Siemens Interface Module GH - CM1542-5 - 76 PDF
Siemens Interface Module GH - CM1542-5 - 76 PDF
Preface
___________________
Guide to the documentation 1
___________________
Product overview 2
SIMATIC NET
___________________
Functional characteristics 3
S7-1500 - PROFIBUS
CM 1542-5 ___________________ 4
Requirements for use
___________________
Connecting up /
commissioning 5
Manual
Interrupts, diagnostics
messages, error and system 6
alarms
___________________
Technical specifications 7
___________________
Approvals 8
11/2014
C79000-G8976-C290-02
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
Conventions
Make sure you read the special notices below:
Note
A notice contains important information on the product described in the documentation,
handling the product or about parts of the documentation you should pay particular attention
to.
Names
● In this document, the term "CM" is also used instead of the full product name.
● The name STEP 7 is used to mean the STEP 7 Professional configuration tool.
License conditions
Note
Open source software
Read the license conditions for open source software carefully before using the product.
You will find license conditions in the following documents on the supplied data medium:
● DOC_OSS-S7CMCP_74.pdf
● DOC_OSS-CM1542-5_76.pdf
CM 1542-5
Manual, 11/2014, C79000-G8976-C290-02 3
Preface
Security information
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, solutions, machines, equipment and/or networks. They are
important components in a holistic industrial security concept. With this in mind, Siemens’
products and solutions undergo continuous development. Siemens recommends strongly
that you regularly check for product updates.
For the secure operation of Siemens products and solutions, it is necessary to take suitable
preventive action (e.g. cell protection concept) and integrate each component into a holistic,
state-of-the-art industrial security concept. Third-party products that may be in use should
also be considered. For more information about industrial security, visit
http://www.siemens.com/industrialsecurity.
To stay informed about product updates as they occur, sign up for a product-specific
newsletter. For more information, visit http://support.automation.siemens.com.
Trademarks
The following and possibly other names not identified by the registered trademark sign ® are
registered trademarks of Siemens AG:
SIMATIC NET, CM 1542-5
CM 1542-5
4 Manual, 11/2014, C79000-G8976-C290-02
Table of contents
Preface ................................................................................................................................................... 3
1 Guide to the documentation .................................................................................................................... 7
2 Product overview .................................................................................................................................... 9
2.1 Properties .................................................................................................................................. 9
2.2 Further functions .....................................................................................................................11
3 Functional characteristics ...................................................................................................................... 13
3.1 Transmission speeds supported .............................................................................................13
3.2 Characteristic data of the DP interface ...................................................................................13
3.3 Characteristics of S7 communication .....................................................................................14
4 Requirements for use ............................................................................................................................ 15
4.1 Configuration limits .................................................................................................................15
4.2 Project engineering .................................................................................................................15
4.3 Programming ..........................................................................................................................15
5 Connecting up / commissioning ............................................................................................................. 17
5.1 Important notes on using the device .......................................................................................17
5.2 Installing and commissioning the CM 1542-5 .........................................................................19
5.3 Replacing a module without a programming device ...............................................................21
5.4 Mode of the CPU - effect on the CM.......................................................................................22
6 Interrupts, diagnostics messages, error and system alarms ................................................................... 23
6.1 Status and error display of the CM .........................................................................................23
6.2 Diagnostics options .................................................................................................................25
6.3 DP slave diagnostics...............................................................................................................25
6.4 Standard diagnostics ..............................................................................................................27
6.5 Device-specific diagnostics in DP-V1 .....................................................................................29
6.6 DP diagnostics frames when the CPU is in STOP .................................................................32
7 Technical specifications ........................................................................................................................ 33
8 Approvals.............................................................................................................................................. 35
Index..................................................................................................................................................... 39
CM 1542-5
Manual, 11/2014, C79000-G8976-C290-02 5
Table of contents
CM 1542-5
6 Manual, 11/2014, C79000-G8976-C290-02
Guide to the documentation 1
Introduction
The documentation of the SIMATIC products has a modular structure and covers topics
relating to your automation system.
The complete documentation for the S7-1500 system consists of a system manual, function
manuals and device manuals.
