Application Note: Universal Relay General Electric T60 Differential Relay 87 Module

This document provides instructions for using TDMS software to test a General Electric T60 differential relay 87 module. It describes how to set up a network model in TDMS to simulate faults, including power transformer vector groups, earthing transformers, and CT connections. It then guides the user through compensating for phase and zero sequence, setting the trip characteristic, performing automatic fault verification, and testing the harmonic restraint characteristic.

Uploaded by

CARLOS LÓPEZ
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
657 views5 pages

Application Note: Universal Relay General Electric T60 Differential Relay 87 Module

This document provides instructions for using TDMS software to test a General Electric T60 differential relay 87 module. It describes how to set up a network model in TDMS to simulate faults, including power transformer vector groups, earthing transformers, and CT connections. It then guides the user through compensating for phase and zero sequence, setting the trip characteristic, performing automatic fault verification, and testing the harmonic restraint characteristic.

Uploaded by

CARLOS LÓPEZ
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
  • Overview of Differential Relay 87 Module: Introduces the Differential Relay 87 Module with TDMS software, outlining primary uses for power transformer tests and safe simulation environments.
  • Setting Up the Power Transformer Vector Group: Guides through step-by-step process to set up the power transformer vector group using TDMS software, focusing on initial configurations.
  • Internal Compensation Adjustments: Describes steps to input internal phase and sequence compensation details for selecting the necessary delta connected CT group.
  • Trip Characteristic Setup: Explains how to set up the trip characteristic by copying relay parameters and performing fault phase and current evaluations.
  • Harmonic Restraint Test: Discusses performing harmonic restraint characteristic tests across harmonics of fundamental frequency to verify operational integrity.
  • Bibliography: Lists bibliographic references for ISA manuals and user guides related to the application note's context.

Application Note

Universal Relay General Electric T60


Differential Relay 87 module
TDMS software

Differential Relay 87 Module


with TDMS software and DRTS 66
A completely new way of testing for
transformer differential protections
is now possible. In few steps the user
can easily set up a complete network
model for the best fault simulation:
. Power Transformer vector group
. Earthing transformers
. Current Transformers connections
(wye, delta)
. YDY Interposing transformers for a
proper phase and zero-sequence
compensation.

TDMS
Application Note
Universal Relay General Electric T60
Differential Relay 87 module
TDMS software
This application note will guide you step by step to perform tests on
Differential Relay, using TDMS software.

Set the Power Transformer vector group, the nominal primary and
secondary voltage and the rated power.

The magnitude compensation


factor must be calculated
according to the GE T60
formulas

Phase and zero sequence can be compensated internally by the


relay or externally with a proper CTs connection, in this example the
compensation is internal:

For General Electric relays the reference


winding for the phase shift compensation
is the first delta, in this case the reference
winding is the primary.
TDMS
Application Note
Universal Relay General Electric T60
Differential Relay 87 module
TDMS software
In case of external compensation, the user must disable the internal
Phase and Zero Sequence compensation and select the proper delta
connected CT group.

The number inside the relay picture


represents the phase shift between
the primary and secondary currents,
it is zero when the phase shift is well
compensated.

TDMS
Application Note
Universal Relay General Electric T60
Differential Relay 87 module
TDMS software
The trip characteristic can be set by copying directly the relay
parameters, the special GE T60 curve will be plotted automatically.

Decide the fault side and the


faulty phase and perform an
automatic verify of the trip
characteristic. The results are
stored in the results table and they are
displayed graphically for a quick and
easy analysis.

TDMS
Application Note
Universal Relay General Electric T60
Differential Relay 87 module
TDMS software
Possibility to perform Harmonic Restraint characteristic test from the
second to the seventh harmonic of the fundamental frequency.

Bibliography
ISA - TDMS user manual - MSE 10015
ISA - DIFF 87 user manual - MSE 20029
ISA - DRTS 66 user manual rev. 1.33 - MIE 10170
General Electric - GE Multilin - T60 Transformer Protection System - UR Series instruction manual