ETAP
Project: Page: 1
Location: 12.6.0H Date: 07-21-2020
Contract: SN:
Engineer: Study Case: LF
Filename: TA FIXXX Config.: Normal
LOAD FLOW REPORT
Bus Voltage Generation Load Load Flow
ID kV
% Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF
* Bus1 150.000 100.000 0.0 21.981 20.558 0 0 Bus3
Bus2 20.000 91.672 -5.6 0 0 0 0 Bus4 3.108
Bus5 3.915 2.960 154.6 79.8
Bus6 2.833 2.206 113.1 78.9
Bus3 -9.856 -7.530 390.6 79.5
Bus3 20.000 91.672 -5.6 0 0 0 0 Bus7 2.614
Bus8 3.222 2.428 127.0 79.9
Bus9 1.755 1.335 69.4 79.6
Bus10 1.268 0.966 50.2 79.5
Bus11 3.182 2.518 127.8 78.4
Bus1 -21.897 -16.785 868.8 79.4
Bus2 9.856 7.530 390.6 79.5
Bus4 20.000 87.379 -6.0 0 0 2.978 2.233 Bus2 -2.978
Bus5 20.000 89.239 -5.8 0 0 3.822 2.867 Bus2 -3.822
Bus6 20.000 80.334 -6.6 0 0 2.517 1.888 Bus2 -2.517
Bus7 20.000 84.601 -6.3 0 0 2.433 1.825 Bus3 -2.433
Bus8 20.000 90.270 -5.7 0 0 3.178 2.383 Bus3 -3.178
Bus9 20.000 87.474 -6.0 0 0 1.683 1.263 Bus3 -1.683
Bus10 20.000 86.922 -6.0 0 0 1.209 0.907 Bus3 -1.209
Bus11 20.000 75.347 -7.1 0 0 2.668 2.001 Bus3 -2.668
Indicates a voltage regulated bus (voltage controlled or swing type machine connected to it)
*
# Indicates a bus with a load mismatch of more than 0.1 MVA
Revision: Base
XFMR
%Tap
21.981 20.558 115.8 73.0
2.364 123.0 79.6
2.007 103.8 79.3
-2.233 123.0 80.0
-2.867 154.6 80.0
-1.888 113.1 80.0
-1.825 103.8 80.0
-2.383 127.0 80.0
-1.263 69.4 80.0
-0.907 50.2 80.0
-2.001 127.8 80.0