The STEP 7 information system (online help) also supports you in configuring and
programming your automation system.
CM 1542-5
Manual, 11/2014, C79000-G8976-C290-02 7
Guide to the documentation
SIMATIC manuals
All current manuals for SIMATIC products are available for download free of charge from the
Internet (http://www.siemens.com/automation/service&support).
CM 1542-5
8 Manual, 11/2014, C79000-G8976-C290-02
Product overview 2
2.1 Properties
① LEDs
② Type plate
③ PROFIBUS interface: 1 x 9-pin D-sub female connector (RS-485)
Figure 2-1 View of the CM 1542-5 with closed (left) and open (right) front cover
CM 1542-5
Manual, 11/2014, C79000-G8976-C290-02 9
Product overview
2.1 Properties
Application
The communications module CM 1542-5 is intended for operation in an S7-1500 automation
system. The CM 1542-5 allows the connection of an S7-1500 station to a PROFIBUS
fieldbus system.
Note
DP master or DP slave
Please note, however: The CM 1542-5 only supports operation either as DP master or
DP slave.
● S7 communication
– PG communication for uploading / downloading of S7 configuration, diagnostics and
routing
– Operator control and monitoring functions (HMI communication)
– Data exchange over S7 connections
● Data record routing / field device parameter assignment
You can use the CM as a router for data records intended for field devices (DP slaves).
Data records from devices that are not connected directly to PROFIBUS and therefore
have no direct access to the DP slaves are forwarded to the DP slaves by the CM.
The services of the CM 1542-5 listed above can be used independently at the same time.
CM 1542-5
10 Manual, 11/2014, C79000-G8976-C290-02
Product overview
2.2 Further functions
Diagnostics requests
As a DP master (class 1), the CM 1542-5 supports diagnostics requests of a DP master
(class 2).
Note
Recommendation for setting the time
It is advisable to set the time-of-day master so that time-of-day frames are sent at intervals of
approximately 10 seconds. This achieves as small a deviation as possible between the
internal time and the absolute time.
Web diagnostics
With the aid of Web diagnostics of the CPU, you read the diagnostics data from an S7
station via the Web browser on the PG/PC.
In terms of the CM, the Web pages provide the following information:
● Module and status information
● Special information on the DP master system (status of the DP slaves)
CM 1542-5
Manual, 11/2014, C79000-G8976-C290-02 11
Product overview
2.2 Further functions
CM 1542-5
12 Manual, 11/2014, C79000-G8976-C290-02
Functional characteristics 3
Note
Measured values of transfer or reaction times
Measurements of transfer and reaction times in Ethernet, PROFIBUS and PROFINET
networks for a series of configurations can be found on the Internet
(http://support.automation.siemens.com/WW/view/en/25209605)
Note
Remember the cable length
The permitted cable length must be kept to depending on the transmission speed.
CM 1542-5
Manual, 11/2014, C79000-G8976-C290-02 13
Functional characteristics
3.3 Characteristics of S7 communication
Diagnostics requests
As a DP master (class 1), the CM 1542-5 supports diagnostics requests of a DP master
(class 2).
DP startup behavior
Note
Increasing the default value for startup parameters - configuration of the CPU
In some situations, it is necessary to increase the default value for the startup parameter
"Parameter assignment time for the distributed I/O" in the configuration of the CPU:
• When there is a large number of modules (DP slaves) configured that can be assigned
parameters.
• When a high value is configured for the constant bus cycle time in the network properties
of the PROFIBUS DP line.
Note
PG or HMI functions or data record routing
If PG or HMI functions or data record routing are used, a suitable number of S7 connections
must be reserved during configuration!
CM 1542-5
14 Manual, 11/2014, C79000-G8976-C290-02
Requirements for use 4
4.1 Configuration limits
When using the CM type described here, the following limits apply:
● The number of CMs that can be operated in a rack depends on the CPU type being used.
Note the information in the documentation of the CPU, see Guide to the documentation
(Page 7)
4.3 Programming
Program blocks
For communications services, there are preprogrammed program blocks (instructions)
available as the interface in your STEP 7 user program.
