BS88 Series
BS88/BS88-LN
ATS CONTROLLER
OPERATING MANUAL
ATS CONTROLLERBS86/BS88-LN ATS CONTROL MODULE
CONTENT
1 SUMMARY...
2 PERFORMANCE AND CHARACTERISTICS .
3. SPECIFICATION...
4 OPERATING
4.1 OPERATION PANEL...
42 Key FUNCTION DESCRIPTION,
5 LCD DISPLAY...
SL MAINSCREEN cn
52 MAINS MENU INTERFACE. aebnseeiee
6 TEST GENERATOR OPERATION.........
7 CONFIGURATION PARAMETERS...
TL PARAMETERS TABLE wns
7.2 INPUT/OUTPUTFUNCTION DESCRIPTION trol
8 TIMING START GENERATOR...
9 DATE AND TIME SETTING..
10 CONTROLLER INFORMATION...
11 ATS OPERATION.
IL MANUAL OPERATION.
1.2 AuTowaric operation
13. ATS power st
12 COMMUNICATION CONFIGURATION..
13 DESCRIPTION OF CONNECTING TERMINAL..
14 TYPICAL WIRING DIAGRAM
15 INSTALLATION
16 FAULT FINDING ..
BS88 Series ATS CONTROLLER —ISSUE2010-07-08 Version 14 Page 2 of 23BS88/ BS88-LN_ATS CONTROL MODULE
1 SUMMARY
BS88 series ATS controller with a programmable function, automatic measurement,
LCD display, digital communications, as one of the intelligent dual-supply switching
module. It combines digital, intelligent, networking, measurement and control
process automation, disoperation, in order to reduce the faults during operation. It
is the best ideal option in ATS.
BS88 series ATS controller be made of microprocessor as its core, can accurately
detect extended-spectrum 2-way-3-phase voltage and also make accurate
judgment and output passive control switch under the abnormal voltage (over or
under, miss phase and over or miss frequency). This controller has full
consideration in various application of ATS (automatic transfer system) can be
directly used for Intelligent ATS, Contactor ATS, Circuit Break ATS etc. It have
compact structure, advanced circuits, simple wiring and high reliability, be widely
used in Electric power, Telecommunications, Petroleum, Coal, Metallurgy, Railways,
Municipal, Intelligent building, Electrical devices, Automatic control and Testing
system etc.
2 PERFORMANCE AND CHARACTERISTICS
|= System type can set for: Mains (1#) & Mains (2#), Mains (1#) & Gens (2#),
Gens (1#) & Mains (2#), Gens (1#) & Gens (2#)
The LCD 128x64, take backlit, two languages (simplified Chinese and English)
display, and gentle press key for operation,
| Measure and shows 2-way 3 phase voltage and frequency parameters:
Wayé# Way#2
Line-Line voltage (Uab, Ube, Uca) —_Line-Line voltage (Uab, Ubc, Uca)
Phase-Nature voltage (Ua, Ub, Uc) Phase-Nature voltage (Ua, Ub, Uc)
Frequency (F1) Frequency (F2)
With over voltage, under voltage, loss of phase, reverse phase sequence,
over frequency, under frequency functions.
With the auto/manual operation mode. In manual mode, may enforce switch to
close or open.
= All parameters can be set in the field. Apply for two-stage password to ensure
authorized staff operation only.
S88 Series ATS CONTROLLER —ISSUEZ010-07-05 Version 14 Page Sof 23BS88/BS88-LN ATS CONTROL MODULE
™ Can be set as on-load/off-load mode in the field for start genset.
® Can make switch to re-close when switch is opened accidentally or make
switch to power off then re-close.
Closing output can be set as pulse or continuous output.
Applicable for ATS of one OFF segment, two OFF segments and none OFF
segment.
With design of two way separate of N circuitries.
Real-time clock (RTC).
Can start or stop genset automatic on scheduler. Also be set as single time
operation, monthly or weekly, and whether with load or not.
Can control two gensets to work in cycle, even the genset running time and
interval rest time can be set.
Widely range of DC power supply. Max.80V DC input can be endured in an
instant,
Bigger space between connecting terminals of AC input. Max.625V input
voltage.
