Fire Alarm Control Panel Manual
Fire Alarm Control Panel Manual
N16
Instruction Manual
This system meets NFPA requirements for operation at 0-49º C/32- This system contains static-sensitive components. Always
120º F and at a relative humidity 93% ± 2% RH (non-condensing) at ground yourself with a proper wrist strap before handling any circuits
32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's so that static charges are removed from the body. Use static sup-
standby batteries and the electronic components may be adversely pressive packaging to protect electronic assemblies removed from
affected by extreme temperature ranges and humidity. Therefore, it the unit.
is recommended that this system and its peripherals be installed in Units with a touchscreen display should be cleaned with a dry,
an environment with a normal room temperature of 15-27º C/60-80º clean, lint free/microfiber cloth. If additional cleaning is required,
F. apply a small amount of Isopropyl alcohol to the cloth and wipe
Verify that wire sizes are adequate for all initiating and indicating clean. Do not use detergents, solvents, or water for cleaning. Do not
device loops. Most devices cannot tolerate more than a 10% I.R. spray liquid directly onto the display.
drop from the specified device voltage. Follow the instructions in the installation, operating, and program-
ming manuals. These instructions must be followed to avoid damage
to the control panel and associated equipment. FACP operation and
reliability depend upon proper installation.
Precau-D2-11-2017
FCC Warning
WARNING: This equipment generates, uses, and can radi- Canadian Requirements
ate radio frequency energy and if not installed and used in This digital apparatus does not exceed the Class A limits for
accordance with the instruction manual may cause interfer- radiation noise emissions from digital apparatus set out in
ence to radio communications. It has been tested and found the Radio Interference Regulations of the Canadian Depart-
to comply with the limits for Class A computing devices pur- ment of Communications.
suant to Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against such Le present appareil numerique n'emet pas de bruits radio-
interference when devices are operated in a commercial electriques depassant les limites applicables aux appareils
environment. Operation of this equipment in a residential numeriques de la classe A prescrites dans le Reglement sur
area is likely to cause interference, in which case the user le brouillage radioelectrique edicte par le ministere des
will be required to correct the interference at his or her own Communications du Canada.
expense.
HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus™, eVance®, FlashScan®, FAAST Fire Alarm Aspiration Sensing Technology®,
Honeywell®, INSPIRE®, Intelligent FAAST®, NOTIFIER®, ONYX®, ONYXWorks®, SWIFT®, VeriFire®, and VIEW® are all registered trademarks of Honeywell
International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is
a registered trademark of The Mozilla Foundation.
©2022 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online
Help or printed manuals, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
[Link]@[Link]
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
Before proceeding, the installer should be familiar with the following documents.
• Underwriters Laboratories Standard UL 864
• UL 2610 for Commercial Premises Security Alarm Units and Systems
• Underwriters Laboratories Standard UL 2017 for General-Purpose Signaling Devices and Systems
• NFPA 72 National Fire Alarm Code
The contents of this manual are important and must be kept in close proximity of the hardware. If building ownership is changed, this
manual and all other testing and maintenance information must also be passed to the current owner of the facility. A copy of this manual
is available from the manufacturer.
This product is intended to be installed in accordance with the following standards UL 864 Tenth Edition Compliance
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for
Fire Alarm Systems, UL 864, 10th Edition. Operation of this product with products not tested for UL 864, 10th Edi-
tion has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
For product compliance, refer to the UL listing cards located on the UL online certification directory at
[Link]
.
NOTE: Firmware version 3.0 or higher must be installed on the N16 for UL 10th Edition compliance.
This Fire Alarm Control Panel complies with the following NFPA standards:
• NFPA 13 Sprinkler Systems
• NFPA 15 Water Spray Systems
• NFPA 72 Central Station Fire Alarm Systems (Automatic, Manual and Waterflow) Protected Premises Unit (requires CGW-MB).
• NFPA 72 Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm Systems.
• NFPA 72 Remote Station (Automatic, Manual and Waterflow) Fire Alarm Systems
• NFPA 72 Proprietary (Automatic, Manual and Waterflow) Fire Alarm Systems (Protected Premises Unit).
The installer should be familiar with the following documents and standards:
• NFPA 72 Initiating Devices for Fire Alarm Systems
• NFPA 72 Inspection, Testing and Maintenance for Fire Alarm Systems
• NFPA 72 Notification Appliances for Fire Alarm Systems
• Underwriters Laboratories (UL)
• UL 38 Manually Actuated Signaling Boxes
• UL 217 Smoke Detectors, Single and Multiple Station
• UL 228 Door Closers - Holders for Fire Protective Signaling Systems
• UL 268 Smoke Detectors for Fire Protective Signaling Systems
• UL 268A Smoke Detectors for Duct Applications
• UL 346 Waterflow Indicators for Fire Protective Signaling Systems
• UL 464 Audible Signaling Appliances
• UL 521 Heat Detectors for Fire Protective Signaling Systems
• UL 864 Standard for Control Units for Fire Protective Signaling Systems
• UL 1481 Power Supplies for Fire Protective Signaling Systems
• UL 1971 Visual Signaling Appliances
• UL 2017 Standard for General-Purpose Signaling Devices and SystemsUL 2610 Standard for Commercial Premises Security Alarm
Units and Systems
•
Other
• NEC Article 300 Wiring Methods
• NEC Article 760 Fire Protective Signaling Systems
• Applicable Local and State Building Codes
• Requirements of the Local Authority Having Jurisdiction
Related Documents
Below is a list of documents referenced in this manual, as well as documents for selected other compatible devices.
Fire Alarm Control Panel (FACP) and Main Power Supply Installation
PMB-AUX Installation Document LS10242-000GE-E
DVC Digital Voice Command Manual 52411
DVC-RPU UL Listing Document 50107424-001
DAA2 and DAX Amplifiers Manual 53265
DS-DB Digital Series Distribution Board and Amplifier 53622
DAL Devices Reference Document 52410
AA-Series Audio Amplifier Manual 52526
SLC Wiring Manual 51253
Communicators
HW-CGW-MBB CLSS Gateway LS10248-051HW-E
Off-line Programming Utility
VeriFire® Tools help file Available for download
Cabinets & Chassis
CAB-3/CAB-4 Series Cabinet Installation Document 15330
CAB-5 Series Cabinet Installation Document LS10244-000GE-E
ABB Series Annunciator Backboxes LS10249-000GE-E
NBB-2 Backbox LS10250-000GE-E
Battery/Peripherals Enclosure Installation Document 50295
Heat Dissipation for Cabinets with Digital Audio Products 53645
Power Supplies, Auxiliary Power Supplies & Battery Chargers
ACPS-610 Installation Manual 53018
APS2-6R Instruction Manual 53232
CHG-120 Battery Charger Manual 50641
HPF24S6/S8 Field Charger/Power Supply 52751
PSE-6/10 Series Power Supply Extenders LS10227-000NF-E
HPF-PS6/10 Series Power Supplies LS10227-003HP-E
Networking
High-Speed Network Communications Module 54014
High-Speed Noti•Fire•Net Instruction Manual 54013
Noti•Fire•Net Manual, Network Version 5.0 51584
NOTE: Unless otherwise specified, the term N16is used to refer to all versions of the panel.
AC Power
Connection
N/O
CLP Connections Trouble N/C NAC 1&2
on N16 Core Relay COM
Located on PMB
behind N16 Core
TX
N16 Core Board and PMB Printer RX Board
Connection CTS
(Stacked) REF
IN+
Remote IN-
Battery Sync OUT+
CLP Bus OUT-
Connection CLP Termination
Connections on PMB Switch
+24
Ground AUX GND
Multiple Units Installed A+
Fault Switch Power A-
Disable +24
(default Address setting for GND
PMB
enabled)
SLM-318 Loop
Module
Mounted on
Chassis with
N16 B+
SLC A+
Connection B-
A-
CLP Connections for
SLM-318
N16 Chassis
(Shown Cropped Not to
Scale)
1.2 Specifications
Refer to Figure 1.1, “N16 Board Layout” on page 13 for terminal locations and connections.
alert bar
events list
LED Indicators
LED indicators are located on the lower right hand corner of the N16 display. They include a power LED and an Off Normal LED.
Power LED
USB Connections
USB connections are located on the front of the N16 display (USB-C) for ease of connecting VeriFire Tools for programming, as well as
on the Core board (USB-A and USB-Micro)
N16 Display Front
10 Inch Color
Touchscreen Display
Piezo Enable/Disable
Switch (SW16)
1.4 Components
Core Board
The N16 Core Board contains connections for both the internal and external AIO Bus, an OCuLink connection for the touchscreen dis-
play, a Trouble and Tamper Input, a NUP connection, a USB-A and USB-Micro Connection for updating the FACP and connecting the
VeriFire Tools Programming Utility and a PMB Power Supply as well as a CLP connection for additional SLM-318 SLC cards.
PMB-AUX/PMB-AUX-RTO
The PMB Power Supply is the power supply for the N16 panel. It features 3 amps of power in standby/8.5 amps of power in alarm, four
power-limited NAC outputs which can be configured for either Class A or Class B wiring, two 24VDC auxiliary power outputs and a
remote sync input. One auxiliary power output, AUX1, can be configured for either class A or class B wiring.
SLM-318
The SLM-318 provides expansion for one loop per module, up to 318 devices per module. Additional SLM-318 cards are available with
a maximum of ten modules on a system. It operates in both CLIP and FlashScan protocols.
CLSS Gateway (CGW-MB)
The CLSS gateway is the system interface, which serves as a portal between the panel, the Cloud and peripheral devices. The HON-
CGW-MBB can also be used as a Fire Alarm Communicator to central station when used with the optional cellular module and feature
activation.
Cabinets
All cabinets are fabricated from 16 gauge steel. The cabinet consists of two basic components: a backbox and a locking door. The back-
box and door are sold separately. Cabinets are available in five sizes: A, B, C, D and E. “A” size accommodates one chassis and two 26
AH batteries. “B” size accommodates two chassis and two 26 AH batteries. “C” size accommodates three chassis and two 26 AH batter-
ies. “D” size accommodates four chassis and two 26 AH batteries. “E” size accommodates five chassis and two 26 AH batteries. Doors
can be mounted on the left or right-hand side. The same hinge works in both configurations, so that this choice can be made in the field.
The door opens 120°. The CAB-5 Series is compatible with the CPU-N16LD and CPU-N16LNDchassis assemblies. The CAB-4 Series
is compatible with the CPU-N16RTOfor retrofit applications.
Batteries
The CAB-4 and CAB-5 Series cabinets provides space for two batteries (up to 18 Amp Hour). Batteries larger than 18 Amp Hour require
an external charger such as the CHG-120 and a UL listed battery box such as the BB-26 or NFS-LBB. Batteries must be ordered sepa-
rately.
1.5 Accessories
1.5.1 VeriFire Tools Programming Utility
The VeriFire Tools Programming Utility can be used to locally or remotely program the FACP from most Windows® compatible com-
puters (PC), running Windows 7 or newer, 32 or 64 bit. The FACP program files can also be created and stored on the PC for future
download to the control panel. VeriFire Tools can be downloaded from [Link]. A standard USB-C cable, which must be pur-
chased separately, is required for local connection of the PC to the USB-C port located on the N16 display under the touchscreen.
Remote programming requires the CLSS Gateway.
1.5.7 RLD
The RLD is a remote display for the N16 that can display up to 50 events. It includes configurable touchpoints for acknowledge, silence,
reset and drill that are only operational when the key switch is unlocked. The display has six programmable touchpoints each capable of
including a descriptor/label, a status indicator, force on/off and enable/disable.
NOTE: This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the inside of the FACP
door is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number
must be provided to the telephone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this
even if other equipment (telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so, alarm dial-
ing equipment must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of all other equipment
attached to the same telephone line. If there are any questions concerning these instructions, consult the telephone company or a quali-
fied installer about installing the RJ31X jack and alarm dialing equipment.
Important! The DACT must not be used to dial a phone number that is call-forwarded.
NOTE: Products marked with a check mark have not received UL 864 9th Edition certification and may only be used in retrofit applications.
For a list of additional compatible devices for the FACP refer to the Device Compatibility Document (15378), the SLC Wiring Manual
(51253) and the SWIFT Wireless Manual (LS10036-000NF-E)
Devices:
• FSP-951 Intelligent Photoelectric Smoke Detector • NBG-12LX Series Addressable Manual Pull Station
• FMM-1 Monitor Module
Electronic Equipment:
• AA-100 100-Watt Audio Amplifier • HS-NCM-MFSF High-Speed Network Communications Module (Multi-Mode Fiber to Single-Mode Fiber)
• AA-120 120-Watt Audio Amplifier • HS-NCM-W/-2 High-Speed Network Communications Module (Wire)
• AA-30 30-Watt Audio Amplifier • HS-NCM-WSF/-2 High-Speed Network Communications Module (Wire to Single-Mode Fiber)
• A2143-00 End of Line Resistor Assembly (system sensor equipment) • HS-NCM-MF High-Speed Network Communications Module (Multi-Mode Fiber)
• ACM-30 Annunciator • HS-NCM-SF High-Speed Network Communications Module (Single-Mode Fiber)
• ACPS-610 Addressable Charger/Power Supply • HS-NCM-WMF/-2 High-Speed Network Communications Module (Wire to Multi-Mode Fiber)
• ACPS2-6R Auxiliary Power Supply • MRD-1 Manual Releasing Disconnect Assembly
• ACT-1 Audio Coupling Transformer • NCD Network Control Display
• ACT-2 Audio Coupling Transformer • NCM-F Network Communications Module (Fiber)
• AKS-1B Annunciator Key Switch • NCM-W Network Communications Module (Wire)
• APJ-1B Annunciator Phone Jack-G • NCS Network Control Station
• A77-716B End-of-Line Resistor Assembly • N-ELR Assortment ELR Pack with Mounting Plate
• APS2-6R Auxiliary Power Supply (for UL applications only) • ONYXWorks Workstation Network Monitoring Workstation
• CMM-1 Communication converter Module • PRN-6 80-Column Printer
• CGW-DACT CLSS Dialer • PRN-7 80-Column Printer
• CGW-MB Common Communicator Module • R-120 120 Ohm End-of-Line Resistor
• CGW-PT POTS Card • R-470 470 End-of-Line Resistor
• CPU-N16-RTOCore Board with Retrofit Chassis • R-27K 27K End-of-Line Resistor
• CPU-N16-LD Core Board with 10HD Display • R-47K 47K End-of-Line Resistor
• CPU-N16-NLD Core Board without Display • R-2.2K 2.2K End-of-Line Resistor
• CPU-N16-RD Core Board • RKS-S Remote Security Keyswitch
• DAA Series Digital Audio Amplifiers • RLDRemote Display
• DAA2 Series Digital Audio Amplifier • RM-1 Remote Microphone
• DAX Digital Audio Amplifier • RM-1SA Remote Microphone
• DS-AMP Audio Amplifier • RPJ-1 Remote Phone Jack
• DS-BDA Backup Audio Amplifier • RPT-485W EIA-485 Repeater (Wire)
• DS-DB Digital Distribution Board • RPT-485SF EIA-485 Repeater (Fiber)
• DS-XF70V Transformer • RPT-485WF EIA-485 Repeater (Wire/Fiber)
• DVC-EM Digital Voice Command • SLC-IM Signaling Line Circuit Integration Module (FlashScan)
• DVC-RPU DVC Remote Paging Unit • SLM-318 SLC Loop Module
• EOL-CR/CB Assortment ELR Pack with Mounting Plate • STS-1 Security Tamper Switch
• EOLR-1 End of Line Resistor Assembly • VeriFire Tools Upload/Download Software
• FCM-1 NAC Module
• FHS Fireman's Handset
• FPJ Fireman's Phone Jack
• FTM-1 Telephone Module
Licenses:
• N16-CAC • N16-NWD
• N16-CLP • N16-UZC
• N16-GZ
• N16-LGZ
1.125”
(2.858cm)
Height of
mounting bolt
0.250”
after installation
(0.635cm)
0.500”
(1.27cm)
0.500”
(1.27cm)
NOTE: The Core board on the N16 can only receive power on J15, it cannot pass power out of J15.
