PROTECTION ENGINEERING DEPARTMENT

13.8kV SWGR. BUS RISER/VT/EARTHING-B


(110/13.8KV SUBSTATION)
ALFANAR ELECTRICAL SYSTEM

alfanar
LED LAMP X7D X7E

SECTION D-D
B A
D D

GND
X1D B13

F98X1

F98X2
F98X
B1 B2 B7 B8
X5
X1E
B14
X3 TH.H XCBF

B15
B9 B10 B11 B12
X8
B16
XHR X3 X4 74CO X7A XV2
B17

X6 X9A DIODE
B18
HRL R1,R2,R3
X7 B19
XV1

C C
B A

SECTION A-A

X7B

X9

SECTION C-C
Toll Free : 800 124 1333
alfanar www.alfanar.com

Manufacturer's Name Alfanar Electrical Systems Rated Voltage (Ur) 17.5 kV.

Country Of Origin K.S.A System Voltage (Un) 13.8 kV.


Rated Frequency (f r) 60 Hz.
Type Designation ALFA-12
Rated Power Frequency Withstand 38 kV.
Reference Of SEC Specification 32-TMSS-01 Rev.02 Voltage (U d)
Rated Lightning Impulse Withstand 95 kV.
Manufacturer's Serial No. ALFA-12/XXX/XX.XXXX/XXX Voltage (U p)
Instruction Book Reference XXXXXX Rated Normal Current (I r) 1250 A.

Rated Short-time WithstandCurrent (I k) 25 kA.


Year Of Manufacture 2023 (for main and earthing circuits)

Applicable Standard IEC 62271-200 Rated Duration Of Short Circuit (t k) 3 sec.


(for main and earthing circuits)
OPEN
Alfanar Sales Order No. 953199 Rated Peak Withstand Current (I p) 65 kA.
CLOSE (for main and earthing circuits)
SEC. Contract No. 4400016205 IAC : AFLR. 25 kA/1s.

Auxiliary Voltage (AC/DC) 230V/110V

alfanar Alfanar Electrical


Alfanar Electrical Systems
Systems

2500.00
OPEN

CLOSE

OPEN

CLOSE
º
% RH
Voltage Transformer (VT) Rack-IN/OUT Procedure
Earth Switch (ES) Operating Instruction (Busbar Earthing)
A. Racking-IN to Service Position: Busbar Earthing: Ensure all circuit breakers in same Section are in 'TEST' position.
1. Ensure that VT knob is in ISOLATE POSITION before closing the VT door.
2. Close the VT door to free the knob. A. Closing the Earth Switch (ES):
3. Pull out & move the VT knob into RACK IN/OUT POSITION. 1. Confirm Circuit Breaker is in Test Position.
4. Insert the handle into the hole of insertion/withdrawable screw. 2. Confirm cables are not energize by checking 'CVI'.
5. Rotate the handle clockwise to rack in VT to service position. 3. Press push button 'PB' in LV door and hold it, during hold you can rotate
6. Remove the handle and move the VT knob into CLOSE POSITION. Earth Switch (ES) knob to open access for ES operating shaft.
7. Padlock the VT knob externally to restrict any unauthorized person to rack out 4. Engage the ES operating handle; rotate it to the left until handle rotation stop to
VT from service position. close the Earth Switch (ES).
5. Check Earth switch (ES) indication shows .
B. Racking-OUT from Service Position:
1. Remove the padlock before operation. B. Opening the Earth Switch (ES):
2. Pull out & move the VT knob into RACK IN/OUT POSITION. 1. Engage the ES operating handle and turn it to the right until handle rotation
3. Fit the handle into the hole of withdrawable/insertion screw. Stop to open the Earth Switch (ES).
4. Rotate the handle anti-clockwise to rack out the VTs from service position. 2. Check Earth switch (ES) indication shows .
5. Remove the handle and move the VT knob into ISOLATE POSITION. 3. Rotate Earth Switch (ES) knob to close the access for ES operating shaft.
6. Padlock the VT knob externally to restrict any unauthorized person to rack in
Note: Access for ES operating shaft remains OPEN if the Earth Switch (ES) is in
VT to service position.
CLOSED position.
7. To pull the VT out of the panel, remove the front stiffener then pull it out.

You might also like