Variable Speed Controller Guide
Variable Speed Controller Guide
Allen-Bradley
Notes
N-1
Notes
N-2
Notes
N-3
Notes
N-4
Summary of Changes
                    Summary     of Changes
                    Summary of Change
Table of Contents
                        Table
                        ImportantofInformation
                                     Contents
                                    Appendix B
                                         CE Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .        B-1
                                         Essential Requirements for a Conforming EMC Installation . . . . . . . . . . . . . . . . . . . .                                   B-1
                                         General Instructions for an EMC Compliant Installation . . . . . . . . . . . . . . . . . . . . . . .                               B-2
                                         Low Voltage Directive 73/23/EEC Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                             B-4
                                    Index
                                         Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I-1
ii
   General Information1
   Receiving – It is your responsibility to                   Unpacking – Remove all packing material,
   thoroughly inspect the equipment before                    wedges, or braces from within and around the
   accepting the shipment from the freight company.           controller. Remove all packing material from the
   Check the item(s) received against the purchase            heat sink.
   order. If any items are obviously damaged, do not          Inspection – After unpacking, check the item(s)
   accept delivery until the freight agent notes the          nameplate catalog number against the purchase
   damage on the freight bill.                                order. An explanation of the catalog numbering
   If you find any concealed damage during                    system for the Bulletin 160 controller is included
   unpacking notify the freight agent. Also, leave the        as an aid for nameplate interpretation. Refer to
   shipping container intact and have the freight             the following page for complete nomenclature.
   agent make a visual inspection of the equipment            Important: Before you install and start up the
   in order to verify damage.                                 controller, inspect the mechanical integrity of the
                                                              system (e.g., look for loose parts, wires,
                                                              connections, etc.).
   General Precautions
   In addition to the precautions listed throughout                      ATTENTION: The surface
   this manual, you must read and understand the                         temperatures of the controller may
   following statements which are general to the                         become hot, which may cause injury.
   system.
                               An “S” in the        A 200 – 240V 1∅            A01       Letter Type       SF1 = Analog   Program
                               Bulletin Number        200 – 240V 3∅            A02       N Open (IP20)           Signal   Keypad Module
                               denotes a single                                          P Chassis Mount ➀       Follower
                               phase input                                     A03
                                                    B 380 – 460V 3∅                        (external
                               voltage.                                        A04                         PS1 = Preset
                                                                                           heatsink)
                                                                               A06                               Speed
                                                                               A08
                                                                               A12
                               ➀    This manual applies only to the open style (IP20) device. Refer to separate instruction sheets for Chassis Mount
                                    and NEMA 4 (IP66) devices.
                                                   I     V:       200-240 3∅    O     V: 200-230 3∅
                                                   N                            U
                                                                                                                  ÎÎ
                                                                                                                   Î
                                                         A:       5.4           T     A: 4.5                                         Nameplate is located on the
                                                   P                                                                                 side of the unit.
                                                        Hz:       50/60         P    Hz: 0-240
                                                                                                                  ÎÎ
                                                                                                                   Î
                                                   U
                                                        VA:       2200          U     Motor
                                                   T                            T     Rating: 0.75kW/1HP
                                                    S/N 32098
                                                       OPERATING AMBIENT TEMP: 0 – 50°C
                                                       SHORT CIRCUIT CURRENT: 10KA
                                                       POWER TERMINAL WIRE: Use 75°C Cu Wire
                                                                               4mm2 – .75mm2 (12 – 18 AWG.)
                                                       IP20                    Torque 1.35 Nm (12 in.-lbs.)
                                                       WARNING: ! Allow 1 Minute after power is removed
                                                       before servicing. Accessible surfaces may be hot.
                                                       Compatible with Type B RCD protection devices only.
1-2
                                                                                                               Chapter 2
   Installation and Wiring
                   Figure 2.2 – Power Wiring For Analog                                         Power Wiring For Preset Speed and Analog
                   Signal Follower and Preset Speed Models                                      Signal Follower Models
                       Required Branch                 Input Line Protective Device –
                       Circuit Disconnect ➀            See Table 2.C and Table 2.D.
                                                                                                Table 2.A – Power Terminal Block Specifications
                                                                    Dynamic Brake
                                                                    Module Option ➁
                                                                                                 Terminal      Screw  Max/Min Wire              Max/Min Torque
                                                                                                  Block         Size Size mm2 (AWG)               Nm. (lb.in.)
                                                                             Terminal
                                                                             Block One              TB1➄         M4        4 – 0.75 (12 – 18)   1.81 – 1.35 (16 – 12)
                       L1         L2      L3      BR        BR               (TB1) – For            TB2➄         M4        4 – 0.75 (12 – 18)   1.81 – 1.35 (16 – 12)
                       R          S       T        –         +               Line Power and
                                                                             Brake Resistor.
                                                   –        +                Terminal Block     ➄   The Bulletin 160 SSC is IP20 with wires installed on power
                       T1        T2       T3
                       U         V        W       DC       DC                Two (TB2) –            terminal blocks.
                                                                             For Motor and
                                                                             Capacitor
                                                                             Module.
                                                                                                Input Power Conditioning
                                  Motor ➂                   Capacitor Module
                                                            Option ➃                            The controller is suitable for direct connection to
                                                                                                AC power lines within the rated voltage of the
                   ➀        For single phase input applications, connect the AC input line to   controller (see Appendix A). Listed below are
                            input terminals (L1) R and (L2) S.                                  certain power line conditions which may cause
                   ➁        Connection for dynamic brake resistors for all models.              component damage or reduction in product
                            Important: P52 – [DB Enable] must be enabled for proper             life. If any of the conditions exist as described in
                            operation. See Appendix A for part numbers.                         the table below, install “one” of the devices listed
                                                                                                under the heading “Corrective Action” on the line
                                                                                                side of the controller. Important: Only one
                   ➂        Bulletin 160 controllers are            and        listed as
                            motor overload protective devices. An external overload relay is
                                                                                                device per branch circuit is required. It should be
                            not required for single motor applications.                         mounted closest to the branch and sized to handle
                   ➃        Connection for an external capacitor module. Provides extended      the total current of the branch circuit.
                            ride through capability and improved inherent braking
                            performance. See Appendix A for part number.                        Table 2.B – Power Line Conditions
                                       ATTENTION: The controller is
                                       intended to be commanded by control                           Power Line Condition                  Corrective Action
                                       input signals that will start and stop the                Available short circuit currents     S Check supply voltage.
                                       motor. A device that routinely disconnects                (fault currents) greater than 10,000 S Line Reactor (See A-4) or
                                       then reapplies line power to the controller               Amps
                                                                                                                                      S Isolation Transformer
                                       for the purpose of starting and stopping the
                                       motor should not be used. If it is necessary              Line has power factor correction     S Line Reactor (See A-4) or
                                                                                                 capacitors                           S Isolation Transformer
                                       to use this method for starting and stopping
                                       or if frequent cycling of power is                        Line has frequent power              S Line Reactor (See A-4) or
                                       unavoidable, make sure that it does not                   interruptions                        S Isolation Transformer
                                       occur more than once a minute.
                                                                                                 Line has high frequency            S MOV option (See A-4) or
                                                                                                 (>10 Hz) noise spikes in excess of S Line Reactor (See A-4) or
                                       ATTENTION: Do not connect power                           900V (Induction heaters, RF
                                                                                                 equipment, choppers)               S Isolation Transformer
                                       factor correction capacitors to controller
                                       output terminals T1, T2, and T3 (U, V, and                Line has intermittent noise spikes   S MOV option (See A-4) or
                                       W) or component damage could occur.                       in excess of 2000V (lightening)      S Line Reactor (See A-4) or
                                                                                                                                      S Isolation Transformer
                   2-2
   Recommended Line Side Protection                                        guidelines must be followed in order to meet the
                                                                           NEC requirements for branch circuit protection:
   The Bulletin 160 Smart Speed Controller has
   been UL tested and approved for use with a fuse,                        Bulletin 140 manual motor starters can be used in
   circuit breaker or manual motor starter installed                       single and group motor applications. In single
   on the line side of the controller. The maximum                         motor applications, a fuse or UL489 rated circuit
   branch circuit protective rating is limited to four                     breaker is required upstream from the Bulletin
   times the rated output current of the drive or                          140 manual motor starter. In group motor
   30 amperes, whichever is less.                                          installations, the Bulletin 140 can be used for
                                                                           protection of an individual motor within the group
   The ratings in Table 2.C and Table 2.D are the                          and “one set” of fuses or a UL489 rated circuit
   “minimum” recommended values for use with                               breaker serves as the Short Circuit Protective
   each drive rating. It should be noted that the                          Device for the entire “Group Installation”.
   products listed under the column heading “Other
   Protective Devices” must follow the proper                              Bulletin 1492 circuit breakers are rated as
   application guidelines stated for those products in                     supplementary protective devices. When using
   order to meet local or national electrical codes.                       this device, upstream fuses or UL489 rated circuit
                                                                           breakers are required for each motor in the branch
   When using Bulletin 140 manual motor starters or                        circuit regardless if it is a single or group motor
   Bulletin 1492 circuit breakers the following                            installation.