With standard insulated RS485 communication interface port. With "remote
controlling, remote measuring, remote communication" function by the
ModBus communication protocol.
Can check the status of controller (including of switch auxiliary output,
over-voltage, and under-voltage etc.)
Suitable for various AC systems (3-phase 4-wires, 3-phase 3-wires,
single-phase 2-wires, and 2-phase 3-wire).
Modular configuration design, flame-resisting ABS plastic shell, inserted type
connection terminals and built-in installation. Compact structure with easy
installation
3 SPECIFICATION
1. DC 8.0V~35.0V, power supply constantly,
Operating voltage | 2. AC160V~280V (BS8B-LN) during AC power L1N1/L2N2
supply)
Power
catriation <3W (Standby mode: <2w)
[AC system BS88 BS88-LN
AC voltage Input | 3-phase 4-wire(L-L) | 80~625V 80~480V
S-phase 3-wire(L-L)[80-625V Not used
8S88 Series ATS CONTROLLER ISSUEZ010-07-05 Version 14 Page 4 of 23BS86/BS88-LN_ATS CONTROL MODULE
t-phase 2-wire(L-N) | 50~360V 50~280V
2-phase 3-wire(A-B) | 80~625V 80~480V
Rated frequency | 60/60Hz
Close and Open
tage rel
Tip Relay oupur_| TOA2S0VAC Free voltage relay output
Programmable
relay output 1GA/TA250VAC_ Free voltage relay output
capacity
Digital Input Connecting to GND is active
‘Communication | RS485, MODBUS Protocol
Dimensions 209mmx153mmxS5mm
Panel cutout 186mm x 141mm
aeons Temp. | Temperature: (-25~-+70)"C; Humidity: (20~90)%
Storage condition
‘Temperature: (-30-+80)°C
Protection rank
P58: Front of module when module is installed into the control
panel with the optional sealing gasket.
IP42: Front of module when module is installed into the control
panel without being sealed to the panel.
Object: Between the input/output/ power supply.
Insulation strength | Quote from standard: IEC688-1992.
Test method: AC1.5kV/1min in current 5mA.
Weight 0.8kg(BS88)/1.0kg(BS88-LN.
S88 Series ATS CONTROLLER ISSUE2010-07-05
Version 14 Page 6 of 23BS88/ BS88-LN_ATS CONTROL MODULE
4 OPERATING
4.1 OPERATION PANEL
ATS CONTROLLER
4.2 KEY FUNCTION DESCRIPTION
The key function is used to transfer 1# power to load
MW Close key | in manual mode.
unk The key function is used to transfer 1# or 2 power
Mee to off-load in manual mode.
The key function is used to transfer #2 powers to
Ni-Close key | kaad x anced mode
Manual key —_| The key function is used to initiate manual operation.
‘Automatic key
The key function is used to i
operation.
iate automatic
Pressing the key can directly enter commissioning
@| @ jeloeeoe
Tesi key interface.
Pressing the key, enter menu interface; Holding
Pressing the key go back to the main current
arnt | operating from that interface. When a fault alarm
controller, holding pressing the key can eliminate
fault alarm.
Page down Page tur. In the adjustment parameters menu as
Idecrease numerical increases.
BS88 Series ATS CONTROLLER —ISSUE2010-07-05 Version 1.4 Page 6 of 23BS88/BS88-LN_ATS CONTROL MODULE
5 LCD DISPLAY
5.1. MAIN SCREEN
This screen will show: lineine voltage
(L1-L2, L2-L3, and L3-L1), frequency and
controller present status is in manual (auto)
mode.
This screen show: 1# and 2# of the three
phase voltage (L-N), real-time clock and
controller working state.
This screen show: 3 phase load current,
active power, apparent power, power factor
and work state of controller.
LCD display I# operating state of power
supply.
LCD display Il# operating state of power
supply.
LCD displays other operating state.
Present status is in manual (auto) mode.
Display priority of the #1 status (upper to lower)
1# Fail to When 1# breaker occur closing failure,
closed a this will display.
9 | te Failto Fut |When 1# breaker occur opening
break failure, this will display.