The fifth SLM-318 in the top section is wired OUT from J4 and IN to J15 on
the N16 Core Board. Termination is always enabled.
N16 Core
and PMB
(Stacked)
The top section of the CLP Bus contains five SLM-318s powered by the PMB
connected to the N16 Core Board. Connections are made to the SLM-318s on the top
section of the CLP bus OUT of J6 on the PMB and IN to J3 on the first SLM-318.
Subsequent SLM-318’s are wired OUT of J4 and IN to J3 on each SLM-318 (as shown
The PMB connected above).
to the N16 Core
Board is wired OUT
from J3 on the PMB
and IN to J6 on the
second PMB-AUX.
The middle section of the CLP Bus contains five SLM-318s. For this section
of the CLP Bus, the power is shared between the middle and the bottom
PMB-AUX.
SW6
PMB-AUX Enabled
Connections are made on the second section of the CLP Bus OUT
from J3 on the third PMB-AUX IN to J3 on the first SLM-318.
Subsequent SLM-318 connections are wired OUT of J4 and IN to
J3 on each SLM-318 (as shown). The last SLM-318 in this section
of the CLP Bus must have the termination switch enabled (SW6).
The middle PMB-AUX
is wired OUT from J3
and IN to J6 on the
bottom PMB-AUX.
PMB-AUX
The bottom section of the CLP Bus contains batteries which are
maintained by the bottom PMB-AUX.
Batteries connected
to TB9 on the bottom
PMB-AUX.
Figure 2.2 Multiple PMB Power Supplies with Ten SLM-318 Modules
NOTE: A maximum of five (5) SLM-318 loop cards can run on one (1) N16 PMB. For additional power needs or loop cards, additional PMB-AUX
power supplies will be required. Each PMB-AUX can power up to five (5) SLM-318 cards for a maximum of ten (10) total SLM-318 cards on a
system. If ten (10) loop cards are installed, two (2) additional PMB-AUX power supplies will be required.
Grounding
Cable #71073
grounding stud
keps nut
keps nut
Class B Only
Optional
(AUX 2)
Class A
Out to Return
Device (AUX 1)
(AUX 1)
TB7
A+ B+
A- B-
A+ B+
A- B-
A+
A-
A+
A-
NOTE: PMB with N16 Core and PMB-AUX are identical for NAC wiring. Drawing is shown with PMB-AUX for clarity of terminal block locations.
NOTE: Relays are power-limited only when connected to power-limited sources for the relay outputs.
.
CAB-5 Front View Side-View Non-power-limited circuit
(Assumes relay is connected Power limited
to a
non-power-limited signal
source)
Separating non-power-
limited and power
limited circuits within the
backbox with adhesive
squares
Non-power-limited
Separating non-
power limited from
power limited circuits
through knockouts Note: Drawing is not to scale; proportions and angles are
exaggerated to show wire placement more clearly.
SLC
Connection
SW2
SW1
SW6
J4 CLP Connection
J3 CLP Connection
NOTE: Response times for CLIP loops may vary. CLIP loops must be tested to assure that
actuation of notification appliances occurs within 10 seconds after activation of an initiating
device. Systems with response time that exceed 10 seconds must be approved by the AHJ.
The following configuration guidelines may be used to improve the response times of CLIP loops:
1. All manual pull stations must be assigned addresses from 1-20.
2. Loops must be programmed for Rapid Poll.
3. Modules on a fully loaded loop must adhere to a ratio of two monitor modules to one control module.
2.7.3 Self-Test Detector Function on the SLC
The SLM-318 is capable of supporting up to 159 Self Test Detectors. When Self-Test Detectors are installed on the SLM-318 and a self
test is being performed the voltage on the SLC Loop will increase to 29.5VDC +/-5% (28.0-30.98VDC). If there is no self test in pro-
cess, the voltage will remain at 24VDC.
NOTE: When the FACP is using back up battery power a self test will not be preformed.
B+ A+ B- A- TB1
Note: the relay connections may be power-limited or nonpower-limited, provided that 0.25” spacing is maintained between conductors
of power-limited and nonpower-limited circuits. Refer to “UL Power-Limited Wiring Requirements” on page 28.
To Control
Module
TB1
SW2
J10 SW1
SW6
J4
TB1
SLM-318
J3
N16 Core/PMB P7
Stacked
NOTE: The following models do not comply with requirements for AC loss delay reporting when used with Central Station Protected Premises
systems: AA-30, AA-120, AA-100, APS-6R, CHG-120
N16
Receiving Unit Compatible Protected Premises Unit
With N16
Type code: Relay
Type code: Security-L Zone mapping: ZF03
ELR-47K
Receiving Unit
SLC Loop IN
Receiving Unit
PPU SLC Loop OUT
SLC Loop OUT
Figure 2.14 Typical Proprietary Fire Alarm Systems Wiring Connections: Detail Views
NOTE: NOTE POLARITY on the ELRD-2.2K. Install the positive side of the ELRD-2.2K on H+ terminal on the Gentex strobe only appliance,
install the negative side of the ELRD-2.2K to the H- terminal on the Gentex strobe only appliance.
Connect to J8
Tamper on the
N16 Core
STS-1 mounting
location
(side opposite of
door hinges)
UL-listed, SLC
normally-open Channel A or B
security switch
47K
End-of-line
Resistor
UL-listed,
normally-closed FMM-1
security switch
Enclosure Annunciator
• Do not run cable adjacent to, or in the same conduit as, 120 volts AC service, “noisy” electrical circuits that are powering
mechanical bells or horns, audio circuits above 25 VRMS, motor control circuits, or SCR power circuits.
If annunciators are to be mounted in a separate cabinet or powered by a remote power supply, see Figure 2.22, “Using Multiple Power
Supplies with the AIO Circuit” on page 38.
Wiring Configuration
Figure 2.19 illustrates the wiring between the FACP’s External AIO-BUS and AIO-BUS [Link] external AIO BUS can be wired
for Class B as well as Class A as it provides for an optional Class A return.
To AIO-Bus Annunciator
Figure 2.20 illustrates the wiring between the FACP’s Internal AIO-BUS and AIO-BUS devices. The Internal AIO BUS can be wired for
class B only.
To AIO-Bus Annunciators
NOTE: All power must be turned off when connecting the 24 VDC power to the annunciator. Reapply power according to the instructions in the
control panel manual.
The ACM-30 power source must be filtered, non-resettable, 24VDC listed for fire-protective signaling use. Sources include FACP
power supplies and auxiliary power supplies. The power run to the annunciator need not contain a power supervision relay because loss
of power is inherently supervised through communication loss (AIO communication loss is registered at the control panel during loss of
power to the annunciator).
Connector P6 is the Main AIO bus connection to wire the router to the FACP. Connectors P3 and P4 are used for the Local AIO bus to
wire from the router to the peripherals. These connectors are interchangeable, providing both power and data from the router. Use the 6”
local AIO cable to wire ACM-30 annunciators in the same row of the cabinet. Use the 48” local AIO cable to wire annunciators on dif-
ferent rows of cabinets.
An Optional Kit (Part number ACM-30CBL) can be obtained if additional rows of ACM-30 are required. The kit contains a longer cable
to connect one row of ACMs to an adjacent row of ACMs and 4 interconnect cables (for connecting ACM in the same row).
Power Connection - P5
- IN from FACP
+
- OUT to next router
+
Local AIO
P3
P4
Ground
-
+ OUT to next router
Ground
-
+ IN from FACP
Main AIO - P6
S40 S40 S40 S40
slide down slide up slide up slide up
18-30VDC power
Fire Alarm
Control Panel AIO Reference
Annunciators in a backbox,
powered from control panel
AIO Circuit
Annunciators in a cabinet,
powered from remote supply
Figure 2.22 Using Multiple Power Supplies with the AIO Circuit
Wire the ACM-30 as shown in Figure 2.21, “Power and AIO Circuit Connections” on page 38 .All power must be turned off when con-
necting the annunciator. These requirements must be followed:
2.13 RLD
2.13.1 Installing the RLD
Select an appropriate knockout on the enclosure for the wiring to run through and snap it out. Pull all annunciator wiring into the enclo-
sure. Connect annunciator wiring to the removable terminal blocks at this time.
The RLD power source must be filtered, non-resettable, 24VDC listed for fire-protective signaling use. Sources include FACP power
supplies and auxiliary power supplies and on-board power supplies (integral to fire alarm control panel). The power run to the annuncia-
tor need not contain a power supervision relay because loss of power is inherently supervised through communication loss (AIO commu-
nication loss is registered at the control panel during loss of power to the annunciator).
NOTE: End of Line resistor and RLD addressing is set through the on screen menu programming of the RLD refer to LS10310-000NF-E for
more information.
NOTE: All power must be turned off when connecting the 24 VDC power to the annunciator. Reapply power according to the instructions in the
control panel manual.
NOTE: The RLD can only be connected to the external AIO Bus
Diagnostic LEDs
S1 Piezo Switch
Enable/Disable To the External
Reference
AIO- AIO Bus on the
S2 Configuration Switch AIO+ N16/NCDor to the
Enable/Disable P2 AIO Bus Reference next AIO Bus
Connection AIO- Device
AIO+
S3 KeySwitch
(Located on Back of Earth
Board Not Shown) GND To AUX power on
P4 Power Input +24
USB-C Connection GND
N16or PMB-AUX
Connection +24
2.14 Networking
The N16 can be networked to another control panel or network control annunciator. Each panel (known as a node when networked)
requires a Network Communications Module (NCM) or High-Speed Network Communications Module (HS-NCM). Refer to the
Noti•Fire•Net Version 5.0 & Higher Manual, (document number 51584) and the NCM Installation Document (document number 54014)
or the High-Speed Noti•Fire•Net Manual (document number 54013) and HS-NCM Installation Document (document number 54014) for
system configuration information
NOTE: NCM hardware is not compatible with HS-NCM hardware and should not be mixed on the same network.
NOTE: See the Noti•Fire•Net Version 5.0 & Higher Manual and the NCM Installation Document or the High-Speed
Noti•Fire•Net Manual for system configuration information. See the BMP-1 Product Installation Drawing if considering
mounting the module (wire version) behind blank module plate in a dress plate or annunciator backbox.
NOTE: Over-bending fiber-optic cable can damage it. Do not exceed a 3 inch (7.62 cm) minimum bend radius.
NOTE: NCM hardware is not compatible with HS-NCM hardware and should not be mixed on the same network.
NCD
For more information on the NCDrefer to the NCDManual (document number LS10210-051NF-E)
DVC-EM
N16 Core Board
For more information on the DVC refer to the DVC Manual (document number 52411)
NOTE: Download operations that change the basic program of the control panel must be
performed by responsible service personnel in attendance at the control panel. After downloading
a program, test the control panel in accordance with NFPA 72.
DB-9 connector on
DB-25 connector on PRN Series Printer
PRN Series Printer
DC IN - DC IN +
3. If installing a Keltron Printer VS4095/5, connect 24 VDC non-resettable power from a UL-listed power supply to the Keltron
printer as shown in Figure 2.26 (14 AWG).
4. If installing a PRN series printer, plug it into your AC power source.
Note: The PRN series of printers require a primary AC power source. Refer to the Manufacturer’s Installation Guide for additional
information. If required for the fire alarm system configuration (for example, a Proprietary Fire Alarm System), a remote printer
requires a secondary power source (battery backup). Because a secondary power source is not provided, use a separate
Uninterruptable Power Supply (UPS) that is UL-listed for Fire Protective Signaling.
5. Plug the DB-25 or DB-9 connector end of the custom cable into the EIA-232 port of your printer. Tighten securely.
NOTE: Depending on which version of the AMPS-24/E is being used, the terminal block
designations may differ from those listed. Please refer to the AMPS-24/E manual.
Device to be
Supervised
N.C. Supervision
Relay Contact FCM-1
Part of EOLR-1
(Not required for
FlashScan type codes
that provide built-in
power supervision.)
*If the SLC device does not match the one in this figure, refer to the SLC manual appendix, which contains wiring conversion charts for
type V and type H modules.
WARNING:
! XP TRANSPONDER CIRCUITS (XPP-1, XPM-8, XPC-8, XPR-8, XPM-8L) ARE NOT SUITABLE
FOR SECURITY APPLICATIONS.