   Table 2.C – Minimum Recommended Line Side Protective Devices for 200 – 240V rated units
        3 ∅ Rating
              at n               1 ∅ Rating
                                       at n          Fuse
                                                      use                   Fuse Types➇                        Other Protective Devices
          k (HP)
          kW ( P)                  k ((HP)
                                   kW   P)          Rating
                                                      at n           Class CC           Class J               Rating          Type
           .37 (1/2)                  N/A              6                                                        16
           .55 (3/4)               .37 (1/2)           6           KLDR/CCMR➁               JDT➁                16           140-MN-****➄
            .75 (1)                .55 (3/4)          10             ATMR➂                  AJT➂                16          1492-CB3-H***➅
            1.5 (2)                 .75 (1)         15 (16)          FNQR➃                  LPJ➃                16            HFD ***L➆
            2.2 (3)                 1.5 (2)           25                                                        20
Table 2.D – Minimum Recommended Line Side Protective Devices for 380 – 460V rated units
        3 ∅ Rating
              at n               1 ∅ Rating
                                       at n          Fuse
                                                      use                   Fuse Types➇                        Other Protective Devices
          k (HP)
          kW ( P)                  k ((HP)
                                   kW   P)          Rating
                                                      at n           Class CC           Class J               Rating          Type
           .37 (1/2)                  N/A           3 (4)➀                                                      6.3
           .55 (3/4)                  N/A           3 (4)➀         KLDR/CCMR➁               JDT➁                6.3                  ****➄
                                                                                                                             140-MN-****
                                                                            ➂               AJT➂                                        ***➅
            .75 ((1))                   A
                                      N/A             6➀           A    A
                                                                   ATDR/ATQR                A                   6.3         1492-CB3-H***
                                                                     FNQR ➃                 LPJ➃                              HFD ***L
                                                                                                                                   *** ➆
            1.5 ((2))                 N/A
                                        A             10                                                        16
            2.2 ((3))                   A
                                      N/A              ( )
                                                    15 (16)                                                     16
   ➀   Must be dual element time delay.                                    ➅    Allen-Bradley Bulletin1492 circuit breaker. Not recommended for
   ➁   Littlefuse                                                               repetitive application of power to the input of the drive.
   ➂   Gould Shawmut
                                                                           ➆    Westinghouse type HFD circuit breaker
   ➃   Bussman
   ➄   Allen-Bradley Bulletin 140 manual motor starter. Not recommended    ➇    Controller is also compatible with RK1, RK5, and BS88
       for repetitive application of power to the input of the drive.           fuse types.
2-5
2-6
   Control Wiring
   Figure 2.3 – TB3 Control Wiring for Analog Signal Follower Model
Shielded Wire
                   Control Wiring (continued)                                      Figure 2.5 – TB3 Three Wire control (Setting 0)
                                                                                                 ( Factory Default Setting)
                   Use P46 – [Input Mode] to select the control                          Shielded Wire
                   method for start, stop, and direction control.                                  TB3 Terminal Signal      Specification
                   Important: Settings 4 through 6 provide                                                5     Reverse     Contact closure input ➀
                   additional flexibility of TB3 control input                                            6     Start       Contact closure input ➀
                                                                                                                                     ➂
                   terminal 8.                                                                                7      Common Common
                                                                                                              8      Stop   Contact closure  input required to
                   D Setting 0 — Three Wire Control. (This is the                                                           operate controller ➀
                     factory default setting). Refer to Figure 2.5.
                                                                                   Important: After a Stop input, the Start input
                   D Setting 1 — Two Wire “Run Forward/Run
                                                                                   must be toggled to Run again.
                     Reverse” Control. Refer to Figure 2.6.
                   D Setting 2 — Program Keypad Module control.                    Figure 2.6 – TB3 Two Wire “Run Forward/Run
                     See Page 3-1.                                                              Reverse” control (Setting 1)
                                                                                       Shielded Wire
                   D Setting 3 — Momentary “Run Forward/Run
                     Reverse” control. Refer to Figure 2.7.                        ➁            TB3 Terminal Signal      Specification
                   D Setting 4 — Two Wire “Accel/Decel” control.                                       5     Run Reverse Contact closure input ➀
2-8
   Figure 2.8 – TB3 Two Wire “Accel/Decel” control                                     Input Mode                TB3-8                   TB3-8
                 (Setting 4)                                                             Setting                 Open                    Closed
       Shielded Wire                                                                                            Accel 2➄                Accel 1
                                                                                            4➃
   ➁                                                                                                            Decel 2                 Decel 1
               TB3 Terminal     Signal        Specification
                      5        Run Reverse    Contact Closure Input①                                          Controller➅             Controller
                                                                                            5➃
                      6        Run Forward    Contact Closure Input①                                           Disabled                Enabled
                      7        Common         Common③
                      8③                      Contact Closure Input①                                         Local (TB3)➆               Remote
                               Accel/decel                                                  6➃
                               select         Used to select Accel/Decel.                                      Control                  Control
   ③ Refer   to Figure 2.11.                                                       ➃   The “Run” input must be a maintained input. After a stop
                                                                                       command, either a “Run Forward” or “Run Reverse” input must
   Figure 2.9 – TB3 Two Wire “Enable” control                                          be toggled to start the controller.
                 (Setting 5)                                                       ➄   When this input is in an open state, P69 – [Accel Time 2] and
       Shielded Wire                                                                   P70 – [Decel Time 2] are active.
   ➁
                                                                                   ➅   When this input in in an open state, all power is removed from
                TB3 Terminal     Signal         Specification                          the motor and it will “coast to rest”.
                       5        Run Reverse     Contact Closure Input①
                                                                                   ➆   When this input is in an open state the Frequency source is
                       6        Run Forward     Contact Closure Input①
                                                                                       always from the terminal block regardless of the setting of
                       7        Common          Common③                                P59 – [Frequency Select].
                        8③      Enable          Contact Closure Input required
                                                to operate controller①             Important: In modes 4 through 6, Terminal
                                                                                   TB3-8 is also used to clear faults. See Figure 2.12
   ③ Refer   to Figure 2.11.                                                       for details.
   Figure 2.10 – TB3 Two Wire “Local/Remote” control                               Important: The system programmer is
                (Setting 6)                                                        responsible for returning terminal TB3-8 to its
       Shielded Wire                                                               original state if necessary.
   ➁
               TB3 Terminal     Signal        Specification                        Figure 2.12
                      5        Run Reverse    Contact Closure Input①
                      6        Run Forward    Contact Closure Input①               TB3-8
                                                                                   CLOSED
                      7        Common         Common③
                      8③       Local/         Contact Closure Input①
                               Remote         Used to select local (TB3)           TB3-8
                                              Control.                             OPEN
                                                                                                 Fault          Fault              Fault       Fault
   ③ Refer   to Figure 2.11.                                                                     occurs         clears             occurs      clears
2-9
2-10
   ➀     Indicates commanded direction. Actual motor rotation could be                decelerating to zero. The opposite LED will illuminate indicating
         different if motor leads are not connected properly. See                     the commanded direction.
         Chapter 4, Start-up for details on how to verify motor rotation.         ➂   Real time frequency adjustment can be achieved when using
   ➁     When the motor is running, pressing this key causes the                      P58 – [Internal Frequency].
         (currently illuminated) LED to flash indicating motor rotation while
                                                                                                                                                    3-1
                                   Insert the module bottom end first and then press on the symbol at the top
                                   of the module until the module is fully seated. The module is fully seated
                                   when its face is flush with the edges of its surrounding case.
3-2
Start-Up Chapter 4
                ATTENTION: Power must be applied to the controller to perform the following start-up procedure. Some of the
                voltages present are at incoming line potential. To avoid electric shock hazard or damage to equipment, only
                qualified service personnel should perform the following procedure. Thoroughly read and understand the
                procedure before beginning. If an event does not occur while performing this procedure, Do Not Proceed.
                Remove Power by opening the branch circuit disconnect device and correct the malfunction before continuing.
                                                            Start-Up Checklist
                            Verify the controller is installed per instructions outlined in Chapter 2 including:
                             D    Minimum clearance distance between controller and other equipment.
                             D    Proper grounding practices have been followed.
                             D    Proper power and control wiring has been used.
                              Verify that the STOP input is present at the TB3 control terminal block.
                              See page 2-9 for details on TB3-8 functionality when using P46 – [Input
                              Mode] settings 4 through 6.
                                                               A
                                                                                                                                          4-1
Chapter 4 – Start-Up
                                                                                   A
                     If you have a blank display panel.           Reconnect the power to the                    If you have a program keypad module.
                                                                  controller.
                           Check for proper motor rotation by setting the frequency            Check for proper motor rotation by selecting P61 –
                           source to its minimum setting.                                      [Preset Frequency 0]. This requires removing all inputs
                                                                                               to SW1, SW2, and SW3 on TB3 [see Figure 2.5 in
                           If you are using a program keypad module, verify that the           Chapter 2]. The factory default setting for P61 – [Preset
                           CLOCKWISE LED is illuminated. If you are using a blank              Frequency 0] is 3 Hz.
                           display panel, verify that the REVERSE input to TB3 is in
                           the OPEN position.                                                  If you are using a program keypad module, verify that the
                                                                                               CLOCKWISE LED is illuminated. If you are using a blank
                           Issue a START command from either the program keypad                display panel, verify that the REVERSE input to TB3 is in
                           module or TB3 control terminal block.                               the OPEN position.
                           Slowly increase the speed until the motor begins to turn.           Issue a START command from either the program
                           Check the direction of the motor.                                   keypad module or TB3 control terminal block. Check the
                                                                                               direction of motor rotation.
                              Issue a STOP command from either the program                         Issue a STOP command from either the program
                              keypad module or TB3 control block terminal.                         keypad module or TB3 control block terminal.
Disconnect and lock out all incoming power to TB1 terminals L1, L2, and L3 [R, S and T].
                                         Switch any two of the three motor leads connected to TB2, terminals T1, T2 and T3 [U, V and W].
                   4-2
   Overview of Parameters
   This chapter covers both display and program parameters. Display parameters are read only (they cannot
   be programmed), while program parameters can be changed to fit your motor control requirements. You
   must have a Program Keypad Module to view/change display and program parameters. The table below
   describes which parameters apply to the Preset Speed and Analog Signal Follower models. Refer to the
   programming example below for programming instructions.
                                                                    ÉÉ
   The following pages contain descriptions of both display and program
   parameters. Any parameter description that is shaded pertains only
   to the Preset Speed or Analog Signal Follower model. Refer to the
   legend to the right.