3. | 1#Over Volt | Indication | When 1# source occur over voltage,
this will display.
1# Loss of fication | When any of 1# three phases is miss,
4 | Phase Indication | this will display.
ication _| When 1# source occur over frequency,
5 | 1# Over Fi
['#Over Freq | Indication | wis wil display.
BS88 Series ATS CONTROLLER ISSUEZ010-07-05 Version 14 Page 7 of 23BS88/[Link] ATS CONTROL MODULE
When 1# source occur under
frequency, this will display.
When 1# source occur under voltage,
6 | 1# Under Freq Indication
7 | 1# Under Volt Indication
this will display.
is error, this
a | 1#Phase Waring | When tit phase sequence i
sequence fault will display.
: When 1# source voltage is normal, this
9 | *#VoItnormal | Indication | si gispiay
Display priority of the #2 status (upper to lower)
4 | 2#Failto Faut | When 2# breaker occur closing failure,
Closed fae this will display.
2 | 2#Failto Faut [When 2# breaker occur opening
Break oaks failure, this will display.
‘cation | When 2# sources occur over voltage,
3 |2# Over Volt | Indication | he wil etplay
4 | BE Loss of Indication | When any of 2# three phases is miss,
Phase this will display.
5 |2#OverFreq | Indication [When 2# sources occur over
frequency, this will display.
When 2# sources occur under
frequency, this will display.
6 | 2#Under Freq | Indication
7 | 2# Under Voit | Indication | When 2# sources occur under voltage,
this will display.
2# Phase When 2# phase sequence is error, this
8 | sequence faut | 2°93 | wit display
9 | 2#Volt normal | Indication | When 2# sources voltage is normal,
this will display.
Display priority of the other status (upper to lower)
Engine starting
2 | Breaking
compulsorily
Display that engine has start
Breaking compulsorily input is active.
Load current is over than the setting
3 | Load over current 7
limit and exceed the setting delay.
Faults: when alarm occurs, alarm lamp will flash and this alarm signal will continue
until long pressing @ key to reset.
Warning: when warming occurs, alarm lamp will flash and will not latch. When a
BS88 Series ATS CONTROLLER —ISSUEZ010-07-05 Version 1.4 Page 6 of 23BS86/ BS88-LN_ATS CONTROL MODULE
warning is inactive, alarm lamp will latch.
5.2 MAINS MENU INTERFACE
Inthe screen, press © key, can enter the main menu interface.
Press © key choose different
parameters (the current line anti-black)
and then press ®) key to confirm, can
enter the corresponding display
screen.
6 TEST GENERATOR OPERATION
On the main screen press © key and directly into the test generator operation
interface, the screen will show as following:
Press ©) key to select corresponding function, and
press ®) key to confirm.
STOP TO TEST: This will stop a start generator signal
immediately.
TEST OFF-LOAD: This will send out a start generator
signal immediately. After 2# source is normal, if 1# source is normal, the ATS will
not act. The ATS will transfer the load to 2# ‘only when 1# source is abnormal. After
1# source return normal, the ATS will transfer the load to 1#. Here the start
generator signal output will keep.
TEST ON-LOAD: This will send out a start generator signal immediately. After 2#
‘source is normal, the ATS will transfer the load to 2# source immediately regardless
Of 1# source normal whether or not.
CYCLE START: When choosing this mode, generator start-signal will cyclic output
according to mains status, user can set the cyclic time. If generator fault of
input-signal, no longer send Start-signal. If in manual mode, will keep the current
status and cancel cycle start.
Conditions under this mode:
ie
[Link] automatic mode.
[Link] port setting: 1# engine start output (Normal Output) and 2 # engine start
‘output (Normal Output).
8888 Series ATS CONTROLLER ISSUE2010.07.05 Version 74 Page 9 of 23BS88/ BS88-LN_ATS CONTROL MODULE
[Link] port setting: 1# generator fault input and 2# generator fault input.
[Link] set the
and the .
[Link] system type set must as Gens(#)&Gens(2#).
Note: In manual mode, after choose commissioning, generator will output
start-signal immediately, but the ATS will not transfer to load automatically except for
operation manually by pressing key mounted on the front panel.
