Electrical Audit & Safety Report

Rabi Enterprise conducted an electrical audit of Dhakeswari Bastralaya. They tested the connected load, electrical installations, and earthing at the property. For the connected load, they found the total load was not properly connected phase-wise on each floor. Electrical installations tests showed readings of 100Megh between each phase and neutral. Earth testing results showed the ground earthing and lightning arrester were in good working order and within specification. Rabi concluded the electrical wiring, earthing, and equipment were in safe condition for use.

Uploaded by

Prithish Das
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
27 views2 pages

Electrical Audit & Safety Report

Rabi Enterprise conducted an electrical audit of Dhakeswari Bastralaya. They tested the connected load, electrical installations, and earthing at the property. For the connected load, they found the total load was not properly connected phase-wise on each floor. Electrical installations tests showed readings of 100Megh between each phase and neutral. Earth testing results showed the ground earthing and lightning arrester were in good working order and within specification. Rabi concluded the electrical wiring, earthing, and equipment were in safe condition for use.

Uploaded by

Prithish Das
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

RABI ENTERPRISE

ALL KIND FIRE & SAFETY INSTALLATION & ELECTRICAL WORKS


GOVT. LICENCE HOLDER
PALTA, P.O. - BENGAL ENAMEL, NORTH 24 PGS.
CONTACT : 9007328684
E-mail : rabisankarduttapalta@[Link]
GST : 19BMNPD6903M1ZL

Ref. Date .......................20


To,
DHAKESWARI BASTRALAYA,
40/1, R. N. TAGORE ROAD,
KRISHNANAGAR, NADIA, PIN- 741101.
KRISHNANAGAR,40/1, R. N. TAGORE ROAD, KRISHNANAGAR, NADIA. PIN- 741101.
DHHAKEGGDGAKESWARI BDHAKESWARI BASTRALAYAASTRALAYA

ELECTRICAL AUDIT REPORT


SUBJECT: Testing of Transformer, H.T. , L.T. Panel and Lighting Load; Testing and Assessment of all
Electrical equipment's, wiring, earthing at ground floor and Lightning Arrester Installation at
above
address.

Dear Sir,

As advised we have tested and checked the electrical installation on 04/05/2022. The report is as
under:

 FLOOR-WISE CONNECTED LOAD -


- GROUND FLOOR :
Red Phase : 10 Amps
Yellow Phase : 15 Amps
Blue Phase : 38 Amps
(Total Load not properly connected phase-wise)
Resistivity : < 0.7 Ω
- FIRST FLOOR :
Red Phase : 22 Amps
Yellow Phase : 18 Amps
Blue Phase : 48 Amps
(Total Load not properly connected phase-wise)
Resistivity : < 0.85 Ω
- SECOND FLOOR :
Red Phase : 15 Amps
Yellow Phase : 11 Amps
Blue Phase : 7.5 Amps
(Total Load not properly connected phase-wise because of some obstruction)
Resistivity : < 0.7 Ω

 ELECTRICAL INSTALLATION TESTING REPORT -


At Main between : Phase I & Neutral=100Megh
Phase II & Neutral=100Megh
Phase III & Neutral=100Megh
Conted........
RABI ENTERPRISE
ALL KIND FIRE & SAFETY INSTALLATION & ELECTRICAL WORKS
GOVT. LICENCE HOLDER
PALTA, P.O. - BENGAL ENAMEL, NORTH 24 PGS.
CONTACT : 9007328684
E-mail : rabisankarduttapalta@[Link]
GST : 19BMNPD6903M1ZL

Ref. Date .......................20


EARTHING FITNESS CERTIFICATE FOR WHOLE BUILDING

SUB: TESTING & CHECKING YOUR GROUND EARHTING & LIGHTNING ARRESTER

Dear Sir,

As your order on us we have tested and checked the Ground Earthing & Lightning Arrester on
09/11/2021.

The Reports are as under:

Testing result for Lightning Arrester :

Between Lighting Arrester I & Ground Earth II 0.2 Ohms


Between Lighting Arrester II & Ground Earth I 0.2 Ohms

Specification of Lightning earthing :

Electrode: 40mm dia X 3.2 Mtrs long perforated galvanized pipe electrode 2nos.
Connection: 40mm X 6mm G.I. strip between electrode & earth bar 2nos.

Testing result for ground earth :

1. Earth testing result -


Between E1 & E2 =0.5 Ohms
Ground Earthing Between E1 & Neutral =0.1 Volts
Ground Earthing Between E2 & Neutral =0.1 Volts

2. Specification of ground earthing -


Electrode: 40mm dia 3.2 mtrs long perforated galvanized pipe electrode 2nos.
Connection: 40mm X 6mm G.I. Strip between electrode & earth bar 2nos.

REMARKS :

The all electrical wiring are in good order and safe condition. There are no leakages & electrical
equipments are
well connected with the Earthing & it is safe for usage.

RABI ENTERPRISE

You might also like