                                                                             = Parameter applies only to the Analog Signal Follower model
                                                                             = Parameter applies only to the Preset Speed model
   Programming Example
   The following is an example of the programming steps required to change a program group parameter setting. In this example,
   parameter 31 – [Decel Time] is changed from its factory default setting of 10.0 seconds to 2.2 seconds. Refer to Chapter 3,
   Figure 3.1 on page 3-1 for an explanation of Program Keypad Module display and programming keys.
   Important: To reset ALL values to original factory default settings, refer to P56 – [Reset Defaults].
        Action                                            Description                                           Keypad Display
                          1. To program the value of a program group parameter, enter the
                              program group by pressing the ESCape key. The “program mode                 3 0.          1 0. 0
                              indicator” will illuminate.                                                Program Mode Indicator
                          2. Press up/down keys until the desired parameter displays. In this case,
                              press the up key until parameter 31 – [Decel Time] displays.
                                                                                                         3 1.           1 0. 0
                          3. Press the SELect key. The program mode indicator flashes indicating
                              that you can use the up/down keys to change the parameter
                                                                                                         3 1.           1 0. 0
                              value.                                                                     Program Mode Indicator Flashes
                          4. Change the decel time value from the factory default of 10 seconds to
                              2.2 seconds by pressing the down key until 2.2 displays.                    3 1.              2. 2
                          Important: Continuously holding the up or down key will cause the value
                          to increase or decrease as long as the key is pressed.
                          5. When the desired value displays, press the ENTER key. This writes            3 1.              2. 2
                              the new value to memory. The program mode indicator will stop               Program Mode Indicator
                              flashing and the display will flash once indicating that the new value      Stops Flashing
                              has been accepted.
                                                                                                          3 1.           1 0. 0
                          Important: If at any time (while in the program mode) you wish to abort
                          the editing process, press the ESCape key. The original value of the           Program Mode Indicator
                          parameter will remain unchanged and you will be exited from the program        Stops Flashing
                          mode.
5-1
                                                                           Display Group
                     P#                                Parameter Description                                                 Min/Max              Units
                                                                                                                              Range
                     01     [Output Frequency] Displays the output frequency at TB2 terminals T1, T2 and                      0 to 240           0.1 Hz
                            T3 (U, V and W).
                     02     [Output Voltage] Displays the output voltage present at TB2 terminals T1, T2 and             0 to [Max Voltage]       1 Volt
                            T3 (U, V and W).
                     03     [Output Current] Displays the output current present at TB2 terminals T1, T2 and               0 to 2 Times         0.01Amps
                                                                                                                          Controller Rated
                            T3 (U, V and W).
                                                                                                                          Output Current
                     04     [Output Power] Displays the output power present at TB2 terminals T1, T2 and T3              0 to 2 Times Rated     0.01 kW
                                                                                                                          Controller Output
                            (U, V and W).
                                                                                                                                Power
                     05     [Bus Voltage] Displays the DC Bus Voltage level.                                             0 to 400 – [230V]        1 Volt
                                                                                                                         0 to 800 – [460V]
                     06     [Frequency Command] Displays the frequency that the controller is
                            commanded to output. This command may come from any of the frequency sources                      0 to 240           0.1 Hz
                            selected by P59 – [Frequency Select] or from a currently selected preset frequency.
                     07     [Last Fault] Displays the coded last fault number. If a fault is currently active (has not        0 to 49         Numeric Value
                            been cleared) the display will flash. See Chapter 6 for fault code descriptions.
                     08     [Heatsink Temperature] Displays the temperature of the controller heatsink.                       0 to 150         1 Degree C
                     09     [Controller Status] Displays the status of the controller in a binary
                            coded format.
10 [Controller Type] Used by Rockwell Automation field service personnel. Numeric Value Numeric Value
                     11     [Control Version] Displays version of controller firmware. Used by Rockwell                     Fixed Value       Numeric Value
                            Automation field service personnel.
5-2
                                                                 Display Group
    P#                                       Parameter Description                                                           Min/Max            Units
                                                                                                                              Range
    12    [Input Status] Displays the open (0) and closed (1) state of the
          inputs to TB3 in binary coded format as follows:
                                                                                        Bit 3   Bit 2   Bit 1 Bit 0
13 [Power Factor Angle] Displays the angle in electrical degrees between motor 0.0 to 180.0 0.1 degrees
  ÁÁÁ                                                                                                                     ÁÁÁÁÁÁ
                                                                                                                               ÁÁÁÁ
          voltage and motor current.
  ÁÁÁ                                                                                                                     ÁÁÁÁÁÁ
                                                                                                                               ÁÁÁÁ
    14    [Memory Probe Display] Used by Rockwell Automation field service                                                 Numeric Value    Numeric Value
  ÁÁÁ                                                                                                                     ÁÁÁÁÁÁ
                                                                                                                               ÁÁÁÁ
          personnel.
    15    [Preset Status] Displays the open (0) and closed (1) state of Terminal Block Three
          (TB3) inputs SW1, SW2, and SW3 in binary coded format. This parameter applies to the
          Preset Speed model only.
                                                                                                                            0000 to 0111    Binary Number
                                                                                                SW1
                                                                                                SW2
                                                                                                SW3
  ÉÉÉ
    ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
                      ÁÁÁÁÁÁ
                           ÁÁÁÁ
                                                                                                Not Used
  ÉÉÉ
    ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
                      ÁÁÁÁÁÁ
                           ÁÁÁÁ
    16    [Analog Input] Displays the analog input as a percent of full scale. Used in setting                             –150 to +150.0       0.1%
  ÉÉÉ
    ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
                      ÁÁÁÁÁÁ
                           ÁÁÁÁ
          P60 – [Zero Offset], P75 – [Analog Input Minimum], and P76 – [Analog Input
          Maximum].
  ÉÉÉ
    ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
                      ÁÁÁÁÁÁ
                           ÁÁÁÁ
          Important: On initial set up of the controller, apply a 0V or 4mA analog command to the
  ÉÉÉ
    ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
                      ÁÁÁÁÁÁ
                           ÁÁÁÁ
          controller. Once applied, if the value of this parameter displays something other than zero,
          program that value into P60 – [Zero Offset]. Important: The value of the [Zero Offset] will
  ÉÉÉ
    ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
     ÉÉÉ              ÁÁÁÁÁÁ
                           ÁÁÁÁ
          be subtracted from the value of this parameter.
                                 =     This parameter applies only to the Preset Speed model.
ÉÉÉ = This parameter applies only to the Analog Signal Follower model.
5-3
                                                                              Program Group
                       P#                            Parameter Description                                            Min/Max             Units          Factory
                                                                                                                       Range                             Default
                       30       [Accel Time 1] Time for the controller to ramp from 0.0 Hz. to P33
                                – [Maximum Frequency]. The rate is linear for any increase in command
                                frequency unless P53 – [S-Curve] is set to a value other than “0”. Setting
                                this to 0.0 sec. gives                                                                                                    10.0
                                                                                                                      0.0 to 600      0.1 Seconds       Seconds
                                0.1 sec acceleration    Max. Frequency '
                                with the initial current
                                limit turned off. This allows     Speed
                                quicker acceleration times
                                for low inertia systems. For
                                medium to high inertia                    0
                                                                              a Accel '   Time        a Decel '
                                systems, the minimum value                    0   Time                  Time
                                should be 0.1 sec.
                       31       [Decel Time 1] Time for the controller to ramp from P33 – [Maximum                    0.1 to 600      0.1 Seconds         10.0
                                Frequency] to 0.0 Hz. The rate is linear for any decrease in command frequency                                          Seconds
                                unless P53 – [S-Curve] is set to a value other than “0”. See P30 – [Accel Time 1]
                                figure above.
                       32➀ [Minimum Frequency] Lowest frequency that controller will output                            0 to 240           1 Hz            0 Hz
                                continuously.
                       33➀ [Maximum Frequency] Highest frequency the controller will output.                           0 to 240           1 Hz            60 Hz
                                Important: This parameter can’t be changed while running.
                       34       [Stop Mode Select] Determines stopping mode used by the controller
                                when a stop is initiated. Refer to the P44 – [DC Hold Time] and P45 – [DC Hold          0 to 3          Numeric             0
                                Voltage] diagrams. Settings: 0 = Ramp to Stop            1 = Coast to Stop                               Value
                                2 = DC Injection Braking          3 = DC Injection Braking (w/Auto Shutoff)
                                Important: DC Injection braking with auto shutoff: works the same as standard
                                DC injection braking except that it may shut off before the P44 – [DC Hold Time].
                                This occurs if the controller is out of current limit before the P44 – [DC Hold
                                Time] expires.
                       35       [Base Frequency] Set value to motor’s rated nameplate frequency.                      10 to 240           1 Hz          60 Hz ➁
                       36       [Base Voltage] Set value to motor’s rated nameplate voltage.                         20 to 460 for       1 Volt       460 Volts for
                                                                                                                    460V units and                     460V units
                                                                                                                     20 to 230 for                    and 230 for
                                                                                                                      230V units                       230V units
                   ➀     The analog inputs to the controller (i.e., 4–20mA, 0 to +10V, or remote potentiometer) can be scaled to P32 – [Minimum Frequency] and
                         P33 – [Maximum Frequency] by programming P75 – [Analog Input Minimum] and P76 – [Analog Input Maximum].
                   ➁     For controllers without a program keypad module, you can change P35 – [Base Frequency] to 50 Hz via a dipswitch located under the blank
                         front panel. See the Removing Program Keypad Module section in Chapter 3.
5-4
                                                                             Program Group
    P#                                             Parameter Description                                          Min/Max        Units      Factory
                                                                                                                   Range                    Default
    37    [Maximum Voltage] Sets the highest voltage that the controller will                                   20 to 510 for    1 Volt   460 Volts for
                                                                                                               460V units and              460V units
          output.                                                                                               20 to 255 for             and 230 for
          P37 – [Maximum Voltage] must be greater than or equal to P36 – [Base Voltage].                         230V units                230V units
    38    [Boost Select] Sets the boost voltage and redefines the Volts per Hz
          curve.
