Forward @ fn+1 =fn +(i‐13,6)*16 12,7<i<14,5 ma (f0 = 25 Hz) Start Stand‐by 12,7<i<14,5 ma Remote
LSLLs ON LSLs ON ‐> OFF LSHs OFF LSHHs ON‐>OFF LSLLs ON LSLs ON LSHs OFF LSHHs OFF
LSLLd ON LSLd OFF‐>ON LSHd OFF‐>ON LSHHd OFF LSLLd ON LSLd ON LSHd OFF LSHHd OFF
Transition from “STOP
due to Anomaly” to
“Stand‐by” by
removing anomalies
and by restoring stand‐
by conditions
LSHHs OFF‐> ON LSHd OFF‐> ON
Local
Reverse @ 10 Hz 12,7<i<14,5 ma Forward @ 10 Hz 12,7<i<14,5 ma
LSLLs ON LSLs ON LSHs ON LSHHs OFF‐>ON STOP due to Anomaly LSLLs ON LSLs ON LSHs ON LSHHs OFF
LSLLd ON LSLd OFF LSHd OFF LSHHd OFF LSLLd ON LSLd OFF LSHd OFF LSHHd OFF‐>ON
Remote
LSHs OFF‐> ON LSHHd OFF‐> ON
Transition to “STOP due to Anomaly” Reverse @ fn+1 =fn +(i‐13,6)*16 12,7<i<14,5 ma
from every phase, inclusive “Local” if LSLLs ON LSLs OFF ‐> ON LSHs OFF‐> ON LSHHs OFF
• STOP command LSLLd ON LSLd ON‐>OFF LSHd OFF LSHHd ON ‐> OFF
• VFD/motor anomaly
• i exceeds limits 12,7 < i < 14,5 ma Local 12,7<i<14,5 ma Local commands are enabled
• f exceeds limits 9 < f < 61 Hz LSLLs ON LSLs ANY LSHs ANY LSHHs OFF
• Any input unduly changes State diagram of the VFD Logic LSLLd ON LSLd ANY LSHd ANY LSHHd OFF
• Any input expected to change Functional cycle in blue
doesn’t within time‐out (f) (TBD)