Load Flow Report for ETAP Analysis

This load flow report summarizes the results of a power flow analysis of an electrical network with 11 buses. It shows the voltage, generation, load, and other power flow details for each bus. The network has one voltage regulated bus supplying power to the other buses through transformers. The power flows were within acceptable limits with no major voltage or current violations found.

Uploaded by

muhammad iqbal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
58 views2 pages

Load Flow Report for ETAP Analysis

This load flow report summarizes the results of a power flow analysis of an electrical network with 11 buses. It shows the voltage, generation, load, and other power flow details for each bus. The network has one voltage regulated bus supplying power to the other buses through transformers. The power flows were within acceptable limits with no major voltage or current violations found.

Uploaded by

muhammad iqbal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd

ETAP

Project: Page: 1
Location: 12.6.0H Date: 07-21-2020
Contract: SN:

Engineer: Study Case: LF


Filename: TA FIXXX Config.: Normal

LOAD FLOW REPORT

Bus Voltage Generation Load Load Flow

ID kV
% Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF

* Bus1 150.000 100.000 0.0 21.981 20.558 0 0 Bus3

Bus2 20.000 91.672 -5.6 0 0 0 0 Bus4 3.108

Bus5 3.915 2.960 154.6 79.8

Bus6 2.833 2.206 113.1 78.9

Bus3 -9.856 -7.530 390.6 79.5

Bus3 20.000 91.672 -5.6 0 0 0 0 Bus7 2.614

Bus8 3.222 2.428 127.0 79.9

Bus9 1.755 1.335 69.4 79.6

Bus10 1.268 0.966 50.2 79.5

Bus11 3.182 2.518 127.8 78.4

Bus1 -21.897 -16.785 868.8 79.4

Bus2 9.856 7.530 390.6 79.5

Bus4 20.000 87.379 -6.0 0 0 2.978 2.233 Bus2 -2.978

Bus5 20.000 89.239 -5.8 0 0 3.822 2.867 Bus2 -3.822

Bus6 20.000 80.334 -6.6 0 0 2.517 1.888 Bus2 -2.517

Bus7 20.000 84.601 -6.3 0 0 2.433 1.825 Bus3 -2.433

Bus8 20.000 90.270 -5.7 0 0 3.178 2.383 Bus3 -3.178

Bus9 20.000 87.474 -6.0 0 0 1.683 1.263 Bus3 -1.683

Bus10 20.000 86.922 -6.0 0 0 1.209 0.907 Bus3 -1.209

Bus11 20.000 75.347 -7.1 0 0 2.668 2.001 Bus3 -2.668

Indicates a voltage regulated bus (voltage controlled or swing type machine connected to it)
*
# Indicates a bus with a load mismatch of more than 0.1 MVA
Revision: Base

XFMR

%Tap

21.981 20.558 115.8 73.0

2.364 123.0 79.6

2.007 103.8 79.3

-2.233 123.0 80.0

-2.867 154.6 80.0

-1.888 113.1 80.0

-1.825 103.8 80.0

-2.383 127.0 80.0

-1.263 69.4 80.0

-0.907 50.2 80.0

-2.001 127.8 80.0