                            100
                      [Base Voltage], %
                                                   1/2
                                          50       Base                      9
                                                   Volts                     10
                                                                             11
                                                                             12
                                  8y
                                                                  1/2 Base
                                                                   Freq.
                                                                     Time
    40    [Skip Frequency Band] Determines the band around the P39 –
          [Skip Frequency] parameter. The actual band width will be 2 times [Skip                                 0 to 30        1 Hz         0 Hz
          Frequency Band] – 1/2 the band above and 1/2 the band below. A value of zero
          will disable the skip frequency.
5-5
                                                                                                                        Program Group
                     P#                                                             Parameter Description                                                                             Min/Max            Units           Factory
                                                                                                                                                                                       Range                             Default
                     41       [Motor Overload Select] Selects the derating factor for the I2t over-
                             load function.
                                                                                 Max Derating
                                                                100
                                                                 80
                                                                                                                                                    Settings:
                                                                 60
                                                                                                                                                     0 = No Derating
                                                                 40
                                                                                                                                                     1 = Minimum Derating
                                                                 20
                                                                                                                                                     2 = Maximum Derating
                                                                        0 25 50 75 100125 150 175 200
                                                                                   % Base Speed
                     42        [Motor Overload Current] Set to motor nameplate full load Amps                                                                                       0.1 to 200%      .01 Amperes        115% of
                                                                                                                                                                                    of controller                       Controller
                               (FLA).                                                                                                                                                   rating                           Rating
                     43        [Current Limit] Maximum output current allowed before current limiting                                                                                1 to 180%            1%             150%
                                                                                                                                                                                    of controller
                               occurs. Value set in percent of controller rated output current.                                                                                         rating
                     44        [DC Hold Time] Time that P45 – [DC Hold Voltage] will be applied to the                                                                                 0 to 25         0.1 Second       0 Seconds
                               motor when P34 – [Stop Mode Select] is set to either “DC Injection Braking” or
                               “Ramp to Stop” mode.
                     45        [DC Hold Voltage] DC Voltage level applied to the motor during braking                                                                                 0 to 115           1 Volt           0 Volts
                               when P34 – [Stop Mode Select] is set to either “DC Injection Braking” or “Ramp
                               to Stop” mode.
                               Important: If the current exceeds P43 – [Current Limit] the voltage applied to
                               the motor will be less than this setting.
5-6
                                                     Program Group
    P#                         Parameter Description                                         Min/Max        Units    Factory
                                                                                              Range                  Default
    46    [Input Mode] Configures the TB3 control inputs for various “3 wire” or “2
          wire run-fwd/run-rev control” schemes. Also enables/disables the program keypad
          module input control. Important: This parameter cannot be programmed while
          the controller is running. Also, power must be cycled or P56 – [Reset Func-         0 to 6       Numeric     0
          tion] must be set to “2” for the change to take effect.                                           Value
5-7
                                                                                   Program Group
                     P#                                      Parameter Description                                Min/Max           Units      Factory
                                                                                                                   Range                       Default
                     48     [Output Threshold] Determines the on/off point for the TB3
                            output relay when [P47 – Output Configure] is set to 6, 7, and 8.
                                                                                                                  0 to 815        Numeric        0
                                                                      Settings    Ranges                                           Value
                                                                         6        0 to 240 Hz
                                                                         7        0 to 180 %
                                                                         8        0 to 815 Volts
                                                       96
                                                       94
                                                       92
                                                                                                                  2.0 to 8.0       0.1 kHz     4.0 kHz
                                                       90
                                                       88
                                                       86
                                                       84
                                                             1    2       3       4       5       6    7   8
                                                                              Carrier Frequency, kHz
                             Important: Ignoring derating guidelines can cause reduced controller perfor-
                             mance.
                     50     [Restart Tries] Maximum number of times the controller will attempt to                  0 to 9        Numeric        0
                                                                                                                                   Value
                            reset a fault.
                     51     [Restart Time] Time between restart attempts.                                         0.5 to 300     0.1 Seconds    10.0
                                                                                                                                               Seconds
                     52     [DB Enable] Enables/disables external dynamic braking.                                0 to 100        Numeric         0
                                                                                                                                   Value
                            Setting “0” = Disable. Settings 1 through 100 = % duty cycle braking.
                            Important: The Rockwell Automation Bulletin 160 DB Resister package is rated
                            for 5% duty cycle. Use of this package above 5% should not be used and voids
                            the UL rating of this device. When setting this parameter to a value above 5%
                            duty cycle the resister must be sized to avoid overheating of the resister package.
                            Important: This parameter cannot be programmed while the controller is
                            running.
5-8
                                                             Program Group
    P#                               Parameter Description                                              Min/Max        Units    Factory
                                                                                                         Range                  Default
    53    [S-Curve] Enables a fixed shape S-Curve. See formula below:
                  Formula:
                     S-Curve Time = Accel or Decel Time x “S-Curve” setting (in percent) ➀              S-Curve
             1/2 S-Curve                                                                                Setting
                                                   1/2 S-Curve          Example:
                 Time                                  Time              Accel Time = 10 seconds         0 = 0%
                                                                         S-Curve Setting = 3
                             '       a    '        a                                                    1 = 10%
                                                                          S-Curve Time = 10 x .3
                     '           a              '       a
                    Accel Time                 Decel Time
                                                           ➀ See values in the Min/Max Range column
    54    [Clear Fault] Setting this parameter to a “1” performs a fault reset. When                      0 to 1      Numeric     0
                                                                                                                       Value
          the fault reset function is complete, the value is automatically set back to “0”.
          Important: This parameter cannot be programmed while the controller is
          running.
    55    [Memory Probe Address] Used by Rockwell Automation field                                    Numeric Value   Numeric   Numeric
                                                                                                                       Value     Value
          service personnel.
5-9
                                                                           Program Group
                     P#                              Parameter Description                                                Min/Max         Units    Factory
                                                                                                                           Range                   Default
                     56     [Reset Functions] When using this parameter, the controller’s                                  0 to 2        Numeric      0
                                                                                                                                          Value
                            parameters and their associated defaults are reset according to the descriptions
                            below:
                            0 = Idle State
                            1 = Reset defaults (restores all controller parameter settings to factory defaults).
                            2 = Update input mode (restores the controller to most recent programmed P46 –
                                [Input Mode] setting).
                            After the reset/update function is complete, this parameter will set itself back to a
                            “0”. This parameter cannot be programmed while the controller is running.
                            Important: For setting “1” only, an F48 – [Reprogram Fault] will occur and must
                            be cleared by cycling the STOP input to the controller. Important: P46 – [Input
                            Mode] factory defaults to “3 wire” control. If using keypad control, change
                            parameter setting back to a “2” to regain program keypad control.
                     57     [Program Lock] When set to a “1”, this parameter protects all controller                       0 to 1        Numeric     0
                                                                                                                                          Value
                            parameters from being changed by unauthorized personnel.
                     58     [Internal Frequency] When P59 – [Frequency Select] is set to a “1”                            0 to 240        0.1 Hz   60.0 Hz
                            this parameter provides the controller frequency command. This parameter will
                            change the frequency command in “Real time”.
                            Important: Follow normal programming procedures. Once the desired
                            command frequency is reached the ENTER key must be pressed to store this
                            value to EEPROM memory. If the ESC key is used before the ENTER key, the
                            frequency will return to the original value following the normal accel/decel curve.
                     59     [Frequency Select] Selects the source of the frequency command for
                            the controller.
                  ÉÉÉ
                                              1 = internal frequency command from P58 – [Internal Frequency].                             Value
                  ÉÉÉ
                     60     [Zero Offset] Used to add or subtract any system offset to the analog                    –50.0 to 50.0       Numeric     0%
                                                                                                                                          Value
                  ÉÉÉÉÉÉ
                            input. See P16 – [Analog Input] for additional information.
                            Important: This parameter cannot be programmed while the drive is running.
ÉÉÉ = This parameter applies only to the Analog Signal Follower model.
5-10
                                                             Program Group
       P#                             Parameter Description                                              Min/Max          Units          Factory
                                                                                                          Range                          Default
       61       [Preset Frequency 0] The programmed value sets the frequency that                        0 to 240        0.1 Hz           3 Hz
                the controller outputs when selected.
       62       [Preset Frequency 1] The programmed value sets the frequency that                        0 to 240        0.1 Hz           20 Hz
                the controller outputs when selected
       63       [Preset Frequency 2] The programmed value sets the frequency that                        0 to 240        0.1 Hz           30 Hz
                the controller outputs when selected.
       64       [Preset Frequency 3] The programmed value sets the frequency that                        0 to 240        0.1 Hz           40 Hz
                the controller outputs when selected.
       65       [Preset Frequency 4] The programmed value sets the frequency that                        0 to 240        0.1 Hz           45Hz
                the controller outputs when selected.
       66       [Preset Frequency 5] The programmed value sets the frequency that                        0 to 240        0.1 Hz           50 Hz
                the controller outputs when selected.
       67       [Preset Frequency 6] The programmed value sets the frequency that                        0 to 240        0.1 Hz           55 Hz
                the controller outputs when selected.
       68       [Preset Frequency 7] The programmed value sets the frequency that                        0 to 240        0.1 Hz           60 Hz
                the controller outputs when selected.
       69       [Accel Time 2] Time for the controller to ramp from 0.0 Hz. to P33 –
                [Maximum Frequency]. The rate is linear for any increase in command frequency           0.0 to 600       0.1 Sec.       20.0 Sec.
                unless P53 – [S-Curve] is set to a value other than “0”. Setting this to 0.0 sec.
                gives 0.1 sec acceleration with the initial current limit turned off. This allows
                quicker acceleration times for low inertia systems. For medium to high inertia
                systems, the minimum value should be 0.1 sec.