[Link]
Figure 2.29 FAAST Connection to the FACP
Process Emerg.
Module Description CS Local RS P (PPU) P(Burg) P Rec
Mana.(1) Sign. (2)
ACM-30 Annunciator O O O O Y O O O
RLD Remote Display O O O O O O O O
ABP-1 Blank Plate for ACM-30 O O O O O O O O
ABB-1 Backbox for One ACM-30 O O O O O O O O
ABB-2 Backbox for Two ACM-30’s O O O O O O O O
BP-5 Battery Dress Panel for CAB-5 O O O O O O O O
Process Emerg.
Module Description CS Local RS P (PPU) P(Burg) P Rec
Mana.(1) Sign. (2)
CGW-MB CLSS Gateway Main Board Y(8) O N N N N O Y(8)
HON-CGW-MBB CLSS Gateway in Plastic Enclosure Y(8) O N N N N O Y(8)
CGW-PT CLSS POTS Board Y(8,10) N N O N N O Y(8)
CGW-BB CGW-MB Enclosure Y(11) 0(11) N N N N 0(11) Y(11)
CGW-DACT CLSS Dialer (CGW-MB with CGW-PT) Y(8,10) N N O N N O Y(8)
CGW-DACT-CH Chassis for CGW-DACT O O O N O O O
HON-CGW-DACT CLSS Dialer in Plastic Enclosure Y(8,10) N N O N N O Y(8)
HWF2A-COM LTE/IP Dialer Capture Alarm O(8,10) N N O N N O O(8)
Communicator
HWF2V-COM LTE/IP Dialer Capture Alarm O(8,10) N N O N N O O(8)
Communicator
TG7LAF02 LTE Dialer Capture Alarm Communicator O(8,10) N N O N N O O(8)
TG7LVF02 LTE Dialer Capture Alarm Communicator O(8,10) N N O N N O O(8)
CCM-ATT-HON AT&T Cellular Module O O N N N N O O
CCM-VZ-HON Verizon Cellular Module O O N N N N O O
CPU-N16LD CPU Board (Core/PMB/SLM-318) with Y(9) Y(9) Y(9) Y(9) Y(9) Y(9) Y(9) Y(9)
10inch HD Display
CPU-N16-RB CPU Board Only (Core) O O O O O O O O
CPU-N16LND CPU Board (Core/PMB/SLM-318) w/o Y(9) Y(9) Y(9) Y(9) Y(9) Y(9) Y(9) Y(9)
Display
CPU-16-RTO Core Board with Retrofit Chassis for CAB-4 0(7) 0(7) 0(7) 0(7) 0(7) 0(7) 0(7) 0(7)
DP-4A Dress Panel, Mounts 4 ACM-30 O O O O O O O O
DP-4A-CB4 Dress Panel, Mounts 4 ACM-30s in a CAB- 0(7) 0(7) 0(7) 0(7) 0(7) 0(7) 0(7) 0(7)
4 Enclosure
DP-BLN Blank Dress Panel O O O O O O O O
DP-T2A Dress Panel for 10inch Display for CAB-5 O O O O O O O O
Enclosure
DP-T2A-CB4 Dress Panel for 10inch Touch Screen 0(7) 0(7) 0(7) 0(7) 0(7) 0(7) 0(7) 0(7)
Display and two ACM-30 Annunciators for
CAB-4 Enclosure
NCA-2* Network Control Annunciator O O O O O O O O
NCD Network Control Display O Y(9) O O O O O O
CPU-NCD-RB NCD Replacement Board O O O O O O O O
NBB-2 Backbox for NCD O O O O O O O O
DVC/DVC-EM Digital Voice Command/Extended Memory O O O O O O N N
Module
DVC-RPU Digital Voice Command Remote Paging O O O O O O N N
Unit
DAA-5025 (E)* Digital Audio Amplifier O O O O O O N N
DAA-5070 (E)* Digital Audio Amplifier O O O O O O N N
DAA-7525 (F) (SF)* Digital Audio Amplifier O O O O O O N N
DIS-10-RD 10inch Touch Screen Display Y(9) Y(9) Y(9) Y(9) Y(9) Y(9) Y(9) Y(9)
NCM-W/F Network Control Module O O O O O O O O
HS-NCM- Network Control Module O O O O O O O O
W/MF/SF/WMF/WSF/M
FSF/W-2/WMF-2/WSF-
2
PMB-AUX Power Supply O O O O O O O O
PMB-AUX-RTO Power Supply with CAB-4 Retrofit Chassis 0(7) 0(7) 0(7) 0(7) 0(7) 0(7) 0(7) 0(7)
Process Emerg.
Module Description CS Local RS P (PPU) P(Burg) P Rec
Mana.(1) Sign. (2)
CMIC-1 Microphone Assembly O O(5) O O O O O O
SLM-318 Signaling Loop Card Y Y Y Y Y Y Y Y
TELH-1 Telephone Assembly O O(5) O O O O O O
N16E-R CPU-N16LD in Red Enclosure O O O O O O O O
N16E CPU-N16LD in Enclosure O O O O O O O O
N16-GZ Panel License for General Zones O O O O O O O O
N16-LGZ Panel License for Logic Zones O O O O O O O O
N16-UZC Panel License for Universal Zone Coding O O O O O O O O
N16-NWD Panel License for Network Display Mode O O O O O O O O
N16-CAC Panel License for Custom Action Buttons O O O O O O O O
N16-CLP Panel License for CLIP Mode Y Y Y Y Y Y Y Y
SBB-A5 CAB-5 Backbox Size A Y Y Y Y Y Y Y Y
SBB-B5 CAB-5 Backbox Size B Y Y Y Y Y Y Y Y
SBB-C5 CAB-5 Backbox Size C Y Y Y Y Y Y Y Y
SBB-D5 CAB-5 Backbox Size D Y Y Y Y Y Y Y Y
SBB-E5 CAB-5 Backbox Size E Y Y Y Y Y Y Y Y
CHS-ADP Chassis for Amplifier 0(7) 0(7) 0(7) 0(7) 0(7) 0(7) 0(7) 0(7)
CHS-CGW Chassis for CGW-MB Communicator 0(7) 0(7) 0(7) 0(7) 0(7) 0(7) 0(7) 0(7)
CAB-A4 Enclosure Y(6) Y(6) Y(6) Y(6) Y(6) Y(6) Y(6) Y(6)
CAB-B4 Enclosure Y(6) Y(6) Y(6) Y(6) Y(6) Y(6) Y(6) Y(6)
CAB-C4 Enclosure Y(6) Y(6) Y(6) Y(6) Y(6) Y(6) Y(6) Y(6)
CAB-D4 Enclosure Y(6) Y(6) Y(6) Y(6) Y(6) Y(6) Y(6) Y(6)
ADDR-B4 Door Assembly O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
ADDR-C4 Door Assembly O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
ADDR-D4 Door Assembly O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
DP-1B Blank Panel O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
BMP-1 Blank Module O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
BP2-4 Battery Plate O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
CA-1 Chassis O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
CA-2 Chassis O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
C5A-M DVC Chassis, Well for Phone and Mic, O O O O O O O O
Includes Mic-1 for CAB-5
C5A-NW DVC Chassis Without Mic and Phone Well O O O O O O O O
for CAB-5
DPA-1A4 Dress Panel O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
DPA-1 Dress Panel O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
DPA-2 Dress Panel O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
DPA-2A5 Dress Plate DVC-KD with 2 Annunciator O O O O O O O O
Positions CAB-5
DPA-C5 Dress Plate, DVC one row for DVC-KD O O O O O O O O
DR-A5 Door Assembly O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
DR-A5B Door Assembly O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
DR-B5 Door Assembly O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
DR-B5B Door Assembly O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
DR-C5 Door Assembly O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
DR-C5B Door Assembly O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
Process Emerg.
Module Description CS Local RS P (PPU) P(Burg) P Rec
Mana.(1) Sign. (2)
DR-D5 Door Assembly O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
DR-D5B Door Assembly O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
DR-E5 Door Assembly O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
DR-E5B Door Assembly O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
DTR-A5 Red Cladding for CAB-5 Enclosure O O O O O O O O
DTR-B5 Red Cladding for CAB-5 Enclosure O O O O O O O O
DTR-C5 Red Cladding for CAB-5 Enclosure O O O O O O O O
DTR-D5 Red Cladding for CAB-5 Enclosure O O O O O O O O
DTR-E5 Red Cladding for CAB-5 Enclosure O O O O O O O O
DVC-KDB DVC Keypad, Black O O O O O O O O
VP-2B Dress Panel O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
DP-DISP2 Dress Panel O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
CHS-M3 Chassis, 1st tier O(7) O(7) O(7) O(7) O(7) O(7) O(7) O(7)
FZM-1 Monitor Module O O O O O O O O
FMM-1* Monitor Module O O O O O O O O
FMM-101* Monitor Module O O O O O O O O
FDM-1* Dual Monitor Module O O O O O O O O
FTM-1* Control Module O O O O O O O O
FCM-1* Control Module O O O O O O O O
FRM-1* Relay Module O O Y O O O O O
AA-30* Amplifier 30 watts O O(5) O O O O O O
AA-100* Amplifier 100 watts O O(5) O O O O O O
AA-120* Amplifier 120 watts O O(5) O O O O O O
ACT-1* Audio Coupling Transformer O O(5) O O O O O O
ACT-2* Audio Coupling Transformer O O(5) O O O O O O
ACT-4 Audio Coupling Transformer O O(5) O O O O O O
ACT-25 Audio Coupling Transformer O O(5) O O O O O O
ACT-70 Audio Coupling Transformer O O(5) O O O O O O
XPM-8L* Transponder Monitor Module O O O O X O O O
PRN-6* Printer O O O O O O O O
PRN-7* Printer O O O O O O O O
AMG-E* Audio Message Generator O O(5) O O O O O O
AKS-1* Annunciator Key Switch O O O O O O O O
RKS-S* Remote Security Keyswitch O O O O Y O O O
RPT-W* Repeater Wire O O O O O O O O
RPT-F* Repeater Fiber O O O O O O O O
RPT-485W* Repeater Wire O O O O O O O O
RPT-485FW* Repeater Wire/Fiber O O O O O O O O
FFT-7* Firefighter’s Telephone O O(5) O O O O O O
FFT-7S* Firefighter’s Telephone O O(5) O O O O O O
FHS* Fireman’s Handset O O(5) O O O O O O
FPJ* Fireman’s Phone Jack O O(5) O O O O O O
NBG-12LX* Addressable Manual Pull Station O O O O O O O O
RM-1, RM-1SA* Remote Microphone O(5) O O O O O O O
BP2-4 Battery Plate Y Y Y Y Y Y Y Y
FCO-851 Fire/CO Detector O O O O O O O O
Process Emerg.
Module Description CS Local RS P (PPU) P(Burg) P Rec
Mana.(1) Sign. (2)
XP6-R 6 Relay Control Module O O Y O O O O O
KEY:
* - Modules are listed separately Y - Yes N - No O - Optional X - Not permitted for security applications
NOTES:
1. Non-emergency
2. Emergency
3. At least one power supply must be utilized.
4. The system must contain one of these units.
5. When configured for Emergency Relocation and Evacuation Equipment, the system must meet Local configuration with a
minimum of one amplifier, one Audio Message Generator, one Voice Control Module. The phones, remote microphones, and
audio coupling transformers are optional. (Voice Alarm System Manual, Part No. 51252, shown in File S635, Vol. 5C, ILL. 1)
6. One of the cab enclosures must be utilized.
7. Various dress panels/dead fronts/trim rings must be employed so that internal components and high voltage is not accessible.
8. Also required when devices for Carbon Monoxide signaling are employed
• When configured for security applications, system must be configured for a maximum of 60 seconds for Entry/Exit delay.
• Standby power must provide 24 hours of standby.
9. In a large networked system, the NCD can be used as a primary display allowing multiple CPU-N16LND to be employed in lieu of
CPU-N16LD
10. Required if utilizing a central station other than supported by CGW-MB
11. Required when using CGW-MB alone OR using a CGW-MB with CGW-PT OR using CGW-DACT.
The units may employ the following features
• Alarm verification (maximum verification period of 60 for field programmable between 0 and 60s)
• Supports standard 2-wire smoke detectors using Models FZM-1. refer to the Device Compatibility Document for compatible 2-wire
smoke detectors
• Supports addressable or analog devices
• Field Programming
• Signal Silence Inhibit
• Remote annunciator outputs
• Automatic Alarm Signal Silence
• Drift compensation
• Detector sensitivity testing per Par. 7-3.2.1 of NFPA 72
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as
indicated below:
Program feature or Permitted in Settings permitted in
Possible settings
option UL864? (Y/N) UL 864
Service Mode No Yes No
No
Timed
Detector Yes SUP L(DUCTI) SUP L(DUCTI)
Programming: SUP T(DUCTI) SUP T(DUCTI)
Supervisory Type SUP T(DUCTP) SUP L(DUCTP)
Codes SUP L(DUCTP) SUP T(DUCTP)
SUP L(ION)
SUP T(ION)
SUP L(PHOTO)
SUP T(PHOTO)
SUP L(LASER)
SUP T(LASER)
P/CO (P SUP)
AC Fail Delay Timer Yes 0 for no delay, or 1-12 hours 1-3 hours
Regional Settings Yes Chicago Chicago
3.1 Licensing
The functionality of the N16 can be enhanced through the addition of the following software based licensed options
FIRE ALARM
Licensing FIRE ALARM
Licensing
CO ALARM General Zones CO ALARM Network Display Mode
Base number of general zones: 250 Network Display Mode: Not Enabled
Purchased number of general zones: 0
Number of general zones in use: 2
SUPERVISORY SUPERVISORY
Remaining number of general zones available: 248 Universal Zone Coding
Logic Zones Universal Zone Coding: Not Enabled
TROUBLE Base number of logic zones: 250 TROUBLE
Purchased number of logic zones: 0
Number of logic zones in use: 0 CLIP Mode
DISABLE Remaining number of logic zones available: 250 DISABLE CLIP Mode: Not Enabled
Custom Action Buttons
Base number of custom action buttons: 8
OTHER Purchased number of custom action buttons: 0 OTHER
Number of custom action buttons in use: 0
SIGNALS Remaining number of custom action buttons available: 8 SIGNALS
SILENCED SILENCED
DISABLE
OTHER
SIGNALS
SILENCED
3.3.2 About
Tap the ABOUT touchpoint to access the system update Tue 11/03/20
screen, model information, application information, System Normal [Link]PM
tion, hardware version, database information, loop Menu - > Settings - > About -> Update
System Update The user must be logged into the N16 Application
FACP as either a level 4 or 5 User to perform a system SUPERVISORY N16OS
update. Move/copy the appropriate firmware update SLM-318 Bootloader
image ([Link]) to a USB A flash drive. Insert the TROUBLE
SLM-318 Application
USB A memory drive to the USB port on the Core PMB Application
ACM-30 Application
board (J11) of the FACP. Select from the following DISABLE Restore Default Wallpaper
update types: N16 APPLICATION, N16OS, SLM BOOT-
LOADER, SLM APPLICATION, PMB APPLICATION,
OTHER
ACM-30 APPLICATION and RESTORE DEFAULT WALL-
PAPER. SIGNALS
SILENCED
Tap the SYSTEM UPDATE touchpoint to access all
Figure 3 System Update Screen
update capabilities. To update a specific application, tap
on that particular application. Tap on PREFORM UPDATE to complete the update.