7 CONFIGURATION PARAMETERS.
In the main interface, press ® key, choose [Link] setting and then press
® key, to enter interface of confirming password.
Input password value 0-9 by ©) key, and to shift Right by ®) key. Press the ®
key in the fourth of password to confirm. If password correct and enter into the
parameter mains interface. While error, directly exit to return to main interface.
Factory Default Password is: 1234. Press © key to tum over and set
Parameters. While setting the current configuration parameters according to press
® key. Then enter current parameter model, and the current value of the first line
screen display against the first black. Press ©) key to change number, press @)
key to shit position, and press @) key again to confirm in the last number position
If the setting value within limits, the value is stored into the intemal controller
FLASH. Beyond the limits, parameters will can't be saved. In the parameters
setting interface, long time press @) key will back to the main display screen
7.1 PARAMETERS TABLE
Parameters item table
N It is the delay of #4 power from
lormal delay of
1 Y oe (0-9999)s 10 | voltage abnormal to voltage
normal.
‘Abnormal delay It is the delay of #1 power from
02 | ort (0-9999)s 5 | voltage normal to voltage
abnormal.
Normal Delay It is the delay of #2 powers
03 | or oe (0-9999)s 10 | from voltage abnormal to
voltage normal,
04 | Abnormal (0-9999)S 5 it is the delay of #2 powers
BSBB Series ATS CONTROLLER —ISSUEZ010-07-05 Version 14 Page 10 of 33BS88/ BS88-LN_ATS CONTROL MODULE
Delay of 2# from voltage normal to voltage
abnormal
; Breaker close pulse. If it is set
05 || Cesedtime: | (e208 5 | to z0F0, the output will hold
06 _| Open time (1-20)8 5 __| Breaker open pulse.
It is the delay from #1 power
Transfer ‘opened to #2 powers starts to
07 interval (o-se8)s * | close or from #2 power opened
to #1 power start to close.
‘Afier the module has received
Exceed transfer a close state input, the breaker
8 | time coe 9-0 | close outputs continue to hold
until the delay is expended.
When the breaker fail to close
for the first time, the module will
open breaker, and then attempt
Again closed to close for the second time, if
9 | time (0-20.9)s 10 | the second time closing
breaker is still failure, the
module will send out closing
breaker failure signal.
When the breaker fail to open
for the first time, the module will
close breaker, and then attempt
Again open to open for the second time, if
10 |i (0-20. .
time (020.08 ‘0 Tthe second time opening
breaker is still failure, the
module will send out opening
breaker failure signal,
Itis the delay from #1 power is
GENS start por
14 | Gelay (0-9999)s 1 [abnormal to send out start
generator signal.
GENS stop Itis the delay from #1 power is
12 | delay (0-9999)S 5 normal to send out stop
generator signal.
13_| Cycle run time | (1-1440)m__| 720 | Gens cycle run time.
Cycle shutdown
+ le "| (4-1440)m 720. | Gens cycle stop time.
15 | Rated volt (100-600)V_[ 230 _| AC system rated voltage
The settings are used to
configure the power over
16 | Over volt (100-150)% | 120 | voltage point in the event of the
voltage rising above the setting
value. This value canbe
BS66 Series ATS CONTROLLER
1SSUE2010-07-05
Version 1.4 Page 11 of 23BS88/BS88-LN ATS CONTROL MODULE
[Num [Wem [Range —[Defauit |Description]
adjusted suit user
requirements.
Normal return value of over
17 | Return over vot} (100-180)% | 118 | Noone,
The settings are used to
configure the power under
48 | Under volt (60-100)% | 80 | voltage point in the event of the
voltage falling below the setting
value.
Return under ; Normal return value of under
19 | vott (60-100)% | 85 | voltage.
When the frequency of power
20 | Over Freq (0.0-75.0)Hz | 55.0 | is over than the point, over
frequency is active.
Reiumn over Normal return value of over
21 | eg (0.0-75.0)H2 | 52.0 | peauency.
When the frequency of power
22 | Under Freq | (0.0-75.0)Hz| 45.0 | is low than the point, low
frequency is active.