CM 1542-5
Manual, 11/2014, C79000-G8976-C290-02 15
Requirements for use
4.3 Programming
Refer to the documentation of the program blocks in the online help of STEP 7
See also
8797900 (http://support.automation.siemens.com/WW/view/en/8797900)
CM 1542-5
16 Manual, 11/2014, C79000-G8976-C290-02
Connecting up / commissioning 5
5.1 Important notes on using the device
General notices
WARNING
Safety extra low voltage
The equipment is designed for operation with Safety Extra-Low Voltage (SELV) by a
Limited Power Source (LPS). (This does not apply to 100 V...240 V devices.)
This means that only SELV / LPS complying with IEC 60950-1 / EN 60950-1 / VDE 0805-1
must be connected to the power supply terminals. The power supply unit for the equipment
power supply must comply with NEC Class 2, as described by the National Electrical Code
(r) (ANSI / NFPA 70).
There is an additional requirement if devices are operated with a redundant power supply:
If the equipment is connected to a redundant power supply (two separate power supplies),
both must meet these requirements.
WARNING
Risk of explosion when connecting or disconnecting the device
EXPLOSION HAZARD
DO NOT CONNECT OR DISCONNECT EQUIPMENT WHEN A FLAMMABLE OR
COMBUSTIBLE ATMOSPHERE IS PRESENT.
CM 1542-5
Manual, 11/2014, C79000-G8976-C290-02 17
Connecting up / commissioning
5.1 Important notes on using the device
WARNING
Replacing components
EXPLOSION HAZARD
SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION
2 OR ZONE 2.
WARNING
Requirements for the cabinet/enclosure
When used in hazardous environments corresponding to Class I, Division 2 or Class I,
Zone 2, the device must be installed in a cabinet or a suitable enclosure.
WARNING
Restricted area of application
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or non-
hazardous locations only.
WARNING
Restricted area of application
This equipment is suitable for use in Class I, Zone 2, Group IIC or non-hazardous locations
only.
WARNING
LAN attachment
A LAN or LAN segment with the attachments belonging to it should be within a single low-
voltage supply system and within a single building. Make sure that the LAN is in an of type
A environment according to IEEE 802.3 or in a type 0 environment according to IEC TR
62101.
Never establish a direct electrical connection to TNV networks (telephone network) or
WANs (Wide Area Network).
WARNING
Requirements for the cabinet/enclosure
To comply with EU Directive 94/9 (ATEX95), this enclosure must meet the requirements of
at least IP54 in compliance with EN 60529.
CM 1542-5
18 Manual, 11/2014, C79000-G8976-C290-02
Connecting up / commissioning
5.2 Installing and commissioning the CM 1542-5
WARNING
Suitable cables for temperatures in excess of 70 °C
If the cable or conduit entry point exceeds 70°C or the branching point of conductors
exceeds 80°C, special precautions must be taken. If the device is operated at ambient
temperatures above 50°C, the permitted temperature range of the selected cable must be
suitable for the temperatures actually measured.
WARNING
Protection against transient voltage surges
Provisions shall be made to prevent the rated voltage from being exceeded by transient
voltage surges of more than 40%. This criterion is fulfilled, if supplies are derived from
SELV (Safety Extra-Low Voltage) only.
WARNING
Read the system manual "S7-1500 Automation System"
Prior to installation, connecting up and commissioning, read the relevant sections in the
system manual "S7-1500 Automation System" (references to documentation, refer to the
section Guide to the documentation (Page 7)).
Make sure that the power supply is turned off when installing/uninstalling the devices.
Configuration
One requirement for the commissioning of the CP is the completeness of the STEP 7 project
data.
CM 1542-5
Manual, 11/2014, C79000-G8976-C290-02 19
Connecting up / commissioning
5.2 Installing and commissioning the CM 1542-5
CM 1542-5
20 Manual, 11/2014, C79000-G8976-C290-02
Connecting up / commissioning
5.3 Replacing a module without a programming device
PROFIBUS interface
The table below shows the terminal assignment of the PROFIBUS interface. The assignment
corresponds to the standard assignment of RS485 interface.