NOTE: The system will copy the image to flash and reboot running the new image. Do not power down the system during this time.
DISABLE Kernel
Version: [Link] Date: 9/25/2020 Time: 11:24AM
M4
OTHER Version: [Link] Date: 2/27/2020 Time: 12:00AM
SIGNALS
SILENCED
Figure 4 About Screens
Tap the UPDATE APPLICATION touch- Tue 11/03/20
point to update all attached loop devices with resident
application software. Tap the UPDATE BOOT touch-
System Normal Ack Silence Reset
[Link]PM
Master
point to update all resident loop devices with the resi- Menu - > Settings - > About
dent boot software. FIRE ALARM
About
CO ALARM Hardware Version
CORE-PCB REV: 1 DIM-PCA REV: 2
Database
SUPERVISORY Version 3.000 Date: 9/25/2020 Time: [Link]M
Loop 1
TROUBLE Application Version: 1.0.67 Date: 6/02/2020 Resident Application Version: 1.0.67 Date: 6/02/20
Boot Version: 1.0.15 Date: 3/26/2020 Resident Boot Version: Not Avalible
SIGNALS
SILENCED
AIO Software Versions Tap the AIO Software Ver- Menu - > Settings - > About
sions touchpoint to view connected AIO devices on FIRE ALARM
both the internal and external AIO bus. Tap the Resi- About
dent Version touchpoint to view connected AIO CO ALARM
Power Supply 1
devices resident application version. Tap the UPDATE Application Version: 1.0.12 Date 5/29/2020 Resident Application Version: 1.0.12 Date: 5/29/2020
(relevant connected AIO device) touchpoint to update SUPERVISORY
all connected AIO devices of that particular type. Update Power Supplies
Tap the Update Application button to update all attached
TROUBLE power supplies with the resident application software
Serial Number
SNB0000013
DISABLE
AIO Software Versions
SIGNALS
SILENCED
word. The default password for the master user Ack Silence Reset Master
account on the N16 is eight zeros Menu - > Settings - > User Accounts
Add User At the main menu tap on the SETTINGS FIRE ALARM
User Accounts Current user access level 5
touchpoint and then USERS. Once in the users menu,
tap on the ADD USER touchpoint. A virtual keyboard CO ALARM Add User Username Tom Show on login screen
will appear. Type in the name of the user to be added.
New
Type in a password for the added user in the NEW SUPERVISORY Password
Access Level 4
PASSWORD box. Re-enter the password in the RE- Re-enter Add User
ENTER PASSWORD box. If the user is to be visible on TROUBLE
Password
user menu, tap on CHANGE PASSWORD. A virtual key- Ack Silence Reset Master
board will appear and prompt to enter the user name Menu - > Settings - > User Accounts
for the password that is changing. Type in the new FIRE ALARM
User Accounts Current user access level 5
password. Tap on CHANGE PASSWORD to save the new
password. CO ALARM
Username
Recovering a Master Password At the main menu,
New
tap on SETTINGS and USERS. Once in the users menu, SUPERVISORY Password
tap on RECOVER PASSWORD and then tap on Re-enter Change Password
GENERATE RECOVERY CODE. Record the code and TROUBLE
Password
3.3.5 Network
Tap on the NETWORK touchpoint to access the Net-
work Mapping screen. Network Mapping allows the
user to view all online nodes, mapped nodes,
unmapped nodes and grid view. Grid view provides
access to view and edit mapped and unmapped node
addresses.
Network Mapping Tap on the MAPPING touchpoint to
view mapped [Link] on the VIEW touchpoint to
select from ALL ONLINE NODES, MAPPED NODES,
UNMAPPED NODES and GRID VIEW. Tap on the circle
next to the desired view. Tap the LEGEND touchpoint
for information on node status for both online and off-
line mapped and unmapped nodes. To map a node, tap
on the desired node number. The number will change
from gray to green indicating it is now mapped. Tap
on the ACCEPT CHANGES touchpoint to save any
changes made in Grid view.
Figure 8 Grid View Screen
FIRE ALARM
Autoprogram
Select Loops
CO ALARM
Loop 1 Loop 6
SUPERVISORY
Loop 2 Loop 7
START AUTOPROGRAM
TROUBLE Loop 3 Loop 8
SIGNALS
SILENCED
NOTE: To delete an installed point, use VeriFire Tools. Autoprogram will not prompt the user to delete a previously installed point. If a point
is removed, it will appear on the loop as unresponsive after autoprogram.
From the Main Menu, tap on Point Information. Then, tap on the SELECT touchpoint. A drop-down menu will appear listing the following
point types: Detector, Module, General Zone, Logic Zone, VEDSA, DAL Speaker Circuit, DAL All Circuits, PAM Point, Releasing Zone,
Special Zone, Trouble Zone and NAC Circuit. Tap on the desired point type. A select box for node will appear. Tap on SELECT for a list of
nodes connected to the N16. Tap the desired node number to select that node. If a point type is not connected to the system, a node number
will not appear. Specific point types will display various menu selections that pertain to that point type. Refer to the following point types for
specific menus:
NAC Circuit If NAC CIRCUIT is selected, a drop-down menu for power supply will appear. Tap on SELECT for a list of power supply address
numbers. Tap on the desired power supply address number (1-3). A drop-down menu for NAC circuit will appear. Tap on SELECT to for a list
of NAC circuits (1-4). Tap on the desired NAC circuit number. Tap GET POINT. The screen will change to the point commands screen. From
this screen, the user can disable the point, view the history, as well as view read status for the point and force on the point. Tap DISABLE to
disable the selected point. Tap READ STATUS to view the programmed settings of the selected point. Tap FORCE ON to force the point to an
active state. Tap POINT HISTORY to view and search the history of the selected point.
Detector/Module/VESDA If a detector module or VESDA is selected, a drop-down menu for loop will appear. Tap SELECT and choose the
desired loop number (1-10). A drop-down menu for detector or module will appear. Tap SELECT to choose the desired point address. Tap GET
POINT. The screen will change to the point commands screen. From this screen the user can disable the point, view the history as well as view
read status for the point and force on the point. Tap DISABLE to disable the selected point. Tap READ STATUS to view the programmed settings
of the selected point. Tap FORCE ON to force the point to an active state. Tap POINT HISTORY to view and search the history of the selected
point.
General Zone/Logic Zone/Special Zone/Releasing Zone/Trouble Zone: A drop-down menu for the selected zone type will appear. Tap on
select to choose the desired point address. Tap on GET POINT. The screen will change to the point commands screen. From this screen the user
can disable the point, view the history as well as view read status for the point and force on the point. Tap DISABLE to disable the selected
point. Tap READ STATUS to view the programmed settings of the selected point. Tap FORCE ON to force the point to an active state. Tap POINT
HISTORY to view and search the history of the selected point.
Bell Circuit If Bell Circuit is selected, a drop-down menu for Bell Circuit will appear. Tap on SELECT to for a list of Bell Circuits (1-4). Tap
on the desired Bell Circuit number. Tap GET POINT. The screen will change to the point commands screen. From this screen, the user can dis-
able the point, view the history for the point and force on/off the point. Tap DISABLE to disable the selected point. Tap FORCE ON to force the
point to an active state. Tap POINT HISTORY to view and search the history of the selected point
PAM Point If PAM POINT is selected, a drop-down menu for node will appear. Tap SELECT to choose the appropriate node number. Tap on
the desired node number. A drop-down menu for Amplifier will appear. Tap on the desired amplifier number. A drop-down menu for speaker
circuit will appear. Tap on the desired speaker circuit. A drop-down menu for input will appear. Tap on the selected input number. Tap GET
POINT. The screen will change to the point commands screen. From this screen, the user can force on/off the point and view the status of the
point. Tap FORCE ON to force the point to an active state.
DAL All Circuits If DAL ALL CIRCUITS is selected, a drop-down menu for node will appear, tap SELECT to choose the appropriate node
number. Tap on the desired node number. A drop-down menu for Amplifier will appear. Tap on the desired amplifier number. Tap GET POINT.
The screen will change to the point commands screen. From this screen, the user can disable the point.
DAL Speaker Circuit If DAL SPEAKER CIRCUITS is selected, a drop-down menu for node will appear, tap SELECT to choose the appropriate
node number. Tap on the desired node number. A drop-down menu for Amplifier will appear. Tap on the desired amplifier number. A drop-
down menu for speaker circuit will appear. Tap on the desired speaker circuit. Tap GET POINT. The screen will change to the point commands
screen. From this screen, the user can disable the point and view the point history.
3.3.8 Diagnostics
Tap the DIAGNOSTICS touchpoint to view the circuit board temperature and the CPU temperature. The screen displays the highest circuit
board temperature and the highest CPU temperature. Each may be reset by tapping on the RESET touchpoint next to the relevant information.
The user can also view and reset all SLM-318 and PMB communication statistics. Tap the RESET touchpoint next to SLM-318 and PMB
Communication Statistics to reset the statistics.
Exporting diagnostics to a USB flash drive Tap on the EXPORT DIAGNOSTICS touchpoint. A pop up box will appear prompting you to
insert a USB memory drive and then tap CONTINUE. Diagnostics will be exported onto the USB memory drive. If the user wishes to cancel
exporting of Diagnostics, tap the touchpoint CANCEL.
NOTE: The user must be logged in as either a lever 5 or 4 user to export panel history and diagnostic information.
3.3.10 History
The history feature allows the user to view the panel history as well as the network history. History views may also be filtered.
Sorting and filtering Tap on the FILTER touchpoint. A touchpoint for SEARCH and CLEAR will appear along with a virtual keyboard. Enter a
date under DATE RANGE to search a specific date range. Type in a keyword in the CONTAINS TEXT section to search the history for particular
text. To clear a search, tap the CLEAR touchpoint. Tap on the EXCLUDE BACKGROUND ACTIVATIONS check box to select that feature. Tap again
to clear the field.
History will show and can be filtered for the follow-
ing:
All Events This displays the entire history buffer,
regardless of event type. The history buffer can dis-
play up to a total of 10,000 events, including alarms.
Alarms Only This displays only the alarm events
stored in the history buffer.
Troubles Only This displays only the trouble events
stored in the history buffer.
Supervisory Only This displays only the supervi-
sory events stored in the history buffer.
Security/Other This displays only security and
events deemed “other” stored in the history buffer.
(i.e. Critical Process, Prealarm CO Alarm, etc.)
Time Date Interval This displays a screen to allow
for the selection of a time period to define the range of
events displayed, as well as specific event type. (i.e.
Figure 3.1 History Search Screen
All Events, Alarms Only, etc.)
Point Range This displays a screen to allow for the selection of a beginning and an end point that defines the range of events to be dis-
played.
Exporting History to USB Flash Drives: Tap on the
VIEW HISTORY touchpoint. Tap on FILTER to preform a
search (refer to , "Sorting and filtering") to display the
history to be exported. Tap on EXPORT, a pop-up box
will appear prompting the user to insert a USB flash
drive or tap CANCEL. Tap CONTINUE. The history will be
exported onto the USB flash drive. TO close the box
without a history search tap CANCEL.
NOTE: The user must be logged in as either a level 5 or 4 user to export panel history and diagnostic information.
NOTE: The Piezo disable is not supervised when the FACP is in alarm and is not an approved method of acknowledging or silencing events on
the FACP.
Alarm Verification Maximum Count: Enter a value from 0-20 for a maximum verification count threshold value that applies to detectors
set to participate in Alarm Verification. A value of zero produces no verification trouble. When the counter exceeds the threshold value
entered, a trouble is generated to the panel. Default: 4
AC Fail Delay: Set the timing for the time delay from AC failure to when the trouble is reported. Choose a value of 1-12 (hours), or select
0. A value of 0 will turn OFF the AC Fail delay.
• The on-board trouble relay (TB2 on the N16) will activate
• CGW-MBs are notified immediately of AC failure by the panel, regardless of the panel’s delay setting. Once the CGW-MB receives
notification, it operates according to its own programmed AC Fail Delay reporting schedule.
• Power LED is NOT delayed and will turn off immediately if all installed PMB supplies lose power.
• Delay timer starts the countdown when the first PMB goes into AC Fail, will not reset if additional PMB’s also go into AC Failure.
Signal Silence Inhibit Time: Enter a value from 0 (disabled) to 5 minutes. This software timer disables the SIGNAL SILENCE function for
the time entered when a fire alarm occurs. The timer starts at the first alarm only; it does not restart with each new alarm. Default: 0
Automatic Silence time: Enter a value from 0 (disabled) to 20 minutes. This global software timer functions like pressing the SIGNAL
SILENCE key. For example, if a value of 10 is entered, the control panel will silence all active outputs programmed as silenceable after ten
minutes. When Auto Silence activates, special function zone ZF40 will activate and will remain active until a system reset, alarm resound, or
drill is initiated. Default: 0
Verify=Pre-Alarm Check the box to enable Verify=Pre-Alarm. Default unchecked.