Return under Normal return value of over
23 | reg (0.0-75.0)H2| 48.0 | fer enoy
24 | CT rate (660005 | _500__| Current Transformer rate.
Rated load
5 ee (6-500) 500 | Load rated current.
26 | Over Current | (499.450)% | 120 | Load over current value.
value
2 eon (0-8999)s | 1296 | Over current alarm delay value.
Equipment
28 tl ines (1-284) 1 | RS485 communication address
23 _| Password 1234_| it applies to modify parameters,
1.1# Mains 2# Gens
System type 2.1# Gens 2# Mains
30 1-4) 1
select i 3.1# Mains 2# Mains
| 4.4# Gens 2# Gens
1. Two Breaking, two OFF
position, such as the ATS
composed of two circuit
Breaking breakers or two contacts.
ot an oul (1-3) 1/2 One Breaking, one OFF
Position (three segments kind),
such as SOCOMEC VE switch.
3. NO Breaking, no OFF
position (two segments kind),
S88 Series ATS CONTROLLER ISSUE2010-07-05 Version 1.4 Page 12.0f 25.BS88/BS88-LN ATS CONTROL MODULE
such as SOCOMEC VS switch.
Select AC
32 system
(1-4)
1. 3-phase 4 wire
2, S-phase 3 wire
3. Single phase 2 wire
4, 2-phase 3 wire
33. | Set Priority (1-3)
1. 1# Priority, setting #1 power
transfer is prior. If #1 and #2 is
normal at the same time, the
switch will transfer load to #1
power source.
2. 2# Priority, setting #2 power
transfers is prior. If #1 and #2
is normal at the same time, the
switch will transfer load to #2
power source.
3. NO Priority, if #1, 2 sources
is normal at the same time and
#1, 2 take no load, the switch
will first transfer load to #1
power source. Only when #1
power is abnormal, the #2
power will supply for load; if the
switch have been taken load, it
will not switched to another
power until abnormality occurs
in the power.
34 | Aux. output 1 (1-28)
25.
35_| Aux. output 2 (1-28)
28
36_| Aux. output 3 (1-28)
13
37_| Aux. output 4 (1-28)
16
38. | Aux. output 5 (1-28)
18
[Link] used
[Link] failure output
[Link] of transfer
04. Warning alarm output
05. Alarm output (delay)
06. 1# Volts normal
07.1# Volts abnormal
08.2# Volts normal
09.2# Volts abnormal
[Link] current output
11. Auto state output
12. Manual state output
13. Gens start output(N/O)
14. Gens start output(N/C)
16.1# switch shutdown output
16. 1# switch break off output
17.2# switch shutdown output
18. 2# switch break off output
BS86 Series ATS CONTROLLER
1SSUE2010-07-05
Version 1.4 Page 13 of 23BS88/ BS88-LN ATS CONTROL MODULE
19. Common alarm output
20. Timing test Gen set
21.1# shutdown state
22.2# shutdown state
23.1#Gens start output
24.2#Gens start output
[Link] power L1
[Link] power L2
[Link] power L3
[Link] power N
39_| Aux. input 1 (1-9) 02 | [Link] used
40_| Aux. input 2 (1-9) 01 __| [Link] compulsorily
41_[ Aux. input 3 (1-9) 01 _| [Link] off-load
a [Link] on-load
05. Test Lamp
i 06. 1# Gens Alarm
42_| Aux. input 4 (1-9) Of | G7 2#Gené Alarm
08. Remote start genset input
09. Reserved
7.2. INPUT/OUTPUT FUNCTION DESCRIPTION
The input port function describes:
tem Description
1 Not used Invalid
2 Breaking compulsorily
‘When active, this will force the breaker to transfer the
ATS to OFF position. It isn't suit for none OFF position
ATS.
3 Test off-load
When active, this will send out a start generator signal
immediately. After 2# source is normal, if 1# source is
normal, the breaker will not act. The breaker will
transfer the load to 2# only when 1# source is
abnormal. After 1# source restore normal, the breaker
will transfer the load to 1#. Here the start generator
signal output will keep.
