Bungalow House Load Schedule & Calculations

The document contains calculations for the electrical load and circuit requirements for 6 circuits in a home. It lists the load description, voltage, watts, amps, recommended wire size, and circuit breaker size for each circuit. Circuit 1 is for lighting outlets and requires 2mm^2 wire and a 20A breaker. Circuit 2 is for convenience outlets, requires 3.5mm^2 wire and a 20A breaker. Circuit 3 is for an air conditioner and requires 2mm^2 wire and a 20A breaker. The largest load is a water heater on Circuit 4, which requires 5.5mm^2 wire and a 25A breaker.

Uploaded by

Kenneth
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
53 views1 page

Bungalow House Load Schedule & Calculations

The document contains calculations for the electrical load and circuit requirements for 6 circuits in a home. It lists the load description, voltage, watts, amps, recommended wire size, and circuit breaker size for each circuit. Circuit 1 is for lighting outlets and requires 2mm^2 wire and a 20A breaker. Circuit 2 is for convenience outlets, requires 3.5mm^2 wire and a 20A breaker. Circuit 3 is for an air conditioner and requires 2mm^2 wire and a 20A breaker. The largest load is a water heater on Circuit 4, which requires 5.5mm^2 wire and a 25A breaker.

Uploaded by

Kenneth
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

COMPUTATIONS

CIRCUIT 1
I=800VA/230V =3.48A
use2-2mm2 THW wire
CB=20AT

CIRCUIT 2
I=1800VA/230V =7.83A SCHEDULE OF LOADS
use 2-3.5mm2
CB=20AT ckt # LOAD DESCRIPTION VOLT WATTS AMPHERE SIZE OF WIRE SIZE OF CB
1 LIGTHING OUTLET(8) 230 800 3.48 2-2 [Link] THW 20
CIRCUIT 3 2 CONVINIENCE OUTLET(10) 230 1800 7.83 2-2 [Link] THW 20
I=(1119VA/230V)1.125 =5.47A
use 2-2mm2 THHN Wire
3 ACU 230 1119 5.47 2-2 [Link] THHN 20
CB=20AT 4 WATER HEATER 230 4500 19.57 2-5.5 [Link] THHN 20
5 WATER PUMP 230 746 3.24 2-2 [Link] THW 20
CIRCUIT 4 6 WASHING MACHINE 230 1500 6.52 2-3.5 [Link] THHN 20
I=4500VA/230V =19.57A
use 2-5.5mm2 THHN WIRE TOTAL 10465 46.11
CB=25AT

CIRCUIT 5
I=746VA/230V =3.24A
use 2-2mm2 THW
CB=20AT

CIRCUIT 6
I=1500VA/230V =5.52A
use 2-3.5mm2 THHN WIRE
CB=20AT

SCHOOL: DESIGNED BY: CHECKED BY: PROJECT TITLE: SHEET CONTENT: SHEET NO.

KENNETH B. BELMONTE
SCHEDULE OF LOADS, 3
ISABELA STATE UNIVERSITY [Link] HUSAY
CITY OF ILAGAN CAMPUS BSEE - 5 INSTRUCTOR BUNGALOW HOUSE
COMPUTATION OF
LOADS
3