Atrium Air System Load Summary

The document provides a detailed summary of the air system design loads for the Atrium project, including cooling and heating data for July. It outlines various zone loads, total system loads, and hourly analysis of airflows and temperatures. The data is prepared by Concordia University and includes specific values for cooling and heating requirements throughout the day.

Uploaded by

David Combs
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
46 views16 pages

Atrium Air System Load Summary

The document provides a detailed summary of the air system design loads for the Atrium project, including cooling and heating data for July. It outlines various zone loads, total system loads, and hourly analysis of airflows and temperatures. The data is prepared by Concordia University and includes specific values for cooling and heating requirements throughout the day.

Uploaded by

David Combs
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Air System Design Load Summary for Atrium

Project Name: Assas_Feb19 03/27/2008


Prepared by: Concordia University 02:54PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.5 °F / 70.8 °F HEATING OA DB / WB -12.0 °F / -12.9 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 3314 ft² 323613 - 3314 ft² - -
Wall Transmission 245 ft² 807 - 245 ft² 2819 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 505 ft² 855 - 505 ft² 11174 -
Skylight Transmission 2809 ft² 4761 - 2809 ft² 62191 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 220 W 751 - 0 0 -
People 100 20830 20500 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 351618 20500 - 76184 0
Zone Conditioning - 336244 20500 - 19111 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 14032 CFM 0 - 3650 CFM 0 -
Ventilation Load 3036 CFM 23470 61802 790 CFM 57135 0
Supply Fan Load 14032 CFM 0 - 3650 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 359715 82302 - 76246 0
Central Cooling Coil - 359715 82308 - 0 0
Zone Heating Unit Coils - 0 - - 76184 -
>> Total Conditioning - 359715 82308 - 76184 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1


Hourly Air System Design Day Loads for Atrium
Project Name: Assas_Feb19 03/27/2008
Prepared by: Concordia University 02:54PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°F) (CFM) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH)
0000 70.6 7884 167.2 219.1 0.0 0.0 0.0 0.0 0.0 0.0
0100 69.7 7120 148.6 183.7 0.0 0.0 0.0 0.0 0.0 0.0
0200 68.8 6680 137.5 170.5 0.0 0.0 0.0 0.0 0.0 0.0
0300 68.1 6267 127.5 158.6 0.0 0.0 0.0 0.0 0.0 0.0
0400 67.6 5878 118.5 147.7 0.0 0.0 0.0 0.0 0.0 0.0
0500 67.4 5865 118.0 147.1 0.0 0.0 0.0 0.0 0.0 0.0
0600 67.8 6506 132.1 164.3 0.0 0.0 0.0 0.0 0.0 0.0
0700 68.6 7538 156.0 193.0 0.0 0.0 0.0 0.0 0.0 0.0
0800 70.2 9076 193.8 251.3 0.0 0.0 0.0 0.0 0.0 0.0
0900 72.5 10339 228.7 292.3 0.0 0.0 0.0 0.0 0.0 0.0
1000 75.1 11529 264.7 334.2 0.0 0.0 0.0 0.0 0.0 0.0
1100 78.1 12565 299.8 374.5 0.0 0.0 0.0 0.0 0.0 0.0
1200 81.0 13367 329.9 408.6 0.0 0.0 0.0 0.0 0.0 0.0
1300 83.1 13869 350.5 431.9 0.0 0.0 0.0 0.0 0.0 0.0
1400 84.5 14032 359.7 442.0 0.0 0.0 0.0 0.0 0.0 0.0
1500 85.0 13829 355.6 437.0 0.0 0.0 0.0 0.0 0.0 0.0
1600 84.5 13246 337.4 415.9 0.0 0.0 0.0 0.0 0.0 0.0
1700 83.2 12329 308.3 382.2 0.0 0.0 0.0 0.0 0.0 0.0
1800 81.3 11259 274.1 342.7 0.0 0.0 0.0 0.0 0.0 0.0
1900 79.0 10425 246.6 311.1 0.0 0.0 0.0 0.0 0.0 0.0
2000 76.7 9859 226.9 288.4 0.0 0.0 0.0 0.0 0.0 0.0
2100 74.8 9325 209.4 268.4 0.0 0.0 0.0 0.0 0.0 0.0
2200 73.0 8816 193.6 250.1 0.0 0.0 0.0 0.0 0.0 0.0
2300 71.6 8338 179.6 233.8 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v.4.3 Page 1 of 1