       70       [Decel Time 2] Time for the controller to ramp from P33 – [Maximum
                Frequency] to 0.0 Hz. The rate is linear for any decrease in command frequency          0.1 to 600       0.1 Sec.       20.0 Sec.
                unless P53 – [S-Curve] is set to a value other than “0”.
5-11
                                                                           Program Group
                     P#                             Parameter Description                                               Min/Max           Units    Factory
                                                                                                                         Range                     Default
                     71     [IR Compensation] The programmed value adds a voltage to the
                            output based on the torque current. An additional 31 volts (150%) are added to              0 to 150           1%       50%
                            460 volt units to compensate for stator resistance. 15.5 volts (150%) is added for
                            230 volt units. If the drive trips on an Overload fault (F7), or has trouble
                            accelerating to commanded speed, this value should be reduced. A setting of 0%
                            disables this function.
                     72     [Slip Compensation] This parameter compensates for the inherent slip in an
                            induction motor. A frequency is added to the commanded output frequency based on            0.0 to 5.0       0.1 Hz    2.0 Hz
                            torque current. If motor shaft speed decreases significantly under heavy loads then this
                            value should be increased. A setting of 0.0 Hz disables the function.
                     73     [Reverse Disable] When this parameter is set to a 1, the reverse is
                            disabled. The reverse command may come from the analog input, the TB3-5 input, the            0 to 1         Numeric     0
                            keypad, or a serial command. With a negative analog input and reverse disabled, the                           value
                            frequency command will be zero in bipolar mode and minimum frequency in unipolar
                            mode. All digital reverse inputs including two-wire “Run Reverse” will be ignored with
                  ÉÉÉ
                            reverse disabled.
                  ÉÉÉ
                            Important: This parameter cannot be programmed while the drive is running.
                     74     [Analog Select]
                  ÉÉÉ
                  ÉÉÉ
                            0 = unipolar analog input 0 to +10V
                            1 = bipolar analog input –10 to +10V
                                                                                                                          0 to 1         Numeric
                                                                                                                                          value
                                                                                                                                                     0
                  ÉÉÉ
                            Important: With bipolar analog input selected, the reverse inputs (keypad, terminal
                            block, serial) are ignored. In addition, two-wire “Run Reverse” commands, P75 –
                  ÉÉÉ
                            [Analog Input Minimum] and P32 – [Minimum Frequency] settings are ignored.
                            Important: This parameter cannot be programmed while the drive is running.
                  ÉÉÉ
                  ÉÉÉ
                     75     [Analog Input Minimum]
                            Important: Do not adjust this parameter until setting P60 – [Zero Offset].
                                                                                                                       0.0 to 150.0       0.1%      0.0%
                  ÉÉÉ
                            Sets the percent of analog input used to represent P32 – [Minimum Frequency]. If
                            the minimum analog input equals minimum frequency no action is needed. If it is
                  ÉÉÉ
                            desired to adjust the analog input to equal [Minimum Frequency], use
                  ÉÉÉ
                             P16 – [Analog Input] to adjust the analog input to the desired level and then enter
                            this value into P75.
                  ÉÉÉ
                            Analog inversion can be accomplished by setting this value larger than P76.
                            Important: This parameter cannot be programmed while the drive is running.
                  ÉÉÉ
                  ÉÉÉ
                     76     [Analog Input Maximum]
                            Important: Do not adjust this parameter until setting P60 – [Zero Offset].
                                                                                                                       0.0 to 150.0       0.1%     100.0%
                  ÉÉÉ
                            Sets the percent of analog input used to represent P33 – [Maximum Frequency]. If
                            the maximum analog input equals maximum frequency no action is needed. If it is
                  ÉÉÉ
                            desired to adjust the analog input to equal [Maximum Frequency], use
                  ÉÉÉ
                            P16 – [Analog Input] to adjust the analog input to the desired level and then enter
                            this value into P76.
                  ÉÉÉ
                            Analog inversion can be accomplished by setting this value smaller than P75.
                            Important: This parameter cannot be programmed while the drive is running.
                     78     [Compensation] Some drive/motor combinations have inherent instabilities
                            which are exhibited as non-sinusoidal motor currents. A setting of 1 will enable this         0 to 1         Numeric     0
                                                                                                                                          value
                     ÉÉÉ
                            parameter and attempt to correct this condition. A setting of 0 disables this function.
                            Important: Available in FRN 6.XX and later.
                     ÉÉÉ
                   5-12
                                          =     This parameter applies only to the Analog Signal Follower model.
   Fault Information
   Figure 6.1 – Fault Display                                            Fault LED – (Without Program Keypad
          P07 – [Last Fault]           Fault Code   Number➀              Module)
                                                                         Controllers without a program keypad module
                                                                         come equipped with a fault LED. When the fault
                                                                         LED illuminates, a fault condition exists.
                                                                         Tips To Clear a Fault
           0 7                                0 4                        Important: If a fault occurs, it is important to
             ➀ See Table 6.A below for fault descriptions.               address and correct the fault as well as the
                                                                         condition that caused the fault.
   Controllers equipped with a program keypad                            To clear a fault, perform one of the following:
   module will flash the display when a fault is                         D Press the program keypad’s stop button.
   present. If a fault occurs, parameter 07 – [Last
   Fault] displays. You can cross reference the                          D Cycle power to the controller.
   number that appears on the display (e.g., 04) with                    D Cycle the input signal at TB3-8 to the
   the fault numbers listed in Table 6.A.                                  controller.
                                                                         D Set P54 – [Clear Fault] parameter to a “1”.
  ÁÁÁ
    ÁÁÁÁ
  ÁÁÁ  ÁÁÁÁÁÁÁÁÁÁÁÁ
    ÁÁÁÁ          ÁÁÁÁÁÁÁÁÁÁÁÁÁ
       ÁÁÁÁÁÁÁÁÁÁÁÁ
   Fault
                  ÁÁÁÁÁÁÁÁÁÁÁÁÁ
                 Fault                        Fault Description                                     Corrective Action
  ÁÁÁ
    ÁÁÁÁ
       ÁÁÁÁÁÁÁÁÁÁÁÁ
                  ÁÁÁÁÁÁÁÁÁÁÁÁÁ
  Number       Indication
  ÁÁÁ
    ÁÁÁÁ
       ÁÁÁÁÁÁÁÁÁÁÁÁ
                  ÁÁÁÁÁÁÁÁÁÁÁÁÁ
     03       Power Loss       DC Bus voltage remains below 85% nominal on         Monitor incoming AC line for low voltage or line
                Fault          power up for longer than 5 seconds.                 power interruption.
  ÁÁÁ
    ÁÁÁÁ
  ÁÁÁ
     04
       ÁÁÁÁÁÁÁÁÁÁÁÁ
    ÁÁÁÁ          ÁÁÁÁÁÁÁÁÁÁÁÁÁ
             Under Voltage DC Bus voltage fell below the minimum. For
       ÁÁÁÁÁÁÁÁÁÁÁÁ
                  ÁÁÁÁÁÁÁÁÁÁÁÁÁ
                Fault
                                                                             Monitor incoming AC line for low voltage or line
                           controllers rated at input voltage 200 – 240V AC, power interruption.
  ÁÁÁ
    ÁÁÁÁ
       ÁÁÁÁÁÁÁÁÁÁÁÁ
                  ÁÁÁÁÁÁÁÁÁÁÁÁÁ
                           undervoltage trip occurs at 210V DC bus voltage
  ÁÁÁ
    ÁÁÁÁ
       ÁÁÁÁÁÁÁÁÁÁÁÁ
                  ÁÁÁÁÁÁÁÁÁÁÁÁÁ
                           (equivalent to 150V AC incoming line voltage).
                           For controllers rated at input voltage
  ÁÁÁ
    ÁÁÁÁ
  ÁÁÁ  ÁÁÁÁÁÁÁÁÁÁÁÁ
    ÁÁÁÁ          ÁÁÁÁÁÁÁÁÁÁÁÁÁ
       ÁÁÁÁÁÁÁÁÁÁÁÁ
                           380 – 460V AC, undervoltage trip occurs at
                  ÁÁÁÁÁÁÁÁÁÁÁÁÁ
                           390V DC bus voltage (equivalent to 275V AC
                           incoming line voltage).
  ÁÁÁ
    ÁÁÁÁ
  ÁÁÁ
     05
       ÁÁÁÁÁÁÁÁÁÁÁÁ
    ÁÁÁÁ          ÁÁÁÁÁÁÁÁÁÁÁÁÁ
              Over Voltage
       ÁÁÁÁÁÁÁÁÁÁÁÁ
                  ÁÁÁÁÁÁÁÁÁÁÁÁÁ
                 Fault
                               DC Bus maximum voltage exceeded. For
                               controllers rated at input voltage 200 – 240V AC,
                                                                                   Bus overvoltage caused by motor regeneration.
                                                                                   Monitor incoming AC line for excessive voltage.
  ÁÁÁ
    ÁÁÁÁ
       ÁÁÁÁÁÁÁÁÁÁÁÁ
                  ÁÁÁÁÁÁÁÁÁÁÁÁÁ
                               overvoltage trip occurs at 410V DC bus voltage      Extend the decel time or install dynamic brake
                                                                                   module or external capacitor module. See
  ÁÁÁ
    ÁÁÁÁ
       ÁÁÁÁÁÁÁÁÁÁÁÁ
                  ÁÁÁÁÁÁÁÁÁÁÁÁÁ
                               (equivalent to 290V AC incoming line voltage).
                                                                                   Appendix A.