4 Test On-Load
When active, this will send out a start generator signal
immediately. After 2# source is normal, the breaker
will transfer the load to 2# immediately regardless of
4# source normal whether or not.
5 Test LED
When active, all Led lamps mounted on the front
panel will illuminate, LCD will fill black block.
6 1# Gens Alarm
In Cycle start, if the input is active, 1 # Gens will not
BS88 Series ATS CONTROLLER
ISSUE2010-07-05 Version 14 Page 14 of 23BS88/BS88-LN_ATS CONTROL MODULE
start
7 2 Gens Alarm In Cycle start, if the input is active, 2 # Gens will not
start
8 Remote start input | This input is necessary for oycle start generator.
‘9 Reserved
The output function describes:
tem Description
1 Not used
Critical fault alarm including switch transform
2 Critical failure output failure,
| Switch failed including 1# closed failure,1# open
eee failure, 2# closed failure, 2# open failure.
General warming includes 1# reverse phase
4 Warning alarm output | sequence; 2# reverse phase sequence, and load
‘over current and compulsory breaks.
i itput 60
5 Alarm output (delay) Serious fault alarm output, continuous outpu
seconds.
6 1# Volts normal twill output when #1 voltage is normal.
7 4# Volts abnormal Itwill output when #1 voltage is abnormal.
8 2# Volts normal It will output when #2 voltages is normal.
9 2# Volts abnormal twill output when #2 voltages is abnormal.
10 Over current output __| Set limits on more load current and exceeds delay.
11 Auto state output In auto state output.
12 Manual state output__| In manual state output.
13Gens start output(N/O) _| When generator starts output (Relay closed).
14Gens start output (N/C)_| When generator starts output (Relay released).
15 1# switch shut output _| #1 Switch close output.
16 1# switch break off
pe #1 Switch open output.
17 2# switch shut output | #2 Switch close output.
18 2# switch break off
pei #2 Switch open output.
19 Common alarm output _| It is include serious fault alarm and common alarm.
20 Timing test Gen set Schedulers start generator function.
21 1# shut state #1 Switch auxiliary close output.
22 2# shut state #2 Switch auxiliary close output.
23 1#Gens start output 4# Gens start output.
24 2#Gens start output 2# Gens start output.
25 ATS power L1
26 ATS power L2
27 ATS power L3
28 ATS power N
ATS power supply.
BS88 Series ATS CONTROLLER ISSUE2010-07-05 Version 1.4 Page 15 of 23BS88/BS88-LN _ATS CONTROL MODULE
8 TIMING START GENERATOR
On the main screen press ® key and select 2 Time
start, and then pressing @) key, the screen will show
the time start interface as follow:
Time start cycle: Include inhibit start; single time,
weekly or monthly.
Load set: Starting generator with load or without load.
Start time: Generator start date and time.
Continue time: Generator continuously run time can be set on the duration of
maximum time for 99 hours 59 minutes.
9 DATE AND TIME SETTING
On the main screen press @) key and select 3 Date
& Time set, and then pressing ® key, the screen
will show the Date & Time Set interface as follow:
Press ©) key according to the corresponding bit
input values 0-9, pressing ® key to carry through the right of bit shift, right shift to
the end of pressing ©) key, according to the key @) on the date and time can be
updated controller.
Date and time format set: year-month-date (week) and hour: minute.
10CONTROLLER INFORMATION
On the main screen press ®) key and select 5 Controller information, and then
pressing ® key, the screen will show the controller information interface as follow:
Display content includes off positions setting and
switching priority choice and controller version,
date.
Pressing @ key will exit and retum to main
screen,
8888 Series ATS CONTROLLER —ISSUE2010-07-05 Version 14 Page 10 of 23BS88/BS88-LN ATS CONTROL MODULE
11 ATS OPERATION
11.1 MANUAL OPERATION
Press ® key and manual operation indicator light, the controller in manual
mode.
« Press @ key, 1# close relay outputs immediately, begin to monitor 1# closing
input, if active, the 1# source LED light, the 1# source connect to load.
© Press @ key, 2# close relay outputs immediately, begin to monitor 2# closing
input, if active, the 2# source LED light, the 2# source connect to load.