Hourly Air System Design Day Loads for Atrium
Project Name: Assas_Feb19 03/27/2008
Prepared by: Concordia University 02:54PM

Data for July

Total Cooling Total Heating


450

400

350

300
Load ( MBH )

250

200

150

100

50

0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program v.4.3 Page 1 of 1


Hourly Zone Loads for Atrium
Project Name: Assas_Feb19 03/27/2008
Prepared by: Concordia University 02:54PM

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°F) (°F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
0000 70.6 75.9 48 7884.2 175853.9 176967.5 0.0 0.0 0.0
0100 69.7 75.7 46 7120.0 156100.8 158567.3 0.0 0.0 0.0
0200 68.8 75.6 46 6680.2 145253.2 148106.3 0.0 0.0 0.0
0300 68.1 75.5 46 6266.8 135174.5 138359.1 0.0 0.0 0.0
0400 67.6 75.4 47 5878.3 125826.3 129273.4 0.0 0.0 0.0
0500 67.4 75.4 47 5864.8 126176.7 128958.3 0.0 0.0 0.0
0600 67.8 75.6 46 6505.7 143385.5 143981.5 0.0 0.0 0.0
0700 68.6 75.8 46 7537.6 170929.3 168585.4 0.0 0.0 0.0
0800 70.2 76.1 47 9076.0 212620.7 206249.4 0.0 0.0 0.0
0900 72.5 76.4 47 10338.9 247456.1 238081.0 0.0 0.0 0.0
1000 75.1 76.7 46 11529.5 280915.6 268879.7 0.0 0.0 0.0
1100 78.1 76.9 45 12565.2 310446.4 296316.5 0.0 0.0 0.0
1200 81.0 77.1 45 13366.5 333437.1 317971.7 0.0 0.0 0.0
1300 83.1 77.2 44 13869.1 347645.7 331746.0 0.0 0.0 0.0
1400 84.5 77.3 44 14032.0 351617.7 336244.3 0.0 0.0 0.0
1500 85.0 77.2 44 13828.8 344522.4 330635.6 0.0 0.0 0.0
1600 84.5 77.1 44 13245.5 326174.1 314676.8 0.0 0.0 0.0
1700 83.2 76.9 45 12329.3 298468.8 290015.0 0.0 0.0 0.0
1800 81.3 76.6 46 11259.1 267166.3 261817.1 0.0 0.0 0.0
1900 79.0 76.4 46 10425.4 243541.8 240293.3 0.0 0.0 0.0
2000 76.7 76.3 47 9858.8 227945.9 225881.6 0.0 0.0 0.0
2100 74.8 76.2 47 9324.6 213501.5 212449.0 0.0 0.0 0.0
2200 73.0 76.1 48 8816.4 200004.3 199809.1 0.0 0.0 0.0
2300 71.6 76.0 48 8337.7 187507.7 188024.9 0.0 0.0 0.0

Hourly Analysis Program v.4.3 Page 1 of 1


Hourly Zone Design Day Loads for Atrium
Project Name: Assas_Feb19 03/27/2008
Prepared by: Concordia University 02:54PM

Zone: Zone 1
Data for July

Zone Sensible Zone Conditioning


350K

300K

250K
BTU/hr

200K

150K

100K

50K

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v.4.3 Page 1 of 1


Atrium Input Data
Project Name: Assas_Feb19 03/27/2008
Prepared by: Concordia University 03:09PM

1. General Details:
Air System Name Atrium
Equipment Type Undefined
Air System Type VAV
Number of zones 1

2. System Components:
Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method Sum of Space OA Airflows
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Central Cooling Data:


Supply Air Temperature 55.0 °F
Coil Bypass Factor 0.100
Cooling Source Any
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0.00 in wg
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
01.A x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 75.0 °F
Cooling T-stat: Unocc. 85.0 °F
Heating T-stat: Occ. 70.0 °F
Heating T-stat: Unocc. 60.0 °F
T-stat Throttling Range 3.00 °F
Diversity Factor 100 %
Direct Exhaust Airflow 0.0 CFM
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type VAV box
Minimum Airflow 0.00 CFM/person

Zone Heating Units:


Zone All

Hourly Analysis Program v.4.3 Page 1 of 2


Atrium Input Data
Project Name: Assas_Feb19 03/27/2008
Prepared by: Concordia University 03:09PM