                               For controllers rated at input voltage
  ÁÁÁ
    ÁÁÁÁ
  ÁÁÁ  ÁÁÁÁÁÁÁÁÁÁÁÁ
    ÁÁÁÁ          ÁÁÁÁÁÁÁÁÁÁÁÁÁ
       ÁÁÁÁÁÁÁÁÁÁÁÁ
                  ÁÁÁÁÁÁÁÁÁÁÁÁÁ
                               380 – 460V AC, overvoltage trip occurs at
                               815V DC bus voltage (equivalent to 575V AC
  ÁÁÁ
    ÁÁÁÁ
       ÁÁÁÁÁÁÁÁÁÁÁÁ
                  ÁÁÁÁÁÁÁÁÁÁÁÁÁ
                               incoming line voltage).
6-1
                  ÁÁÁÁ
                     ÁÁÁÁ
                        ÁÁÁÁÁÁÁÁÁÁÁÁ
                                   ÁÁÁÁÁÁÁÁÁÁÁÁ
                      Fault        Fault                       Fault Description                                     Corrective Action
                     Number      Indication
                  ÁÁÁÁ
                     ÁÁÁÁ
                  ÁÁÁÁ  ÁÁÁÁÁÁÁÁÁÁÁÁ
                     ÁÁÁÁ
                         06
                                   ÁÁÁÁÁÁÁÁÁÁÁÁ
                                 Motor Stall
                        ÁÁÁÁÁÁÁÁÁÁÁÁ
                                   ÁÁÁÁÁÁÁÁÁÁÁÁ
                                   Fault
                                                Motor has stalled. Motor load is excessive.          Longer acceleration time or a reduced load
                                                                                                     required.
                  ÁÁÁÁ
                     ÁÁÁÁ
                  ÁÁÁÁ  ÁÁÁÁÁÁÁÁÁÁÁÁ
                     ÁÁÁÁ
                         07
                                   ÁÁÁÁÁÁÁÁÁÁÁÁ
                                   Motor
                        ÁÁÁÁÁÁÁÁÁÁÁÁ
                                   ÁÁÁÁÁÁÁÁÁÁÁÁ
                                  Overload
                                   Fault
                                                Internal electronic overload trip. Excessive
                                                motor load exists.
                                                                                                     Reduce motor load until controller output current
                                                                                                     does not exceed the current set by P42 – [Motor
                                                                                                     Overload Current]. Reduce P38 – [Boost
                  ÁÁÁÁ
                     ÁÁÁÁ
                  ÁÁÁÁ  ÁÁÁÁÁÁÁÁÁÁÁÁ
                     ÁÁÁÁ          ÁÁÁÁÁÁÁÁÁÁÁÁ
                        ÁÁÁÁÁÁÁÁÁÁÁÁ
                         08
                                   ÁÁÁÁÁÁÁÁÁÁÁÁ
                                   Over         Excessive heat detected.
                                                                                                     Select].
                                                                                                     Clear blocked or dirty heat sink fins. Check
                  ÁÁÁÁ
                     ÁÁÁÁ
                        ÁÁÁÁÁÁÁÁÁÁÁÁ
                                   ÁÁÁÁÁÁÁÁÁÁÁÁ
                                Temperature                                                          ambient temperature. Check for blocked or
                                   Fault                                                             non-operating fan.
                  ÁÁÁÁ
                     ÁÁÁÁ
                  ÁÁÁÁ  ÁÁÁÁÁÁÁÁÁÁÁÁ
                     ÁÁÁÁ
                         11
                                   ÁÁÁÁÁÁÁÁÁÁÁÁ
                                  Operator
                        ÁÁÁÁÁÁÁÁÁÁÁÁ
                                   ÁÁÁÁÁÁÁÁÁÁÁÁ
                                   Fault
                                                Keypad has been removed while controller is
                                                powered.
                                                                                                     Clear fault. Do not remove keypad under power.
                  ÁÁÁÁ
                     ÁÁÁÁ
                  ÁÁÁÁ  ÁÁÁÁÁÁÁÁÁÁÁÁ
                     ÁÁÁÁ
                         12
                                   ÁÁÁÁÁÁÁÁÁÁÁÁ
                                Overcurrent
                        ÁÁÁÁÁÁÁÁÁÁÁÁ
                         32        ÁÁÁÁÁÁÁÁÁÁÁÁ
                                  FauIt
                                 EEPROM
                                                Overcurrent detected in hardware trip circuit.
6-2
   Can not operate in “RUN FWD/       1. Verify that P46 – [Input Mode] is set to “1”.
   RUN REV” mode.                     2. Verify that P73 – [Reverse Disable] or P74 – [Analog Select] are not set to “1”.
                                      3. Verify that power has been cycled for above change to take effect.
                                      4. Verify that both RUN FORWARD and RUN REVERSE switches are NOT closed simultaneously.
6-3
L1/R T1/U
                                L2/S                                                                                       T2/V
                                                                                                                                               Motor
                                L3/T                                                                                       T3/W
                                                                                                                            GND/PE
                                              GND/PE          Control         Bus
                                                              Power           Voltage              Current
                                              TB3 - 1                                              Circuitry
                    F   R                                                     Circuitry
                    r   e –10 to +10V         TB3 - 2
                    e   f  or
                    q   e Potentiometer       TB3 - 3
                    u   r                     (Common)
                    e   e or                                                                         Fault Feedback
                    n   n
                    c   c 4 – 20 mA           TB3 - 4
                    y   e                                                                                                   Program Keypad
                                                                                    CPU                                     Module
                                   Reverse
                                              TB3 - 5
                                   Start
                                              TB3 - 6         Opto
                                   Stop                       Isolator                                                     TB3 - 9
                                              TB3 - 8                                                                               Customer
                                                                                                         Relay
                                   Common                                                                Circuitry         TB3 - 10 Programmable
                                                                                                                                    Output
                                              TB3 - 7                                                                      TB3 - 11
6-4
   Controller Specifications
   Table A.1 and Table A.2 contain information that is unique to each SSC Controller rating. Table A.3
   contains information that applies to all Controller ratings.
   Table A.1 – Specifications for Controllers Rated 200 – 240V Single and Three Phase Input
                                                                                      Controller Catalog Number
   Single Phase (input)                                   160S-AA02          160S-AA03         160S-AA04     160S-AA08
   Three Phase (input)                                     160-AA02           160-AA03          160-AA04     160-AA08        160-AA12
   Output Ratings
         3 Phase Motor Rating kW (HP)                       0.37 (1/2)        0.55 (3/4)        0.75 (1)       1.5 (2)        2.2 (3)
         Output Current (A) Max                                2.3               3.0              4.5           8.0            12.0
         Power Dissipation (Watts)                             20                25               40             70            105
   Input Ratings
         Input Voltage, Frequency                                          200/240V Single Phase and Three Phase, 50/60 Hz
         Operational Range (V)                                                                 180 – 265V
         Input kVA                                             1.1               1.4              2.2           3.7            5.7
   Environmental Specifications
         Cooling Method                                            Convection Cooled                        Fan Cooled
   AC Dynamic Braking Torque ➀
       With external Dynamic Brake Module (%)                 300                233              200           150            115
       Without external Dynamic Brake Module (%)              100                100              100            50             50
   Table A.2 – Specifications for Controllers Rated 380 – 460V Three Phase Input
                                                                                   Controller Catalog Number
   Three Phase (input)                                     160-BA01          160-BA02          160-BA03      160-BA04        160-BA06
   Output Ratings
         3 Phase Motor Rating kW (HP)                       0.37 (1/2)        0.55 (3/4)        0.75 (1)       1.5 (2)        2.2 (3)
         Output Current (A) Max                               1.2                1.7              2.3           4.0            6.0
         Power Dissipation (Watts)                             25                30               40             65             80
   Input Ratings
         Input Voltage, Frequency                                                  380/460V Three Phase, 50/60 Hz
         Operational Range (V)                                                                340 – 506V
         Input kVA                                            1.1                1.6              2.2           3.7            5.7
   Environmental Specifications
         Cooling Method                                        Convection Cooled                            Fan Cooled
   AC Dynamic Braking Torque ➀
         With external Dynamic Brake Module (%)                300               233              200           150            115
         Without external Dynamic Brake Module (%)             100               100              100            50             50
   ➀   Estimated. Actual value depends on motor characteristics.
A-1
                                                                                                                                       ÎÎ
                                                                                                                                        ÎÎ
                                                                                                                                         ÎÎ
                                                                                                                                          ÎÎ
                    Approvals and Standards Compliance (All Controller Ratings)
                           Approvals
                                                                                                                                       ÎÎ
                                                                                                                                        ÎÎ
                                                                                                                                         ÎÎ
                                                                                                                                          ÎÎ
                                                                                                                                        ÎÎ
                                                                                                                                         ÎÎ
                                                                                                                                          ÎÎ
                                                                            UL508C                                  CSA 22.2
A-3
                  ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
                   Accessories
                  ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
                               ÁÁÁÁ
                                  ÁÁÁÁ
                                     ÁÁÁÁÁÁÁ
                                           ÁÁÁÁ
                  ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
                  ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
                               ÁÁÁÁ
                                  ÁÁÁÁ
                                     ÁÁÁÁÁÁÁ
                                           ÁÁÁÁ
                                    Controller
                                                           For All Controller Ratings – 0.37 to 2.2kW (1/2 to 3 HP)
                                                                     Dynamic         MOV          3% Line                    Line                 Capacitor
                  ÁÁÁÁÁÁÁÁÁÁ
                  ÁÁÁÁÁÁ
                       ÁÁÁ  ÁÁÁÁ
                          ÁÁÁ
                  ÁÁÁÁÁÁÁÁÁÁ   ÁÁÁÁ
                            ÁÁÁÁ  ÁÁÁÁ
                               ÁÁÁÁ  ÁÁÁÁÁÁÁ
                                     ÁÁÁÁ
                                  ÁÁÁÁ     ÁÁÁÁ
                                     Ratings
                                        ÁÁÁÁ
                                     ÁÁÁÁÁÁÁ
                                           ÁÁÁÁ
                                                                      Brake
                                                                     Module
                                                                                    Module        Reactors
                                                                                                   Open
                                                                                                   Style➀
                                                                                                                            Filters                Module
                  ÁÁÁÁÁÁ
                       ÁÁÁ
                  ÁÁÁÁÁÁ
                       ÁÁÁÁÁÁ
                            ÁÁÁÁ
                          ÁÁÁ  ÁÁÁÁ
                            ÁÁÁÁ  ÁÁÁÁ
                       Input Voltage
                               ÁÁÁÁ
                          Rating
                                     ÁÁÁÁ
                                  ÁÁÁÁ  ÁÁÁÁ
                                     ÁÁÁÁ  ÁÁÁÁ
                                        ÁÁÁÁ
                                           ÁÁÁÁ
                                                   HP       kW       Cat. No.       Cat. No.      Cat. No.          Cat. No.②     Cat. No.③        Cat. No.