© Press © key and 4# or 2# open relay outputs immediately, begin to monitor
1# or 2# closing input, if inactive, the 1# and 2# source LED extinguish, and
1# and 2# source disconnect with load.
"1: For the ATS of no OFF position, press © key is invalid.
11.2 AUTOMATIC OPERATION
Press the @ key and the automatic LED light, enter AUTO mode and controller
can automatically switch load to 1# or 24,
11.3 ATS POWER SUPPLY
The power of ATS is supplied by controller, so long as one power is normal, this can
guarantee ATS voltage power supply normally and can be transferred normally.
Users should select power supply voltage (phase voltage or line voltage) based on
ATS type. If power supplied by phase voltage, connect the phase A1 to Pin5 in AUX.
output and A2 to Pin7, and connect the phase N1 to Pin8 in AUX. output2 and N2
to Pin10, then connect the common output of AUX. outputt&2 to ATS power
supplies. Then controller power on, enter parameters setting menu, and set the
AUX output! as "ATS power L1”. If the ATS power supplied by Line voltage, set as
‘same as above, and only need to change phase N to phase B. Wiring diagrams are
5S86 Series ATS CONTROLLER _ISSUE2010-07-08 Version 14 Page 17 of 23BS88/ BS88-LN ATS CONTROL MODULE
shown as following:
z zi g 2
& fi f
3 2 3
2 3 2 8
AI @ A2 Nig na AIO AD Bi Bz
8] 1 8] 9} 10) 8) 1 4 9} 10}
Ld d
‘Aux x
ourrtrs ourpurz outers ourrura
(168) (186A) (164) (164)
ATSPOWERL1 ATS POWERN ATSPOWERL1 —ATSPOWERL2
ATS L-N voltage power supply
ATS L-L voltage power supply
Note: Normal Closed input voltage must come from the same one circuit voltage.
12 COMMUNICATION CONFIGURATION
BS88 series has RS485 serial port, be allowed to connect the local area network
with open structure. Its apply protocols of ModBus communication with PC or data
acquisition system running on software. Also can provide a simple and practical to
factories, telecom, industrial and civil buildings dual power switching management
plan, achieve dual power monitor and “remote controlling, remote measuring,
remote communication” functions.
More information of Communication Protocol, see the “BS88 communication
protocol”.
Communication parameters,
Module address 1 (range: 1-254, User can set it)
Baud rate 9600 bps
Data bit Bbit
Parity bit None
Stop bit 1 bit or 2-bits(set via PC)
BS86 Series ATS CONTROLLER —ISSUE2010-07-05 Version 14 Page 18 of 23BS88/ BS88-LN ATS CONTROL MODULE
13DESCRIPTION OF CONNECTING TERMINAL
ISIC OMOIOIOIOIOIG
Oloiois
+ | s# closed output | Passive relay contact | ateg 250168
2 output
3 Passive relay contact
4] 2 losed output | Pa Rated 250V16A
5 NC The default is | Free voltage relay
6 | Aux. output1 [Common _| ATS power of | contracts
ia NO U1 output. Rated 250V16A,
8 NC The default is | Free voltage relay
9 | Aux. output 2 Common | ATS power of | contracts
10 NO Li output. _| Rated 250V16A
1 At
voltage input
1# AC 3phase 4 wire
If the input for
single-phase, only
connect A1, N14
voltage input
[42 [et
13 [Ct
14 [NA
15 [Az
16 | B2
17 [¢2
18 N2
2# AC 3-phase 4 wire
If the input for
single-phase, only
connect A2, N2
BS86 Series ATS CONTROLLER
ISSUE2010-07-05
Version 1.4
Page 19 of 23BS88/BS88-LN ATS CONTROL MODULE
connect the generator
fii SND battery negative pole DC negative input
When you need to start
generator, connect the
terminal to the generator
battery positive pole
Detection of 1 # switch
21 1# closed input closing state, voltage free | It is active to GND