Enable Alarm Delay: Check the check box to enable Alarm Delay. Set the timer for
between 0-59 seconds. Default is 15 seconds. Program Setting for: Default:
Presignal Delay Time: Enter a value of 00:00 (disabled) or a value of 1:00 to 3:00 Verification Time 30 seconds
minutes (in the format MM:SS, where MM= minutes, SS= seconds). This feature ini-
tially causes alarm signals to sound only in specific areas, monitored by qualified Max. Verification 0 (disabled)
personnel. This allows delay of the alarm for up to 3 minutes after the start of alarm Time
processing. Default: 3:00 Verification 60 seconds
Conformation Time
NOTE: An error box will appear if entering a value greater than 3:00 for the Presignal
Delay Time AC Fail Delay 2 hours
Silence Inhibit 0 (disabled)
Auto Silence 0 (disabled)
Verify=Prealarm Unchecked
Alarm Delay Unchecked
Presignal Delay 3 minutes
Alarm Delay Timer 15 Seconds
Supervision Settings
Printer: Types: NONE, 40-COLUMN, 40-COLUMN SUPERVISED, 80-COLUMN, 80-COLUMN SUPERVISED, The printer will not be
active if NONE is selected. If a SUPERVISED selection is made, the printer will be supervised. Default: NONE
Choice of Baud Rate Settings:
• 300bps
• 2400bps
• 4800bps
• 9600bps
• 19.2Kbps
• 38.4Kbps
• 57.6Kbps
Power Supply (PMB): AUX trouble input if connected to trouble contacts of an N16 for supervision. Auxiliary Trouble Reporting
Check the box to enable Auxiliary trouble reporting.
Tamper Input: There are three options are available: Not Used, Security Alarm and AKS Key Switch.
• Not Used: Does not report a tamper situation at the panel cabinet door
• Security Alarm: Reports a tamper security event at the panel when the cabinet door is using an STS-1 tamper switch.
• AKS Key Switch: Should be used when there is an AKS-1 key switch connected to the panel cabinet door. The AKS switch may
enable level 2 access. Must be programmed to do so in the password database and enabled in the NCD programming database
3.4.10 Loop Configuration
Installed: Choose between YES and NO, depending on whether an SLC is installed at this address
Detector Mode: Select Loop Polling mode for detectors on this loop.
Module Mode: Select Loop Polling mode for modules on this loop.
Wiring style: Select the NFPA wiring Class (B or A) of the loop. If Class A is entered when the wiring is Class B, a trouble message will be
generated at the panel.
LED Disable: Enable or disable individual SLC loop device LEDs.
Flow Fault Delay: Set the amount of time before the panel indicates the Flow Fault. Range 0-255 seconds
DEFAULT: 200s
NOTE: Specific nodes can be excluded from having the ability to initiate a resound on the local fire panel. This option is programmable via
VeriFire Tools.
Reference Detector Address: Set a detector for to be used as a reference for air flow for other FAAST detectors. All 5 detectors of each
FAAST device using this detector as a reference must be set with the same reference detector address, have the same Threshold value (set via
PipeIQ) and must be on the same loop as the reference detector. Range: 0, 1-159
DEFAULT: 0 (No reference detector programmed)
Zone Map: Up to 10 zones available. During initial programming, the primary zone (position 1) displayed is associated with the loop the
device is installed on. For example, the device’s default programming set the primary zone as Z003, indicating that the device is installed on
Loop 3. Certain zone map positions are used for specific functions.
• Position 1 - Use to link zone label to detector and for group zone disable.
• Position 3 - Fire/CO detector only: Activates when the photo element of the Fire/CO detector activates.
• Position 4 - Fire/CO and PHOTO/CO detectors only: Activates when the CO element of the Fire/CO detector activates. (Map the
zone in this location to one of the Aux Controls of the intelligent sounder bases in order to play the Temp-4 tone for CO Alarms.)
• Position 5 - Fire/CO, PHOTO/CO and CO detectors only: Activates when the Fire/CO detector reports a CO Pre-Alarm.
• Position 9 - Used to activate sounder/relay bases of FlashScan detectors.
When mapped to the same zone as Position 10, the sounder or relay base will activate when the detector goes into prealarm (Action).
When mapped to a general or logic zone and this zone activates, the panel is searched for any detector with the same zone mapped in
its 9th position. The sounder base of any FlashScan detector that matches the search will activate. Continuous tone only. Position 9 is
not typically used with intelligent sounder bases.
Position 10 - Used for detectors set to Prealarm, Action. This zone will activate when the detector reaches its Prealarm threshold; no
other zones in this detector’s zone map will activate.
Sensitivity: The N16 Control panel provides 9 levels of Prealarm and Alarm in percent per foot obscuration with the following 3 exceptions:
• for heat detectors, the settings are in degrees Centigrade.
• for beam detectors, there are only 6 levels of Alarm. Prealarm is not an option for beam detectors in CLIP mode.
• for Intelliquad FSC-851 detectors, there are only six levels of Alarm and Prealarm for FlashScan mode, The sixth level is a fixed
135oF and it is not available in CLIP mode.
Alarm Sensitivity Values range from one to nine; one represents the most sensitive level, nine the least sensitive.
Prealarm Sensitivity: 3.4.14 values range from zero to nine; Zero indicates no prealarm, a value of one can be a self-optimizing setting where the
control panel selects a suitable prealarm level for the detector. Values one or two through nine represent decreasing sensitivity, with nine being the least
sensitive. Sounder Base Setup
AUX Tone 1: Select CONTINUOUS, TEMP-3, TEMP-4, MARCH or CUSTOM for the first auxiliary tone of the intelligent sounder base.
AUX Tone 1 Control: Enter the Logic Zone or General Zone that will control the activation of the first auxiliary tone of the intelligent
sounder base.
AUX Tone 2: Select CONTINUOUS, TEMP-3, TEMP-4, MARCH or CUSTOM for the second auxiliary tone of the intelligent sounder
base.
AUX Tone 2 Control: Enter the Logic Zone or General Zone that will control the activation of the second auxiliary tone of the intelligent
sounder base.
Volume: Select LOW or HIGH for the intelligent sounder base volume level.
Zone Map: Displays the zones mapped to this device. Refer to Appendix D, “CBE Zones and Equations” for a list of available zone types
and their descriptions. Certain zone map positions are used for specific functions.
Position 1 - Use to link zone label to detector and for group zone disable.
Alarm Verification: Choosing Yes will set the device participation to the values entered in Panel Timers. The only module type that can par-
ticipate in alarm verification is the FZM-1.
Local Mode: During communication loss between the panel and the SLM-318 devices selected for Local Mode participation and place in a
local mode zone will continue to function across all the panel’s SLCs in a limited manner. Input points will activate output points mapped to
the same local mode zone. For example: SLC inputs mapped to “local mode zone 2” will activate mapped SLC outputs also placed in “local
mode zone 2”.
In addition to creating a “local mode zone” map, inputs and outputs must also be enabled for “local mode participation” to work at the device
level.
Waterflow delay: When the WATERFLOW DELAY option is set to 0, waterflow events are immediately reported to the panel upon activa-
tion. If a non-zero value is entered in the WATERFLOW DELAY, activation of a waterflow event is delayed for the duration of that time. The
waterflow event will have to remain active for the duration of the delay. If the waterflow event does not remain active for the entire delay
duration, the waterflow event will not be reported to the panel.
Default: 0
Range: 0-60 seconds
3.4.19 Zones
The following is a list of available zone types for CBE (Control-By-Event) and Zone Map programming when programming devices.
Module Example:
OR(TBL(L1M1)) will activate when local loop 1 module 1 goes into trouble and not when it activates.
OR(TBL(N1L1M1)) will activate when node 1 loop 1 module 1 goes into trouble and not when it activates.
System Trouble Example:
OR(TBL(T1)) will activate when local system trouble 1 is active.
OR(TBL(N1T1)) will activate when node 1 system trouble 1 is active.
OR(T1) will activate when local system trouble 1 is active.
OR(N1T1) will activate when node 1 system trouble 1 is active.
Table 3.1
Arguments:
LxxD1 - LxxD159 detectors loop xx (159 per loop)
LxxM1 - LxxM159 modules loop xx (159 per loop)
(Nxxx)Z0 - (Nxxx)Z999* general zones (2000)
ZF1 - ZF7, ZF9 - ZF22, ZF36 - ZF40 special zones (27)
T0 - T510 system troubles (trouble equations only) (511)
(Nxxx)ZL1 - (Nxxx)ZL1000 logic zones (2000)
xx = loop number (01 through 10)
(Nxxx) = Node number, necessary for CCBE programming. The node number identifies what node the panel will watch for a particular zone activation.
Table 3.2
Logic Functions:
“AND” Operator Requires that each argument be active.
Example: AND(Z02,Z05,L2D12)
All three arguments in the equation must be active for the logic zone to be activated.
“OR” Operator Requires that any argument be active.
Example: OR(Z02,Z05,L2D12)
If any one of the three arguments in the equation is active the logic zone will be activated.
“NOT” Operator Inverts the state of the argument (activated to deactivated OR deactivated to activated).
Example: NOT(Z02)
The logic zone will remain activated until the argument activates.
If the argument activates the logic zone will deactivate.
“ONLY1” Operator Requires that only one argument be active.
Example: ONLY1(Z02,Z05,Z09)
If only one of the arguments activates the logic zone will be activated.
“ANYX” Operator Requires that the amount of arguments specified by the number preceding the arguments be active.
Example: ANYX(2,Z02,Z05,Z09)
If any two or more of the arguments are in alarm the output point will be activated.
The X amount may be a value from 1 through 9.
“XZONE” Operator Requires that any combination of two or more input devices programmed to a zone be active. (Local General Zones only)
Example: XZONE(Z02)
If any combination of two or more initiating devices that have been mapped to this software zone come into alarm, then
outputs mapped to this zone will activate.
“RANGE” Operator Each argument within the range must conform to the requirements of the governing function. The range limit is 20
consecutive arguments.
Example: AND(RANGE(Z1,Z20))
Zone 1 through Zone 20 must all be active to activate the logic zone.
“DIS(point argument)” Operator Requires that the point argument be disabled for the operator to go active.
“PRE(point argument)” Operator Requires that the point argument be in prealarm for the operator to go active.
Example: AND(L1D1,PRE(L1D2))
The detector at address L1D1 must be active and the detector at L1D2 must be in prealarm for this equation to go active.
“SUP(point argument)” Operator Requires that the point argument be in an active supervisory state for the operator to go active.
Example: OR(L1D1,SUP(L1M1))
The detector at address L1D1 must be active, or the module at L1M1 must be in an active supervisory state, for the
equation to go active.
“FIRE(point argument)” Requires that the point argument be in an active fire alarm state for the operator to go active.
Operator Example: AND(L1D1,FIRE(L1M1),FIRE(L1M2))
The detector at address L1D1 must be active and the modules at L1M1 and L1M2 must be in an active fire alarm state,
for the equation to go active.
“NON(point argument)” Requires that the point argument be in an active non-alarm state for the operator to go active.
Operator Example: AND(L1D1,NON(L1M1))
The detector at address L1D1 must be active and the module at address L1M1 must be in an active non-fire alarm state,
for the equation to go active.
“SEC(point argument)” Operator Requires that the point argument be in an active security alarm state for the operator to go active.
Example: AND(L1M1,SEC(L1M2))
The module at address L1M1 must be active and the module at address L1M2 must be in an active security alarm state,
for the equation to go active.
Table 3.3
The N16, when installed in accordance with the above manuals, comply with the following NFPA 72 standards for fire protective signaling
systems:
• Central station (protected-premises unit, requires CGW-MB)
• Local, remote station (protected-premises unit, requires UL 864 10th edition listed contact closure DACT)
• Proprietary (protected-premises unit)
• Proprietary (receiving unit)
• Emergency communication (requires DVC/DAA/DAA-2)
• Relocation
The N16 is also suitable for use as the following:
• Proprietary burglar alarm unit, (multiplex requires ACM-30)
• Type of signaling service: Non-Coded, March Time, Coded.
• Class A or B power-limited initiating device circuits
• Class A or B power-limited notification appliance circuits
• Power-limited communications loop meeting NFPA 72 Class A, B and X requirements
• Alarm signal cutoff (if enabled) programmable from 180 – 1200 seconds
• Presignal delay (if enabled) programmable from 60 – 180 seconds
• Signal inhibit (if enabled) programmable from 0 – 300 seconds
• Performance based Technologies (requires CGW-MB)
Types of signals: automatic fire alarm, manual fire alarm, waterflow alarm, sprinkler supervisory service
Type of signaling device: Type NM (non-monitoring) and SM (self-monitoring). Installation limits in all categories of service are under the
jurisdiction of the local authority and in accordance with NFPA70 National Electrical Code. System and peripherals for indoor dry use (with-
out specific marine listings) in a recommended environment with a nominal room temperature of 15°C to 27°C (60°F to 80°F).
Electrical ratings: 2.5A @ 120V or 1.25 A @ 240 V, 50/60 Hz (primary power source) and 24 VDC battery (standby power source). Operat-
ing system software: software version information may be displayed by navigating to the Settings > About menu on the main display.
Local Applications:
• Emergency relocation (paging, live and pre-recorded)
• Emergency communication (telephone)
Protected premises unit:
• Central station
• Remote station
• Proprietary
• Local
Communication transmission path:
• POTS communication off premises using CGW-MB
• Performance-based with CGW-MB
Process control, non-critical
Regional settings
• Chicago
– Panel signal silence button will not function
– Annunciator control modules and SLC modules given a drill or signal silence mode or type code will not allow local drill or signal
silence initiation
– Events must be acknowledged prior to system reset
4.2 Functionality
The following are approved functions for the N16.
• Drift Compensation
• Connected Capabilities (CLSS gateway required for Connected Capabilities)
– CLSS gateway
– Remote access for diagnostics
– Remote communication session- requires FACP to be in service mode. Technician required on site
• Service Mode
– Remote programming. Technician required on-site
• Multiple Detector Operation
– Units employing multiple detector operation shall include a minimum of two detectors in each protected space and reduce the
detector installation spacing to 0.7 times the linear spacing in accordance with National Fire Alarm Code, NFPA
• Alarm Delay
• Pre-signal
• Alarm verification
• Two-wire compatibility
– One alarm per initiating device circuit
• Polling Style limitations
– Polling Style is FlashScan or CLIP (Classic Loop Protocol)
– All detectors and modules on an SLC may be programmed as FlashScan. All detectors and modules must be FlashScan type devices.