                  ÁÁÁÁÁÁ
                       ÁÁÁÁÁÁ
                            ÁÁÁÁ
                               ÁÁÁÁ
                                  ÁÁÁÁ
                                     ÁÁÁÁ
                                        ÁÁÁÁ
                                           ÁÁÁÁ
                                                   1/2      0.37    160-BMA1       160-MMA1            –        160S-LFA1        160S-RFA-6-A    160-CMA1
                           200 – 240V
                                                   3/4      0.55    160-BMA1       160-MMA1            –        160S-LFA1        160S-RFA-6-A    160-CMA1
                  ÁÁÁÁÁÁ
                       ÁÁÁÁÁÁ
                            ÁÁÁÁ
                               ÁÁÁÁ
                                  ÁÁÁÁ
                                     ÁÁÁÁ
                                        ÁÁÁÁ
                                           ÁÁÁÁ
                            50/60Hz
                            1 Phase                1        0.75    160-BMA1       160-MMA1            –        160S-LFA1        160S-RFA-10-A   160-CMA1
                  ÁÁÁÁÁÁ
                       Á
                       ÁÁÁ
                         ÁÁ
                          ÁÁÁ
                            ÁÁÁÁ
                               ÁÁÁÁ
                                  ÁÁÁÁ
                                     ÁÁÁÁ
                                        ÁÁÁÁ
                                           ÁÁÁÁ
                                                   2         1.5    160-BMA2       160-MMA1            –        160S-LFA1        160S-RFA-16-A   ④
                  ÁÁÁÁÁÁ
                       ÁÁÁÁÁÁ
                            ÁÁÁÁ
                               ÁÁÁÁ
                                  ÁÁÁÁ
                                     ÁÁÁÁ
                                        ÁÁÁÁ
                                           ÁÁÁÁ
                                                   1/2      0.37    160-BMA1       160-MMA1      1321-3R4-B     160-LFA1         160-RFB-3-A     160-CMA1
                           200 – 230V
                  ÁÁÁÁÁÁ
                       ÁÁÁÁÁÁ
                            ÁÁÁÁ
                               ÁÁÁÁ
                                  ÁÁÁÁ
                                     ÁÁÁÁ
                                        ÁÁÁÁ
                                           ÁÁÁÁ
                                                   3/4      0.55    160-BMA1       160-MMA1      1321-3R4-A     160-LFA1         160-RFB-3-A     160-CMA1
                            50/60Hz
                            3 Phase                1        0.75    160-BMA1       160-MMA1      1321-3R4-A     160-LFA1         160-RFB-9-A     160-CMA1
                  ÁÁÁÁÁÁ
                       ÁÁÁ
                  ÁÁÁÁÁÁ
                       ÁÁÁÁÁÁ
                            ÁÁÁÁ
                          ÁÁÁ  ÁÁÁÁ
                            ÁÁÁÁ  ÁÁÁÁ
                               ÁÁÁÁ  ÁÁÁÁ
                                  ÁÁÁÁ  ÁÁÁÁ
                                     ÁÁÁÁ  ÁÁÁÁ
                                        ÁÁÁÁ
                                           ÁÁÁÁ
                                                   2
                                                   3
                                                             1.5
                                                             2.2
                                                                    160-BMA2
                                                                    160-BMA2
                                                                                   160-MMA1
                                                                                   160-MMA1
                                                                                                 1321-3R8-A
                                                                                                 1321-3R12-A
                                                                                                                160-LFA1
                                                                                                                160-LFA2
                                                                                                                                 160-RFB-9-A
                                                                                                                                        –
                                                                                                                                                 160-CMA1
                                                                                                                                                 160-CMA1
                  ÁÁÁÁÁÁ
                       ÁÁÁÁÁÁ
                            ÁÁÁÁ
                               ÁÁÁÁ
                                  ÁÁÁÁ
                                     ÁÁÁÁ
                                        ÁÁÁÁ
                                           ÁÁÁÁ
                                                   1/2      0.37    160-BMB1       160-MMB1      1321-3R2-B     160-LFB1         160-RFB-3-A     160-CMB1
                           380 – 460V
                  ÁÁÁÁÁÁ
                       ÁÁÁÁÁÁ
                            ÁÁÁÁ
                               ÁÁÁÁ
                                  ÁÁÁÁ
                                     ÁÁÁÁ
                                        ÁÁÁÁ
                                           ÁÁÁÁ
                                                   3/4      0.55    160-BMB1       160-MMB1      1321-3R2-A     160-LFB1         160-RFB-3-A     160-CMB1
                            50/60Hz
                                                   1        0.75    160-BMB1       160-MMB1      1321-3R2-A     160-LFB1         160-RFB-3-A     160-CMB1
                  ÁÁÁÁÁÁ
                       ÁÁÁÁÁÁ
                            ÁÁÁÁ
                               ÁÁÁÁ
                                  ÁÁÁÁ
                                     ÁÁÁÁ
                                        ÁÁÁÁ
                                           ÁÁÁÁ
                            3 Phase
                                                   2         1.5    160-BMB2       160-MMB1      1321-3R4-B     160-LFB1         160-RFB-9-A     160-CMB1
                  ÁÁÁÁÁÁ
                       ÁÁÁÁÁÁ
                            ÁÁÁÁ
                               ÁÁÁÁ
                                  ÁÁÁÁ
                                     ÁÁÁÁ
                                        ÁÁÁÁ
                                           ÁÁÁÁ    3         2.2    160-BMB2       160-MMB1      1321-3R8-B     160-LFB1         160-RFB-9-A     160-CMB1
                  ÁÁÁÁ
                     ÁÁÁÁ
                        ÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁ
                                       ÁÁÁÁÁÁÁÁÁ
                   Replacement Parts and Accessories
                                  ÁÁÁÁÁÁ
                  ÁÁÁÁ
                     ÁÁÁÁ
                  ÁÁÁÁ  ÁÁÁÁ
                       Fan ➄
                     ÁÁÁÁ
                        ÁÁÁÁÁÁÁÁÁ
                            ÁÁÁÁÁ
                    Replacement        ÁÁÁÁÁÁÁÁÁ
                                  ÁÁÁÁÁÁ
                                        Ready/
                                         Fault
                                                         Program
                                                         Keypad
                                                                      DeviceNet
                                                                    Communication
                                                                                                      Drivee Mo
                                                                                                      Dr     Model
                                                                                                                el                     24V DC Interface ➅
                                                                                                                                             Cat. No.
                  ÁÁÁÁ            ÁÁÁÁÁÁ
                         Kit            Panel            Module        Module
                                                                                                           Analog                           160-DM-SF1
                  ÁÁÁÁ            ÁÁÁÁÁÁ
                       Cat. No.         Cat. No.         Cat. No.       Cat. No.
                                                                                                           Preset                           160-DM-PS1
                       160-FRK1          160-B1           160-P1         160-DN1
                   ➀   Catalog numbers listed are for 3% impedance open style units. NEMA 1 and 5% impedance reactor types are also available, refer to
                       Publication 1321-2.0 for detailed information.
                   ➁   The 160-LF type filters are designed to meet Class A conducted emissions. These units have been tested with a maximum motor cable length of
                       75m (250 ft.) for 230V units and 40m (133 ft.) for 460V units.
                   ➂   The 160-RF type filters are designed to meet Class A and B conducted emissions. These units have been tested with a maximum motor cable length
                       of 25m (80 ft.) for both 230V and 460V units.
                   ➃   Included with controller.
                   ➄   The MTBF for the fan is 40,000 hours at 50_C.
                   ➅   Allows 24V DC sinking inputs.
A-4
➀ External capacitor modules are provided with this model and mount separately.
   Use the drilling template at the back of the manual for mounting the controller.
   Figure A.2 – Mounting Requirements                                                      Dimensions                    Metric             English
   DIN Mounting                                                                          Min. Panel Thickness (14 GA)   19mm              0.0747 in.
                                                                                         Mounting Base Screws           m4 x 0.7          # 8 – 32
                                                             Debris Cover
                                                                                         Mounting Torque                1.13 to 1.56 Nm   10 – 14 lb. in.
                   Approximate Dimensions
                   Dimensions are shown in millimeters (inches). Dimensions are not to be used for manufacturing
                   purposes.
