1
> Titre de la prsentation - Date - Rfrences
intertripping DIP 5000
Commercial presentation
> Titre de la prsentation - Date - Rfrences
Introduction
Introduction
> Titre de la prsentation - Date - Rfrences
intertripping Function
Intertripping is designed to transfer protection commands originating, in most cases, from distance protection relay contacts to ONE remote location through a communication medium. Communication between the intertripping equipment is a bidirectional point-to-point communication
Poste lectrique A Ligne HT
Poste lectrique B
Digital Telecom network Intertripping DIP 5000
And / or direct fiber optic link
Intertripping DIP 5000
Protection relay
Monitoring system TMS 5000
4 > Titre de la prsentation - Date - Rfrences
Protection relay
intertripping Function
Functioning in voice frequency mode on Power line carrier
Line Trap H.V. TRANSPORT NETWORK
Services Services
Line matching unit LMU5000
Power line Carrier PLC5000
Control command or SCADA
Intertripping DIP 5000
Management software for PLC 5000 and DIP 5000
5
> Titre de la prsentation - Date - Rfrences
intertripping Criteria
The 3 main characteristics of intertripping are :
Transfer time : During a fault, damage incurred to HV equipment will depend on the fault clearance time.
The transfer time of the intertripping equipment, (the time between the acquisition of a protection signal to its restitution at the other end), must therefore be as short as possible to minimize the fault clearance time.
Reliability/Dependability : Since the communication can be altered by noise due to the high voltage environment, the intertripping signal shall be transmitted in a way to minimize the risk of losing a command that would lead to the non functioning of the fault clearance process. This value is expressed as the Probability of Missing command Pmc.
> Titre de la prsentation - Date - Rfrences
intertripping Criteria
The 3 main characteristics of a intertripping are (continued ):
Security : Since intertripping is often used to protect strategic lines on which a shutdown would have heavy consequences, the intertripping has to ensure that a command that can disconnect an HV line is a TRUE command and not due to noise coming from the HV environment. This value is expressed as the probability of unwanted command Puc for the worst-case being with the highest noise .
All intertripping equipment shall meet as a minimum, the security, dependability and transfer time criteria defined by an IEC standard IEC 60834-1
> Titre de la prsentation - Date - Rfrences
DIP5000 Requirements
Digital TP What we are expecting From
> Titre de la prsentation - Date - Rfrences
What we are waiting for from Digital intertripping
To Increase the safety of the electrical network
Faster transfer time Increase reliability and security Increase monitoring capabilities Increase the number of commands
To reduce cost ownership
Easier and faster commissioning Preserve the investment
- A faster return on Invest 9 > Titre de la prsentation - Date - Rfrences 9
DIP5000 Characteristics and Advantages
How DIP5000 fit these requirements
10
> Titre de la prsentation - Date - Rfrences
10
DIP 5000 DIGITAL intertripping
DIP 5000 is Improving transfer time and is Increasing reliability and security
Built to operate for at least 25 years without maintenance Added security with possibility of duplicated power supply
Faster transfer time : The fault clearance process is reduced saving expensive HV equipment.
Protection Mode Tra nsfer Time With E1 Interfa ce 4 or 8 comma nds 1 ms 1 ms 1.5 ms Relia bility (Pmc) Security (Puc) Worst ca se
Blocking Permissive Direct Tripping
1E- 30 1E- 35 1E- 19
< 2E- 7 6E- 14 1E- 20
- Increase the safety of your electrical network 11 > Titre de la prsentation - Date - Rfrences 11
DIP 5000 DIGITAL intertripping
Characteristics with digital communication interface
- Increase the safety of your electrical newtork 12 > Titre de la prsentation - Date - Rfrences 12
DIP 5000 DIGITAL intertripping
Characteristics with voice frequency interface
13
> Titre de la prsentation - Date - Rfrences
13
DIP 5000 DIGITAL intertripping
DIP 5000 is increasing monitoring capabilities
Continuous self testing of the equipment and continuous monitoring of the communication channel with REAL TIME BER and Transfer Time monitoring Event and alarm recording
Possibility to select alarms in case of too high transmission time or high BER or Programmable alarms contacts on lengthy command 512 events 1 ms stamping allowing fault analysis and tracking
- Increase the safety of your electrical network 14 > Titre de la prsentation - Date - Rfrences 14
DIP 5000 DIGITAL intertripping
DIP 5000 is Easy to Install and to do commissioning
Configuration on line, off line, downloaded on site to the local and remote DIP5000 with PC ( digital interface only )