Maximum number of devices per SLC: 159 detectors, 159 modules.
– All detectors and modules on an SLC may be programmed as CLIP. Detectors and modules may be a mix of CLIP and FlashScan
type devices, but all must be programmed as CLIP. Maximum number of devices per SLC: 99 detectors, 99 modules.
– All detectors may be programmed as CLIP, all modules as FlashScan, on an SLC. Detectors may be a mix of CLIP and FlashScan
type devices, modules must all be FlashScan type devices. Maximum number of devices per SLC: 99 CLIP detectors, 159 FlashScan
modules.
• NAC Resound
• Primary power source failure indication
• CGW-MB Communication Format
– TCP/IP
• Interconnected control panels
– Alarm, supervisory and trouble conditions, as well as reset, alarm silence, or trouble silence actuation originating at this panel are
annunciated at this panel.
• Integrated/network local functionality
• Circuit disables
• Network Mapping
• Detection/alarm algorithms
• Day/night sensitivity
• Detection sensitivity adjustment
• Extent/limitations of combination system
– Priority of signals
alert bar
events list
work programming and Autoprogram options. Refer Circuit Board Temperature, CPU Temperature, Statistics, Lamp
to “Network” on page 58 and “Autoprogram” on TROUBLE TEST/DIAGNOSTICS Test, Panel History
page 59 for more information.
CUSTOM Custom Actions
Point Information Allows the user to enable/disable DISABLE
points, control points on/off, perform read status of a
point and view point [Link] to “Point Informa- OTHER
tion” on page 59 for more information.
SIGNALS
Test/Diagnostics This menu provides access to SILENCED
Diagnostics and also allows for the export of diagnos- Figure 2 Main Menu Screen
tics, along with: Lamp Test, Clear Database, View
History and Reboot. Refer to “History” on page 60,
“Diagnostics” on page 60 and “Lamp Test” on page 60 for more information.
Custom Allows the user to customize virtual buttons that can be mapped and assigned to manually control common system commands such
as enable/disable points.
Thu 2/22/18
FIRE ALARM Ack Silence Reset
[Link]PM
1 Step 1 Acknowledge each event. This is secondary text to explain what acknowledging an event means and who should do it.
SUPERVISORY
TROUBLE
DISABLE
OTHER
SIGNALS
SILENCED
Thu 2/22/18
TROUBLE Ack Silence Reset
[Link]PM
Step 1 Acknowledge each event. This is secondary text to explain what acknowledging an event means and who should do it.
SUPERVISORY
1
TROUBLE
DISABLE
OTHER
SIGNALS
SILENCED
4.8 CO Alarm
CO Alarm Event
• Activation of a device (detector or module) with a CO Alarm type code. (Refer to Table G.2, “Type Codes for Monitor Modules,” on
page 112)
• Produces a pulsed audible tone
• CO ALARM appears in the Header Bar
• CO ALARM illuminates in the Alert Bar as a blue color indicator and provides CO event counts
• Illuminates the yellow Off Normal LED
• Displays CO ALARM and specific device information in the Events List
• Displays information on how to react to the event in the Instructional Text Area
NOTE: If an unacknowledged, higher priority event exists, the control panel will retain the indications of the higher priority event, such as an
audible tone, etc. The flashing the CO Pre-Alarm Graphic and sending the CO Pre-Alarm message to the history buffer and printer and
annunciators will still occur at the time of the event.
Thu 2/22/18
CO ALARM Ack Silence Reset
[Link]PM
Step 1 Acknowledge each event. This is secondary text to explain what acknowledging an event means and who should do it.
SUPERVISORY
TROUBLE
DISABLE
OTHER
SIGNALS
SILENCED
Thu 2/22/18
SECURITY ALARM Ack Silence Reset
[Link]PM
Step 1 Acknowledge each event. This is secondary text to explain what acknowledging an event means and who should do it.
SUPERVISORY
TROUBLE
DISABLE
1
OTHER
SIGNALS
SILENCED
4.10 Supervisory
Supervisory Event (If a fire alarm exists and alarms are silenced, a supervisory alarm will resound the panel sounder)
• Produces a warbling audible tone
• SUPERVISORY appears in the Header Bar
• SUPERVISORY illuminates on the Alert Bar as a yellow color indicator and provides Supervisory event counts
• Illuminates the yellow off normal LED
• Displays SUPERVISORY and specific device information in the Events List
• Displays information on how to react to the event in the Instructional Text Area
Thu 2/22/18
SUPERVISORY Ack Silence Reset
[Link]PM
Step 1 Acknowledge each event. This is secondary text to explain what acknowledging an event means and who should do it.
SUPERVISORY
TROUBLE
DISABLE
OTHER
SIGNALS
SILENCED
Thu 2/22/18
DISABLED Ack Silence Reset
[Link]PM
Step 1 Acknowledge each event. This is secondary text to explain what acknowledging an event means and who should do it.
SUPERVISORY
TROUBLE
1
DISABLE
OTHER
SIGNALS
SILENCED
tion, hardware version, database information, loop Menu - > Settings - > About -> Update
OTHER
SIGNALS
SILENCED
update image ([Link]) to a USB A flash drive. Menu - > Settings - > About
Insert the USB A memory drive to the USB port on FIRE ALARM
the Core board (J11) of the FACP. Select from the fol- About
lowing update types: N16 APPLICATION, N16 OS, CO ALARM System Update
SLM BOOTLOADER, SLM APPLICATION, PMB APPLI- Model
CATION, ACM-30 APPLICATION and RESTORE N16
SUPERVISORY
DEFAULT WALLPAPER. Application
Version: 3.0.831.4054 Date: 9/25/2020 Time: 11:24AM
TROUBLE Boot
Version: 13.0.0 Date: 9/25/2020 Time: 7:22AM
DISABLE Kernel
Version: [Link] Date: 9/25/2020 Time: 11:24AM
M4
OTHER Version: [Link] Date: 2/27/2020 Time: 12:00AM
SIGNALS
SILENCED
NOTE: The system will copy the image to flash and reboot running the new image. Do not power down the system during this time.
Updating the N16 When updating the N16 the user should connect the flash drive with the update file on it to the N16 via the USB A port
located on the Core Board. The update for the N16 must be initiated from the either the N16 or the NCD and will require a file with a .sys
extension.
Updating the NCD When updating the NCD the user should connect the flash drive with the update file on it to the NCD via the USB A port
located on the Core Board. The update for the NCD must be initiated from either the NCD or the N16 and will require a file with a .sys
extension.
extension. Loop 1
TROUBLE Application Version: 1.0.67 Date: 6/02/2020 Resident Application Version: 1.0.67 Date: 6/02/20
Boot Version: 1.0.15 Date: 3/26/2020 Resident Boot Version: Not Avalible
SIGNALS
SILENCED
Updating the PMB A PMB firmware update can be Menu - > Settings - > About
initiated from the N16 or the NCD using a flash drive FIRE ALARM
both the internal and external AIO bus. Tap the Resi- Serial Number
SNB0000013
dent Version touchpoint to view connected AIO DISABLE
devices resident application version. Tap the UPDATE AIO Software Versions
(relevant connected AIO device) touchpoint to update OTHER Network: HS-NCM
Version: 30.10.006 Date: 6/30/2015 Time: 9:13AM
all connected AIO devices of that particular type.
SIGNALS
SILENCED
.
Step 1. Disconnect the SLC channel B (Out) and SLC channel A (Return) at the control panel.
Step 2. Measure and record the resistance at SLC Out.
Step 3. Measure and record the resistance at SLC Return.
STEP 2 STEP 3
SLC Out
SLC Out
SLC Return
SLC Return
NOTE: If using multiple power supplies with one set of batteries, refer to the PMB-AUX power supply manual for connection requirements.
NOTE: When disabling the battery charger on the PMB Power Supply, the batteries must be shared with a UL 864 compliant, supervised power
supply capable of charging batteries with a charger voltage not to exceed 29VDC.
Alarm Time
Battery Capacity
5 10 15 20 30
7 0.118 0.089 N/A N/A N/A
12 0.285 0.255 0.225 0.196 0.136
18 0.485 0.455 0.425 0.396 0.336
26 0.752 0.722 0.692 0.662 0.603
33 0.985 0.955 0.925 0.896 0.836
75 2.385 2.355 2.325 2.296 2.236
100 3.218 3.189 3.159 3.129 3.069
Table A.3 Maximum Battery Standby Loads for 24 Hour Standby on the PMB Power Supply
Maximum resistance 50 ohms (supervised and power-limited). For additional notes on SLC resistance values, see Section 6.2
“Operational Checks”.
NOTE: If running an SLC in conduit with Notification Appliance Circuits, you can reduce problems by exclusively using electronic sounders
(such as the MA/SS-24 Series) instead of more electronically noisy notification appliances (such as electromechanical bells or horns).
Distance
Circuit Type Circuit Function Wire Requirements Typical Wire Type
(feet/meters)
SLC Connects to intelligent and Twisted-unshielded pair, 12 to 18 AWG 12,500 ft (3,810 m) 12 AWG (3.31 mm2)
(power limited) addressable modules. (3.25 to 0.75mm2). 50 ohms, maximum 9,500 ft. (2,895.6 m) 14 AWG (2.08 mm2)
per length of Style 6 & 7 loops. 50 ohms 6,000 ft. (1,828.8 m) 16 AWG (1.31 mm2)
per branch maximum for Style 4 loop. 3,700 ft. (1,127.76 m) 18 AWG (0.82 mm2)
or Twisted-shielded pair. 5,000 ft (1524 m) 12 to 16 AWG (3.31
NOTE: mm2 to 1.31 mm2)
• Shields must be isolated from ground. 3,700 ft. (1,127.76 m) 18 AWG (0.82 mm2)
• Shields should be broken at each
device.
or Untwisted, unshielded wire, in conduit or 5,000 ft (1524 m) 12 to 16 AWG (3.31
outside of conduit. mm2 to 1.31 mm2)
3,700 ft. (1,127.76 m) 18 AWG (0.82 mm2)
NOTE: Maximum total capacitance for all
SLC wiring (both between conductors and
from any conductor to ground) should not
exceed 0.5 microfarads
CLP Connection Carry RS-485 data and internal
24V power to the SLM-318 loop
cards and the core board on the
N16 CPU assembly
PMB power supplies use only the
RS-485 data
Topic Page
Intelligent Sensing features – Descriptions of Intelligent Sensing features, such as Drift Compensation, Sensitivity Adjust,
programmable on a per-detector basis.
Pre-Alarm – Alert and Action settings, programming (global settings).
Detector Sensitivity Settings – Pre-Alarm and Alarm sensitivity settings for photo, ion, laser and multi-sensor detectors programmable
on a per-detector basis.
Detector Maintenance Features – Instructions for viewing and printing detector maintenance information.
Alarm Level
Without Compensation
Analog
Reading With Compensation and Smoothing
DIRTY
[Link]
MAINTENANCE REQ
Acceptable
Range
LOW THRESHOLD
Low
Value
Prealarm Threshold
Analog
[Link]
Reading
Time (days)
• Pre-Alarm Sensitivity Levels You can select one of nine levels from 1 to 9 (0=no Pre-Alarm, 1=self-optimizing, 2=highest
sensitivity, 9=lowest sensitivity). You can set Pre-Alarm operation to Action (latching) or Alert (non-latching) and to activate Special
Zones.
You can set the sensitivity levels as fixed or programmed for day and night operation.
A sample sensitivity window for a laser detector:
2.1%
Figure B.4 Sample Sensitivity Levels for a FlashScan View Laser Detector
Combined
Alarm
SMOKE OBSCURATION
3 Sensors
Time (minutes)
B.3 Pre-Alarm
B.3.1 Definition
The Pre-Alarm function is a programmable option which determines the system’s response to real-time detector sensing values
above the programmed setting. Use the Pre-Alarm function to get an early warning of incipient or potential fire conditions.
There are two levels of Pre-Alarm:
• Alert (Refer to “Alert Level” below)
• Action (Refer to “Action Level” below)
Alert and Action Pre-Alarm settings are set with point programming. Unique Pre-Alarm sensitivity levels (PA) for individual
detectors are listed in Appendix B.4, “Detector Sensitivity Settings”, on page 93.
The LEDs on detectors polled in FlashScan mode will light steady green when in pre-alarm.
C.2 Presignal
Purpose
Presignal is a feature that initially causes alarm signals to only sound in specific areas, monitored by qualified persons. This allows delay of
the alarm up to 180 seconds after the start of alarm processing. The control panel Presignal feature provides two selections:
• A Presignal Delay Timer (1:00 to 3:00 minutes) that delays activation of all outputs with a CBE that includes Special Zone ZF0.
An illustration of Presignal timing.
Presignal Delay Timer (60-180 s)
PAS (15 s)
The control panel delays activation of outputs containing ZF0 in their zone maps for all alarm initiating devices that contain ZF0 in their
CBE list. A subsequent alarm will abort the Presignal Delay Timer and execute CBE lists.
Notes on using ZF0
• The Presignal Delay timer countdown can be stopped by pressing the SYSTEM RESET key before the timer expires.
• Program zone ZF0 to participating inputs and outputs.
Restrictions on using ZF0
• Do not include ZF0 in the CBE list for any monitor module that connects to a device other than an automatic fire detector.
C.3 Drill
What is Drill?
Drill is a feature that customizes drill activations, allowing only specific devices on the N16 to activate when a local or network Drill is per-
formed. Each output must be checked to participate in drill in VeriFire Tools. These devices require the drill zone (Special Function Zone 11)
to be added to the zone mapping of each point. ZF11 When the drill touchpoint is tapped or drill is performed, ZF11 will go active. ZF11 will
go to normal after a 5 second delay.
D.1 Zones
There are four types of zones that may be listed to a point for CBE purposes.