Note
PROFIBUS interface
The CM provides no 24 VDC power supply on the PROFIBUS interface. I/O devices (for
example, PC adapter 6ES7972-0CB20-0XA0) are therefore not operational on the interface).
General procedure
The configuration data of the CM is stored on the CPU. This means that this module can be
replaced by a module of the same type (identical article number) without using a PG.
CM 1542-5
Manual, 11/2014, C79000-G8976-C290-02 21
Connecting up / commissioning
5.4 Mode of the CPU - effect on the CM
CM 1542-5
22 Manual, 11/2014, C79000-G8976-C290-02
Interrupts, diagnostics messages, error and
system alarms 6
The status and error displays of the CM 1542-5 are described below.
You can find additional information on "Interrupts" in the STEP 7 online help.
You can find additional information on "Diagnostics" and "System alarms" in the System
diagnostics (http://support.automation.siemens.com/WW/view/en/59192926) function
manual.
LED display
The following figure shows the LEDs of the CM 1542-5.
① RUN/STOP LED
② ERROR LED
③ MAINT LED
CM 1542-5
Manual, 11/2014, C79000-G8976-C290-02 23
Interrupts, diagnostics messages, error and system alarms
6.1 Status and error display of the CM
The following table shows the meaning of the various combinations of colors of the
RUN/STOP, ERROR and MAINT LEDs.
CM 1542-5
24 Manual, 11/2014, C79000-G8976-C290-02
Interrupts, diagnostics messages, error and system alarms
6.2 Diagnostics options
Diagnostics options
You have the following diagnostics options available for the module:
● The LEDs of the module
For information on the LED displays, refer to the section Status and error display of the
CM (Page 23).
● STEP 7: The "Diagnostics" tab in the Inspector window
Here, you can obtain the following information on the selected module:
– Entries in the diagnostics buffer of the CPU
– Information on the online status of the module
● STEP 7: Diagnostics functions in the "Online > Online and diagnostics" menu
Here, you can obtain static information on the selected module:
– General information on the module
– Diagnostics status
– Information on the PROFIBUS interface
You can obtain further information on the diagnostics functions of STEP 7 in the STEP 7
online help.
● DP diagnostics
The DP diagnostics of the CM is described below.
The evaluation of diagnostics data records requested by the DP master and the
diagnostics interrupts or diagnostics alarms of the DP slaves is handled in the user
program of the DP master station.
CM 1542-5
Manual, 11/2014, C79000-G8976-C290-02 25
Interrupts, diagnostics messages, error and system alarms
6.3 DP slave diagnostics
Standard diagnostics
Byte Meaning
0 Station status 1
1 Station status 2
2 Station status 3
3 Master address
4...5 Vendor ID of the slave
Device-specific diagnostics
Byte Meaning
0 Header
1 Variant Variant
Interrupt type Status type
2 Slot number
3 Variant Variant
Interrupt specifier Status specifier
4...62 Module-specific diagnostics data
CM 1542-5
26 Manual, 11/2014, C79000-G8976-C290-02
Interrupts, diagnostics messages, error and system alarms
6.4 Standard diagnostics
CM 1542-5
Manual, 11/2014, C79000-G8976-C290-02 27
Interrupts, diagnostics messages, error and system alarms
6.4 Standard diagnostics
CM 1542-5
28 Manual, 11/2014, C79000-G8976-C290-02
Interrupts, diagnostics messages, error and system alarms
6.5 Device-specific diagnostics in DP-V1
Byte 0: Header
The two most significant bits have the value 00. This identifies the "module-specific
diagnostics data" field (see bytes 4... 62) as a whole.
The remaining six bits indicate the length of the data field including byte 0.
If status interrupts are received in quick succession, older status interrupts may be
overwritten by newer interrupts.
CM 1542-5
Manual, 11/2014, C79000-G8976-C290-02 29
Interrupts, diagnostics messages, error and system alarms
6.5 Device-specific diagnostics in DP-V1
CM 1542-5
30 Manual, 11/2014, C79000-G8976-C290-02
Interrupts, diagnostics messages, error and system alarms
6.5 Device-specific diagnostics in DP-V1
Bytes 4...62: Module-specific diagnostics with "status type" and "module status"
With the variant "status type" of the device-specific diagnostics of DP-V1 slaves (see byte 1,
bit 7) and the setting "Modul_Status" (see byte 1, bits 0...6), there are two status bits here for
each slot (= module). Bits not required are set to 0.