Zone Heating Unit Type Fan coil, OAT control


Trip Temperature 30.0 °F
Design Supply Temperature 110.0 °F
Fan Performance 0.00 in wg
Fan Efficiency 50 %

Zone Unit Heat Source Any


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 55.0 °F
Supply Fan Airflow 16870.1 CFM
Ventilation Airflow 3649.6 CFM

Hydronic Sizing Specifications:


Chilled Water Delta-T 10.0 °F
Hot Water Delta-T 20.0 °F

Safety Factors:
Cooling Sensible 0 %
Cooling Latent 0 %
Heating 0 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(CFM) (MBH) (MBH) (CFM)
1 16870.1 76.2 -

5. Equipment Data
No Equipment Data required for this system.

Hourly Analysis Program v.4.3 Page 2 of 2


Psychrometric Analysis for Atrium
Project Name: Assas_Feb19 03/27/2008
Prepared by: Concordia University 02:54PM

Location: Montreal IAP, Quebec


Altitude: 118.0 ft.
Data for: July DESIGN COOLING DAY, 1400
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0.018
5. Room Air

0.016

Specific Humidity ( lb/lb )


1 0.014

0.012
2
0.010
34 5

0.008

0.006

0.004

0.002

0.000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program v.4.3 Page 1 of 1


System Psychrometrics for Atrium
Project Name: Assas_Feb19 03/27/2008
Prepared by: Concordia University 02:54PM

July DESIGN COOLING DAY, 1400

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 84.5 0.01312 3036 400 23470 61802
Vent - Return Mixing Outlet 78.8 0.00974 14032 744 - -
Central Cooling Coil Outlet 55.0 0.00850 14032 744 359715 82308
Supply Fan Outlet 55.0 0.00850 14032 744 0 -
Cold Supply Duct Outlet 55.0 0.00850 14032 744 - -
Zone Air - 77.3 0.00881 14032 839 336244 20500
Return Plenum Outlet 77.3 0.00881 14032 839 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.075 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4726.4 BTU/(hr-CFM)
Site Altitude = 118.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 351618 Cooling 336244 77.3 14032 839 0 0

Hourly Analysis Program v.4.3 Page 1 of 2


System Psychrometrics for Atrium
Project Name: Assas_Feb19 03/27/2008
Prepared by: Concordia University 02:54PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet -12.0 0.00020 790 400 -57135 0
Vent - Return Mixing Outlet 40.7 0.00020 3650 435 - -
Central Cooling Coil Outlet 40.7 0.00020 3650 435 0 0
Supply Fan Outlet 40.7 0.00020 3650 435 0 -
Cold Supply Duct Outlet 40.7 0.00020 3650 435 - -
Zone Air - 55.3 0.00020 3650 445 -19111 0
Return Plenum Outlet 55.3 0.00020 3650 445 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.075 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4726.4 BTU/(hr-CFM)
Site Altitude = 118.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 0 Deadband -19111 55.3 3650 445 0 76184

Hourly Analysis Program v.4.3 Page 2 of 2


Space Design Load Summary for Atrium
Project Name: Assas_Feb19 03/27/2008
Prepared by: Concordia University 02:54PM

TABLE [Link] LOADS FOR SPACE '' 01.A '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 81.5 °F / 68.8 °F HEATING OA DB / WB -12.0 °F / -12.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 3314 ft² 337661 - 3314 ft² - -
Wall Transmission 245 ft² 668 - 245 ft² 2819 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 505 ft² 447 - 505 ft² 11174 -
Skylight Transmission 2809 ft² 2486 - 2809 ft² 62191 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 220 W 751 - 0 0 -
People 100 20830 20500 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 362842 20500 - 76184 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 01.A '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 123 0.140 - 202 - 1410
WINDOW 1 252 0.270 0.150 223 1027 5587
S EXPOSURE
WALL 123 0.140 - 465 - 1410
WINDOW 1 252 0.270 0.150 223 2075 5587
H EXPOSURE
SKYLIGHT 2809 0.270 0.811 2486 334559 62191

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Sizing Summary for Atrium
Project Name: Assas_Feb19 03/27/2008
Prepared by: Concordia University 02:54PM

Air System Information


Air System Name Atrium Number of zones 1
Equipment Class UNDEF Floor Area 4562.0 ft²
Air System Type VAV Location Montreal IAP, Quebec