User friendly Man Machine Interface Under Windows NT or Later
- To reduce cost ownership 15 > Titre de la prsentation - Date - Rfrences 15
DIP 5000 DIGITAL intertripping
DIP 5000 is adapated to all kind of communication
All interfaces available to suit your needs:
Two Types of BUILT IN Single mode Optical Fiber
Medium Range Laser 1310 nm e.g 60 km with fiber 9/25m - 0.25 dB/km Long range Laser 1550 nm e.g 110 km with fiber 9/25m - 0.25 dB/km
Electrical interfacesj
V11/RS422 G703.1 (64 Kbit/s) G703.6 (E1 2 Mbit/s) Analogue interface for pilot wires or communication
with Power line carrier
- To reduce cost ownership 16 > Titre de la prsentation - Date - Rfrences 16
DIP 5000 DIGITAL intertripping
DIP 5000 is also available for voice frequency communication
Voice frequency interface for communication on pilot wires or leased line or communication with Power line carrier (PLC ) ( 4 wires interface ) . Up to 4 independant commands No requirement for extra bandwitdh when used with PLC ( silent mode )
17
> Titre de la prsentation - Date - Rfrences
17
DIP 5000 DIGITAL INTERTRIPPING
Optical / electrical converter OCM 5000 developed by AREVA for
use in harsh substation environment in compliance with IEC standard
You can use electrical converter OCM 5000 optical to electrical converter to fit with your substation constraints
50km
50km
50km
- To reduce cost ownership 18 > Titre de la prsentation - Date - Rfrences 18
DIP 5000 DIGITAL intertripping
DIP 5000 is Easy to install and to commission
Protection room Telecom room
V11 G703 64 kbit/s G703 Mbit/s Up to 8 Commands
DIP5000
OCM5000 V11 Or V24
You can use OCM5000 converter to fit your installation constraints
Direct optical fibre connection
Up to 8 Commands DIP5000
Up to 4 Commands
V11 G703 64 kbit/s G703 2Mbit/s Or optical I
Analogue 4 wires
- To reduce cost ownership 19 > Titre de la prsentation - Date - Rfrences 19
DIP 5000 DIGITAL intertripping
DIP 5000 is Easy to Install and to commission
Programmable alarms contacts on lengthy command
Customer is able to qualify its link with 1. Test mode with trip transfer 2. loop back function
- To reduce cost ownership 20 > Titre de la prsentation - Date - Rfrences 20
DIP 5000 DIGITAL intertripping
DIP 5000 is preserving your investment Plug-in easy access boards inside the DIP 5000 reducing repair time
You can easily modify your interfaces or upgrade from copper to optical interface
- To reduce cost ownership 21 > Titre de la prsentation - Date - Rfrences 21
DIP5000 Architecture
Technical data
22
> Titre de la prsentation - Date - Rfrences
22
DIP5000 Technical data
Input / Output logic combination capacity Firmware Up gradable on site by simple download 24 to 250 VDC power supply with power supply duplication as an option Up to 8 independent fast solid state relay output + 1 copy contact for each output : Rating Max 2A, cut off power 120 W
- intertripping DIP 5000 23 > Titre de la prsentation - Date - Rfrences 23
DIP5000 Technical data
Type tested as per IEC 60834-1 by Bureau Veritas / LCIE Laboratory
Compliance with latest IEC standart : IEC 68-2
EMC compliance as per IEC 61000
Conforms to European Directives
EN 50204 EN 55011 EN 55022
Class A Class A Class A
Equipment is CE compliant.
- DIP 5000 Type tested 24 > Titre de la prsentation - Date - Rfrences 24
DIP5000 Architecture
New features
25
> Titre de la prsentation - Date - Rfrences
25
DIP5000 Remote supervision
Access IP / LAN et network management
Possibility
to connect the AREVA TMS 5000 monitoring software to monitor a DIP 5000 network alarm status on a real time basis
Intranet network
DIP 5000 Real time monitoring
26 > Titre de la prsentation - Date - Rfrences 26
DIP5000 Back up Optical / digital interface
Capacity to switch communication from the optical interface to an other digital interface according to user defined criteria
Alternate
path V11 or G703
Main path
27
> Titre de la prsentation - Date - Rfrences
27
DIP5000 References
References
28
> Titre de la prsentation - Date - Rfrences
28
DIP 5000 REFERENCES
MORE THAN 1500 UNITS IN OPERATION SINCE Year 2000 IN OPERATION IN MORE THAN 15 COUNTRIES FOR UP TO 500 KV NO RECORD OF FALSE OR UNWANTED COMMAND DUE TO THE EQUIPMENT
- A RELIABLE PRODUCT IN USE IN MORE THAN 15 COUNTRIES 29 > Titre de la prsentation - Date - Rfrences 29
DIP5000 Conclusion
Conclusion
30
> Titre de la prsentation - Date - Rfrences
30
Conclusion
DIP 5000 is the best way to
Increase the safety of the electrical network
Fastest transfer time Highest level of reliability and security Enhanced monitoring capabilities Built in optical interface Up to 8 independent commands TESTED as per latest IEC and ANSI EMC requirement
Reduce your entry cost and your cost ownership
Intuitive commissioning Powerful HMI Plug in board for easy hardware upgrade
- The Reference in terms of intertripping equipment 31 > Titre de la prsentation - Date - Rfrences 31