass or configure
mode (bumpless transfer).

NOTE: If S19 equals zero, and if there is a bad or unwired input, then the con-
trol module is tripped.

Specifications
S1 – IOSLV (Control I/O module address) I/O module address set by the
address dipswitch on the I/O module. Available addresses are
zero through 63.
S2 to S9 (AIZn and AISPn) Set the zero and span values for four analog
inputs. If an analog value goes below the zero value or exceeds
the span by more than five percent, it will produce a bad qual-
ity output. A specified span other than zero (default) for an
unused analog input produces a bad quality signal for that
input.
S10 – AO1 Block address of input for analog output one.
S11 – AO2 Block address of input for analog output two.
S12 to S14 - DIn Set the logic sense for three digital inputs. Digital inputs can
be defined for direct or reverse acting logic operations. These
are defined as follows:

0 = reverse acting (logic 0 = closed, logic 1 = open)


1 = direct acting (logic 0 = open, logic 1 = closed)
2 = unused input
S15 to S18 - DOn Block addresses of the inputs for the four digital outputs.
S19 – FAIL Value defines the module response in case of control I/O mod-
ule failure. Lack of I/O module response or a bad analog input
reference voltage will cause a transfer to error mode.

WBPEEUI210504C0 79 - 3
Specification S19 also determines which failure conditions
cause the I/O module status flag output N+9 to go to logic 1
(bad).
X X X
Failure Action
0 = trip control module
1 = continue operation
Reserved for Future Use
I/O Module Status Flag
0 = selects the I/O module status flag output N+9 to equal logic 1
(bad quality) when the I/O module is failed or in error mode.
1 = selects the I/O module status flag output N+9 to equal logic 1
(bad quality) when the control I/O module is in error mode
or a defined I/O point (AI, AO, DI or DO) is bad quality.

79 - 4 WBPEEUI210504C0