INSPECTION & TESTING REQUIREMENTS REVISION: 01/29/2011 CODE NUMBER: PAGE:
SAUDI ARAMCO FORM-175 REPLACES: 06/15/2007 IR173400 1 of 2
SCOPE: UNINTERRUPTIBLE POWER SUPPLY (UPS) SYSTEMS: 10 kVA or Larger Rated Capacity.
TEST AND INSPECTION PER: 17-SAMSS-516, and Specifications As Noted Below.
(1) VISUAL INSPECTION WITNESSING BY INSPECTOR (Note 1)
(2) CERTIFICATES / RECORDS TO BE CHECKED BY INSPECTOR
(3) CERTIFICATES / DATA TO BE PROVIDED BY VENDOR / SUPPLIER / MANUFACTURER
0010
0010
*** X
Pre-Fabrication/Production Requirements
Type test
Specification Details / Notes:
The test is to be conducted on each model on a one time basis
and must comply with performance specification table in
17-SAMSS-516.
0020 *** In process inspection & test requirement Specification Details / Notes:
0030
0010
*** X
Final inspection & test requirements
Printed Circuit Cards: Corrosion Protection Coating
Specification Details / Notes:
0020 Workmanship, Components and Dimensions:
0030 X a) Power Semiconductor Circuits All circuits shall be fused. Indicating lamps or an alphanumeric
message shall be provided to indicate blown fuses.
0040 X b) Rectifier / Charger, Inverter, Static Switch, Maintenance By Per 17-SAMSS-516.Section 6.7
pass switch
0080 X X c) Input, Output, and Bypass Transformers Transformers test certificates shall be provided and shall be in
accordance with ANSI / NEMA ST-20 or IEC 60076 see
SAMSS for details.
0090 X d) Protective Devices, alarm, displays, controls ,wiring cables Per 17-SAMSS-516. Section 6.7
and Devices
0140 X e) Enclosure Cabinets Shall be NEMA 250 Type 1 or IEC 60529 IP 21.
0150 X f) Grounding Shall be as per requirement of NFPA 70 "Chapter: Wiring and
Protection, Section: Grounding" or IEC 62040-1-2
0160 Factory Testing:
0170 X X a) Burn-in test The UPS system shall sustain full rated load (burn-in test) for at
least continuous 8 hours. Provide test certificate and report
during FAT
0180 X X b) Demonstration of the integrity of the output waveforms during
all operation modes.
0190 X X c) Factory acceptance test. Shall be conducted to demonstrate performance and
functionality per specifications.
IR173400 Continued...
INSPECTION & TESTING REQUIREMENTS REVISION: 01/29/2011 CODE NUMBER: PAGE:
SAUDI ARAMCO FORM-175 REPLACES: 06/15/2007 IR173400 2 of 2
(1) VISUAL INSPECTION WITNESSING BY INSPECTOR (Note 1)
(2) CERTIFICATES / RECORDS TO BE CHECKED BY INSPECTOR
(3) CERTIFICATES / DATA TO BE PROVIDED BY VENDOR / SUPPLIER / MANUFACTURER
0200 X X Nameplate Markings and Legends Per 17-SAMSS-516. Section 6.7.16
Notes:
(1) May only be waived by the responsible Saudi Aramco, ASC, or AOC Inspection Offices.
(2) See form SA175 - 000003 (page 2 of 2) for instructions on using this form.
End of IR173400