                   Figure A.3 – Dynamic Brake Module – Both Sizes
                                                6,8
                              72
                                                (.230)                       86,4
                              (2.8)
                                                4 places                     (3.4)
                              50               8                 14                  7,5
                              (1.9)            (.315)            (.551)              (.295)
                                                A
                                          B
GND BR BR
                                                                     29
                                                                     (1.1)
                            Cat. No.            A            B
                    160-BMA1 & 160-BMB1       245          225
                                              (9.64)       (8.86)
                    160-BMA2 & 160-BMB2       334          314
                                              (13.15)      (12.36)
A-6
                                       MOV
                  L1   L2    L3     MODULE
     40,2         R    S     T                       45,4
     (1.6)                                           (1.8)
                                                                                          0,54
                                                                                          (.021)
                            71
                            (2.8)
                                                               5,1
                                                               (.199)
                                                                 Pin
                                                               Extension
D C
A-7
                                                                                                                       B
                                                                                          mm
                                                                                          (in.)                                                                 C
                                                                                                                       E
A D
                      Line Filter
                       Module             A              B             C              D                E                   F                        G                H
                    160S-RFA-6-A
                    160S-RFA-10-A   182.0 (7.17)     75.0 (2.95)   30.0 (1.18)   167.0 (6.57)     60.0 (2.36)
                                                                                                                6.5 x 4.5 (0.26 x 0.18)         4.2 (0.17)           200
                    160S-RFA-16-A                                                                                      hole dim.                 dia. hole          (7.87)
                    160-RFB-3-A     182.0 (7.17)     75.0 (2.95)   35.0 (1.38)   167.0 (6.57)     60.0 (2.36)         ( places)
                                                                                                                      (2 p ces)                 ( places)
                                                                                                                                                (2 p ces)
                    160-RFB-9-A     182.0 (7.17)     75.0 (2.95)   47.5 (1.87)   167.0 (6.57)     60.0 (2.36)
                    160-LF          174.0 (6.85)     75.0 (2.95)   50.0 (1.97)   163.0 (6.41)     60.0 (2.36)         6.9 x 5.25                 6.9 x 5.25          200
                    (All Types)                                                                                    (0.272 x 0.207)            (0.272 x 0.207)       (7.87)
                                                                                                                      hole dim.                   hole dim.
A-8
                            50
                            (1.97)
               4,5          40                                 110,9
               (.177)       (1.5)                              (4.37)
      Mounting Holes
          140
          (5.51)
                                                                                      150,9
                   130                                                                (5.94)
                   (5.11)
A-9
                           17,34                                    161,2
                           (0.68) Required                          (6.35) Overall Height
                           for Removal                              with DeviceNet Module
                                                                  167,82
                                                                  (6.61) Overall Height
                                                                  with DeviceNet Connector
                                                                                 29 ➀
                                                                               (1.14)
A-10
Appendix B – CE Compliance
B-1
Appendix B – CE Compliance
                   General Instructions for an EMC                                                D Input power, output power and control wiring
                   Compliant Installation                                                           outside the enclosure must use separate
                                                                                                    shielded cables, or separate conduit.
                   Refer to Figure B.1.
                                            R (L1)                      T (L3)
                                                   Line                 S (L2)
                                  AC        S (L2) Filter
                           Input Line       T (L3)                      R (L1)
Ground Tab – PE
                                                                              L1     L2     L3    BR   BR
                                                         Line Power TB1       R      S      T      –    +
                                                                                          FAULT
                                                                                          READY
                                                                                                                      to TB3        Control
                                                                                   1 2 3 4 5 6 7 8 9 10 11
                                                                                                                                   Cabinet *
                                                      Control Wiring TB3
                                                        Motor Wiring TB2      TI
                                                                              U
                                                                                     T2
                                                                                     V
                                                                                            T3
                                                                                            W
                                                                                                   –
                                                                                                  DC
                                                                                                        +
                                                                                                       DC
                                                                                                             W (T3)
                                                                                                             V (T2)                   to Motor
                                                                                                             U (T1)
                                          Shielded Enclosure
                                      L1     L2     L3    BR   BR
                                      R      S      T      –    +
                                                  FAULT
                                                  READY
                                           1 2 3 4 5 6 7 8 9 10 11                           4 Wire
                                                                                      Shielded Motor Cable
                 Motor Wiring TB2     TI
                                      U
                                             T2
                                             V
                                                    T3
                                                    W
                                                           –
                                                          DC
                                                                +
                                                               DC
                                                                     W (T3)
                                                                     V (T2)
                                                                     U (T1)
                 Shielded Enclosure
B-3
Appendix B – CE Compliance
                   Control Cable
                   D Control wiring must use shielded cable, or
                     grounded metal conduit. Refer to Figure B.3
                     and Figure B.4.
                   D The shield must be connected to signal
                     common at both ends of the cable.
                   D The Common terminals (TB3-3 & 7) must be
                     solidly connected (and as short as possible) to
                     the PE terminal of the controller.
                                                                  L1     L2     L3    BR   BR
                                                                  R      S      T      –    +
                                                                              FAULT
                                                                              READY
                                                                                                                         Control
                                                                                                                        Cabinet *
                                           Control Wiring TB3          1 2 3 4 5 6 7 8 9 10 11
                                                                                                       to TB3
                                                                                                                          Signal
                                                                  TI     T2     T3     –    +                             Common
                                                                  U      V      W     DC   DC
                                                                                                                   Shielded Control
                                                                                                                        Cable
                                              Shielded Enclosure
B-4
Index
                                                                             
                                                                  fan/pump volts/hz patterns, 5-5
   cable length recommendations
                                                                  fault buffer, 5-2
      capacitive current, 2-5                                     fault information, troubleshooting, 6-1
      reflected wave, 2-4                                         fault LED, 6-1
   capacitive current, cable length recommendations, 2-5          faults, clearing, 5-9, 6-1
   capacitor module, A-9                                          frequency dipswitch, 3-2
      connecting, 2-2                                             frequency source selection
   carrier frequency, pwm, 5-8, A-3                                  Analog Signal Follower model, 2-6, 2-7, 5-10
   catalog number description, 1-2
                                                                     Preset Speed Model, 2-6, 2-7, 5-11
   CE, 2-1, A-2, B-1
   changing base frequency, from factory default, 3-2                         
   clearing faults, 5-9, 6-1
   compensation, 5-12                                             general precautions, 1-1
   control wiring                                                 grounding, 2-6
      Analog Signal Follower model, 2-6
      Preset Speed model, 2-6                                                 
   control wiring requirements
                                                                  input mode selection, 2-8, 5-7
      Analog Signal Follower model, 2-6, 2-7
                                                                  input power conditioning, 2-2
      Preset Speed model, 2-6, 2-7
   controller features, 2-1
   controller specifications, A-1
   conventions used in this manual, 1-2                           line filters, A-4, A-8
   CSA, A-2                                                       line reactor, A-4, A-8
   CUL, A-2                                                       line side protection, 2-3
                                                                                                                         I-1
Index
                                                                                       
                   min/max frequency, 5-4                                    reflected wave, cable length recommendations, 2-4
                   minimum clearance, 2-1                                    replacement parts, A-4
                   motor cable lengths, effects, 2-4                         resetting, to factory defaults, 5-10
                   motor cable recommendations, 2-4                          reverse, 2-6, 3-1
                   mounting requirements, 2-1, A-5                           RWR (reflected wave reducer), 2-4, 2-5
                   MOV module, A-4, A-7
                                                                                        
                             
                                                                             S-curve, 5-9
                   nameplate information, 1-2                                skip frequency, 5-5
                                                                             specifications, A-1, A-2, A-3
                                                                            standards compliance, A-2
                                                                             start, 2-7, 2-8, 2-9, 3-1
                   operating controller
                                                                             start-up, 4-1
                     with program keypad module, 2-1, 3-1
                                                                             stopping, 2-7, 2-8, 2-9, 3-1, 5-4
                     without program keypad module, 2-1                      storage temperature, 2-1, A-2
                   output contacts, 2-7, 5-7
                   output ratings, A-1
                   overload protection, 2-2, 5-6
                                                                                        
                                                                             terminal blocks
                                                                               specifications, 2-2, 2-6
                   parameters                                                   TB1, 2-1, 2-2
                      display group, 5-2                                        TB2, 2-1, 2-2
                      overview, 5-1                                             TB3, 2-1, 2-2, 2-7
                      program group, 5-4                                     torque ratings, A-1
                   potentiometer wiring, 2-6                                 troubleshooting, 6-3
                   power, wiring, 2-2                                           fault descriptions, 6-1
                   precautions, 1-1
                   preset frequencies, 2-7, 5-11                                        
                   program group, parameters, 5-4                            vibration, A-2
                   program keypad module                                     voltage rating, A-1
                      description, 3-1
                      display mode, 3-1
                      features, 3-1
                      installation, 3-2                                      wiring
                      key descriptions, 3-1                                     control and signal, 2-6, 2-7, 2-8, 2-9
                      program mode, 3-1                                         input line fuses, 2-3
                      removal, 3-2                                              motor cable recommendations, 2-4
                   program lock, 5-10                                           terminal blocks specifications, 2-2, 2-6
                   program mode, 3-1                                            wire size recommendations, 2-2, 2-6
I-2
                    Worldwide representation.
                    Argentina • Australia • Austria • Bahrain • Belgium • Bolivia • Brazil • Bulgaria • Canada • Chile • China, People’s Republic of • Colombia • Costa
                    Rica • Croatia • Cyprus • Czech Republic • Denmark • Dominican Republic • Ecuador • Egypt • El Salvador • Finland • France • Germany • Ghana •
                    Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Iran • Ireland • Israel • Italy • Jamaica • Japan • Jordan
                    • Korea • Kuwait • Lebanon • Macau • Malaysia • Malta • Mexico • Morocco • The Netherlands • New Zealand • Nigeria • Norway • Oman •
                    Pakistan • Panama • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia • Saudi Arabia • Singapore • Slovakia • Slovenia
                    • South Africa, Republic of • Spain • Sweden • Switzerland • Taiwan • Thailand • Trinidad • Tunisia • Turkey • United Arab Emirates • United Kingdom •
                    United States • Uruguay • Venezuela
                    Rockwell Automation Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000
                    Fax: (1) 414 382-4444
                    Publication 0160-5.9 – May 1998                                                                                                                                  40055–180–01(01)
Supercedes Publications 0160-5.9 – December 1996, 0160-5.9DU2 – May 1997, 0160-5.9DU4 – January 1998 Copyright 1996 Allen-Bradley Company, Inc., a Rockwell International company