contact input
Detection of 2 # switch
22 2# closed input closing state, voltage free | It is active to GND
contact input
DC positive input
8-35V controller
power supply
20 | DC power input
23 | Aux. input 1
24 | Aux. input 2
25 | Aux. input 3
26 | Aux. input 4
Itis active to GND
27 Voltage free relay contacts
38 | Aux. output 3 algal Rated 250V7A
29 Voltage free relay contacts
30 | Aux. output 4 Lait Rated 250V7A
31 Voltage free relay contacts
39 | Aux. output 5 cat Rated 250V7A
33 | RS485 A+
Sart pease ae RS485 communications
por
35 | RS485 GND
36 | !Alinput Sensing from Secondary
37 1A Output phase A current
38 | IB Input Sensing from Secondary
39 [1B Output phase B current
40 | !C Input Sensing from Secondary
41 | 1C Output phase C current join
tcp
CONTR | LCD Display Adjust the LCD contrast
AST
LINK | Program port Factory update
'5S86 Series ATS CONTROLLER 1SSUE2010-07-05 Version 1.4 Page 200125BS88/BS8B-LN ATS CONTROL MODULE
14TYPICAL WIRING DIAGRAM
ATYS3 Diagram (With Current)
LOAD
uN
‘1#voltage input, 2#tvoltage input
Ri 5% Re
st oe s2
TH ss 2
i ne
Ni
ATYSS
i 7prspse[s14] 84
no 19}
36 | Close il Close
7 Break
1H lose inp
ATS CONTROL MODULE
Generator}
icon
3 phase current input
2 position Manual Switch Diagram (63A to 630A, with Current)
LOAD
Mains input rater input
Ro
82
n
i
[Generator
CONTROL MooULE
E
t
:
BS88 Series ATS CONTROLLER —ISSUEZ010-07-05 Version 14 Page 21 of 3BS88/BS8B-LN ATS CONTROL MODULE
Contactor Diagram (With Current)
LOAD
uRBN
1@voltage input 2avoltage input
RI
st
1
Nt
R2
82
12
Nz
Eontactor Contactor
& e405 fs
2 Aintse
5 37
5 eure 20} finns 5
3 (aad? j9}mnr- 8
Ficbu ATS CONTROL MODULE zege
ATYSMSS Diagram
LOAD
bRoN
1#voltage input
RI
s1
1
Nt
2#voltage input
R2
s2
12
N2
gtalal
ATYSM3S |
i715 313314] 14] 11
fro 7]r03]
Gno 19] —
45
18
1
18 Close input
26 Close input
8
Iai ATS CONTROL MODULE
3 phase current input
$
2
Generator
BS88 Series ATS CONTROLLER —ISSUE2010-07-05 Version 14 Page 22.01 23.BS88/ BS88-LN_ATS CONTROL MODULE
15INSTALLATION
en | Vesen
16FAULT FINDING
CUT OFF
Controller no operation
Check the Phase A1, N1 or Phase A1, N1 voltage.
Check connection wirings from the controller to ATS.
Check DC fuse.
RS485 communication
failure
Check whether the RS485 is wrong connection between
negative and positive.
‘Check whether the RS485 adapt is abnormal.
Check whether the parameter settings in the module
addresses are incorrect.
If the above methods are no using, you can try to
connect the GND of controller with RS485 GND (or PC
GND).
Recommend that the A and B lines of the 485 network
should be terminated at each end with a 1200 resistor.
LU Programmable output
Check programmable output connections, pay attention
{to Normally opened and closed.
Peet |Check the output parameters settings.
Ensure that the programmable input connect to GND!
Programmable input | reliably when it’s active, and hung up when it is inactive.
abnormal (Note: The input will be possibly destroyed when
connected with voltage)
ATS is not work while
|Generator running
Check ATS.
Check the connection wirings between the controller
and the ATS.
Ensure that the ATS OFF position numbers are same as
the setting OFF position numbers.
BS88 Series ATS CONTROLLER ISSUE2010-07-05 Version 14 Page 23 of 23zl
3 from
i Matis SUPPLY
oN
3 PI
se Fh oe BRB
not FSA wo
| faye
| | noma
ale
BR =o] | movers
fa] | comer
oO 2
>
4 e “4 2a NSA
3] 3 e|~/T 2° ELL
3) 5 i Eke
a eel | ekeer
4 es 5 fa[s|Sner]| ~