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM Peak zone sensible load Calculation Months Jan to Dec
Space CFM Individual peak space loads Sizing Data Calculated

Central Cooling Coil Sizing Data


Total coil load 36.8 Tons Load occurs at Jul 1400
Total coil load 442.0 MBH OA DB / WB 84.5 / 70.8 °F
Sensible coil load 359.7 MBH Entering DB / WB 78.8 / 64.5 °F
Coil CFM at Jul 1400 14032 CFM Leaving DB / WB 55.0 / 53.7 °F
Max block CFM at Jun 1400 16870 CFM Coil ADP 52.4 °F
Sum of peak zone CFM 16870 CFM Bypass Factor 0.100
Sensible heat ratio 0.814 Resulting RH 44 %
ft²/Ton 123.8 Design supply temp. 55.0 °F
BTU/(hr-ft²) 96.9 Zone T-stat Check 1 of 1 OK
Water flow @ 10.0 °F rise 88.45 gpm Max zone temperature deviation 0.0 °F

Supply Fan Sizing Data


Actual max CFM at Jun 1400 16870 CFM Fan motor BHP 0.00 BHP
Standard CFM 16798 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 3.70 CFM/ft² Fan static 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM 3650 CFM CFM/person 36.50 CFM/person
CFM/ft² 0.80 CFM/ft²

Hourly Analysis Program v.4.3 Page 1 of 1


Ventilation Sizing Summary for Atrium
Project Name: Assas_Feb19 03/27/2008
Prepared by: Concordia University 02:54PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 3650 CFM

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft²) Occupants (CFM) (CFM/person) (CFM/ft²) (CFM) (% of supply) (CFM)
Zone 1
01.A 1 4562.0 100.0 16870.1 0.00 0.80 0.0 0.0 3649.6
Totals (incl. Space Multipliers) 16870.1 3649.6

Hourly Analysis Program v.4.3 Page 1 of 1


Zone Design Load Summary for Atrium
Project Name: Assas_Feb19 03/27/2008
Prepared by: Concordia University 02:54PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 81.5 °F / 68.8 °F HEATING OA DB / WB -12.0 °F / -12.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 3314 ft² 337661 - 3314 ft² - -
Wall Transmission 245 ft² 668 - 245 ft² 2819 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 505 ft² 447 - 505 ft² 11174 -
Skylight Transmission 2809 ft² 2486 - 2809 ft² 62191 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 220 W 751 - 0 0 -
People 100 20830 20500 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 362842 20500 - 76184 0

Hourly Analysis Program v.4.3 Page 1 of 1


Zone Sizing Summary for Atrium
Project Name: Assas_Feb19 03/27/2008
Prepared by: Concordia University 02:54PM

Air System Information


Air System Name Atrium Number of zones 1
Equipment Class UNDEF Floor Area 4562.0 ft²
Air System Type VAV Location Montreal IAP, Quebec

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM Peak zone sensible load Calculation Months Jan to Dec
Space CFM Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft²) CFM/ft²
Zone 1 362.8 16870 3650 Jun 1400 76.2 4562.0 3.70

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load gpm Load gpm Airflow
Zone Name (MBH) @ 20.0 °F (MBH) @ 20.0 °F (CFM)
Zone 1 0.0 0.00 76.2 7.62 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
01.A 1 362.8 Jun 1400 16870 76.2 4562.0 3.70

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Design Load Summary for Theater
Project Name: Assas_Feb19 03/27/2008
Prepared by: Concordia University 02:55PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1900 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.0 °F / 69.2 °F HEATING OA DB / WB -12.0 °F / -12.9 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 685 ft² 1131 - 685 ft² 7872 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 3488 W 8535 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 125 W 373 - 0 0 -
People 146 21715 17520 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 31753 17520 - 7872 0
Zone Conditioning - 22036 17520 - 7260 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1898 CFM 0 - 1898 CFM 0 -
Ventilation Load 1898 CFM 0 17284 1898 CFM 7808 0
Supply Fan Load 1898 CFM 0 - 1898 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 22036 34804 - 15068 0
Central Cooling Coil - 39224 34804 - 0 0
Central Heating Coil - -17188 - - 0 -
Terminal Reheat Coils - 0 - - 15068 -
>> Total Conditioning - 22036 34804 - 15068 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1