Water treatment Plant
• Introduction
• Problem s & Solutions
RO Plant
Introduction To WTP
Raw water source
Raw water reservoir
RO Pre-treatment system
RO plant
DM plant
Three well water turbines located at APL site with pumping
capacity of 155 cubic meter each.
Raw water reservoir consist of two cells and have overall
capacity of 9500 cubic meter.
RO treatment consists of multi grade filter and Cartridge
filters which removes TSS from feed water and prepare for
RO plant.
SDI ( plugging factor) of RO plant must be <3 in RO feed
water .
RO plant & Demineralization Plant
RO plant is double stage and single pass have production
capacity of 45 Cubic meter/Hr permeate.
Permeate water passes through degasser which removes
dissolved CO2 and then water goes for Demineralization
plant.
Demineralization system consists of two Mixed Bed Ion
exchange polishers have production capacity of 38 cubic
meter/Hr.
Problems & Solutions at RO plant
Problems Solutions
Biological Fouling Proper Biocide during operation
Scaling and deposition and non operation period.
Iron fouling To remove scaling and deposition,
Silt Density Index
Online acid injected and also
periodic chemical cleaning done as
per requirement.
To prevent from iron fouling and
high TSS, we are using Suji sand
(Silica Sand) in MGF which is very
effective in removal of Iron ,
Biological growth and TSS by
mechanical filtration.
Boiler water Chemistry
Purpose of Boiler Water Treatment
To remove hardness producing salts by blow down as non-adherent
sludge.
To inhibit the corrosion & scaling in the system.
To maintain the magnetite layer in the system.
To remove oxygen by (Chemical De-Aeration)dosing oxygen scavenger.
To maintain PH in the system.
Chemical Treatment
Nalco Eliminox ( Oxygen scavenger)
Tri Sodium Phosphate
Nalco Tri-Act 2813 ( Neutralizing Amine)
Boiler Water Requirements as per OEM (DESCON Engineering)
Parameter Limits/Unit Required Values Actual Values
pH - 9.0-10.0 9.6
Conductivity µs/cm ˂150 50
Silica ppm ˂4.0 ˂1.0
Phosphate ppm 4-6 5
Iron ppm As per CF 0.02
Copper ppm As per CF 0.003
Total Alkalinity ppm ppm 14
Chlorides ppm ppm 1.0
Steam Quality as per Standard
Parameter Limits/Unit Required Values Actual Values
Conductivity µs/cm ˂0.2 0.2
Silica ˂0.02 ˂0.02 0.014
Total Iron ˂0.02 ˂0.02 0.01
Total Copper ˂0.003 ˂0.003 0.001
Sodium ˂0.01 ˂0.01 ND
Cooling Tower Treatment
Cooling Water Treatment Window
PARAMETER CONTROL RANGE
pH 7.9-8.1
Conductivity < 4700 us/cm
Calcium Hardness < 470 ppm
Mg Hardness < 310 ppm
Silica as SiO2 < 85 ppm
M-Alkalinity < 250 ppm
Ortho-Phosphate 6 –8 ppm
Cooling water Total Iron < 3 ppm
T-Zn 0.5-2.0 ppm
Mild Steel - Corrosion Rate < 3 Mpy
Free-Chlorine 0.2-0.4 ppm
Total Bacterial Counts < 10^4 CFU/ml
COC 3 (season and off season)
Problem & solutions in C/T
Problems Solutions
High amount of blow down Improved feed water filtration
Higher-quality side-stream
filtration
Increased cycle of concentration
Maintaining better makeup
water chemistry by removing
scale forming and corrosion
causing impurities.
Change or closely manage the
cooling tower feed chemistry
program.
Problems Solutions
Low cycle of concentration Maintain better makeup water
chemistry to achieve over five
Scale formation
COC.
pH/alkalinity control to
minimize scale formation.
Decrease feed hardness, iron
and silica.
Biological Growth
Manage microbial growth by
dosing Sodium Hypo Chlorite
Cooling Tower Corrosion Graph
Thanks for participation
Hafiz Muhammad Ilyas Mian
Chief plant Chemist [Link] IPP, USM, JDW-II.