Zone Type Description/Function
General Zone A general zone is used to link input and output devices. When an input device activates, any general zone in its zone map will be
active and any output device that has an active general zone in its map will be active. General zones can be used as arguments
in logic equations.
Zone Z000 is a general alarm zone: those points listing Z000 in their zone map participate in a general alarm.
The panel will support up to 1000 general zones, designated as Z0 through Z999. General zones can be used in CCBE
applications when a node number is entered before the zone number.
Logic Zone A logic zone consists of a logic equation. Whenever the logic equation becomes true, all output points mapped to the logic zone
will activate.
The panel will support up to 1000 logic zones, designated as ZL1 through ZL1000. Logic zones can be used in CCBE
applications when a node number is entered before the zone number.
Trouble Zone A trouble zone consists of a trouble equation. Whenever the trouble equation becomes true, all output points mapped to the
trouble zone will activate.
The panel will support up to one hundred trouble zones, designated as ZT001 through ZT100. Trouble zones can be used in
CCBE applications when a node number is entered before the zone number.
NOTE: Trouble zones can be used only in CCBE applications between NFS2-3030, NFS-3030 and NFS-640 FACPs. Trouble zones will not
activate with other combinations.
Special Zone ZF0 An output participates in Presignal with this special zone in its zone map.
ZF1 (Trouble less AC) An output programmed to turn on/off if a system trouble - other than an AC power loss - occurs.
ZF2 (AC Trouble) An output programmed to turn on/off if an AC power loss or a brownout condition occurs.
ZF5 Alternate Sensitivity An input programmed to switch from the active detector alarm sensitivities to the alternate alarm
Activation sensitivities when a non-fire point with ZF5 in its CBE activates.
ZF6 Plant Isolate special zone for Australian Mode. When the Plant Isolate button is pressed, ZF6 will
toggle between Normal and Active.
ZF7 Drill for Australian Mode. In the event of a drill activation, ZF7 will activate and will remain active until
a reset is performed on the fire panel.
ZF10 Any detector or module in alarm verification will activate this zone.
ZF11 When the drill (alarm signal for Canadian applications) key is pushed or drill/alarm signal is
performed, ZF11 will go active. ZF11 will go to normal after a 5 second delay.
ZF12 When the acknowledge key is pushed, or a block or event acknowledge is performed, ZF12 will go
active. After a five-second delay, ZF12 will go to normal.
ZF13 When the signal silence key is pushed or a signal silence is performed, ZF13 will go active. After a
five-second delay, ZF13 will go to normal.
ZF14 When the system reset key is pushed or a system reset is performed, ZF14 will go active. After a ten-
second delay, ZF14 will go to normal.
ZF15 When there are disabled events present in the system, ZF15 will be set to active. When all disabled
events have cleared, the state of ZF15 will go to normal.
ZF16 Drill Zone (Alarm Signal Zone for Canadian applications). This zone used when Drill/Alarm Signal
Mode is set to Custom. When a drill/alarm signal is performed on the fire panel, ZF16 will be set to
active. ZF16 will return to normal following a system reset.
ZF17 Signal Silence for Australian Mode operations. When a signal silence is performed, ZF17 will go
active and will remain active until a System Reset is performed. The special zone will only function
when Australian Mode is enabled.
ZF20 When an mass notification alarm occurs on the fire panel, ZF20 will go active. If mass notification
events have priority over fire, network nodes MN mapped to the fire panel (via VeriFire Tools) will
suppress any active fire events. ZF20 will remain active until a system reset is performed and the MN
alarm is cleared
ZF21 When a mass notification supervisory event occurs, ZF21 will activate. ZF21 will remain active until
the MN Supervisory condition is cleared. If the supervisory is latched, a system reset will need to be
performed to clear the condition.
ZF22 When a mass notification trouble occurs on the fire panel, ZF22 will activate. ZF22 will remain active
until the MN trouble is cleared
ZF36 With DCC enabled: If the panel or an LCD-160 connected to the panel is in control of the network
(Control Active LED illuminated), ZF36 for the panel will activate. ZF36 will remain active until a
different node on the network is given control.
For Canadian Applications: If an LCD-160 is connected to the NFS2-3030 and DCC is enabled, local control
should be disabled.
ZF37 Automatic Alarm Signal Activation Timer. ZF37 will activate when the first (alert) stage of Two-Stage
notification has begun and will remain active until the duration of the first stage is complete (3 or 5
minute timer has expired) or canceled (signal silence or system reset performed).
ZF38 Second Stage. ZF38 will activate when the second stage (evacuation) of Two-Stage notification has
begun and will remain active until a signal silence or system reset is performed OR if a subsequent
fire alarm returns the panel to the First Stage.
ZF39* Automatic Alarm Signal Activation Canceled. ZF39 will activate when the first (alert) stage of the Two-
Stage notification has been canceled via an ACM series annunciator control point mapped to ZF39.
ZF39 will remain active till a signal silence or system reset is performed, a subsequent alarm restarts
the Two-Stage 3/Two-Stage 5 first (alert) stage timer, a drill/alarm signal is performed, or a device
programmed as an Evacuate Switch is activated.
ZF40 Auto Silence Activation. ZF40 will activate when the auto silence timer has expired and silenceable
outputs on the fire panel have been silenced as a result. ZF40 will remain active until a System Reset,
resound, or Drill (Alarm Signal for Canadian applications) is performed.
D.2 Equations
Logic and Trouble Equations can define complex relationships between input and output devices.
The FACP supports up to 1000 Logic Equations, each designated with a Logic Zone number of ZL1 through ZL1000. It also supports up to
100 Trouble Zones, each designated with a Trouble Zone number of ZT001 through ZT100. Once created, these equations can be included in
input/output zone mapping.
1. Equations will always begin with a logic function. The function set is listed below.
2. Equations will be a maximum of 80 characters long, including parentheses and commas.
3. Logic and Trouble Equations can have a maximum of 10 logic functions unless a time delay function is used: a time delay function must
be the only function in its equation.
4. Equations are evaluated after all other devices have been evaluated.
5. One logic equation can be used as an argument in another logic equation, or one trouble equation can be used in another trouble
equation, only if the equation used has previously been evaluated; that is, only zones with a lower number than the zone currently being
edited can be used as arguments.
6. A logic function can have a maximum of 20 arguments (inclusive start and stop address).
7. Maximum for the delay timer is 23 hours, 59 minutes, 59 seconds ([Link]).
8. CO Monitor devices: A device with the type ID of “CO Monitor” should not be used in logic equations. To include a CO Monitor in a
logic equation, use zones mapped to the CO Monitor in the equation.
Equations are entered using Point Programming for logic or trouble zones. Refer to these sections in this manual for instruction. The panel
will check for errors after the user has entered the complete equation. Possible errors are too many or too few parentheses, too many or too
few arguments inside the parentheses, unknown function and unknown device type.
Equations are made up of two basic components: functions (either logic or time delay) and arguments.
D.3 Arguments
Arguments are discrete parts of a logic or time delay function used in a logic or trouble equation. They can consist of another function,
another equation, or any of the devices listed below.
Example: XZONE(Z02)
If any combination of two or more initiating devices that have been mapped to this software zone come into alarm, then outputs mapped
to this zone will activate.
• The “RANGE” Operator
Each argument within the range must conform to the requirements of the governing function. The range limit is 20 consecutive
arguments.
Example: AND(RANGE(Z1,Z20))
Zone 1 through Zone 20 must all be active to activate the logic zone.
• The “DIS(point argument)” Operator
Requires that the point argument be disabled for the operator to go active.
• The “PRE(point argument)” Operator
Requires that the point argument be in prealarm for the operator to go active.
Example: AND(L1D1,PRE(L1D2))
The detector at address L1D1 must be active and the detector at L1D2 must be in prealarm for this equation to go active.
• The “SUP(point argument)” Operator
Requires that the point argument be in an active supervisory state for the operator to go active.
Example: OR(L1D1,SUP(L1M1))
The detector at address L1D1 must be active, or the module at L1M1 must be in an active supervisory state for the equation to go active.
• The “FIRE(point argument)” Operator
Requires that the point argument be in an active fire alarm state for the operator to go active.
Example: AND(L1D1,FIRE(L1M1),FIRE(L1M2))
The detector at address L1D1 must be active and the modules at L1M1 and L1M2 must be in an active fire alarm state for the equation
to go active.
• The “NON(point argument)” Operator
Requires that the point argument be in an active non-alarm state for the operator to go active.
Example: AND(L1D1,NON(L1M1))
The detector at address L1D1 must be active and the module at address L1M1 must be in an active non-fire alarm state for the equation
to go active.
• The “SEC(point argument)” Operator
Requires that the point argument be in an active security alarm state for the operator to go active.
Example: AND(L1M1,SEC(L1M2))
The module at address L1M1 must be active and the module at address L1M2 must be in an active security alarm state for the equation
to go active.
• The “AUTO(point argument)” Operator*
This operator will evaluate as “Active” if all of the SCS switches or specified switch group are in the “Auto” position. When the SCS-
8L/SCE-8L is disabled, the evaluation will be based on the switch position prior to the disable.
Examples:
The switch associated with switch group 16 on Annunciator 1 must be set as “Auto” for the equation to go active.
OR(AUTO(A1G16))
All the switches of Annunciator 1 must be set to “Auto” for the equation to go active.
OR(AUTO(A1))
• The “NORM(point argument)” Operator*
This operator will evaluate as “Active” if the entire SCS device or a specified switch group is in a normal state.
Examples:
Switch group 16 on Annunciator 1 must be in the “normal” (no trouble) state for the equation to go active.
OR(NORM(A1G16))
(All switches groups on) Annunciator 1 must be in the “normal” (no trouble) state for the equation to go active.
OR(NORM(A1)
• The “SCSDIS(point argument)” Operator*
For use with the SCS-8L only. This operator will evaluate as “Active” if the keyswitch on the specified SCS device is in the disabled
position.
Example:
If the keyswitch on annunciator 25 is disabled, this equation will go active.
OR(SCSDIS(A25))
* For use with local SCS applications
Time-based Functions
The panel supports three time-based functions: DEL, SDEL and TIM. Special rules apply to an equation containing a time-based function:
• Only one time-based function may be used in an equation.
• The time-based function must appear only once, as the first entry of the equation.
• It may not be nested within parentheses in the equation.
• Logic functions may be used in an equation that begins with a DEL or SDEL time-based function: however, they must appear within
parentheses following the time-based function.
Delay and duration times are in 24-hour format (HHMMSS); the allowable range is [Link] to [Link].
The “DEL” Function
Used for delayed operation.
Example: DEL([Link], [Link],AND(L1M1,L1M140))
• The first [Link] is the delay time, the second [Link] is the duration time. If the argument - AND(L1M1,L1M140) - in the
example above activates, the function becomes true after the argument has been active for the delay time and continues to be true for
the duration time as long as the argument stays active. If the argument goes inactive during the delay time or the duration time, the
function reverts to false and the timing would begin all over again if reactivated.
• If duration time of zero is entered (00.00.00), the equation will evaluate true when the delay time expires if the argument remains
active throughout the delay time period.
• If no duration or delay is specified, then the function will follow the input argument, indicating true while it is active and false when
it is inactive. DEL assumes a value of false on reset.
The “SDEL” Function
A latched version of the DEL function.
Example: SDEL([Link], [Link],L1M140)
• The first [Link] is the delay time, the second [Link] is the duration time. If the argument (L1M140 in the example above)
activates, the function becomes true after the delay time and will remain active for the duration even if the argument becomes
inactive during either the delay or duration time.
• If delay time of zero is entered (00.00.00), the equation will evaluate true as soon as the argument (L1M140) activates and will
remain that way for the specified duration, even if the argument becomes inactive during that time.
• If no duration or delay time is specified, then the argument will not deactivate until reset, even if the argument becomes inactive.
The “TIM” Operator
The TIM function is used to specify activation on specific days of the week or year.
Examples:
TIM(7-11-06) will evaluate as true for 24 hours starting at midnight ([Link]) on July 11, 2006.
TIM(MO,TU,WE,TH,FR,[Link],[Link]) will evaluate as true at 8:00 AM and remain true until 11:00 PM (23:00) for the list of
days supplied.
TIM(MO,TU,WE,TH,FR,[Link]) will evaluate as true at 8:00 AM and remain true until [Link] of the current day for the list of
days supplied.
TIM(TU,[Link],[Link]) will evaluate as true every Tuesday between 7:45 AM until 6:30 PM.
TIM(MO,TU,WE,TH,FR) will evaluate as true from Monday morning at 12:01 AM until Friday evening at [Link] PM.
Logic Equation Syntax Example
OR(AND(L1D1,L1D4),AND(L2D6,L2M3,NOT(L2M4)),ANYX(2,L1M13,L1M14,L1M15))
Equation begins with a logic function - OR
67 Characters (maximum of 80) - includes parentheses and commas.
5 Logic Functions (maximum of 10) - OR, AND, AND, NOT and ANYX.
8 Arguments (maximum of 20 per logic function) - L1D1,L1D4,L2D6,L2M3,L2M4…
The equation contains no spaces.
Evaluating an Equation
To evaluate an equation, start from the innermost part of the equation and work outwards. For this equation to evaluate TRUE and thus turn
on any output mapped to it, the following conditions must be met:
OR(AND(L1D1,L1D4),AND(L2D6,L2M3,NOT(L2M4)),ANYX(2,L1M13,L1M14,L1M15))
for this part to be TRUE for this part to be TRUE for this part to be TRUE
Then all outputs programmed with this equation will be turned ON.
NOTE: The control panel only performs detector initialization if it senses that a detector was removed for at least 15
seconds.
Step Action
5 In VeriFire Tools customize the label, zoning, etc for the new detector.
Latching
Activates
Type Code Point Type (Y=yes Device/Point Function
CBE
N=no)
SMOKE(PHOTO) fire Y Y Photoelectric smoke detector
†
SUP L(PHOTO) supervisory Y Y Photoelectric smoke detector
SUP T(PHOTO)† and ‡ supervisory N Y Photoelectric smoke detector
SMOKE(DUCTP) fire Y Y Duct Photoelectric smoke detector
SUP L(DUCTP) supervisory Y Y Photoelectric smoke detector used as a duct detector to report supervisory
condition rather than alarm
SUP T(DUCTP)‡ supervisory N Y Photoelectric smoke detector used as a duct detector to report supervisory
condition rather than alarm.
