Comprehensive Water Treatment Guide

This document summarizes the water treatment processes at a plant, including: - Raw water is sourced from three wells and stored in a reservoir before being treated with multi-grade filters and cartridge filters to prepare it for the reverse osmosis plant. - The double-stage reverse osmosis plant has a production capacity of 45 cubic meters per hour. The permeate then undergoes degasification and demi plant processes. - Problems at the reverse osmosis plant include biological fouling, scaling, iron fouling, and high silt density index. Solutions involve biocides, acid cleaning, and silica sand filtration. - Boiler water, steam, and cooling

Uploaded by

Talha Sheikh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
309 views14 pages

Comprehensive Water Treatment Guide

This document summarizes the water treatment processes at a plant, including: - Raw water is sourced from three wells and stored in a reservoir before being treated with multi-grade filters and cartridge filters to prepare it for the reverse osmosis plant. - The double-stage reverse osmosis plant has a production capacity of 45 cubic meters per hour. The permeate then undergoes degasification and demi plant processes. - Problems at the reverse osmosis plant include biological fouling, scaling, iron fouling, and high silt density index. Solutions involve biocides, acid cleaning, and silica sand filtration. - Boiler water, steam, and cooling

Uploaded by

Talha Sheikh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
  • Water Treatment Plant
  • Boiler Water Chemistry

Water treatment Plant

• Introduction
• Problem s & Solutions

RO Plant
Introduction To WTP

 Raw water source


 Raw water reservoir
 RO Pre-treatment system
 RO plant
 DM plant
 Three well water turbines located at APL site with pumping
capacity of 155 cubic meter each.
 Raw water reservoir consist of two cells and have overall
capacity of 9500 cubic meter.
 RO treatment consists of multi grade filter and Cartridge
filters which removes TSS from feed water and prepare for
RO plant.
 SDI ( plugging factor) of RO plant must be <3 in RO feed
water .
RO plant & Demineralization Plant

 RO plant is double stage and single pass have production


capacity of 45 Cubic meter/Hr permeate.
 Permeate water passes through degasser which removes
dissolved CO2 and then water goes for Demineralization
plant.
 Demineralization system consists of two Mixed Bed Ion
exchange polishers have production capacity of 38 cubic
meter/Hr.
Problems & Solutions at RO plant
Problems Solutions
 Biological Fouling  Proper Biocide during operation
 Scaling and deposition and non operation period.
 Iron fouling  To remove scaling and deposition,
 Silt Density Index
Online acid injected and also
periodic chemical cleaning done as
per requirement.
 To prevent from iron fouling and
high TSS, we are using Suji sand
(Silica Sand) in MGF which is very
effective in removal of Iron ,
Biological growth and TSS by
mechanical filtration.
Boiler water Chemistry
 Purpose of Boiler Water Treatment
 To remove hardness producing salts by blow down as non-adherent
sludge.
 To inhibit the corrosion & scaling in the system.
 To maintain the magnetite layer in the system.
 To remove oxygen by (Chemical De-Aeration)dosing oxygen scavenger.
 To maintain PH in the system.
Chemical Treatment
 Nalco Eliminox ( Oxygen scavenger)
 Tri Sodium Phosphate
 Nalco Tri-Act 2813 ( Neutralizing Amine)
Boiler Water Requirements as per OEM (DESCON Engineering)
Parameter Limits/Unit Required Values Actual Values

pH - 9.0-10.0 9.6

Conductivity µs/cm ˂150 50

Silica ppm ˂4.0 ˂1.0

Phosphate ppm 4-6 5

Iron ppm As per CF 0.02

Copper ppm As per CF 0.003

Total Alkalinity ppm ppm 14

Chlorides ppm ppm 1.0


Steam Quality as per Standard
Parameter Limits/Unit Required Values Actual Values

Conductivity µs/cm ˂0.2 0.2

Silica ˂0.02 ˂0.02 0.014

Total Iron ˂0.02 ˂0.02 0.01

Total Copper ˂0.003 ˂0.003 0.001

Sodium ˂0.01 ˂0.01 ND


Cooling Tower Treatment
Cooling Water Treatment Window

PARAMETER CONTROL RANGE


pH 7.9-8.1
Conductivity < 4700 us/cm
Calcium Hardness < 470 ppm
Mg Hardness < 310 ppm
Silica as SiO2 < 85 ppm
M-Alkalinity < 250 ppm
Ortho-Phosphate 6 –8 ppm
Cooling water Total Iron < 3 ppm
T-Zn 0.5-2.0 ppm
Mild Steel - Corrosion Rate < 3 Mpy
Free-Chlorine 0.2-0.4 ppm
Total Bacterial Counts < 10^4 CFU/ml
COC 3 (season and off season)
Problem & solutions in C/T
Problems Solutions
 High amount of blow down  Improved feed water filtration
 Higher-quality side-stream
filtration
 Increased cycle of concentration
 Maintaining better makeup
water chemistry by removing
scale forming and corrosion
causing impurities.
 Change or closely manage the
cooling tower feed chemistry
program.
Problems Solutions
 Low cycle of concentration  Maintain better makeup water
chemistry to achieve over five
 Scale formation
COC.
 pH/alkalinity control to
minimize scale formation.
 Decrease feed hardness, iron
and silica.

 Biological Growth
 Manage microbial growth by
dosing Sodium Hypo Chlorite
Cooling Tower Corrosion Graph
Thanks for participation

Hafiz Muhammad Ilyas Mian


Chief plant Chemist [Link] IPP, USM, JDW-II.