Value Meaning
00 Data valid
01 Data invalid - error (for example short-circuit)
10 Data invalid - wrong module
11 Data invalid - no module plugged in
CM 1542-5
Manual, 11/2014, C79000-G8976-C290-02 31
Interrupts, diagnostics messages, error and system alarms
6.6 DP diagnostics frames when the CPU is in STOP
CM 1542-5
32 Manual, 11/2014, C79000-G8976-C290-02
Technical specifications 7
Note the information in the System description of SIMATIC S7-1500 (Page 7).
In addition to the information in the system description, the following technical specifications
apply to the module.
6GK7 542-5DX00-0XE0
Product type name CM 1542-5
Connection to PROFIBUS
• Number 1 x PROFIBUS interface
Electrical data
Power supply
• via S7-1500 backplane bus 15 V
Current consumption
• From backplane bus 200 mA
• Power dissipation 3W
Insulation
Insulation tested with 707 VDC (type test)
Product functions *
* You will find the product functions in the section Functional characteristics (Page 13).
CM 1542-5
Manual, 11/2014, C79000-G8976-C290-02 33
Technical specifications
CM 1542-5
34 Manual, 11/2014, C79000-G8976-C290-02
Approvals 8
Approvals issued
Note
Issued approvals on the type plate of the device
The specified approvals - with the exception of the certificates for shipbuilding - have only
been obtained when there is a corresponding mark on the product. You can check which of
the following approvals have been granted for your product by the markings on the type
plate. The approvals for shipbuilding are an exception to this.
IEC 61131–2
The SIMATIC NET S7 CPs described in this manual fulfill the requirements and criteria of
the IEC 61131-2 standard (Programmable Logic Controllers, Part 2: equipment requirements
and verifications).
CM 1542-5
Manual, 11/2014, C79000-G8976-C290-02 35
Approvals
CE mark
The SIMATIC NET S7-CPs described in this manual fulfill the requirements and protection
goals of the following EC directives and meet the harmonized European standards (EN) that
have been published for the programmable logic controllers in the official journals of the
European communities:
● 2004/108/EEC "Electromagnetic Compatibility" (EMC Directive)
● 94/9/EC "Equipment and protective systems intended for use in potentially explosive
atmospheres" (Explosion Protection Directive)
The EC Declarations of Conformity are available for the responsible authorities according to
the above-mentioned EC Directive at the following address:
● Siemens Aktiengesellschaft
Industry Automation
Industrielle Kommunikation SIMATIC NET
Postfach 4848
D-90327 Nürnberg
You will find the EC Declaration of Conformity at the following address / under the following
entry ID on the Internet (http://support.automation.siemens.com/WW/view/en/16689636)
EMC directive
The SIMATIC NET S7 CPs listed above are designed for use in an industrial environment.
Note
When using (installing) SIMATIC NET products in hazardous area zone 2, make absolutely
sure that the associated conditions are adhered to!
You will find these conditions here:
• In the SIMATIC NET Manual Collection under
"All Documents" > "Use of subassemblies/modules in a Zone 2 Hazardous Area"
CM 1542-5
36 Manual, 11/2014, C79000-G8976-C290-02
Approvals
AVIS CANADIEN
Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
Note
You will recognize the approval, UL/CSA or cULus, assigned to your product from the mark
on the rating plate.
UL approval
UL Recognition Mark Underwriters Laboratories (UL) nach Standard UL 508:
● Report E 85972
CSA approval
CSA Certification Mark Canadian Standard Association (CSA) nach Standard C 22.2 No.
142:
● Certification Record 063533–C-000
CM 1542-5
Manual, 11/2014, C79000-G8976-C290-02 37
Approvals
You will find the temperature class on the type plate on the module.
WARNING
Explosion Hazard -
Do not disconnect while circuit is live unless area is known to be non hazardous.