RFSMOKE(PHOTO) fire Y Y Wireless Photoelectric smoke detector
SMOKE(HARSH) fire Y Y HARSH smoke detector
SMOKE(LASER) fire Y Y Laser smoke detector
† ‡
SUP T (LASER) and supervisory N Y Laser Smoke Detector
SUP L (LASER)† supervisory Y Y Laser Smoke Detector
SMOKE(DUCTL) fire Y Y Duct Laser smoke detector
SUP L(DUCTL) supervisory Y Y Laser smoke detector used as a duct detector to report supervisory condition
rather than alarm.
SUP T(DUCTL)‡ supervisory N Y Laser smoke detector used as a duct detector to report supervisory condition
rather than alarm.
FIRE/CO fire Y Y Combination Photoelectric/CO detector
*
F/CO (P SUP) fire Y (See Note Y Combination Photoelectric/CO detector. Photo element activation generates a
below) supervisory condition.
F/CO (C SUP) fire Y (See Note Y Combination Photoelectric/CO detector. CO element activation generates a
below) supervisory condition.
Note: For Fire/CO detectors:
Detectors programmed as F/CO (P SUP), the Heat and CO elements will latch and require a system reset to clear. The Photo element will latch or track,
depending on the Fire/CO (Photo SUP) setting.
Detectors programmed as F/CO (C SUP), the Heat and Photo elements will latch and require a system reset to clear. The CO element will latch or track,
depending on the Fire/CO (CO SUP) setting.
PHOTO/CO Fire Y Y PHOTO CO detector.
P/CO (P SUP) PHOTO- Y (See note Y PHOTO CO detector
Supervisory below)
CO- Alarm
P/CO (C SUP) PHOTO- Fire Y Y PHOTO CO detector
CO-
Supervisory
CO Alarm CO Alarm Y Y CO detector
CO SUP Supervisory Y (See note Y CO detector
below)
Note: PHOTO/CO and CO Detectors programmed as PHOTO/CO (P SUP)/CO (CO SUP) will either latch or track, depending on the setting.
AIR REF fire Y Y Assign to one or more FSL-751detectors used to monitor the quality of air
entering the protected area. The air quality measurement allows the VIEW
system to compensate for vehicle fumes, fog, or other particles brought into the
protected area through the ventilation system. Poor air quality will lower the
sensitivity of all FSL-751 detectors on the SLC. The detector sensitivity, however,
remains within approved limits (always less than 1% obscuration per foot).
Note: A reference detector still functions as a smoke detector, but the detector sensitivity level should be set to the least sensitive level—AL:9 and PA:9
Alarm and Pre-Alarm sensitivity. Refer to Table B.2, “Detector Sensitivity Settings,” on page 94 for a complete list of detector sensitivity settings.
HEAT fire Y Y 190oF heat detector
HEAT+ fire Y Y 190oF heat detector with low temperature warning
HEAT(FIXED) fire Y Y 135oF intelligent thermal sensor
HEAT (ROR) fire Y Y 15oF per minute rate-of-rise detector
Latching
Activates
Type Code Point Type (Y=yes Device/Point Function
CBE
N=no)
SMOKE ACCLIM fire Y Y Combination Photoelectric/heat detector
SMOKE(ACCLI+) fire Y Y Combination Photoelectric/heat detector with low temperature warning, or
Intelliquad FSC-851 Photoelectric Multi-Criteria Smoke Sensor.
SMOKE(MULTI)‡ fire Y Y Multi-sensor smoke detector
SMOKE(BEAM) fire Y Y Beam Smoke Detector
ACCL(P SUP) fire Y (See note Y Combination Photoelectric/Heat detector. Photo element activation generates a
below) supervisory condition.
ACCL+(P SUP) fire Y (See note Y Combination Photoelectric/Heat detector with low temperature warning. Photo
below) element activation generates a supervisory condition.
Note: For ACCL/ACCL+ detectors:
Detectors programmed as ACCL (P SUP) or ACCL+(P SUP), the Heat element will latch and require a system reset to clear. The Photo element will
latch or track, depending on the ACCL (P SUP) Latching setting.
Point Characteristics
Type Code Point Type Latching Activates
Device Function
(Y=yes, N=no) CBE
MONITOR fire alarm Y Y Alarm-monitoring device
NC MONITOR fire alarm Y Y Alarm monitoring device, where an open circuit=active.
PULL STATION fire alarm Y Y Manual fire-alarm-activating device
SMOKE CONVEN fire alarm Y Y Indicates activation of a conventional smoke detector. An FZM-1 must be used
for alarm verification of a two-wire conventional detector.
SMOKE DETECT fire alarm Y Y Indicates activation of a conventional smoke detector. An FZM-1 must be used
for alarm verification of a two-wire conventional detector
WATERFLOW fire alarm Y Y Monitor for waterflow alarm switch
WATERFLOW S supervisory Y Y Indicates supervisory condition for activated waterflow switch
ACCESS MONTR non-alarm N Y Used for monitoring building access
security
AREA MONITOR security Y Y Monitors building access
AUDIO SYSTEM trouble N N Used for monitoring audio equipment (use trouble zones for activations)
EQUIP MONITR non-alarm N Y Used for monitoring equipment
security
SECURITY L security Y Y Indicates activation of security alarm
LATCH SUPERV supervisory Y Y Indicates latching supervisory condition
NC SUP L supervisory Y Y Indicates latching supervisory condition, where an open circuit=active.
TRACK SUPERV supervisory N Y Monitors for waterflow tamper switches for alarm points
NC SUP T supervisory N Y Indicates tracking supervisory condition, where an open circuit=active.
SPRINKLR SYS supervisory Y Y Monitors a waterflow device
SYS MONITOR security Y Y Monitors equipment security
TAMPER supervisory Y Y Indicates activation of tamper switch
ACK SWITCH non-alarm N N Performs Acknowledge function
ALLCALL PAGE non-alarm N Y Performs function AMG-1 All-call and telephone page
DRILL SWITCH non-alarm Y N Performs Drill function (Not for use in Canadian Applications)
Point Characteristics
Type Code Point Type Latching Activates
Device Function
(Y=yes, N=no) CBE
EVACUATE SWITCH non-alarm Y N Performs Drill function (Alarm Signal for Canadian applications), activates
silenceable fire outputs
FIRE CONTROL non-alarm N Y Monitors non-fire activations
NON FIRE non-alarm N Y Monitors non-fire activations
NC NON FIRE non-alarm N Y Monitors non-fire activations, where an open circuit =active.
POWER MONITR trouble N N Monitors main and auxiliary power supplies (use trouble zones for activations)
RESET SWITCH non-alarm N N Performs Reset function
SIL SWITCH non alarm N N Performs Signal Silence function
TELE PAGE non-alarm N Y Performs function of page button on FFT-7. Allows remote paging to a fire area
DISABLE MON disable N N When this point activates it will create a disable on the panel for that point. No
CBE generated. Modules cannot be disabled via ACS, Alter Status, or over the
network.
TROUBLE MON trouble N N Monitors trouble inputs (use trouble zones for activations)
Blank fire alarm Y Y Monitors for a device with no description
HEAT DETECT fire alarm Y Y Monitors for conventional heat detector
RF MON MODUL fire alarm Y Y Wireless alarm-monitoring device
RF PULL STA fire alarm Y Y Wireless manual fire-alarm-activating device
RF SUPERVSRY supervisory N Y Wireless supervisory-monitoring device
HAZARD ALRT non-fire N Y Monitors for a hazard alert
WEATHER ALRT non-fire N Y Monitors for a weather alert
PROCESS MON critical Y Y Monitors for a critical process
process
PROCESS AUTO critical N Y Monitors for a critical process
process
CO MONITOR CO alarm Y Y Monitors conventional CO detectors for a CO alarm condition.
RF GATEWAY non-alarm N Y Provides communication between wireless devices and the fire panel.
ALARM TRACK* alarm N Y This unit must be installed in accordance with the following requirements:
Monitor modules located with the protected premises which are responsible for
supervising the state of the protected premises control unit may be programmed
for Tracking (non-latching) operation. The supervised protected premises control
unit shall be responsible for all notification and evacuation.
Local
Switch
Silenceable Mode
Inhibit SLC Output
Type Code (Y=yes Group Device Function
(Y=yes, Point
N=no)* Point
N=No)*
Types
CONTROL† Y N NAC fire Supervised NAC
†
RELAY Y N Relay n/a Relay output
BELL CIRCUIT Y N NAC fire Supervised NAC
STROBE CKT† Y N NAC fire Supervised NAC
HORN CIRCUIT† Y N NAC fire Supervised NAC
AUDIBLE CKT Y N NAC fire Supervised NAC
SPEAKER Y N NAC fire Supervised NAC for speaker circuits
* Values represent program defaults Table G.3 SLC Control Module Type Codes (2 of 2)
† With LCM-320 revision 2.0 and higher, this Type Code has external power supervision (FlashScan only). An external power-supervision
relay is not required. Note that Type Codes RELAY, REL FORM C and FORM C RESET are for use only with FRM-1 modules. Refer to the
section on devices requiring external power supervision in this panel’s installation manual
‡ The FCM-1-REL checks for shorts with all releasing type codes.
I.1.1 Limitations
When in Network Display Mode:
1. Only the following network node types can be mapped to the N16:
• NFS2-3030 • DVC
• NFS2-640 • NCD
• NFS-320
•
2. Read Status, Control On/Off, Disable/Enable and Network Control-By-Event will only function for the nodes that are mapped to the
N16.
3. The number of display type nodes for the entire network is limited to a total of 25. Display nodes include NCA, NCA-2, a Gateway
node, or an N16 in Network Display Mode.
NOTE: Initiating an Acknowledge, System Reset, Signal Silence or Drill/AlarmSignal on a network node mapped to the
N16 may affect nodes that are not participating in Network Display Mode through Logic Zone Programming.
ACCL(P SUP) Combination Photoelectric/Heat Detector. Photo element activation generates a supervisory
condition.
ACCL+(P SUP) Combination Photoelectric/Heat Detector with low temperature warning. Photo element
activation generates a supervisory condition.
ACK SWITCH Monitor used to silence panel sounder and to give an acknowledge message on the panel
display
AIR REF FSL-751 detector used to monitor air quality entering a protected area
ALARMS PEND Control module or NAC for output that will activate upon receipt of an alarm condition and
remain in the alarm state until all alarms have been acknowledged. Programmed for switch
inhibit
ALLCALL PAGE Monitor used for emulation of AMG-1 All-call switch, activating all speaker circuits
ASPIR. (NON) For use with an aspiration detector, reports to the fire panel as a non-fire event when its
threshold is reached
ASPIR. (PRE) For use with an aspiration detector, reports to the fire panel as a prealarm condition when its
threshold is reached
ASPIR. (REF) For use with an aspiration detector, reports to the fire panel as a non-fire activation, used as a
reference for other aspiration detectors on the loop
ASPIR. (SUP) For use with an aspiration detector, reports to the fire panel as a supervisory when its threshold
is reached
ASPIRATION For use with an aspiration detector, reports to the fire panel as a fire alarm when threshold is
reached
CO MONITOR Monitor Module for use with conventional CO detectors. Activation will generate a CO Alarm on
the FACP.
DRILL SWITCH Monitor used for activation that emulates panel Drill switch, activating silenceable fire outputs
EVACUATE SWITCH Monitor used for activation that emulates panel Drill switch, activating silenceable fire outputs
FORM C RESET Control module used to interrupt 24V power to four-wire conventional detectors for 30 seconds
upon reset. Used in conjunction with a monitor module with a conventional detector Type ID
GEN ALARM Control module, XPC-8 circuit, or XP5-C (NAC mode) configured as a Municipal Box
Transmitter for NFPA 72 Auxiliary Fire Alarm Systems applications (MBT-1 required). This
Type ID can also be used for general alarm activation. It is programmed as “switch inhibit”.
GEN PEND Control module, XPC-8 circuit, or XP5-C (NAC mode) that will activate upon receipt of an alarm
and/or trouble condition and remain in the ON state until all events have been acknowledged
GEN SUPERVIS Control module, XPC-8, or XP5-C (NAC mode) activated under any supervisory condition
(includes sprinkler type). It is programmed as “switch inhibit”
GEN TROUBLE Control module, XPC-8, or XP5-C (NAC mode) activated under any System Trouble condition.
It is programmed as “switch inhibit”
HORN CIRCUIT Control module relay module used with NAC with horns
ISOLATED NAC Supervised NAC for notification appliance, used with audio isolators. Activates even if there is
a short on its NAC circuit. Canada installations only.
ISOLATED SPK Supervised NAC for speaker circuit, used with audio isolators. Activates even if there is a short
on its audio circuit. Canada installations only.
P/CO (C SUP) For use with a Photo/CO detector. If the CO element in the detector activates, a supervisory
condition is generated on the fire panel. An activation via the heat or photo element of the
Photo/CO detector will generate an alarm condition on the panel.
P/CO (P SUP)** For use with a Photo/CO detector. If the photo element in the detector activates, a supervisory
condition is generated on the fire panel. An activation via the CO or heat element of the
Photo/CO detector will generate an alarm condition on the panel.
PHOTO/CO For use with a Photo/CO detector. Activation of the CO, photo or heat elements will generate
an alarm condition on the fire panel.
REL. FORM C Form-C relay that directs outputs to perform a releasing function
SIL SWITCH Monitor used as Signal Silence switch, turning off all activated silenceable outputs
SUP L(DUCTP) Photoelectric smoke detector used as a duct detector to report supervisory condition rather
than alarm, latching
SUP T(DUCTP)*, ** Photoelectric smoke detector used as a duct detector to report supervisory condition rather
than alarm, tracking
TELE PAGE Monitor used to emulate the page button on an FFT-7, allowing remote paging to a fire area
TRACKING SUPERV Monitor for waterflow tamper switches for alarm points
CHG-120 [ ] X 2.00 =
[ ] X [ ] =
Sum Column for AC Branch Current Required =
Table K.1 AC Branch Circuit Requirements
[Link]