Explosion Hazard -
Substitution of components may impair suitability for Class I, Division 2.
Note
This equipment is suitable for use in Class I, Division 2, Group A, B, C, D or non-hazardous
locations only.
Note
For devices with C-PLUG memory: The C-PLUG memory module may only be inserted or
removed when the power is off.
Note
This plant has to be mounted according to the NEC (National Electrical Code) stipulations.
When used in environments according to class I, division 2 (see above) , the SIMATIC NET
S7 CPs must be mounted in an enclosure.
FM approval
Factory Mutual Approval Standard Class Number 3611,
Class I, Division 2, Group A, B, C, D, T3...T6 or
Class I, Zone 2, Group IIC, T3...T6.
You will find the temperature class on the type plate on the module.
WARNING
Personal injury and damage to property may occur.
In hazardous areas, personal injury or property damage can result if you create or break an
electrical circuit during operation of a SIMATIC NET S7 CP (for example, by means of plug-
in connections, fuses, switches).
WARNING - EXPLOSION HAZARD: DO NOT DISCONNECT EQUIPMENT WHEN A
FLAMMABLE OR COMBUSTIBLE ATMOSPHERE IS PRESENT.
When used in hazardous locations (division 2 or zone 2), the device must be installed in an
enclosure.
CM 1542-5
38 Manual, 11/2014, C79000-G8976-C290-02
Index
DP mode
General characteristic data, 13
A DP slave, 10, 11
Operation as, 10
ATEX, 18
DP slave mode, 22
DP slaves
General characteristic data, 13
B
Bus topology, 11
E
EMC - electromagnetic compatibility, 36
C
Error status codes, 23
Cabinet, 18
Cable length, 13
Cables for temperatures in excess of 70 °C, 19 F
Calling program blocks (instructions) for distributed
field device parameter assignment, 10
I/O, 16
FM
CE mark, 36
Approval, 38
Changeover
CPU from RUN to STOP, 22
CPU from STOP to RUN, 22
G
Characteristic data, 13, 14
Configuration data Glossary, 4
Configuration and downloading, 15
CSA
Approval, 37 H
C-Tick
Hazardous area, 17
Approval, 37
Hazardous areas according to ATEX, 18
HMI functions, 14
D
Data record routing, 10, 14 I
Diagnostics, 23
IEC 61131-2, 35
Diagnostics options, 25
Installation and commissioning, 20
Diagnostics repeater (DP slave), 11
Instruction
Diagnostics requests, 11, 14, 14
ALARM, 16
Direct data exchange, 10
D_ACT_DP, 16
Downloading project data, 20
DE_ACT, 11
Downloads, 8
DP_TOPOL, 15
DP diagnostics, 25
DPNRM_DG, 15
DP diagnostics frames when the CPU is in STOP, 32
DPRD_DAT, 16
DP master
DPSYC_FR, 15
Operation as, 10
DPWR_DAT, 16
DP master (class 1), 10, 11
GETIO, 15
DP master mode, 22
GETIO_PART, 16, 16
DP masters (class 2), 11
RALARM, 16
RALRM, 16
CM 1542-5
Manual, 11/2014, C79000-G8976-C290-02 39
Index
M T
Manual Collection, 8
Time master, 11
Measured values
Time slave, 11
of values of transfer or reaction times, 13
Time-of-day synchronization, 11, 22
Module replacement, 21
Transmission speed, 13
N U
Number of operable CMs, 15
UL
Approval, 37
O
Operating mode of the CPU, 22 V
Version history, 8
P
PG functions, 14 W
PG/OP communication, 10
Web diagnostics, 11
PROFIBUS
S7 connections, 11
DP-V0 and DPV1 standard, 10
PROFIBUS DP
EN 50170 DPV1, 10
PROFIBUS interface, 21
Program blocks, 16
Protection against transient voltage surges, 19
R
Replacing components, 18
RS-485 interface, 21
RS-485 socket, 20
S
S7 communication, 10
S7 connections, 10, 14
General characteristic data, 14
S7 routing function, 22
CM 1542-5
40 Manual, 11/2014, C79000-G8976-C290-02